Line Differential - Test Report For Alstom Make Micom P546 Relay
Line Differential - Test Report For Alstom Make Micom P546 Relay
1. RELAY CHARACTERISTICS:
Type No.: MiCOM P546 Designation : **
Model No : P54631NH7M0710M Nominal Current : 1A
Serial Number : 32178851/06/12 Nominal Voltage :Vn 100- 120 VAC – 50/60 HZ
Make : ALSTOM Aux. Volts : Vx 110-250 VDC 100-240 VAC
Note: This particular relay is configured according to the site schematic provided.
2. CT & VT DATA:
CT rated primary current set as 2000 A
CT rated secondary current set as 1.0A
Ignd-CT rated primary current set as 2000 A
Ignd-CT rated secondary current set as 1.0A
Rated primary voltage (L-L) set as 132 KV
Rated secondary voltage (L-L) set as 110 V
3. PRELIMINARY CHECKS:
Case earth installed?
LCD front panel display
Clock set to local time?
4. GENERAL CHECKS
Checking Results
Dry cell battery voltage (Remove battery isolation strip)
Auxiliary voltage value on terminals M2 ( + ) and M1 ( - )
Watchdog contact Terminals M11 and M12 Closed
when relay OFF Terminals M13 and M14 Open
Watchdog contact Terminals M11 and M12 Open
when relay ON Terminals M13 and M14 Closed
Check if the frequency is set on required value
Healthy relay LED operation check
5. DISPLAY READINGS
Displayed Value
Circuit Injected Value Phases Expected Value
Primary
VAN 76.21 kV 76.23 kV
VBN 76.21 kV 76.25 kV
63.5
Phase A / 0° VCN 76.21 kV 76.30 kV
Voltage
Phase B / -120° VAB 132.0 kV 132.1 kV
Phase C / 120°
VBC 132.0 kV 132.1 kV
VCA 132.0 kV 132.1 kV
IA 2000 A 2002 A
1.0 A
Phase A / 0° IB 2000 A 1999 A
Current
Phase B / -120° IC 2000 A 2007 A
Phase C / 120°
IN 0.00 A 10.39 A
Frequency 60.0 Hz - 60.0 Hz 60.0 Hz
MW Va, Vb, Vc = 57.74V - 457.3 MVA 458.1 MVA
MVAR Ia, Ib, Ic =1A - 0.0 MVAR -0.12 MVAr
MVA Angle between V&I = 0.0 degree - 457.3 MW 458.3 MW
6. FUNCTIONAL TESTS
6.1 Current differential bias characteristic (87-1)
Setting:
Item Description Setting
1 IS1 0.20 A
2 Is2 2.0 A
3 K1 30 %
4 K2 150 %
5 T 0 Sec
Pick-up & Time test:-
*NOTE: The Relay will be tested at loopback internal mode
It should be noted that the minimum operating current is related, but not equal to the Is1 SETTING
Consider a single end fed fault with no load but fault current, I:-
|Idiff| = I
|Ibias| = ½I
Assuming |Ibias| < Is2, then, using the equations from section 2.1( from manual ), the relay will operate if:-
|Idiff| > k1.| Ibias| + Is1 or
I > k1.½I + Is1 or
I> Is1 / (1 - 0.5 k1)
The minimum operating current is therefore a function of the Is1 and k1 settings. Since k1 is recommended to be
set to 30%, the minimum operating current will be:-
Imin = 1.176 1s1
I Diff I > ( k1 * I I Bias I+ Is1 )/2 = 0.118 A
Expected Trip Actual Trip Time
Expected Pickup Actual Pickup Drop-off
Fault Type Time in m-sec at
In Amp In Amp In Amp
in m-sec 2 x I Pickup
A-N 0.118 A 0.120 0.088 <40 ms 31
B-N 0.118 A 0.120 0.089 <40 ms 28
C-N 0.118 A 0.120 0.088 <40 ms 35
Lower slope test (Injected current < Is2)
|Ιdiff| >( k1.| Ιbias| + Ιs1)/2=0.25 A
Phase Normal Voltage Pick up Drop off Set Time (Sec) Measured Time (Sec)
One phase 63.5 33.58 35.12 5.022
5.0
Two phase 63.5 33.58 35.10 5.024
- CHECK THE FUSE FAIL BLOCKING BY I2> inhibit (simulate 3 phase voltage to get fuse Fail,
for I2> Apply 3 Phase equal current (Ir A) with balanced angles and increase one phase to get I2 more than the setting
Value it will inhibit fuse fail then decrease again phase till you get fuse fail
-Check the relay trip unblocking during the internal fuse fail by any fault : [ ok ]
Simulate 2 stages: - stage 1; inject 3 phase voltage to get fuse fail and zero current.
- stage 2; inject the same voltage as in stage 1, inject 3 phase current to get a value greater than I2> inhibit.
7.6.2 Loss of all 3 phase voltages under load condition test (detect 3p):
Fixed Setting: a- for fuse fail pick up; V1=10 volts.
b- for fuse fail reset; V1=30 volts.
Pick up (v) Reset (v)
10.0 30.03
Check the blocking of the relay when the general block functions (VT MCB TRIP) is activated [ ok ]
7.7.1 Distance Directional Test:
Fixed Direction Measured Direction
Forward 330° - 150° Forward 329.6 – 149.6
Reverse 150° - 330° Reverse 149.7 – 329.5
Fault Type Fault Impedance Z (Ω) Expected display (km) Actual display (km)
A-N(25)% 3.83 5.38 5.374
A-B(50)% 7.66 10.75 10.76
A-B(75)% 11.49 16.13 16.16
A-B-C(100)% 15.32 21.51 21.44
*We inject Z with line angle
9. Directional earth fault protection - DEF (67N-1)
DEF status : Enabled DEF polarizing : Zero sequence
DEF VNpol set : 5.0 V DEF Forward threshold : 150.0 mA
DEF Char angle : -60° DEF Reverse threshold : 100.0 mA
RCA Angle (Degree) Forward Operating Area (from-to in Degree) Reverse Operating area (from-to in Degree)
Fault type t rev guard setting (m sec) t rev guard measured (m sec)