0% found this document useful (0 votes)
123 views14 pages

Installation Instructions R 410A Split System Air Conditioner

Uploaded by

Paulo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
123 views14 pages

Installation Instructions R 410A Split System Air Conditioner

Uploaded by

Paulo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 14

INSTALLATION INSTRUCTIONS

R−410A Split System Air Conditioner


CSA6, HSA6, TSA6

These instructions must be read and understood completely before attempting installation.
IMPORTANT: Effective January 1, 2015, all split system and packaged air conditioners must be installed pursuant to
applicable regional efficiency standards issued by the Department of Energy.

Safety Labeling and Signal Words


DANGER, WARNING, CAUTION, and
NOTE Signal Words in Manuals
The signal words DANGER, WARNING, The signal word WARNING is used throughout this
CAUTION, and NOTE are used to identify levels of manual in the following manner:
WARNING
hazard seriousness. The signal word DANGER is
only used on product labels to signify an immediate ! WARNING
hazard. The signal words WARNING, CAUTION,
and NOTE will be used on product labels and The signal word CAUTION is used throughout this
throughout this manual and other manuals that may manual in the following manner:
apply to the product.
DANGER − Immediate hazards which will result in ! CAUTION
severe personal injury or death.
WARNING − Hazards or unsafe practices which Signal Words on Product Labeling
could result in severe personal injury or death. Signal words are used in combination with colors
CAUTION − Hazards or unsafe practices which and/or pictures on product labels.
may result in minor personal injury or product or
property damage.
NOTE − Used to highlight suggestions which will
result in enhanced installation, reliability, or
operation.

TABLE OF CONTENTS
Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
! WARNING
Installation Requirements . . . . . . . . . . . . . . . . . . . . . . . . 2 ELECTRICAL SHOCK HAZARD
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Failure to follow this warning could result in per-
sonal injury and/or death.
Start−up Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Before installing, modifying, or servicing system,
General Sequence of Operation . . . . . . . . . . . . . . . . . . 8 main electrical disconnect switch must be in the
OFF position. There may be more than 1 discon-
Control Functions & Sequence of Operation . . . . . . . . 8 nect switch. Lock out and tag switch with a suit-
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 able warning label.

Status Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 ! CAUTION


CUT HAZARD
Failure to follow this caution may result in per-
sonal injury
Sheet metal parts may have sharp edges or burrs.
Use care and wear appropriate protective clothing
and gloves when handling parts.

421 01 5104 03 02/11/15


Downloaded from www.Manualslib.com manuals search engine
INSTALLATION INSTRUCTIONS R−410A Split System Air Conditioner

SAFETY CONSIDERATIONS Figure 1 Connecting Tube Installation


Improper installation, adjustment, alteration, service,
maintenance, or use can cause explosion, fire, electrical NOTE: Avoid contact between tubing and structure

shock, or other conditions which may cause death, personal OUTDOOR WALL INDOOR WALL

injury, or property damage. Consult a qualified installer, CAULK


LIQUID TUBE
service agency, or your distributor or branch for information or
assistance. The qualified installer or agency must use
factory−authorized kits or accessories when modifying this
VAPOR TUBE
product. Refer to the individual instructions packaged with INSULATION

the kits or accessories when installing. THROUGH THE WALL

Follow all safety codes. Wear safety glasses, protective JOIST


HANGER STRAP
clothing, and work gloves. Use quenching cloth for brazing (AROUND VAPOR
TUBE ONLY) INSULATION
operations. Have fire extinguisher available. Read these VAPOR TUBE

instructions thoroughly and follow all warnings or cautions


included in literature and attached to the unit. Consult local
building codes and current editions of the National Electrical
Code ( NEC ) NFPA 70. In Canada, refer to current editions 1″ (25.4 mm)MIN.
LIQUID TUBE
of the Canadian electrical code CSA 22.1. SUSPENSION

Recognize safety information. This is the safety−alert symbol


!! When you see this symbol on the unit and in instructions Outdoor unit contains system refrigerant charge for operation
or manuals, be alert to the potential for personal injury. with AHRI rated indoor unit when connected by 15 ft. (4.57
Understand these signal words; DANGER, WARNING, and m) of field−supplied or factory accessory tubing. For proper
CAUTION. These words are used with the safety−alert unit operation, check refrigerant charge using charging
symbol. DANGER identifies the most serious hazards which information located on control box cover and/or in the Check
will result in severe personal injury or death. WARNING Charge section of this instruction.
signifies hazards which could result in personal injury or IMPORTANT: Maximum liquid−line size is 3/8−in. OD for all
death. CAUTION is used to identify unsafe practices which residential applications including long line.
would result in minor personal injury or product and property IMPORTANT: Always install the factory−supplied liquid−line
damage. NOTE is used to highlight suggestions which will filter drier. Obtain replacement filter driers from your
result in enhanced installation, reliability, or operation. distributor or branch.
INSTALLATION RECOMMENDATIONS INSTALLATION
NOTE: In some cases noise in the living area has been
traced to gas pulsations from improper installation of
! WARNING
equipment. UNIT OPERATION AND SAFETY HAZARD
1. Locate unit away from windows, patios, decks, etc. Failure to follow this warning could result in personal
where unit operation sound may disturb customer. injury or equipment damage.
R−410A refrigerant systems operate at higher pressures
2. Ensure that vapor and liquid tube diameters are than standard R−22 systems. Do not use R−22 service
appropriate for unit capacity. equipment or components on R−410A refrigerant
equipment.
3. Run refrigerant tubes as directly as possible by
avoiding unnecessary turns and bends. Specifications for this unit in residential new construction
4. Leave some slack between structure and unit to market require the outdoor unit, indoor unit, refrigerant tubing
absorb vibration. sets, metering device, and filter drier listed in presale
literature. There can be no deviation.
5. When passing refrigerant tubes through the wall, seal
Check Equipment and Job Site
opening with RTV or other pliable silicon−based caulk.
(See Fig. 1.) Unpack Unit
Move to final location. Remove carton taking care not to
6. Avoid direct tubing contact with water pipes, duct work, damage unit.
floor joists, wall studs, floors, and walls.
Inspect Equipment
7. Do not suspend refrigerant tubing from joists and studs File claim with shipping company prior to installation if
with a rigid wire or strap which comes in direct contact shipment is damaged or incomplete. Locate unit rating plate
with tubing.(See Fig. 1.) on unit corner panel. It contains information needed to
8. Ensure that tubing insulation is pliable and completely properly install unit. Check rating plate to be sure unit
surrounds vapor tube. matches job specifications.
Install on a Solid, Level Mounting Pad
9. When necessary, use hanger straps which are 1 in.
(25.4 mm) wide and conform to shape of tubing If conditions or local codes require the unit be attached to
insulation. (See Fig. 1.) pad, tie down bolts should be used and fastened through
knockouts provided in unit base pan. Refer to unit mounting
10. Isolate hanger straps from insulation by using metal pattern in Fig. 2 to determine base pan size and knockout
sleeves bent to conform to shape of insulation. hole location.

Specifications subject to change without notice.


2 421 01 5104 03
Downloaded from www.Manualslib.com manuals search engine
INSTALLATION INSTRUCTIONS R−410A Split System Air Conditioner
For hurricane tie downs − contact your local distributor for Make Piping Connections
details and PE (Professional Certification), if required by local
authorities.
On rooftop applications, mount on level platform or frame.
! WARNING
Place unit above a load−bearing wall and isolate unit and PERSONAL INJURY AND ENVIRONMENTAL
tubing set from structure. Arrange supporting members to HAZARD
adequately support unit and minimize transmission of Failure to follow this warning could result in personal
vibration to building. Consult local codes governing rooftop injury or death.
applications. Relieve pressure and recover all refrigerant before system
Roof mounted units exposed to winds may require wind repair or final unit disposal.
baffles. Consult the Low−Ambient pressure switch installation Use all service ports and open all flow−control devices,
instructions for wind baffle construction. including solenoid valves.
NOTE: Unit must be level to within ±2_ (±3/8 in./ft..) per
compressor manufacturer specifications.
Clearance Requirements ! CAUTION
UNIT DAMAGE HAZARD
When installing, allow sufficient space for airflow clearance,
wiring, refrigerant piping, and service. Allow 30 in. (762 mm) Failure to follow this caution may result in equipment
clearance to service end of unit and 48 in. (1219.2 mm) damage or improper operation.
above unit. For proper airflow, a 6 in. (152.4 mm) clearance Do not leave system open to atmosphere any longer than
on one side of unit and 12 in. (304.8 mm) on all remaining minimum required for installation. POE oil in compressor is
sides must be maintained. Maintain a distance of 24 in. extremely susceptible to moisture absorption. Always keep
(609.6 mm) between units. Position so water, snow, or ice ends of tubing sealed during installation.
from roof or eaves cannot fall directly on unit. If ANY refrigerant tubing is buried, provide a 6 in. (152.4
mm) vertical rise at service valve. Refrigerant tubing
Figure 2 Tie Down Knockouts lengths up to 36 in. (914.4 mm) may be buried without
further special consideration. Do not bury lines more than
3/8-in. (9.53 mm) Dia.
36 in. (914.4 mm).
Tiedown Knockouts in
Basepan(2) Places
Outdoor units may be connected to indoor section using
accessory tubing package or field−supplied refrigerant grade
tubing of correct size and condition. For tubing requirements
beyond 80 ft/24.38 m, substantial capacity and performance
losses can occur. Following the recommendations in the
Long Line Applications Guideline for Split−System Air
Conditioners and Heat Pumps will reduce these losses. Refer
View From Top to Table 1 for accessory requirements. Refer to Table 2 for
field tubing diameters.

TIEDOWN KNOCKOUT LOCATIONS in. (mm)


There are no buried−line applications greater than 36 in.
UNIT BASE PAN
Dimension A B C (914.4 mm).
31–1/2 X 31–1/2 9–1/8 (231.8) 6–9/16 (166.7) 24–11/16 (627.1) If refrigerant tubes or indoor coil are exposed to atmosphere,
35 X 35 9–1/8 (231.8) 6–9/16 (166.7) 28–7/16 (722.3) they must be evacuated to 500 microns to eliminate
contamination and moisture in the system.
On rooftop applications, locate unit at least 6 in. (152.4 mm)
above roof surface. Outdoor Unit Connected to Factory Approved
Indoor Unit
Operating Ambient
Outdoor unit contains correct system refrigerant charge for
The minimum outdoor operating ambient in cooling mode is operation with factory approved AHRI rated indoor unit when
55°F (12.78_C) without low ambient cooling enabled, and the connected by 15 ft. (4.57 m) of field −supplied or
maximum outdoor operating ambient in cooling mode is factory−accessory tubing, and factory supplied filter drier.
125°F (51.67_C). Check refrigerant charge for maximum efficiency.
Table 1 − Accessory Usage
REQUIRED FOR LOW−AMBIENT
COOLING APPLICATIONS REQUIRED FOR LONG LINE
Accessory (Below 555F / 12.85C) APPLICATIONS* (Over 80 ft. / 24.38 m)
Crankcase Heater Yes Yes
Compressor Start Assist Capacitor and Relay Yes Yes
Evaporator Freeze Thermostat Yes No
Liquid Line Solenoid Valve No See Long Line Applications Guideline
Low−ambient Pressure Switch Yes No
Support Feet Recommended No
Thermal Expansion Valve (TXV)
Yes Yes
Hard Shutoff
Winter Start Control Yes No
* For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 20 ft. (6.09 m) vertical differential, refer to Long Line Applications Guideline.
Specifications subject to change without notice.
421 01 5104 03 3
Downloaded from www.Manualslib.com manuals search engine
INSTALLATION INSTRUCTIONS R−410A Split System Air Conditioner
Table 2 − Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters (In.)
RATED VAPOR
LIQUID up to 80 ft. (24.38 m)*
Connection and Tube Connection Rated Tube
UNIT SIZE Diameter Diameter Diameter
18, 24, 30, 3/8 3/4 3/4
36, 42, 48 3/8 7/8 7/8
60 3/8 7/8 1−1/8
* Units are rated with 25 ft. (7.6 m) of lineset. See Specification sheet for performance data when using different size and length linesets.
Notes:
1. Do not apply capillary tube or fixed orifice indoor coils to these units.
2. For Tubing Set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 35 ft. (10.7 m) vertical differential 250 ft. (76.2 m) Total Equivalent Length),
refer to the Long Line Applications Guideline.
Install Liquid Line Filter Drier Indoor Evacuate Refrigerant Tubing and Indoor Coil

! CAUTION ! CAUTION
UNIT DAMAGE HAZARD UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment Failure to follow this caution may result in equipment
damage or improper operation. damage or improper operation.
Installation of filter drier in liquid line is required. Never use the system compressor as a vacuum pump.
Filter drier must be wrapped in a heat−sinking material
such as a wet cloth while brazing. Refrigerant tubes and indoor coil should be evacuated using
the recommended deep vacuum method of 500 microns. An
Refer to Fig. 3 and install filter drier as follows: alternate triple evacuation method may be used. See triple
1. Braze 5 in. (127 mm) liquid tube to the indoor coil. evacuation method in Service Manual.
2. Wrap filter drier with damp cloth. IMPORTANT: Always break a vacuum with dry nitrogen.
3. Braze filter drier to above 5 in. (127 mm) liquid tube. Deep Vacuum Method
Flow arrow must point towards indoor coil. The deep vacuum method requires a vacuum pump capable
4. Connect and braze liquid refrigerant tube to the filter of pulling a vacuum of 500 microns and a vacuum gage
drier. capable of accurately measuring this vacuum depth. The
deep vacuum method is the most positive way of assuring a
Figure 3 Liquid Line Filter Drier system is free of air and liquid water. (See Fig. 4)

Figure 4 Deep Vacuum Graph

5000
4500
4000
3500 LEAK IN
MICRONS

SYSTEM
3000
2500
2000
1500 VACUUM TIGHT
Refrigerant Tubing Connection Outdoor TOO WET
Connect vapor tube to fitting on outdoor unit vapor service 1000
TIGHT
valves (see Table 2.) Connect and braze the 3/8” coupling 500 DRY SYSTEM
(provided with the filter drier) to the liquid service valve and
connect and braze the liquid tubing to the other end of this 0 1 2 3 4 5 6 7 A95424

coupling. Use refrigerant grade tubing. MINUTES


Sweat Connection Final Tubing Check
IMPORTANT: Check to be certain factory tubing on both
! CAUTION indoor and outdoor unit has not shifted during shipment.
Ensure tubes are not rubbing against each other or any
UNIT DAMAGE HAZARD sheet metal. Pay close attention to feeder tubes, making sure
Failure to follow this caution may result in equipment wire ties on feeder tubes are secure and tight.
damage or improper operation. Make Electrical Connections
Service valves must be wrapped in a heat−sinking
material such as a wet cloth. ! WARNING
Service valves are closed from factory and ready for brazing. ELECTRICAL SHOCK HAZARD
After wrapping service valve with a wet cloth, braze sweat Failure to follow this warning could result in personal
connections using industry accepted methods and materials. injury or death.
Consult local code requirements. Refrigerant tubing and
Do not supply power to unit with compressor terminal box
indoor coil are now ready for leak testing. This check should
cover removed.
include all field and factory joints.
Specifications subject to change without notice.
4 421 01 5104 03
Downloaded from www.Manualslib.com manuals search engine
INSTALLATION INSTRUCTIONS R−410A Split System Air Conditioner
Be sure field wiring complies with local and national fire, All wiring must be NEC Class 1 and must be separated from
safety, and electrical codes, and voltage to system is within incoming power leads.
limits shown on unit rating plate. Contact local power
company for correction of improper voltage. See unit rating Use furnace transformer, fan coil transformer, or accessory
plate for recommended circuit protection device. transformer for control power, 24−v/40−va minimum.

NOTE: Operation of unit on improper line voltage constitutes NOTE: Use of available 24−v accessories may exceed the
abuse and could affect unit reliability. See unit rating plate. minimum 40−va power requirement. Determine total
Do not install unit in system where voltage may fluctuate transformer load and increase the transformer capacity or
above or below permissible limits. split the load with an accessory transformer as required.

NOTE: Use copper wire only between disconnect switch and Final Wiring Check
unit. IMPORTANT: Check factory wiring and field wire
connections to ensure terminations are secured properly.
NOTE: Install branch circuit disconnect of adequate size per
Check wire routing to ensure wires are not in contact with
NEC to handle unit starting current. Locate disconnect within
tubing, sheet metal, etc.
sight from and readily accessible from unit, per Section
440−14 of NEC. Compressor Crankcase Heater
Route Ground and Power Wires When equipped with a crankcase heater, furnish power to
heater a minimum of 24 hr before starting unit. To furnish
Remove access panel to gain access to unit wiring. Extend
power to heater only, set thermostat to OFF and close
wires from disconnect through power wiring hole provided
electrical disconnect to outdoor unit.
and into unit control box.
A crankcase heater is required for low−ambient cooling or if
refrigerant tubing is longer than 80 ft. (24.38 m). Refer to the
Long Line Applications Guideline − Residential Split−System
! WARNING Air Conditioners and Heat Pumps Using R−410A Refrigerant.

ELECTRICAL SHOCK HAZARD Install Electrical Accessories


Failure to follow this warning could result in personal Refer to the individual instructions packaged with kits or
injury or death. accessories when installing.
The unit cabinet must have an uninterrupted or
unbroken ground to minimize personal injury if an Check OAT Thermistor and OCT Thermistor
electrical fault should occur. The ground may consist Attachments
of electrical wire or metal conduit when installed in
accordance with existing electrical codes. Outdoor Air Temperature (OAT) Thermistor is factory installed
by inserting the nibs on either sides of the thermistor body
through a keyhole in the bottom shelf of the control box and
locking it in place by turning it 90 degrees, such that the
Connect Ground and Power Wires spherical end of a nib faces the front of the control box.
Connect ground wire to ground connection in control box for Check to make sure the OAT is locked in place. See Fig. 6.
safety. Connect power wiring to contactor as shown in Fig. 5.

Figure 6 Outdoor Air Thermistor (OAT) Attachment


Figure 5 Line Power Connections
OAT Thermistor must be locked in place
DISCONNECT with spherical nib end facing towards
PER N. E. C. AND/OR
LOCAL CODES the front of the control box
CONTACTOR
FIELD POWER
WIRING
DX+ DX- C R

FIELD GROUND
WIRING
GROUND
LUG

Connect Control Wiring


Route 24−v control wires through control wiring grommet and
connect leads to control wiring. (See Fig. 10 & Fig. 11)
The Outdoor Coil Temperature (OCT) Thermistor is factory
Use No. 18 AWG color−coded, insulated (35_C minimum) installed on the liquid tube between the coil assembly and the
wire. If thermostat is located more than 100 ft. (30.48 m) liquid service valve. See Fig. 7.
from unit, as measured along the control voltage wires, use
No. 16 AWG color−coded, insulated wire to avoid excessive Check to make sure the thermistor is securely attached on
voltage drop. the liquid tube with the clip as shown in Fig. 7.
Specifications subject to change without notice.
421 01 5104 03 5
Downloaded from www.Manualslib.com manuals search engine
INSTALLATION INSTRUCTIONS R−410A Split System Air Conditioner
4. Set room thermostat at desired temperature. Be sure
Figure 7 Outdoor Coil Thermistor (OAT) Attachment
set point is below indoor ambient temperature.
5. Set room thermostat to COOL and fan control to ON or
OCT Thermistor must be
AUTO mode, as desired. Operate unit for 15 minutes.
secured tight on the liquid tube. Check system refrigerant charge.
Check Charge
Factory charge amount and desired subcooling are shown
on unit rating plate. Charging method is shown on information
plate inside unit. To properly check or adjust charge,
conditions must be favorable for subcooling charging.
Favorable conditions exist when the outdoor temperature is
between 70_F and 100_F (21.11_C and 37.78_C), and the
indoor temperature is between 70_F and 80_F (21.11_C and
26.67_C). Follow the procedure below:
Unit is factory charged for 15ft (4.57 m) of lineset. Adjust
charge by adding or removing 0.6 oz/ft of 3/8 liquid line
above or below 15ft (4.57 m) respectively.
For standard refrigerant line lengths (80 ft/24.38 m or less),
Start−Up allow system to operate in cooling mode at least 15 minutes.
When operating with the Observer Wall Control in
! CAUTION communicating mode, make sure that indoor airflow is set to
“efficiency” during charging. If conditions are favorable, check
UNIT OPERATION AND SAFETY HAZARD system charge by subcooling method. If any adjustment is
necessary, adjust charge slowly and allow system to operate
Failure to follow this caution may result in minor personal
for 15 minutes to stabilize before declaring a properly
injury, equipment damage or improper operation.
charged system.
To prevent compressor damage or personal injury, If the indoor temperature is above 80_F (26.67_C), and the
observe the following: outdoor temperature is in the favorable range, adjust system
S Do not overcharge system with refrigerant. charge by weight based on line length and allow the indoor
S Do not operate unit in a vacuum or at negative temperature to drop to 80_F (26.67_C) before attempting to
pressure. check system charge by subcooling method as described
above.
S Do not disable low pressure switch in scroll compressor
If the indoor temperature is below 70_F (21.11_C), or the
applications. outdoor temperature is not in the favorable range, adjust
S Dome temperatures may be hot. charge for line set length above or below 15ft (4.57 m) only.
Charge level should then be appropriate for the system to
achieve rated capacity. The charge level could then be

! CAUTION checked at another time when the both indoor and outdoor
temperatures are in a more favorable range.
NOTE: If line length is beyond 80 ft (24.38 m) or greater than
PERSONAL INJURY HAZARD
20 ft (6.10 m) vertical separation, See Long Line Applications
Failure to follow this caution may result in personal injury. Guideline for special charging requirements.
Wear safety glasses, protective clothing, and gloves Major Components
when handling refrigerant and observe the following: Control Board
S Front seating service valves are equipped with The AC control board controls the following functions:
Schrader valves. S Compressor contactor operation
S Outdoor fan motor operation

CAUTION
S Compressor external protection
! S Pressure switch monitoring
ENVIRONMENTAL HAZARD S Time Delays
Field Connections
Failure to follow this caution may result in environmental
damage. When using communicating control, 4 field wires are required
to be connected to the factory wires already wired to the
Federal regulations require that you do not vent refrigerant
DX+DX−C R terminal (see Fig. 10). Unit as provided by
to the atmosphere. Recover during system repair or final
manufacturer is set up for communicating control.
unit disposal.
When used with a standard non−communicating thermostat,
Follow these steps to properly start up the it is recommended to use 3 thermostat control wires to be
system: connected to R, Y and C. When using 3 wires, all diagnostic
a n d t im e d e la y f e a tu re s a re e n a b le d ( S e e F ig . 11 ).
1. After system is evacuated, fully open liquid and vapor Disconnect factory provided wires from DX+, DX−, C & R
service valves. terminals. Using factory provided wires, connect to R, C, and
2. Unit is shipped with valve stem(s) front seated (closed) Y on the control board for 3 wire thermostat control. Connect
and caps installed. field 24V wires to factory provided wires now connected to R,
Replace stem caps after system is opened to C, and Y and cap both sides or remove unused factory
refrigerant flow. Replace caps finger−tight and tighten provided wires.
with wrench an additional 1/12 turn When only 2 thermostat control wires are available, units will
3. Close electrical disconnects to energize system. function, but some control features are lost. (See Fig. 12).
Specifications subject to change without notice.
6 421 01 5104 03
Downloaded from www.Manualslib.com manuals search engine
INSTALLATION INSTRUCTIONS R−410A Split System Air Conditioner
With only 2 wires connected, the circuit board will be received within 2 minutes, the LED will be turned OFF until
powered down whenever there is no call for cooling, and the the next valid communication.
following will result: Amber Status Light
S Compressor time delay is reduced from 5 minutes to 10 An amber colored STATUS light is used to display the
seconds o p e ra tio n m o d e a n d f a u lt c o d e s a s s p e c ifie d i n t h e
S When the thermostat is not calling for cooling, the amber troubleshooting section. See Table 3 for codes and
status light will be off, and no diagnostics codes will be definitions.
available NOTE: Only one fault code will be displayed on the outdoor
S All system counters will be reset on each new call for unit control board (the most recent, with the highest priority).
cooling
Crankcase Heater Operation
Disconnect factory provided wires from DX+, DX−, C and R
terminals. Using factory provided wires, connect to C and Y The crankcase heater (when applicable) is energized during
on the control board for 2 wire thermostat control. A field the off cycle below 65_F (37.78_C)
installed jumper wire is also required between R and Y (See Outdoor Fan motor Operation
Fig. 12). Connect field 24V wires to factory provided wires The outdoor unit control energizes outdoor fan any time the
now connected to C and Y and cap both sides or remove compressor is operating. The outdoor fan remains energized
unused factory provided wires. for 15 minutes if a pressure switch or compressor thermal
Compressor Internal Relief protector should open. Outdoor fan motor will continue to
operate for one minute after the compressor shuts off when
The compressor is protected by an Internal Pressure Relief
the outdoor ambient is greater than or equal to 100 _F
(IPR) which relieves discharge gas into the compressor shell
(37.78_C).
when differential between suction and discharge pressure
exceeds 550−625 psi. The compressor is also protected by Time Delays
an internal overload attached to motor windings. The unit time delays include:
GENERAL SEQUENCE OF OPERATION S Five minute time delay to start cooling operation when
there is a call from the thermostat or communicating wall
STANDARD THERMOSTAT control.
Turn on power to indoor and outdoor units. Transformer is S When operating the unit with 2 wires, this delay is
energized. shortened to 10 seconds.
On a call for cooling, thermostat makes circuits R−Y and S Five minute compressor recycle delay on return from a
R−G. Circuit R−Y energizes contactor, starting outdoor fan brown out condition
motor and compressor circuit. R−G energizes indoor unit S Two minute time delay to return to standby operation from
blower relay, starting indoor blower motor on high speed. last valid communications (with communicating only)
S One minute time delay of outdoor fan at termination of
NOTE: To achieve the rated system performance, the indoor
cooling mode when outdoor ambient is greater than or
unit or the thermostat must be equipped with a time delay
equal to 100_F (37.78_C).
relay circuit.
Utility Interface
When thermostat is satisfied, its contacts open,
With Non−Communicating Thermostats
de−energizing contactor and blower relay. Compressor and
motors stop. If indoor unit is equipped with a time−delay relay Utility curtailment will only work when the unit is operating
circuit, the indoor blower will run an additional 90 sec to with a non−communicating thermostat.
increase system efficiency. When the utility curtailment interface is applied with a
non−communicating thermostat, the utility relay should be
CONTROL FUNCTIONS wired in series with the Y input.
AND SEQUENCE OF OPERATION Low Ambient Cooling
The outdoor unit control system has special functions. The When this unit is required to operate below 55_F (12.78_C) to
following is an overview of the control functions. a minimum of 0 _F (−17.78 _C) outdoor temperature,
SEQUENCE OF OPERATION provisions must be made for low ambient operation.
Cooling Operation Low ambient applications require the installation of
accessory kits:
This product utilizes either a standard indoor thermostat or
S Low Ambient Pressure Switch Kit
Observer t Communicating Wall Control. With a call for
S Evaporator Freeze Thermostat
cooling, the outdoor fan and compressor are energized.
S Hard Start kit
When the cooling demand is satisfied, the compressor and
fan will shut off. S Crankcase Heater
Support feet are recommended for low ambient cooling. See
NOTE: The outdoor fan motor will continue to operate for one P ro d u c t S p e c ific a tio n s h e e t f o r k it p a rt n u m b e rs o n
minute after compressor shuts off, when the outdoor ambient appropriate unit size and series unit.
is greater than or equal to 100_F (37.78_C).
For low ambient cooling with the Observer
Communication and Status Function Lights Communicating Wall Control the cooling lockout must be
Green Communications (COMM) Light (Communicating set to “Off” in the Wall Control setup.
Control only): Liquid Line Solenoid
A green LED (COMM light) on the outdoor board indicates When operating in communicating mode the standard
successful communication with the other system products. thermostat terminals will not function. A terminal on the
The green LED will remain OFF until communications is non−communicating thermostat bus labeled “LS” on the AC
established. Once a valid command is received, the green control board is provided for wiring liquid line solenoids when
LED will turn ON continuously. If no communication is in communicating mode. For operation in communicating
Specifications subject to change without notice.
421 01 5104 03 7
Downloaded from www.Manualslib.com manuals search engine
INSTALLATION INSTRUCTIONS R−410A Split System Air Conditioner
mode wire solenoid valve kit NASA401LS across LS and C contactor every 15 minutes. If the thermal protector closes,
terminals . For operation in non−communicating mode wire (at the next 15 minute interval check), the unit will resume
solenoid valve kit NASA401LS across C and Y terminals. operation.
TROUBLESHOOTING If the thermal cutout trips for three consecutive cycles, then
unit operation is locked out for 4 hours and the appropriate
SYSTEMS COMMUNICATION FAILURE fault code (See Table 3) is displayed.
If communication between outdoor unit, control board, and CONTACTOR SHORTED DETECTION
indoor wall control has failed, the control will flash the If there is compressor voltage sensed when there is no
appropriate fault code. (See table 3) Check the wiring to the demand for compressor operation, the contactor may be
wall control, indoor and outdoor units. stuck closed. The control will flash the appropriate fault
PRESSURE SWITCH PROTECTION code. Check the contactor and control box wiring.
The outdoor unit is equipped with high− and low−pressure NO 230V AT COMPRESSOR
switches. If the control senses the opening of a high or If the compressor voltage is not sensed when the
low−pressure switch, it will de−energize the compressor compressor should be starting, the contactor may be stuck
contactor, keep the outdoor fan operating for 15 minutes and open or the unit disconnect or circuit breaker may be open.
display the appropriate fault code. (See table 3) The control will flash the appropriate fault code. Check the
After a 15 minute delay, if there is still a call for cooling, and contactor, unit disconnect or circuit breaker and control box
the LPS or HPS is reset, the compressor contactor is wiring.
energized. If the LPS or HPS has not closed after a 15 TEMPERATURE THERMISTORS
minute delay, the outdoor fan is turned off. If the open switch Thermistors are electronic devices which sense temperature.
closes anytime after the 15−minute delay, then the unit will As the temperature increases, the resistance decreases.
resume operation with a call for cooling. Thermistors are used to sense outdoor air (OAT) and coil
If the LPS or HPS trips for five consecutive cycles, then unit temperature (OCT).
operation is locked out for 4 hours and the appropriate fault If the outdoor air or coil thermistor should fail, the control will
code (See table 3) is displayed. flash the appropriate fault code. (See table 3).
In the event of a high−pressure switch trip or high−pressure IMPORTANT: The outdoor air thermistor and coil thermistor
lockout, check the refrigerant charge, outdoor fan operation are factory mounted in the correct locations. Do not re−locate
and outdoor coil for airflow restrictions. thermistor sensors.
In the event of a low−pressure switch trip or low−pressure THERMISTOR SENSOR COMPARISON
lockout, check the refrigerant charge and indoor airflow. The control continuously monitors and compares the outdoor
CONTROL FAULT air temperature sensor and outdoor coil temperature sensor
If the outdoor unit control board has failed, the control will to ensure proper operating conditions. The comparison is, if
flash the appropriate fault code. (See table 3) The control the outdoor air sensor indicates ≥10_F (≥ −12.22_C) warmer
board should be replaced. than the coil sensor (or) the outdoor air sensor indicates
≥20_F (≥ −6.67_C) cooler than the coil sensor, the sensors
24V BROWN OUT PROTECTION are out of range.
If the control voltage is less than 15.5volts for at least 4 If the sensors are out of range, the control will flash the
seconds, the compressor contactor and fan relay are appropriate fault code. (See Table 3).
de−energized. Compressor and fan operation are not FAILED THERMISTOR DEFAULT OPERATION
allowed until control voltage is a minimum of 17.5volts. The
control will flash the appropriate fault code. (See table 3) Factory defaults have been provided in the event of failure of
Verify the control voltage is in the allowable range of outdoor air thermistor and/or coil thermistor.
18−30volts. Thermistor Curve: The resistance vs. temperature chart
shown in Figure 8 enables the technician to check the
COMPRESSOR VOLTAGE SENSING
outdoor air and outdoor coil thermistors for proper resistance.
The input terminals labeled VR and VS on the control board Unplug the thermistor assembly from the circuit board and
(see Fig. 9) are used to detect compressor voltage status, measure resistance across each thermistor. For example, if
and alert the user of potential problems. The control the outdoor temperature is 60_F (15.56_C), the resistance
continuously monitors the high voltage on the run capacitor reading across the outdoor air thermistor should be around
of the compressor motor. Voltage should be present any time 16,000 Ohms.
the compressor contactor is energized, and voltage should
STATUS CODES
not be present when the contactor is de−energized.
Table 3 shows the status codes flashed by the amber status
COMPRESSOR THERMAL CUTOUT OR LOSS OF light. Most system problems can be diagnosed by reading
230V POWER the status code as flashed by the amber status light on the
If the control senses the compressor voltage after start−up, control board.
and is then absent for 10 consecutive seconds while cooling The codes are flashed by a series of short and long flashes
demand exists, it will de−energize the compressor contactor, of the status light. The short flashes indicate the first digit in
keep the outdoor fan operating for 15 minutes (if 230v power the status code, followed by long flashes indicating the
present) and display the appropriate fault code. (See table 3) second digit of the error code. The short flash is 0.25 second
Possible causes are compressor internal overload trip or loss ON and the long flash is 1.0 second ON. Time between
of high voltage (230V) to compressor without loss of control flashes is 0.25 second. Time between short flash and first
voltage. long flash is 1.0 second. Time between code repeating is 2.5
After a 15 minute delay, if there is still a call for cooling, the seconds with LED OFF.
compressor contactor is energized. If the thermal protector Count the number of short and long flashes to determine the
has not re−set, the outdoor fan is turned off. If the call for appropriate flash code. Table 3 gives possible causes and
cooling continues, the control will energize the compressor actions related to each error.
Specifications subject to change without notice.
8 421 01 5104 03
Downloaded from www.Manualslib.com manuals search engine
INSTALLATION INSTRUCTIONS R−410A Split System Air Conditioner
Example: 3 short flashes followed by 2 long flashes indicates
a 32 code. Table 3 shows this to be low pressure switch
open.

Table 3 − Status Codes


AMBER LED
OPERATION FAULT Possible Cause and Action
FLASH CODE
Standby – no call
None On solid, no flash Normal operation − with communicating Control
for unit operation
Standby – no call Normal operation − No call for cooling with 2−wire connection or indoor unit not pow-
None Off
for unit operation ered.
Cooling Operation None 1, pause Normal operation
System Communications Communication with wall control lost. Check wiring to wall control, indoor and outdoor
16
Failure units
High Pressure High pressure switch trip. Check refrigerant charge, outdoor fan operation and coils
31
Switch Open for airflow restrictions.
Low Pressure
32 Low pressure switch trip. Check refrigerant charge and indoor air flow
Switch Open
Outdoor unit control board has failed. Control board needs to be replaced.
Control Fault 45

The control voltage is less than 15.5v for at least 4 seconds. Compressor and fan
Brown Out
46 operation not allowed until control voltage is a minimum of 17.5v. Verify control volt-
(24 v)
age.
Outdoor Air Temp Sensor
53 Outdoor air sensor not reading or out of range. Ohm out sensor and check wiring
Fault
Outdoor Coil Sensor Fault 55 Coil sensor not reading or out of range. Ohm out sensor and check wiring
Thermistors out Improper relationship between coil sensor and outdoor air sensor. Ohm out sensors
56
of range and check wiring.
Compressor voltage sensed after start−up, then absent for 10 consecutive seconds
while cooling demand exists. Possible causes are internal compressor overload trip or
Thermal Cutout 72 loss of high voltage to compressor without loss of control voltage. The control will
continue fan operation and wait 15 minutes to attempt a restart. Fault will clear when
restart is successful, or low voltage power is cycled.

Compressor voltage sensed when no demand for compressor operation exists. Con-
Contactor Shorted 73
tactor may be stuck closed or there is a wiring error.

No 230V at Compressor voltage not sensed when compressor should be starting. Disconnect may
74
Compressor be open or contactor may be stuck open or there is a wiring error.
Thermal cutout occurs in three consecutive cycles. Unit operation locked out for 4
Thermal Lockout 82
hours or until 24v power recycled.
Low pressure switch trip has occurred during 3 consecutive cycles. Unit operation
Low Pressure Lockout 83
locked out for 4 hours or until 24v power recycled.
High Pressure High pressure switch trip has occurred during 3 consecutive cycles. Unit operation
84
Lockout locked out for 4 hours or until 24v power recycled.

Figure 8 Resistance vs Temperature Chart

THERMISTOR CURVE
90
80
RESISTANCE (KOHMS)

70
60
50

40
30
20

10
0
0 20 40 60 80 100 120
(-17.77) (-6.67) (4.44) (15.56) (26.67) (37.78) (48.89)
TEMPERATURE °F (°C)

Specifications subject to change without notice.


421 01 5104 03 9
Downloaded from www.Manualslib.com manuals search engine
INSTALLATION INSTRUCTIONS R−410A Split System Air Conditioner

Figure 9 Single Stage Control Board

Specifications subject to change without notice.


10 421 01 5104 03
Downloaded from www.Manualslib.com manuals search engine
INSTALLATION INSTRUCTIONS R−410A Split System Air Conditioner

Observer Communicating Wall Control Four−Wire Connection Wiring Diagrams


Figure 10
(See Thermostat Installation Instructions for specific unit combinations)

Variable Speed
Wall Control Furnace/Fan Coil Outdoor

Green Green
DX+ DX+ DX+
Yellow Yellow
DX− DX− DX−
White White
C C C
Red Red
R R R
S1 Optional Remote
Room Sensor Humidifier
S2 HUM LEGEND
Connection

COM 24V FACTORY WIRING


24V FIELD WIRING

FIELD SPLICE CONNECTION

Non−Communicating Standard Thermostat 3−Wire 24V Circuit Connections


Figure 11 (See Thermostat Installation Instructions for
Specific Unit combinations)

LEGEND
24−V FACTORY WIRING

24−V FIELD WIRING

FIELD SPLICE CONNECTION

! CAUTION
ELECTRICAL OPERATION HAZARD
Failure to follow this caution may result in
equipment damage or improper operation.
A minimum of three wire thermostat wiring is
required for the system to operate.

Specifications subject to change without notice.


421 01 5104 03 11
Downloaded from www.Manualslib.com manuals search engine
INSTALLATION INSTRUCTIONS R−410A Split System Air Conditioner

Non−Communicating Standard Thermostat


Figure 12
2−Wire 24V Circuit Connections

TPPICAL FURNACE
OR
A/C THERMOSTAT FAN COIL AIR CONDITIONER

24VAC HOT R R R

24VAC COM C C C

HEAT STAGE 1 W/W1 W

HEAT STAGE 2 Y/Y2 Y Y

INDOOR FAN G G

FIEL INSTALLED JUMPER WIRE


LEGEND

24V FACTORY WIRING


24V FIELD WIRING

FIELD SPLICE CONNECTION

NOTE: Wiring must conform to NEC or local codes.


Figure 13 Non−Communicating Indoor with Observer Communicating Wall Control

Wall
Control NAXA00101DB
Green
DX+ DX+
Red
R R
White
C C
Yellow
DX- DX-
Communicating
Outdoor

C C C
R R R
W2 W2
Y/Y2 Y Y
G G
O

Non-Communicating 
Indoor
NOTE: This installation requires the daughter board  OAT
accessory, NAXA00101DB. OAT Sensor
NOTE: This installation does not allow for communicating
feature functionality.

Specifications subject to change without notice.


12 421 01 5104 03
Downloaded from www.Manualslib.com manuals search engine
INSTALLATION INSTRUCTIONS R−410A Split System Air Conditioner

R−410A QUICK REFERENCE GUIDE

• R−410A refrigerant operates at 50% − 70% higher pressures than R−22. Be sure that servicing equipment and
replacement components are designed to operate with R−410A.

• R−410A refrigerant cylinders are rose colored.

• Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.

• R−410A systems should be charged with liquid refrigerant. Use a commercial type metering device in the
manifold hose.

• Manifold sets should be 750 psig high−side and 200 psig low−side with 520 psig low−side retard.

• Use hoses with 750 psig service pressure rating.

• Leak detectors should be designed to detect HFC refrigerant.

• R−410A, as with other HFC refrigerants, is only compatible with POE oils.

• Vacuum pumps will not remove moisture from oil.

• Do not use liquid line filter−driers with rated working pressures less than 600 psig.

• Do not install a suction line filter−drier in liquid line.

• POE oils absorb moisture rapidly. Do not expose oil to atmosphere.

• POE oils may cause damage to certain plastics and roofing materials.

• Wrap all filter−driers and service valves with wet cloth when brazing.

• A liquid line filter−drier is required on every unit.

• Do not use with an R−22 TXV.

• If indoor unit is equipped with an R−22 TXV, it must be changed to an R−410A TXV.

• Never open system to atmosphere while it is under a vacuum.

• When system must be opened for service, break vacuum with dry nitrogen and replace all filter−driers.

• Do not vent R−410A into the atmosphere.

• Do not use capillary tube indoor coils.

• Observe all WARNINGS, CAUTIONS, NOTES, and bold text.

Specifications subject to change without notice.


421 01 5104 03 13
Downloaded from www.Manualslib.com manuals search engine
INSTALLATION INSTRUCTIONS R−410A Split System Air Conditioner

Specifications subject to change without notice.


14 421 01 5104 03
Copyright 2015 International Comfort Products
Downloaded from www.Manualslib.com manuals search engine Lewisburg, TN 37091 USA

You might also like