SLC Wiring Manual
SLC Wiring Manual
SLC Wiring Manual
SLC
Wiring Manual
This system meets NFPA requirements for operation at 0-49º C/32- This system contains static-sensitive components. Always
120º F and at a relative humidity 93% ± 2% RH (non-condensing) at ground yourself with a proper wrist strap before handling any circuits
32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's so that static charges are removed from the body. Use static sup-
standby batteries and the electronic components may be adversely pressive packaging to protect electronic assemblies removed from
affected by extreme temperature ranges and humidity. Therefore, it the unit.
is recommended that this system and its peripherals be installed in Units with a touchscreen display should be cleaned with a dry,
an environment with a normal room temperature of 15-27º C/60-80º clean, lint free/microfiber cloth. If additional cleaning is required,
F. apply a small amount of Isopropyl alcohol to the cloth and wipe
Verify that wire sizes are adequate for all initiating and indicating clean. Do not use detergents, solvents, or water for cleaning. Do not
device loops. Most devices cannot tolerate more than a 10% I.R. spray liquid directly onto the display.
drop from the specified device voltage. Follow the instructions in the installation, operating, and program-
ming manuals. These instructions must be followed to avoid damage
to the control panel and associated equipment. FACP operation and
reliability depend upon proper installation.
Precau-D2-11-2017
FCC Warning
WARNING: This equipment generates, uses, and can Canadian Requirements
radiate radio frequency energy and if not installed and This digital apparatus does not exceed the Class A limits
used in accordance with the instruction manual may for radiation noise emissions from digital apparatus set
cause interference to radio communications. It has been out in the Radio Interference Regulations of the Cana-
tested and found to comply with the limits for class A dian Department of Communications.
computing devices pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable Le present appareil numerique n'emet pas de bruits radi-
protection against such interference when devices are oelectriques depassant les limites applicables aux appa-
operated in a commercial environment. Operation of this reils numeriques de la classe A prescrites dans le
equipment in a residential area is likely to cause interfer- Reglement sur le brouillage radioelectrique edicte par le
ence, in which case the user will be required to correct ministere des Communications du Canada.
the interference at his or her own expense.
LiteSpeed™ and Lite-Connect™ are trademarks; and Fire-Lite® Alarms, Honeywell®, and SWIFT® are registered trademarks of Honeywell International Inc.
Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. Chrome™ and Google™ are trademarks of Google Inc. Firefox® is a registered
trademark of The Mozilla Foundation.
©2021 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online
Help or printed manuals, you can email us.
Please include the following information:
• Product name and version number (if applicable)
• Printed manual or online Help
• Topic Title (for online Help)
• Page number (for printed manual)
• Brief description of content you think should be improved or corrected
• Your suggestion for how to correct/improve documentation
Send email messages to:
[email protected]
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical
Services.
NOTE: Any reference in this manual to the MS-9200, MS-9200UD, MS-9200UDLS, MS-9600, MS-9600LS, MS-9600UDLS, MS-9050UD,
ES-50X, or ES-200X includes the MS-9200E, MS-9200UDE, MS-9200UDLSE, MS-9200UDLSC, MS-9600E, MS-9600LSE, MS-9600LSC,
MS-9600UDLSE, MS-9050UDC, MS-9050UDE, ES-50XC, or ES-200XC respectively unless otherwise specified.
Additional information about the specific control panel and the modules and detectors referenced in this document can be found in the
respective installation manual as listed in Section 1.1.1, “Reference Documentation”.
Currently, there are two styles of modules available, legacy version and newer version. The obvious difference between the two styles is
the orientation of the rotary dials. Refer to the diagram below for an example of each.
CMF-300 CMF-300
Legacy Version Module Newer Version Module
(Vertical Rotary Dial) (Horizontal Rotary Dial)
NOTE: Only the MMF-300, MMF-302, CRF-300, CMF-300, and MDF-300 modules are available as newer type modules. Both the legacy
and newer versions share the same part numbers. The newer version modules will be phased in, replacing the legacy version. This manual
contains information and wiring diagrams for the newer version of the modules. Refer to “Terminal Conversion Charts for New & Legacy
Devices” on page 69 for additional information.
Currently, there are two styles of detector bases available, legacy version and newer version. The obvious difference between the two
styles is the orientation of the screw terminals. Refer to Section 9 and Appendix D for an illustration of each.
NOTE: Only the B501 Detector Base, B210LP Detector Base (replacement base for B350LP), B224RB Relay Base, and B224BI Isolator
Base are available as newer type bases. Both the legacy and newer versions share the same part numbers. The newer version bases will
be phased in, replacing the legacy version. This manual contains information and wiring diagrams for the newer version of the bases. Refer
to “Intelligent Detector Base Layouts for Legacy Devices” on page 72 for additional information.
1.2 Overview
Communication between the control panel and intelligent addressable monitor and control devices takes place through a Signaling Line
Circuit (SLC), which can be wired to meet the requirements of NFPA Class A, Class B, or Class X.
At least one secondary surge protector must be used with each SLC wiring pair whenever SLC wiring runs outside the building. For
detailed information refer to “Surge Suppression” on page 65.
When switching between polling protocols, the loop circuit must be powered down for at least 30 seconds to reset the devices.
1.4 Devices
1.4.1 Isolator Modules
Isolator Modules permit a zone of detectors and modules to be fault isolated from the remainder of the SLC loop, allowing critical com-
ponents to function in the event of a circuit fault. Isolator modules are required to meet the requirements of an NFPA Class X circuit.
I300 - Single fault isolator module
ISO-6 - Six fault isolator module
SD365CO - addressable device that provides both fire and carbon monoxide (CO) detection. It combines four separate sensing elements
in one unit (smoke, CO, light/flame, and heat) to sense multiple components of a fire. The detector’s electrochemical sensing cell creates
a separate signal for life safety CO detection. This model functions in LiteSpeed only.
BEAM355 - An addressable long range projected beam smoke detector designed to provide open area protection. The BEAM355S has
an integral sensitivity test feature that consists of a test filter attached to a servomotor inside the detector optics.
DNR(W) - Innovair Flex, intelligent, non-relay, low flow, photoelectric duct detector housing. This requires the SD355R or SD365R
photoelectric smoke detector. Accommodates the installation of the CRF-300 relay module. The DNRW is a watertight housing.
OSI-RI-FL - An addressable long range projected beam smoke detector designed to provide open area protection. Operates in LiteSpeed
or CLIP mode.
NOTE: The W-GATE, as part of the wireless network, has been tested for compliance with the Federal Communications Commission
(FCC) requirements of the United States Government. It has not been evaluated for use outside the USA. Use of this system outside the
USA is subject to local laws and rules to which this product may not conform. It is the sole responsibility of the user to determine if this
product may be legally used outside the USA.
Refer to the manufacturer’s installation instructions for information on wiring and programming.
NOTE: SLC operation meeting Class X requirements isolates each device on the SLC from faults that may occur within other areas of the
SLC.
Wiring Class requirements are determined by national and local codes. Consult with the Authority Having Jurisdiction before wiring the
SLC. The table below (derived from NFPA 72-1999) lists the trouble conditions that result when a fault exists on an SLC.
Type of Fault Class B Class A Class X
Single Open Trouble Alarm, Trouble Alarm, Trouble
Single Ground Alarm, Trouble (ground) Alarm, Trouble (ground) Alarm, Trouble (ground)
Short Trouble Trouble Alarm, Trouble
Short and open Trouble Trouble Trouble
Short and ground Trouble Trouble Alarm, Trouble
Open and ground Trouble Alarm, Trouble Alarm, Trouble
Communications loss Trouble Trouble Trouble
• Trouble - The control panel will indicate a trouble condition for this type of fault.
• Alarm - The control panel must be able to process an alarm input signal in the presence of this type of fault.
Table 1.1 SLC Performance
Short Point
SLC Out
SLC-meas1.wmf
Branch
SLC-meas2.wmf
SLC Terminal
Block
SLC Out
SLC-meas3.wmf
Short Point
SLC Return
SLC-meas4.wmf
SLC Terminal
Block B+ B– A– A+
NOTE: Use of good wiring practice consistent with local electrical codes is expected.
CAUTION:
! DO NOT LET THE SHIELD DRAIN WIRE OR THE SHIELD FOIL TOUCH THE SYSTEM CABINET OR BE CONNECTED
TO EARTH GROUND AT ANY POINT.
MS-9600
MS-9600LS
MS-9600UDLS
MS-9200UD
MS-9200UDLS
MS-9050UD MS-9200
Shield Drain Wire
Cabinet
SLC-shieldterm.wmf
Shield Foil
Conduit
2.4.1 MS-9200
TB4 provides three types of 24 VDC power; Unregulated, Nonresettable and Resettable.
TB6 provides connections for the SLC wiring.
198 addresses are available per loop (99 detectors and 99 modules).
Unregulated Power
Nonresettable Power
Resettable Power
Connections for wire shield
SLC-9200tb.wmf
SHIELD SLC SLC
TB4
TB6
SLC
Return
SLC Out
SLC-9600tb.wmf
TB3 TB8
SLC Return
SLC Out
SLC
SLC-9200udtb.wmf
TB1
TB10
SLC Return
SLC Out
SLC
SLC-9200udtb.wmf
TB1
TB10
SLC Return
SLC Out
2.4.5 MS-9050UD
24 VDC power may be supplied by a remote power supply such as the Fire-Lite FCPS-24FS6/8.
TB2 provides connections for the SLC wiring.
50 addresses are available (any combination of detectors and modules).
Connections for wire shield
SLC-9050udtb.wmf
SLC Return
SLC Out
Figure 2.10 MS-9050UD Terminal Block
2.4.6 ES-50X
TB11 provides two types of 24 VDC power; Nonresettable and Resettable, user programmable.
TB12 provides connections for the SLC wiring.
50 addresses are available (any combination of detectors and modules).
Resettable or Nonresettable Power-
user programmable
24VDC SLC
RTN RTN
SLC-es50tb.wmf
TB11
TB12
SLC Return
SLC Out
2.4.7 ES-200X
TB11 provides two types of 24 VDC power; Nonresettable and Resettable, user programmable. PWR1 has a user programmable Class A
wiring option.
TB12 provides connections for the SLC wiring.
198 addresses are available per loop (99 detectors and 99 modules).
Resettable or Nonresettable Power, Class A optional, user programmable
Resettable or Nonresettable Power-
user programmable
TB12
SLC-es200tb.wmf
SLC Return
SLC Out
Addressable Module
T-tapped Circuits
B+ B–
SLC-style4.wmf
Control Panel
SLC
SLC Out
Addressable Module
SLC Return
SLC-style6.cdrwmf
B+ B– A– A+
Control Panel
SLC
IN (-)
IN (+)
OUT (-)
OUT (+)
SLC-isowire2.wmf
SLC
Isolated branch
of the SLC
ISOLATOR 6
ISOLATOR 5
ISOLATOR 4
ISOLATOR 3
ISOLATOR 2
iso-6wire.wmf
ISOLATOR 1
-
SLC out to +
next device -
Isolator Module
Two-wire Addressable Detector
Isolated Branch
Isolator Module
Isolated Branch
Isolator Module
Isolated Branch
SLC-style4iso.wmf
B– B+ Control Panel
SLC
A variation of a Class B operation using an ISO-6 isolator module to protect each branch of the SLC is shown below. Each terminal on
the ISO-6 acts as a single I300 module. Refer to Figure 4.2 for ISO-6 wiring and to Section 4.1 for limitations. Note that the ISO-6 can-
not accept two wires at one pin. Wire Class B SLC loops as shown in the figure below.
Two-wire Addressable Detector
Out -
ISOLATOR 1
Out +
In -
In + Isolated Branch
Addressable Pull Station
ISOLATOR 2
ISOLATOR 3
Isolated Branch
ISOLATOR 4
ISOLATOR 5
Isolated Branch
SLC-style4ISO-6.wmf
ISOLATOR 6
Control Panel
SLC
ISO-6
Isolator Isolator
Module Module
Section B
Two-wire
Addressable Section C
Detector
Addressable
Pull Station
Section A
Isolator Isolator
Module Module
Control Panel
1 3 1 3
Isolator Isolator
Module Module
Two-wire
Addressable
Detector
3 4 2 1
Isolator Isolator
Module Module
Two-Wire
Addressable
Addressable
Pull Station
Detector
3 4 2 1
Isolator Isolator
Module Module
3 4 2 1
Isolator Isolator
Module Module
SLC Out SLC Return
NOTE: For more information on the individual module specifications refer to the Installation Instructions that are provided with these
devices.
SLC–
IDC Return – Rotary
SLC+
Switches
IDC Return +
IDC Out +
FMMtpH.wmf
IDC Out -
mmf-300-10.wmf
24 VDC –
24 VDC + SLC–
Rotary
IDC Return – SLC+ Switches
IDC Return +
IDC Out +
IDC Out -
FZMtpH.wmf
Areas used to record the device
address and SLC number.
T1 T2 T3 T4
T0
– + – + – + – + – + – + – + – + – + – +
T6 T5
A/B SELECT
A/B SELECT
DISABLE 2
DISABLE 1
4
3
2
5
1 0
6 7 8 9
BASE ADDRESS
15 14
J1
13
10
12
11
SW1
4
3
2
5
10
6 7 8 9
BASE ADDRESS +0 BASE ADDRESS +1 BASE ADDRESS +2 BASE ADDRESS +3 BASE ADDRESS +4 BASE ADDRESS +5
SLC Address
Disable Address Set rotary switches to base
Place shunt in: (first) address of modules
Disable 1 position to disable highest module address
Disable 2 position to disable highest two module addresses
Rotary
Switches
Address +1 { 89 H+
H–
SLC–
SLC+
Base Address { 7L+
6L–
fmmtph.wmf
Areas used to record the device
address and SLC number.
5.2 Installation
When installing any of these modules DO NOT mix the following services that the IDC provides:
• Fire alarm service
• Automatic and manual waterflow alarm service with normally open contact devices
• Sprinkler supervision with normally open contact devices
NOTE: The MS-9050UD and ES-50X can support addresses 01 - 50. The MS-9200, MS-9200UD, MS-9200UDLS, and ES-200X, can
support module addresses of 01 - 99. The MS-9600, MS-9600LS, and MS-9600UDLS can support module addresses 01 - 159. The plastic
stop located on the Tens switch must be removed to set addresses above 99.
To set an SLC address, use a screwdriver to adjust the rotary switches on the module to the desired address. The module below is set at
“35”. When finished, mark the address on the module face in the place provided.
SLC-setadd.cdr,SLC-setaddtpH.wmf, SLCbrktabs.wmf
6 7 8 9 10 6789
5 5
4 11 4 Breakaway Tab - Modules come with
3 12 3 a raised breakaway tab on the TENS
2 13 2 rotary switch. This tab must be
1 0 1514 10 removed when the module is on an
TENS ONES FACP that uses more than 99
addresses.
Modules with Rotary
Switches in
horizontal position
Modules with
Rotary Switches Dual monitor modules: On dual monitor modules, only even
in vertical numbers appear on the ONES rotary switch. The module takes
position both the selected address and the next-higher address.
NOTE: The MS-9050UD and ES-50X can support addresses 01 - 50. The MS-9200, MS-9200UD, MS-9200UDLS, and ES-200X, can
support module addresses of 01 - 99. The MS-9600, MS-9600LS, and MS-9600UDLS can support module addresses 01 - 159. The plastic
stop located on the Tens switch must be removed to set addresses above 99.
To set an SLC address, use a common screwdriver to adjust the rotary switches on the module to the desired address. The module below
is set at “28”.
4
3
2
5
10
6 7 8 9
TENS
15 14
13
10
Plastic Stop
12
11
Rotary Switches
4
3
2
multroty.wmf
10
6 7 8 9
ONES
From Supply
24 VDC
Four-wire
Detector Base 24 VDC Power
Filtered, Regulated,
Resettable
Manual pull
station
To Next IDC
or
47K ELR
Supervision Device
(supplied
with module)
SLC
Heat MMF-300
detector
SLC-idcB1tpH.wmf
IDC
From
Supply
24 VDC
Four-wire
24 VDC Power
Detector Base
Filtered, Regulated,
Resettable
Manual pull
station
To Next IDC
or
Supervision Device
SLC
MMF-300
Heat
detector
SLC-idcD1tpH.wmf
IDC
47K ELR
(supplied
with module)
SLC + -
- +
UL-listed Signaling
appliance such as the
Fire-Lite FSS-2400E
IDC
SLC-emer.wmf
MMF-300 Module
programmed for Tornado,
Hazard, or Medical operation.
Refer to the control panel
installation manual.
24 VDC Power
Filtered, Regulated, Resettable
24 VDC Four-wire
Detector Base
IDC
Out
SLC MMF-300-10
SLC-idcB4.wmf
24 VDC Power
Filtered, Regulated, Resettable
Heat
Manual Pull Detector
24 VDC Four-wire Station
Detector Base
IDC IDC
Return Out
SLC MMF-300-10
SLC-idcD3.cdwmf
Figure 5.13 Typical Class A IDC Wiring with an MMF-300-10
Manual Manual
Pull Pull
Station Station
SLC-idcB3fdm1tph.wmf
T8 T3
T7 T4
T6 T5
MMF-302
IDC
SLC-idcB2tpH.wmf
Two-wire
smoke 24 VDC Resettable power.
detectors 90 mA External 24 volt supply required
SLC
MMF-302
IDC
SLC-idcD2tpH.wmf
3.9K ELR
(supplied with module)
IDC
Out
SLC MMF-302-6
SLC-idcB5.wmf
Figure 5.17 Typical Class B IDC Wiring with an MMF-302-6
IDC IDC
Return Out
MMF-302-6
SLC
SLC-idcD4.wmf
Figure 5.18 Typical Class A IDC Wiring with an MMF-302-6
6.1 Description
The CMF-300 and CMF-300-6 modules are addressable modules that can be used for monitoring and switching 24 VDC Notification
Appliance Circuit (NAC) power for NFPA Class B and NFPA Class A circuits.
Ratings for the relay contacts on the module are:
NOTE: For more information on module specifications, refer to the Installation Instructions provided with these devices.
FCMFZMtph.wmf
NOTE: Module polarities are shown in alarm condition.
• A power supervision relay is required only on the last module of the power run.
• Do not T-tap or branch a Class B circuit.
• Terminate the circuit across the last device using an End-of-Line Resistor 47K, 1/2-watt,
P/N SSD A2143-00 (ELR-47K in Canada).
• Do not loop wiring under the screw terminals of any notification appliance. To maintain supervision, break the wire run at each
device.
SLC
24 VDC Nonresettable power CMF-300
NOTE: A power
supervision relay is
required only on the
ELR last module of the
24 VDC Notification power run.
47K, 1/2-watt
Appliances
SLC-nacY.wmf
NAC
NOTE: Refer to the Device Compatibility Document for compatible notification appliances and relays.
NAC Return
NAC Out
SLC-nacZtpH.wmf
NOTE: The MS-9050UD and ES-50X can support addresses 01 - 50. The MS-9200, MS-9200UD, MS-9200UDLS, and ES-200X can
support module addresses of 01 - 99. The MS-9600, MS-9600LS, MS-9600LSC, and MS-9600UDLS can support module addresses 01 -
159.
To set an SLC address, use a common screwdriver to adjust the rotary switches on the module to the desired address. See Figure 6.4 on
page 47.
NOTE: For use with the MS-9600, MS-9600LS, MS-9600LSC, and MS-9600UDLS, remove the stop on the upper rotary switch.
A/B SELECT
addresses. If two module addresses are disabled, the lowest four addresses will be functional, while the high-
DISABLE 3
DISABLE 2
DISABLE 1
est two will be disabled. For example, if the shunt is placed on ‘DISABLE 2’ and the base address is set to
28, the module addresses will be assigned to 28, 29, 30 and 31.
In Class A operation, placing a small shunt on ‘DISABLE 3’ will disable all three addresses. Placing it on
‘DISABLE 2’ will disable two out of three addresses.
To disable addresses, securely place one of the supplied small shunts onto the desired set of pins. See draw-
SLC-disable1.wmf
ing and Figure 6.4 on page 47.
J1
6.4.5 Short Circuit Protection
Protection is disabled for each module address when there is a large shunt installed on the corresponding pins of the pin block (as
shipped, all six addresses are disabled).
When enabled, the module will not switch power supply if a short circuit condition exists on a NAC.
To enable “Short Circuit Protection” for an address, remove the large shunt from the corresponding pins of the pin block. See Figure 6.4
on page 47. Place unused shunts on single pin to store on board for future use.
#1 #2 #3 #4 #5 #6
Status Indicators
Green LEDs are
CMF-300-6.wmf
controlled by FACP to
indicate status of each
module address.
NOTE: Refer to the Device Compatibility Document for compatible notification appliances and relays.
24 VDC
nonresettable
power
ELR 47K,
1/2-watt 24 VDC notification appliances
– +
NAC Out
SLC
Relay Connector Assembly + –
CMF-300-6
T0
+0 – + – + – + – + – + – + – + – + – + – +
T1 T2 T3 T4 T5
– + – +
SLC-nacY2.wmf
+1 +2 +3 +4 +5
T12 T13 T14 T15
T10 T11 T16
NOTE: Refer to the Device Compatibility Document for compatible notification appliances and relays.
Power Supervision
Relay
(EOLR-1)
24 VDC
nonresettable
power
NAC
Out
SLC
NAC
Return
CMF-300-6
SLC-nacZ3.cwmf
Maximum Current
Load Description Application
Voltage Rating
Resistive Non-Coded 30 VDC 3.0 A
Resistive Coded 30 VDC 2.0 A
Resistive Non-Coded 110 VDC 0.9 A
Resistive Non-Coded 125 VAC 0.9 A
Inductive (L/R = 5ms) Coded 30 VDC 0.5 A
Inductive (L/R = 2ms) Coded 30 VDC 1.0 A
Inductive (PF = 0.35) Non-Coded 70.7 VAC 0.7 A
Inductive (PF = 0.35) Non-Coded 125 VAC 0.5 A
NOTE: For more information on the module specifications refer to the Installation Instructions provided with these devices.
CRF-300
C
NC
NO
C
NC NO
SLC-frmCtpH.wmf
T102
COMM
COMM
COMM
N.O.
N.C.
COMM
N.O.
N.C.
COMM
N.O.
N.C.
N.O.
N.C.
N.O.
N.C.
BASE ADDRESS +0 BASE ADDRESS +1 BASE ADDRESS +2 BASE ADDRESS +4 BASE ADDRESS +5
THREE
NONE
TWO
ONE
ADDRESS
DISABLE
Disable Address
Place shunt onto
required pins.
crf-300-6.wmf
Status Indicators
Green LEDs are
controlled by FACP to
indicate status of each
module address.
SLC Address
Set rotary switches to
address required.
NOTE: The MS-9050UD and ES-50Xcan support addresses 01 - 50. The MS-9200,MS-9200UD,MS-9200UDLS, and ES-200X can
support module addresses of 01 - 99. The MS-9600, MS-9600LS, and MS-9600UDLS can support module addresses 01 - 159. To set an
SLC address, use a common screwdriver to adjust the rotary switches on the module to the desired address. See Figure 6.4 on page 47.
For use with an MS-9600, MS-9600LS, MS-9600LSC, and MS-9600UDLS, remove the stop on the upper rotary switch.
SLC-disable2.wmf
To disable addresses, remove the shunt from its storage location and securely place it onto the desired set of
pins. See illustration.
J1
Shunt Storage
Location
–
+
–
+
CRF-300-6
– + – +
SLC-fmC1.wmf
Maximum Current
Load Description Application
Voltage Rating
Inductive (PF = 0.35) Non-Coded 25 VAC 2.0 A
Resistive Non-Coded 30 VDC 3.0 A
Resistive Coded 30 VDC 2.0 A
Inductive (L/R = 20ms) Non-Coded 30 VDC 0.46 A
Inductive (PF = 0.35) Non-Coded 70.7 VAC 0.7 A
Resistive Non-Coded 125 VDC 0.9 A
Inductive (PF = 0.75) Non-Coded 125 VAC 0.5 A
Inductive (PF = 0.35) Non-Coded 125 VAC 0.3 A
NOTE: For more information on the module specifications refer to the Installation Instructions provided with these devices.
NC
C
NO IDC 1 (+)
NC IDC 1 (-)
C IDC 2 (+)
NO IDC 2 (-)
fdrm-1.wmf
Normally Closed
Common
Normally Open
Normally Closed
Common
Normally Open
NOTE: When using a Wireless Gateway on the SLC loop, the panel cannot have ANY modules (wired or wireless) in the address range
from 140 to 159.
For details about the wireless network and its devices, see the SWIFT™ Smart Wireless Integrated Fire Technology Instruction Manual
#LS10036-000FL-E.
–
To Next Device
on SLC
+
RA100Z /
RA400Z
SLC-B5012wire.wmf
Remote LED
Annunciator
(Optional)
+ –
NOTE: The B300-6 andd B210LP base wiring is identical to the B501. B501 is the flangeless model.
SLC In
+ –
Conduit
slc-224bi2wire.wmf
I300 Isolator Module
Normally Closed
Common
Normally Open
slc-b224rb2wire.wmf
+-
SLC
Optional Sounder
Interconnect
slc-b200srwire.wmf
+ -
UL-Listed
24V Power
+- Supply
SLC
NOTE: For more detailed wiring on the sounder base, refer to the device’s installation instructions.
NOTE: It is recommended to use the same wire gauge if there are multiple connections to the same terminal.
2.4.wmf
Figure 9.5 W-GATE Mounting Plate - Terminal Layout
Jumpers
2.5.wmf
2.6.wmf
SLC in from FACP/device
NOTE: This section provides basic wiring and addressing information For critical information on device installation, operation and
alignment, refer to the Installation Instructions provided with these devices.
Alignment Mirror
Alignment Gunsight Digital Signal
Strength Readout
Alignment Position
Indicator
Horizontal Adjustment
Optics Lock-down
Screws
Alignment Switch
Sensitivity Switch
ONES
ADDRESSING
SWITCHES
CODE
Test Switch
TENS
Vertical Adjustment
Reset Input
Test Input
Aux (-)
RTS151/KEY& RTS-451/KEY
Connections
Typical wiring of an OSI-RI-FL beam detector connected to an SLC is illustrated in the figure below.
Rotary address
switches
Not used
Not used
Heater Power -
Heater Power +
Aux -
Remote test input
Remote trouble output
Remote alarm output
} RTS151/KEY
connections
USB port
NOTE: For more information refer to the Installation Instructions provided with this device.
11.2 Installation
11.2.1 Setting an SLC address
Each unit is factory preset with an address of “00.” To set an SLC address refer to “Setting an SLC address for a Single Point Module”
on page 33.
–
To next device
+ on SLC
SLC +
–
US PAT4440991
SLC-bg12lx2.wmf
For NACs:
(Vms - Vom)
Rmax =
(Nb)(Ib)
Where:
Rmax = maximum resistance of the 24 VDC wires
Vms = minimum supply voltage
Vom = minimum operating voltage of the detector or end-of-line relay, whichever is greater, in volts
N = total number of detectors on the 24 VDC supply circuit
Is = detector current in standby
Na = number of detectors on the 24 VDC power circuit which must function at the same time in alarm
Ia = detector current in alarm
Ir = end-of-line relay current
Nb = number of Notification Appliance Devices
Ib = Notification Appliance current when activated
NOTE: This simplified equation assumes that the devices are at the end of a long wire run.
The minimum supply voltages produced by Fire•Lite power supplies are listed below:
Power Supervision
Relay
(EOLR-1)
SLC-psrtpH.cdr
Supervised NAC
ELR
47K
Figure A.1 Supervised 24 VDC Circuit
ELR 47K
Power Supervision
Relay
(EOLR-1)
MMF-300
SLC-psr-2addresstpH.wmf
There are three (3) primary surge protectors that are approved for use with the MS-9200, MS-9200UD, MS-9200UDLS, MS-9600, MS-
9600LS, MS-9600UDLS, and MS-9050UD.
• DTK-2LVLP-F Diversified Technology Group, Inc. 1720 Starkey Rd. Largo, FL 33771 (727) 812-5000
• SLCP-30 EDCO 1805 N.E. 19th Ave. Ocala, FL 34470 (352) 732-3029
• PLP-42N Northern Technologies, Inc. 23123 E. Madison Ave. Liberty Lake, WA 99019 (800) 727-9119
NOTE: For detailed information, refer to the Installation Instructions supplied with the unit.
One primary surge protector must be used with each SLC wiring pair whenever SLC wiring runs outside the building.
• Install primary protection only as shown in this document.
• Refer to NEC Article 800 and local building code requirements.
Additional primary surge suppressors may be added as required by the NEC. Add these additional suppressors in series with the SLC
wiring at the building entry/exit.
Wiring connected to the surge suppressor output must remain within the building while wiring connected to the surge suppressor input
may be routed outside the building as shown below.
Building #2 Building #1
P P
FACP
P = Primary
S = Secondary S
P P S
Surge Suppressor
SLC-
Primary devices meet Secondary devices meet
NEC Requirements UL1459 (UL1950)
B.2 Installation
Mounting of the surge suppressor must be inside the FACP enclosure or in a separate enclosure listed for fire protective signaling use.
• Locate on an available stud and secure with nut.
• Unit is connected in series with the SLC Loop to protect the Control Panel.
• Provide a common ground to eliminate the possibility of a differential in ground potentials.
IN OUT
SLC Terminal Block
2LVLP-F A-
B-
– A+
+ B+
A Shield
SLC-lvlp1.wmf
B Shield
SLC Loop
IN OUT
PLP-42N Connections
PLP-42N
GRND
L4
L4
L3
Class A
L2
L2
L1
L1
A+
L4
L4
SLC-plpn1.wmf
B+
OUTPUT
L3
INPUT
L3
A Shield
L2
L2
L1
NOTE: Use 12AWG (3.25mm2) to 18AWG (0.75mm2) wire with crimp-on connectors to connect the unit’s ground terminal to equipment
ground. Wire length must be minimized to provide best protection.
SLCP-30 Connections
2LCP-30
IN OUT
SLC Terminal Block
2LCP-30 A-
SLC Loop B-
– A+
+ B+
SLC-slcp1.wmf
A Shield
B Shield
IN OUT
IN OUT
SLC-lvlp4.wmf
A-
SLC Loop
A Shield
IN OUT B Shield
PLP-42N Connections
PLP-42N GRND
L4
L4
L3
Class A
L2
L2
L1
L1
PLP-42N B+
A+
+
GRND
B-
L4
L4
– A-
OUTPUT
L3
INPUT
L3
A Shield
SLC-plpn4.wmf
L2
L2
L1
NOTE: Use 12AWG (3.25mm2) to 18AWG (0.75mm2) wire with crimp-on connectors to connect the unit’s ground terminal to equipment
ground. Wire length must be minimized to provide best protection.
SLCP-30 Connections
2LCP-30
IN OUT
SLC Terminal Block
2LCP-30
SLC Loop
+ B+
A+
–
B-
SLC-slcp4.wmf
A-
A Shield
B Shield
IN OUT
SLC-lvlp5.wmf
Optional 4-wire Return Loop
Class A
IN OUT
PLP-42N Connections
PLP-42N
GRND
L4
L4
L3
Class A
L2
L2
SLC-plpn5.wmf
L1
L1
PLP-42N B+
+ A+
GRND
L4
L4
– B-
OUTPUT
L3
INPUT
L3
A-
Ground stud on inside of backbox
L2
L2
L1
NOTE: Use 12AWG (3.25mm2) to 18AWG (0.75mm2) wire with crimp-on connectors to connect the unit’s ground terminal to equipment
ground. Wire length must be minimized to provide best protection.
SLCP-30 Connections
2LCP-30
IN OUT
SLC Terminal Block
2LCP-30
SLC Loop B+
+
– A+
B-
A-
Ground stud on inside of backbox
Refer to Figure 2.4 in the FACP manual
IN OUT
Common 2 Common 2
SLC - SLC -
Closed 2 Closed 2
SLC + SLC +
Open 2 Open 2
Common 1 Common 1
Closed 1 Open 1
Open 1
A- VDC -
SLC - VDC + SLC -
A+
SLC + A- SLC +
B/A +
B/A - VDC - A+
VDC + B/A +
C.3 MMF-300
Class A Supervision -
Class A Supervision+ SLC -
SLC - Class A Supervision -
Class A/B Supervision + SLC +
SLC + Class A Supervision+
Class A/B Supervision - Class A/B Supervision +
C.4 MDF-300
Legacy Module
(V-Type) Newer Module
(H-Type)
3 1(–) –
To next device
on SLC
+
RA100Z/ SLC-B501wire.wmf
RA400Z
Remote LED
Annunciator
(Optional)
+ –
NOTE: The B350LP base wiring is identical to the B501, except there is no shield terminal.
SLC In
Conduit
SLC-224BIwire.wmf
I300
Isolator Module
To next device
on SLC
For connection of
cable shield
3 Relay Common
2 Normally Open
1 Normally Closed
SLC
b224rb.wmf
+ -
Optional
Sounder
Interconnect
slc-b501bhwiring.wmf
SLC + SLC -
Figure D.4 Wiring the Legacy B501BH(-2) and B501BHT(-2) Sounder Bases
P T
performance 12 terminal blocks 17
photoelectric 54 termination of shield 16
PLP-42N 65 thermal detector 54
polling protocols 10 thermistor sensing circuit 11
power run 63, 64 trouble conditions 13, 22
power supervision relay 45, 48, 49, 64 T-tapping 14, 20, 21, 26, 27
power supplies 63 twisted-pair shielded wiring 14
proper gauge wire 63 two-wire configuration 44, 48
pull station 12, 27 two-wire detectors 64
wiring of 62
U
R unregulated power 17
RA100Z 55
RA400Z 55
rate of rise 11
V
ratings, relay contact 44, 50, 53 verification cycle 54
relay base 22
wiring of 56 W
relay contact ratings 44, 50, 53 waterflow alarm service, automatic and manual 32
relay module 11 W-GATE 12, 57
relays external power 59
Form-C 11 SLC connections 58
remote LED annunciator 55 SLC power 58
resettable power 17 wire length 15, 16
resistance 14, 15 wire size 14
rotary switches 33, 38, 39, 40, 41, 42, 43, 54 wireless gateway 12, 57
external power 59
S SLC connections 58
SD350 Detector 11 SLC power 58
SD350T Detector 11 wiring
SD355 Detector 11, 54 I300 22
Warn-HL-08-2009.fm