Apacheview User Guide: Ies Virtual Environment 2012
Apacheview User Guide: Ies Virtual Environment 2012
Virtual Environment
Thermal category
Apache View
Apache is the name given to the thermal analysis programs in the Virtual Environment. The
Apache view provides facilities for:
Preparation of input data for the thermal analysis programs ApacheSim ASHRAE
Loads and CIBSE Loads
Calculations and simulations using ApacheSim, ApacheHVAC, MacroFlo, ASHRAE
Loads and CIBSE Loads.
The preparation of thermal input data consists of three main tasks:
Specification of building location and weather data
Specification of building element data (properties of the building fabric)
Specification of room data (conditions in each room)
The interfaces to the thermal analysis programs provide facilities for:
Setting up the calculations and simulations
Specifying the results to be recorded
These menus provide functions used throughout the Virtual environment and Apache view.
Please refer to the Virtual Environment User Guide for further information.
These icons provide a quick route to functions on the Apache menu bar.
Model workspace
This displays the model geometry and provides a graphical means of selecting geometrical
objects.
This provides functions for manipulating the view of the geometrical model.
This list of rooms, opening up to display surfaces and openings in those rooms, provides an
alternative way to view and select geometrical objects.
These tools allow the creation, application and selection of Room Grouping Schemes. See the
ModelIT user guide for further information.
These buttons invoke the thermal analysis programs CIBSE Loads, ASHRAE Loads and
ApacheSim, and Batch Simulation.
When the Loads Methodology on the Apache View Settings menu is set to ASHRAE,
CIBSE Loads is replaced by ASHRAE Loads.
Every building element has an attribute specifying its construction type. When the element is
created in ModelIT, its construction type is set by the active Apache Constructions Template.
This setting can later be changed using tools provided in the Apache view. The construction type
attribute for an element consists of a pointer to one of the construction types defined in APcdb.
This means that if the construction type data is edited in APcdb, the change immediately and
automatically takes effect for all elements to which that construction type is assigned.
There are several ways to select a set of building elements in the Apache view.
At model level
At the model level of decomposition you may select a single room or a set of rooms by clicking
in the model workspace or the model browser. For the purposes of construction type setting,
this selects all the elements contained in those rooms.
At space level
At the space level of decomposition (surface mode applies here) you may select a room surface.
For the purposes of construction type setting, this selects all the elements contained in that
surface.
At surface level (opening mode)
At the surface level of decomposition (opening mode) you may select a single opening or a set
of openings.
At surface level (adjacency mode)
At the surface level of decomposition (adjacency mode) you may select a single adjacency.
The dialog shows the adjacent space, the area of the element, the Construction Type (which
may be changed here) and the Adjacent Condition.
When parts of the model (layers) are made inactive (switched OFF) they will not be included in
the thermal simulations and no solar gain will be present on ceilings, floors, walls, fenestration,
etc. that form an adjacency to a space that is on an inactive layer.
Room
Room Name
The name given to the room in ModelIT
General Template
The Room General Templates assigned to the room
Thermal Template
The Room Thermal Templates assigned to the room
Room ID
The ID assigned to the room in ModelIT (information only)
Volume (m3)
The calculated volume of the room (information only)
Floor
Area (m2)
The calculated floor area of the room, used for the calculation of internal gains (information
only). Floor area is calculated as the sum of the areas of all opaque floor elements. It excludes
the areas of any holes or glazing elements in the floor.
Include in building floor area? (checkbox)
Set if this zone contributes to the building floor area. Uncheck if it should not.
Lettable Area (%)
The percentage of the floor area that is lettable
Room Conditions
DHW
These parameters specify the demand for domestic hot water.
Consumption pattern
This specifies the procedure for determining the how the room’s DHW demand varies with time.
The demand can be linked to room occupancy (as set in the Internal Gains tab) or governed by
an independent profile.
Pattern of use profile
When DHW Consumption Pattern is set to ‘Independent Profile’ this option specifies which
profile is to be used to modulate the DHW demand.
DHW consumption
The maximum rate of hot water consumption. The unit is litres per hour per person or litres per
hour (or equivalent IP units) depending on the specified Consumption pattern.
Hot water consumption is accounted for in ApacheSim, and optionally in ASHRAE Loads and
CIBSE Loads.
Cooling
Cooling profile
A modulating profile scheduling the operation of the cooling plant. Cooling will operate when
the modulating profile value exceeds 0.5. Profiles are created and edited in APpro, the Profiles
Database Manager.
In the case of ApacheSim this parameter is overridden if the room is modelled in ApacheHVAC.
Cooling Set Point
The temperature set point for cooling control. This value must be greater than or equal to the
Heating Set Point at all times. The Cooling Set Point can be constant or it can follow an absolute
profile.
This parameter is overridden if the room is modelled in ApacheHVAC.
Model settings
Solar Reflected Fraction
(CIBSE Loads only) The fraction of solar radiation entering the room which is assumed to be
scattered back out through glazing. The value of this parameter depends primarily on internal
surface solar absorptance and room geometry.
In ApacheSim, the retransmission of solar radiation is calculated directly from this data.
Furniture Mass Factor
(not CIBSE Loads). An allowance for the thermal inertia of furniture. Lightweight furniture can
be modelled by assuming that its temperature closely follows the room air temperature. Under
these conditions its effect is the same as that of an increase in the thermal capacity of the air in
the room. The Simulation Furniture Mass Factor is the factor by which the thermal capacity of
the furniture exceeds the thermal capacity of the air. If furniture is to be ignored, a value of 0
should be entered.
Humidity control
Percentage saturation lower limit
The minimum percentage saturation level to be maintained in the room during periods of plant
operation, as specified by the Cooling profile. If the percentage saturation in the space falls
below the value entered here during plant operation, humidification will occur to meet this
limit. Setting this parameter to 0% disables humidification control.
Percentage saturation upper limit
The maximum Percentage Saturation level to be maintained during periods of plant operation,
as specified by the Cooling profile. If the percentage saturation in the space rises above the
value entered here during plant operation, dehumidification will occur to meet this limit. Setting
this parameter to 100% disables dehumidification control.
Max humidification
An autosized value set by ASHRAE Loads and CIBSE Loads (ApacheCalc) runs. It records the
maximum level of humidification required during the run.
System
This tab allows you to specify an Apache System serving the room and set its parameters. It also
displays autosized room parameters generated by ASHRAE Loads and CIBSE Loads.
In ApacheSim, the system parameters entered here will be overridden (with one exception) in
any rooms that feature in an attached ApacheHVAC system. The exception is the setting
‘Auxiliary mech. vent. system’. A room served by an ApacheHVAC system may also have one or
more auxiliary ventilation air supplies defined on the Air Exchange tab, and these are always
associated with an Apache System.
Systems
System
The Apache System serving the room. Select a system from a list of those defined in the Apache
Systems utility, or use the option ‘None’ to indicate an unconditioned room. The system will
initially be set by the room thermal template. The template specifies a type of system (currently
there is only one type – Generic heating & cooling), which is then instantiated by the following
procedure. For each type of system a specific system is nominated in Apache Systems as the
default system of that type. It is this system that is assigned to the room. System assignments,
like other Room Data parameters, can be overridden by un-ticking the Template check box and
editing the setting.
Use same system for auxiliary mech. vent.
If there are air exchanges of the ‘Auxiliary ventilation’ type defined on the Air Exchange tab
these will be supplied by an Apache System. By default they will be handled by the main system
serving the room, but you can source them from another system by un-ticking this check box
and specifying a second system for this purpose.
Auxiliary vent. system
The Apache System handling auxiliary ventilation air exchanges defined on the Air Exchange tab.
The auxiliary ventilation system will calculate the heating, cooling and dehumidification
required to process outside air to the specified supply condition.
Use same system for DHW (Domestic Hot Water)
If hot water use is included in the Room Conditions tab the energy use associated with this will
be calculated by an Apache System. By default they will be handled by the main system serving
the room, but you can source them from another system by un-ticking this check box and
specifying a second system for this purpose.
DHW system
The Apache System that handles Domestic Hot Water. The DHW system will calculate the
energy required, using a model which assumes a temperature rise of 50K between the mains
water supply temperature and the hot water temperature.
Heating
Heating unit size
During ASHRAE Loads and CIBSE Loads runs the value of this parameter is automatically updated
(autosized) to record the maximum heating unit demand encountered during the loads analysis.
Simulation heating unit capacity
This parameter only applies to simulation runs, not to ASHRAE Loads or CIBSE Loads. It allows
you to specify a maximum capacity available from the heating units in the room.
Cooling
Cooling unit size
During ASHRAE Loads and CIBSE Loads (ApacheCalc) runs the value of this parameter is
automatically updated (autosized) to record the maximum cooling unit demand encountered
during the loads analysis.
Simulation cooling unit capacity
This parameter only applies to simulation runs, not to ASHRAE Loads or CIBSE Loads. It allows
you to specify a maximum capacity available from the cooling units in the room.
Cooling plant radiant fraction
The fraction of the cooling plant’s output that is in the form of radiant, rather than convected,
heat. A value of 0.0 is appropriate for air conditioning. See Table 13 for further guidance.
This tab is for viewing and specifying room internal gains (sometimes called casual gains).
The dialog displays a list of internal gains present in the room. By clicking on an item from the
list of you can view, and if appropriate edit, its specification.
Gains can be specified in Watts or W/m2. For people (occupancy), gains can be specified in
Watts or W/person, and the occupancy density can be specified in number of persons or
m2/person. For lighting gains the power density can also be specified by the Installed Power
density per 100lux (or per fc).
If you click on the Add button, the Internal Gains List will appear, allowing you to select those
gains you wish to include in the room in addition to those attached to the Room Thermal
Template. Any gain you add to a room must first be created in the Internal Gains List. This is
done in the Template Manager. Any gain originating from the Room Thermal Template is
marked with a ‘T’. Other gains are unmarked.
Note: Not all items listed below are needed for each type of Internal Gain.
A list at the top of the dialog displays the Apache Systems in the model. You can add further
systems using the ‘Add’ button and remove them (if they are not in use) using the ‘Remove’
button. The properties of the currently selected system are displayed in the main dialog area.
A tick in the ‘Default?’ column indicates that the system will be assigned by default to imported
room templates. You can change the default system by double clicking in the ‘Default?’ column.
The system assignment may be overridden, like other template assignments, in Room Data.
Name
The name of the system.
UK NCM system type
The type of system chosen in the UK NCM system data wizard (if used).
This button launches the system data wizard that aids users in filling out the variables required
by the Apache Systems dialog. Refer to section 6 of this user guide for more details.
The main dialog area displays the properties of the currently selected system and allows them
to be edited. Boxes labelled in blue represent autosized parameters calculated by the loads
analysis programs. The values of autosized parameters do not affect simulation performance or
compliance/certification results. They may not be edited in this dialog. They may, however, be
reset to zero or wound back to the values applying before the last loads analysis using options
on the ASHRAE and CIBSE Loads dialogs.
The main of the dialog is spread over eight tabs, as follows.
Generator
Fuel
The fuel supplying the heating system. This setting is used to total fuel consumptions and
determine carbon emissions.
Seasonal efficiency
The seasonal efficiency of the boiler or other heat source.
Is it a heat pump?
Tick this box is heat is supplied by a heat pump (applies to UK NCM only).
Heating delivery efficiency
The efficiency of heat delivery to the room from the system.
SCoP
The seasonal coefficient of performance of the entire heating system.
Generator size
The maximum load on the boiler or other heat source that occurred during the heating loads
analysis. An uneditable autosized parameter.
Heat recovery
Ventilation heat recovery effectiveness
The effectiveness of a generic sensible heat recovery device. If the recovery effectiveness is set
to zero no heat is recovered. The magnitude of the heat recovery is established from the system
air flow rate and the heat recovery return air temperature.
CH(C)P
Is this heat source used in conjunction with CHP?
Tick this box to specify that the system can receive heat input from the building’s CHP or CHCP
(tri-generation) plant, if it has one (see Section 7). If no CH(C)P has been defined for the
building, this setting is ignored. CH(C) is also ignored for Loads analyses.
What ranking does this heat source have after the CH(C)P plant?
If there is a CH(C)P system, the boiler ranking defines the sequence in which different heating
systems will be switched in to make up any shortfall in the heat provided by the CHP system.
Boilers with low boiler ranking will be switched on first. These will normally be the most
efficient. Where two boilers have the same boiler ranking the CHP plant will contribute the
same fraction of the heating load for both systems.
Cooling
Generator
Cooling/ventilation mechanism
The mechanism for cooling and ventilation. Select Air conditioning, Mechanical ventilation or
Natural ventilation. This setting determines the options available for the calculation of auxiliary
energy, and categorizes the system for UK compliance and certification. When Mechanical
Ventilation is selected, the rooms receiving mechanical ventilation should be indicated at room
level on the Room Data System tab, under the heading ‘Ventilation & exhaust’.
Fuel
The fuel supplying the cooling system – most commonly electricity. This setting is used to total
fuel consumptions and determine carbon emissions.
Operation
Changeover Mixed Mode free cooling mechanism
This parameter is only required for UK regulations compliance and certification. For a
changeover mixed mode system, indicate whether the free cooling is achieved by natural or
mechanical ventilation. If the system is not a changeover mixed mode system, use the setting
‘Not a CMM system’.
Heat rejection
Pump & fan power (% of rejected heat)
Heat rejection pump and fan power, expressed as a percentage of heat rejected by the chiller.
Hot Water
This tab allows you to describe the characteristics of the domestic hot water heating systems.
This approach is suitable for use in Building Regulations compliance tests, ApacheSim, ASHRAE
Loads and CIBSE Loads.
Storage
Is this a storage system?
Tick this box if the hot water system has a storage tank.
Storage volume
The volume of the DHW storage tank. This is used, with the following parameters, to calculate
tank losses.
Insulation type
This parameter and the following are alternative ways of specifying the insulation of the tank.
The options for ‘Insulation type’ are ‘Uninsulated’, ‘Loose jacket’ and ‘Factory insulated’.
Storage losses
The DHW storage tank loss factor (kWh/l/day).
The following tables from SAP (2005) may be helpful in setting this parameter.
When using the data in Table 2, the loss is to be multiplied by the volume factor.
2) Alternatively, the volume factor can be calculated using the equation
VF = (120 / Vc )1/3
Where:
Vc – volume of cylinder or storage, litres
Secondary circulation
Does the system have secondary circulation?
Tick this box if the hot water system has secondary circulation. A secondary circulation system
pumps water continuously round a circuit connecting the heat source to the outlets to provide
instant hot water.
Circulation Losses
The loss factor of the secondary circulation system, per unit length of pipework (W/m).
Pump Power
The rated power of the secondary system pump (kW).
Loop Length
The length of the secondary circulation system (m).
Storage tank
Volume
Volume of the storage tank. This is used to calculate tank losses.
Storage loss at maximum temperature
The DHW storage tank loss factor (kWh/l/day). This is used, with the preceding parameter, to
calculate tank losses.
Tables 2 and 2a from SAP (2005), quoted above in relation to DHW storage, may be helpful in
setting this parameter.
Auxiliary energy
Auxiliary energy is energy consumed by fans, pumps and controls (excluding heat rejection).
Fans
Air supply mechanism (only available if Cooling/vent. Mechanism under Cooling System is
other than ‘Natural ventilation’)
This parameter is only required for UK regulations compliance and certification. Select the
appropriate mechanism from the given options covering centralised, zonal and local systems.
Auxiliary energy
Auxiliary energy value (only available if AEV has been selected)
Energy use of fans, pumps and controls, expressed per unit floor area. Auxiliary energy
consumption is calculated from this parameter at times when there is a load on the system.
Equivalent to
The auxiliary energy value expressed in units of energy per unit floor area per year, normalised
to a basis of 3255 hours of operation per year. This parameter is uneditable.
Off-schedule heating/cooling AEV
The auxiliary energy value associated with a room when the room’s heating and cooling
availability profiles are both off.
Air supply
Cost
Cost tab inputs for CostPlan and IMPACT only, please refer to CostPlan User Guide for further
explanation.
Control
The five tabs of the UK NCM system data wizard define different aspects of system
performance. Each tab is enabled only when relevant to the chosen system type. For example
for the type ‘Central heating using water: radiators’ the Cooling system tab will not be editable.
The UK NCM system data wizard translates the inputs into the following parameters which are
displayed at the bottom of the wizard and passed back to the Apache Systems:
Heating SCoP
Cooling SSEER
Auxiliary Energy Value
The system types appearing at the top of the list that involve heating only, and do not specify a
ventilation mechanism, are assumed by default to be served by mechanical ventilation. In cases
where the building is naturally ventilated, this should be specified on the Apache Systems dialog
using the ‘Cooling/ventilation mechanism’ setting.
The following additional guidance is provided in the SBEM documentation, and applies to the
analogous settings in the UK NCM system data wizard:
The system type selected in the General sub-tab automatically brings with it some assumptions.
For example, whether mechanical ventilation is an integral part of the system and the degree of
local time and temperature control that is (or can be provided). The majority of system types
used in UK buildings can be found in the system type drop down box. However, there are a few
systems which require further guidance:
VRF Systems have been removed, for these systems select ‘split or multisplit
system with natural ventilation’ – you will need to define a suitable efficiency.
Multisplit is suitable for use with VRF as it is essentially a type of split/multisplit
system. If these systems have additional mechanical ventilation, then this
mechanical ventilation rate should now be selected at zone level with a suitable
ventilation SFP.
If Chilled ceiling is selected, the default assumption is that there is displacement
ventilation.
Chilled ceiling with no mechanical ventilation – select ‘Chilled ceilings or passive
chilled beams and displacement ventilation’ and then set the specific fan power
to zero.
Chilled ceiling with mixing ventilation – select ‘Chilled ceilings or passive chilled
beams and displacement ventilation’ and then use twice the actual specific fan
power in order to capture the effect of the higher ventilation rate.
Heat source
Type of heat generator (eg boiler) used in the system.
Fuel type
Fuel used by the heat generator chosen for the system.
Tick if this system also uses CHP
Tick to use a CHP system as the base load for this heating system.
Generator seasonal efficiency
Enter the seasonal efficiency of the heat generator if known. Accept the default if not known.
Does it qualify for ECAs?
Indicate whether the generator qualifies for ECAs (Enhanced Capital Allowances). Generators on
the ECA list can be expected to have improved efficiencies, and this is reflected in the default
seasonal efficiency value.
Was it installed on or after 1998?
This affects the default seasonal efficiency.
Control provision
Choose whether the system has metering provision and whether the metering can warn about
“out of range values”.
Control correction
The used Control Correction factor is displayed here, according to the settings under Control
provision
Ventilation
Available cooling/ventilation mechanisms include
Air conditioning
Mechanical ventilation and
Natural ventilation.
However, depending on the selected system type, not all options are available.
For example, if a system type has been selected that allows for a cooling system (Cooling system
– tab has been activated), cooling/ventilation mechanism can only be set to Air conditioning.
For those systems the Cooling system tab has not been activated, the user can select between
Mechanical and Natural ventilation.
Select the Air supply mechanism from the drop-down list. Note: This option is only available for
Cooling/Vent. mechanisms other than Natural ventilation.
Heat recovery
Up to 4 panels can be added. For each panel the following data must be entered:
7.1.3.1 Area
The area of the panel (m2).
7.1.3.2 Azimuth
Panel azimuth angle in degrees clockwise from north.
7.1.3.3 Tilt
Panel tilt angle in degrees from horizontal.
This dialog allows you to describe a wind generator supplying electrical power to the building.
Click on Define power curve to display the power curve parameters for editing.
You can use the default power curve or specify your own.
This dialog allows you to describe a combined heat and power plant supplying heat and
electrical power to the building.
As currently configured, the CHP system operates a heat matching strategy, attempting to
provide the heating needs of the building while generating electricity as a by-product. The
operation of the CHP plant is dependent on:
The enabling of the appropriate heating systems for CHP input.
The minimum and maximum power output of the CHP system.
The profile for heat matching.
Each heating system (Apache System, ApacheHVAC boiler or ApacheHVAC direct acting heater)
must be enabled for CHP input if it is to receive heat from the CHP system. This is done by
ticking the CHP box for the system in question. Next to the CHP box is a Boiler Ranking
parameter which allows you to specify the order in which the boilers are switched on when the
CHP system is either off or unable to meet the total heating load. Boilers with low Boiler
Ranking will be switched on first. These will normally be the most efficient. Where two boilers
The following properties define the performance of the generator at its rated output.
The following properties define the performance of the generator at its minimum heat output.
7.3.4 Profiles
Three types of thermal analysis may be carried out in the Apache view:
CIBSE Loads (ApacheCalc)
ASHRAE Loads
ApacheSim (Dynamic Simulation)
ASHRAE Loads replaces CIBSE Loads (ApacheCalc) when the Loads Methodology option in the
Settings menu is set to ASHRAE. Batch simulation allows a number of ApacheSim dynamic
simulations to be performed one after the next.
All of the batch simulation results are held in the Vista sub directory of the relevant project and
can be viewed in Vista.
9.2.1 Undo
9.2.2 Redo
9.2.3 Query
Use this option to edit or view or edit the attributes of a single selected object. The object may
be a room or a building element, depending on the current level of decomposition. In the case
of an element, with the decomposition mode set to adjacency, the Query function allows you to
edit the element’s thermal boundary condition.
9.2.4.2 Constructions
Launches the Assign Constructions dialog.
9.3.1 Toolbars
For the options on this menu, please refer to the ModelIT User Guide.
For the options on this menu, please refer to the ModelIT User Guide.
Opens Building Template Manager dialog to edit current Templates in the project.
9.4.2 APLocate
Opens the ShowMe Report Generator dialog, van be used to generate a report of model inputs.
Opens the Room Group Creator dialog, can be used to aid Room Groups generation.
9.4.5 Auto-save
For the options on this menu, please refer to the ModelIT User Guide.
9.4.7 Preferences
Edit User Preferences for project such as Units and ModelViewer settings.
9.4.8 ApPro
9.4.9 ApCDB
9.5.1 Save
This facility allows you to export the room data and geometry data to a text (.TXT) file, for
subsequent use in other applications (eg a spreadsheet).
9.6.1 Building
This option deals with parameters used in the calculation of carbon emissions and energy
consumptions.
‘Carbon emissions data for fuels’ lists the fuels available in the Apache and ApacheHVAC views
and allows you to set their carbon emission factors. Default figures can be chosen for both the
current Part L2 and Section 6 of the England & Wales and Scottish Building Regulations
respectively.
This option opens the Loads Methodology dialog box, and allows you to choose between
ASHRAE and CIBSE for steady state heat loss or heat gain calculations.
The calculate Loads button at the bottom of the Apache workspace displays the current selected
Loads methodology.
This options opens the Layer Properties dialog, and allows the manipulation of zone layer
properties. The Properties tab allows the user to swith layers ON/OFF. This option allows part
of the model to be made inactive (switched OFF). For the purpose of reducing the number of
thermal zones, rooms, or spaces during initial simulation runs or for isolating a particular
thermal zone, may sometimes be useful to place thermal zones on a separate layer that can
1. Thermal zones or three-dimensional spaces on layers that are turned OFF will be excluded
from thermal simulation. The icons for these zones will be grey in the Model Browser and such
spaces will not be present in the Model Viewer.
2. No solar gain will be present on exterior roofs, walls, fenestration, etc. for these zones.
3. No solar gain will be present on surfaces of interior walls, ceilings, etc. that are facing the
interior of these zones.
4. The SunCast calculations will not need to be re-run, so long as the geometry for the spaces
that remain active has not changed.
5. There will be no heat transfer in either direction across adjacencies where these zones abut
other zones i.e., shared walls, floors, ceilings, etc. will be treated as adiabatic.
6. For constructions of shared walls, floors, ceilings, etc., the physical properties of surfaces
facing into zones that remain on active layers will be unchanged. However, the thermal mass
effects of these shared constructions will be somewhat reduced. The boundary conditions for
conductive elements of the building are dictated by conditions in the spaces either side of the
element. These spaces may be internal or external. Where an adjacent room has been rendered
inactive (for example by it being assigned in inactive layer, or not being ticked for inclusion in a
<VE> Compliance analysis) the conditions on the far side are assumed to be identical to those on
the near side (a reflexive boundary condition). In this way the thermal mass of the element is
taken into account, while the time-averaged heat transfer through it tends to zero.
Refer to ApacheSim Calculation Methods section 3.5 Boundary Conditions for more information.
10.9 Query
Edit or view the attributes of a single selected object. The object may be a room or a building
element, depending on the current level of decomposition. In the case of an element, with the
decomposition mode set to adjacency, the Query function allows you to edit the element’s
thermal boundary condition.
10.12 Renewables
Edit or view renewables systems. The Renewables allow you to describe the characteristics of
systems supplying energy to the building such as photovoltaics, wind turbines and CHP.