Rcbos Ex9Nl-N 3P+N, 6 Ka
Rcbos Ex9Nl-N 3P+N, 6 Ka
■ 3+N-pole version
■ Rated currents up to 40 A
■ 4-module width
Ex9NL residual current circuit breakers are suitable for domestic as well as industrial applications. They are
based on combination of residual current device with permanent magnet principle and circuit breaker with
thermal overload release and magnetic short circuit current release. It brings the advantage of voltage inde-
pendent function of the residual current device. Adequate voltage is only necessary when testing the RCBO
with the T test button. Magnetic RCBOs should be tested regularly. Recommend is to test it every 6 months
in fair enviroment and every month in heavy condition.
Type Key
B _: AC 30 mA
Ex9 NL: RCBO -N: 6 kA 3P+N 6 — 40 A
C A: A 300 mA
Certification marks
1
RCBOs Ex9NL-N 3P+N, 6 kA
AC type, characteristic B
AC type, characteristic C
2
RCBOs Ex9NL-N 3P+N, 6 kA
A type, characteristic B
• A type of residual current circuit breaker sensitive on residual AC and pulsating DC current
• B characteristic of installed circuit breaker
• Without time delay
• Suitable for protection of people in case of direct and indirect contact with live parts and exposed conductive part during a fault,
respectively
A type, characteristic C
• A type of residual current circuit breaker sensitive on residual AC and pulsating DC current
• C characteristic of installed circuit breaker
• Without time delay
• Suitable for protection of people in case of direct and indirect contact with live parts and exposed conductive part during a fault,
respectively
3
Technical Data Ex9NL-N 3P+N
Residual Current Breakers with Overload protection Ex9NL-N 3P+N, 6 kA
General parameters
Combination of MCB and RCCB in one case - saves 50 % space in comparison to combination of stand-alone MCB and RCCB
Tripping characteristics of installed circuit breaker B and C
AC and A type of residual current device
3+N-pole version
Suitable for household as well as industrial applications
Permanent magnet priciple of residual current device - Voltage independent tripping function
Recommend is to test device every 6 months in fair enviroment and every month in heavy condition.
Signaling of contacts status
Electrical parameters
Tested according to IEC/EN 61009-1
Rated op. voltage Ue 400 V AC
Min. voltage for RCD function voltage independent
Voltage range of the test button T 340 — 440 V AC
Rated frequency 50/60 Hz
Rated breaking capacity Icn 6 kA
Rated current 6 — 40 A
Rated residual current 30, 300 mA
Sensitivity to residual current AC type - AC residual current
A type - residual AC and pulsating DC current
Time characteristic of RCD undelayed type
Tripping characteristics of MCB B, C
Rated impulse withstand voltage Uimp 4 kV
Rated insulation voltage Ui 500 V
Surge current proof 3000 A
Mechanical service life 10 000 operation cycles
Electrical service life 2 000 operation cycles
Selectivity class 3
Back-up fuse/breaker max. 125 A gG
Line voltage connection arbitrary above or below
Mechanical parameters
Device width 72 mm
Device height 82 mm including rail clip
Frame size 45 mm
Mounting easy fastening onto 35 mm device rail (DIN)
Degree of protection IP20
Terminals combined lift + open mouthed
Terminal capacity 1 — 16 mm2
Fastening torque of terminals 2Nm
Busbar thickness 0.8 — 1.5 mm
Ambient temperature -25 — +40 °C
Altitude ≤ 2000 m
Relative humidity ≤ 95 %
Resistance to humidity and heat class 2
Pollution degree 2
Installation class III
Weight 0.432 kg
4
Technical Data Ex9NL-N 3P+N
Residual Current Breakers with Overload protection Ex9NL-N 3P+N, 6 kA
L-N Ex9NL-N
Dimensions
RCBO
Proudový chránič s nadpr. ochr.
Prúdový chránič s nadpr. ochr.
1 4
Wyłącznik nadprąd. z mod. różnicowoprąd.
Intrerupator diferential/automate
34.5
45
86
FI/LS-Schalter
Interrupteur differential
ДAB
Автоматичен прекьсвач с вградена ДТЗ
60.7
Kombinovana diferencijalna zaštitna sklopka 72
77.5
6
Tripping characteristics of MCB
**O
Characteristic B Characteristic C
UT UT
L-N
Ex9NL-N
6
I I
**O **O
UT
UT
I
5
Technical Data Ex9NL-N 3P+N
Residual Current Breakers with Overload protection Ex9NL-N 3P+N, 6 kA
Power loss
In [A] 6A 10 A 13 A 16 A 20 A 25 A 32 A 40 A
P [W] 2.8 5.3 5.3 8.4 6.9 10.7 14.6 17.8