Main Engines Manual Fuel Treatment System Operations Manual
Main Engines Manual Fuel Treatment System Operations Manual
KFWA BY 1– 4
© Copyright 2015
Page 2
Table of contents
1 Introduction ............................................................................................................................................................ 5
1.1 Manufacturer .................................................................................................................................................................. 5
1.2 About these operating instructions ................................................................................................................................. 5
1.3 Typographical conventions ............................................................................................................................................ 6
1.3.1 Safety instructions .............................................................................................................................................. 6
1.3.2 Other instructions................................................................................................................................................ 6
1.4 Abbreviations ................................................................................................................................................................. 6
2 Safety ...................................................................................................................................................................... 7
2.1 Intended use .................................................................................................................................................................. 7
2.2 Qualification ................................................................................................................................................................... 7
2.3 Basic safety instructions ................................................................................................................................................ 7
2.3.1 Blocked evacuation routes.................................................................................................................................. 7
2.3.2 Live components ................................................................................................................................................ 7
2.3.3 Salt- and oil-containing media ............................................................................................................................ 8
2.3.4 Warning and mandatory signs ............................................................................................................................ 8
5 Assembly .............................................................................................................................................................. 15
5.1 Setup ........................................................................................................................................................................... 15
5.2 Assembly and disassembly of the piping ..................................................................................................................... 15
5.3 Electrical connection .................................................................................................................................................... 15
Page 3
7.4.2 Shutting down the system for a prolonged period (more than 48 hrs) .............................................................. 25
9 Troubleshooting .................................................................................................................................................. 30
9.1 Troubleshooting chart .................................................................................................................................................. 30
Page 4
1 Introduction
1.1 Manufacturer
These operating instructions are intended to help the operator make optimum use of the system. If
you refer to all of the instructions, you can avoid potential dangers and extend the life of the system.
These operating instructions are to assist personnel with special technical knowledge for operating
the system. If you have any further questions on the content of the operating instructions or opera-
tion of the system, please contact the manufacturer.
These operating instructions are included with the system. Read the operating instructions com-
pletely before putting the system into operation. Each person who works on and with the system
must have read and understood the operating instructions beforehand.
Always keep these operating instructions available on site. Enclosed instructions for use from man-
ufacturers of components are part of the operating instructions for the system. Further information
on individual components such as pumps and measuring devices can be found in the correspond-
ing instructions for use supplied by the relevant manufacturers.
Page 5
In these operating instructions four signal words are used to indicate different hazard severities.
Type of Hazard
Describes the consequences of the hazard. The consequences will be severe or fatal inju-
ry.
• Specifies the steps that must be taken to avoid the hazard.
Type of Hazard
Describes the consequences of the hazard. The consequences may be severe injury to
death.
• Specifies the steps that must be taken to avoid the hazard.
Type of Hazard
Describes the consequences of the hazard. The consequences may be minor injury.
• Specifies the steps that must be taken to avoid the hazard.
Type of Hazard
Describes the consequences of the hazard. The consequences may be material damage.
• Specifies the steps that must be taken to avoid the hazard.
1.4 Abbreviations
Page 6
2 Safety
The KFWA fuel treatment system is a system for automatically processing fuel. The system is in-
tended for fuel filtration and subsequent water separation.
The system may only be operated in accordance with order-specific performance data. Only
properly installed original spare parts may be used.
All other applications, unauthorised modifications or modes of operation as well as changes to the
system's hardware or software are considered contrary to the intended use and may result in im-
pairment of operational safety and void the warranty.
2.2 Qualification
The system may only be operated by qualified, experienced persons authorized by the owner. Spe-
cialist knowledge must be obtained through regular training.
Safety instructions are for the purpose of work safety and accident prevention.
To protect personnel from harm, all work on the system must be carried out attentively and with
care.
Please also refer to the safety regulations of the owner and the regulations applicable in the area in
which the system is operated.
Blocked evacuation routes and inaccessible working areas could cause serious injury or material
damage.
• Keep the working area free and accessible at all times.
• Never place objects in the working area.
• Ensure that no objects can fall or topple onto lines.
After an EMERGENCY STOP, certain components in the control cabinet are still live. Contact with
these components can lead to fatal or serious injury.
• Keep the control cabinet closed.
• In case of malfunctions, call in an electrician or contact the manufacturer.
Page 7
The collected medium and operating or cleaning fluids flowing out can cause environmental dam-
age and irritation of the skin upon contact.
• Keep a suitable tank at hand to catch residues and flushing quantities.
• Refer to product-specific safety regulations and datasheets.
• Wear protective clothing where necessary.
Page 8
3 General description
The KFWA fuel treatment system is a filter coalescer system. The fuel is pumped by a gear pump
from the inside to the outside through the coalescer element. The fuel first flows through the filter
layer and then the coalescing layer, where the water is separated. To separate the water, various
hydrophilic materials are incorporated into the coalescing element, which are able to retain very
small water droplets. After a certain time, the small water droplets combine into large drops of ap-
prox. 3 mm , which emerge from the element and sink to the bottom of the tank.
The accumulation of water is monitored by a level probe and emptied through the automatic water
drain valve when the maximum level is reached. The water drain valve opens and closes automati-
cally during ongoing operation of the system. No subsequent venting of the KFWA is necessary.
Contamination of the filter/coalescing element is monitored via differential pressure. When differen-
tial pressure reaches the value set for for the pre-alarm, a warning alert to this effect appears. If dif-
ferential pressure rises to the value set for the main alarm, another warning alert appears and the
element must be replaced immediately. If the element is not replaced, pressure will continue to rise
up to the predefined pressure at which the overflow valve opens. In this situation, the fuel is
pumped to the tank without being cleaned.
Page 9
Item Component
1 Splash guard
2 KFWA pressure tank with filter/coalescer elements
3 Differential pressure gauge, switch with 2 contacts for pre and main alarm
4 Control unit (control cabinet), with controls
5 Fuel pump, gear pump with electric motor, included separately
6 Shut-off valve
Page 10
Item Description
F1 Inlet
F2 Water drain
F3 Drain
F4 Vent/sampling point outlet
F5 Outlet
F6 Sampling inlet
Page 11
Item Description
A Customer-supplied bunker tank
B Customer-supplied prime mover
C Customer-supplied overflow
1 Fuel pump
2 2-stage filter water separator
3 Level probe (water level electrode)
4 Pressure gauge and ball valve
5 Ball drain valve
6 Dirt trap
7 Automatic water drain
8 Disco check valve (700 mbar ±15%)
9 Venting ball valve
10 Overflow valve, 3 bar
11 Control unit (control cabinet)
12 Differential pressure gauge
13 Ball valve (KFWA inlet)
14 Ball valve (KFWA outlet)
15 Sampling
Page 12
4 System control
The system control is programmed and set by Filtration Group GmbH. No custo-
mer-side settings can be made or changed.
Page 13
• Prior to switching on control voltage, make sure that the selector switch for operating mode Fig.
4 (10) is set to "Off".
• Switch on the system from from main switch Fig. 4 (8). The "Control voltage" indicator lamp
Fig. 4 (9) must go on.
• Turn selector switch Fig. 4 (10) to "On" position to start the system. The fuel pump Fig. 1 (5)
starts.
BMK in
accord-
Component ance with Function Setting value
wiring
diagram
75 kΩ
Electrode relay 2A1 Interface measurement
(500 kΩ/15%)
Time delay relay 2KT1 Max. drain valve opening time 3 minutes
Time delay relay 2KT2 Differential pressure alarm delay 1 minute
Differential pressure warning (pre-
Differential pressure 1.8 bar
2B2 alarm)
switch
Differential pressure alarm (main alarm) 2.0 bar
Page 14
5 Assembly
Prior to assembly, the system must be inspected for damage and the proper seating
of all installed and mounted parts. All systems have been subjected to a comprehen-
sive factory test, but parts may have become loose during transport however.
5.1 Setup
Pressure at interfaces
Personal injury or material damage.
• Depressurise all interfaces of the system prior to assembly or disassembly.
The required electrical supply is centrally located in the control cabinet. Connect the control cabinet
according to the wiring diagram.
Page 15
• Check vacuum line for dirt and foreign bodies and clean if necessary.
• Check piping connections and tighten if necessary.
• Tighten all screws.
• Close all drain valves on the enclosure.
• Open all intake and outlet valves.
• Open ball valve for the differential pressure contact gauge on intake and outlet connections.
Page 16
Page 17
The level probe may only be checked when the system is at a complete stop.
Page 18
8. Immerse the level probe up to the threading in a container filled with water (Fig. 7).
9. After being immersed, the water drain must automatically activate and open the water dis-
charge valve. Leave the level probe in the container to trigger the water alarm.
10. An alarm must ensue on the control after the predefined time (factory setting 3 minutes).
The functional test of the pump is used to determine the wear limit. If wear and tear has been
found, the pump should be immediately overhauled.
The pump may only be checked when the system is at a complete stop.
On the vacuum side the customer must provide on connector P4 (½“) a fine pressure
gauge (Fig. 8) that is removed after the test. The test of the gauge takes place at the
intake of the KFWA enclosure on the pressure side.
Page 19
1. Switch on the system, see Chapter 4.2 Switching on/starting on the system.
2. Slowly close ball valve F5 at the outlet of the KFWA, read and take note of the pressure on the
gauge.
Closing ball valve F5 may activate the pressure control valve on the pump. Any nois-
es are cause by overflowing fuel and may be ignored.
3. Leave the system switched on and check the pressure as described in the following chapter.
Page 20
1. Throttle the pump unit vacuum line creating a vacuum of 0.8 bar on the vacuum side of the
pump.
2. Again read and note down the pressure from the gauge on the pressure side of the pump.
3. Open ball valves F1 (on inlet of the KFWA) and F5 (on outlet of the KFWA).
If the pressure found in Chapter 6.5.1 is 10% lower than the pressure found in Chap-
ter 6.5.2, the wear limit of the pump has been reached. The pump should be over-
hauled immediately.
Sample calculation
• Pressure of 3 bar is found on the pressure side (see Chapter 6.5.1 Checking pump
pressure).
• After throttling to -0.8 bar on the vacuum side, pressure of 2.6 bar is measured on the pressure
side (see Chapter
Page 21
Page 22
Prior to initial start-up and following maintenance work, the system must first be filled and ventilat-
ed.
1. Switch on the system (see Chapter 4.2 Switching on/starting on the system).
2. Activate the fuel pump and check the direction of rotation.
3. Check the operating pressure on the pressure gauge.
4. During operation, carefully vent via ball valve F4.
5. Close ball valve F1 to vent the bypass line. The bypass line is vented via the service tank.
6. Open ball valve F1 again.
Initial differential pressure should not exceed 0.3 bar. The temperature and viscosity
of the medium must otherwise be checked.
If during initial operation or after replacing an element the differential pressure gauge
does not show any differential pressure this may be an indication of a bypass within
the system. In this event, check that the element in the KFWA is properly seated and
attached.
Page 23
Prior to the start of filtration, open all customer-provided fittings in the inlet and outlet
lines.
1. Prior to switching on control voltage, make sure that the selector switch Fig. 4 (10) for operating
mode is set to "Off".
2. Switch on the system from the main switch Fig. 4 (8). The "Control voltage" indicator lamp Fig. 4
(9) must go on.
3. Turn selector switch Fig. 4 (10) to "On" position.
→ The fuel pump starts. The fuel flows through the system and is filtered.
Page 24
No special monitoring is required during operation. Only the indicator lamps on the control cabinet
(Fig. 4) have to be monitored and any alarms have to be responded to.
However, the following checks must be performed on a daily basis:
• Operating and differential pressure
• Leak integrity of the system
• "Water drain" function
If the filter/coalescer element is soiled, differential pressure will rise above the predefined value and
an alarm message will ensue. If the element is not replaced, pressure will continue to rise until the
overflow valve Fig. 3 (10) on the bypass opens.
The fuel now flows into the bypass, past the KFWA, and into the service tank and the motor-side fil-
ters take over filtration. Water will no longer be separated from the fuel.
1. Stop Filtration mode: turn selector switch (Fig. 4) (10) to "Off" position.
→ The fuel pump stops.
2. Switch on the system from the main switch Fig. 4 (8).
7.4.2 Shutting down the system for a prolonged period (more than 48 hrs)
1. Stop Filtration mode: Turn selector switch Fig. 4 (10) to "Off" position.
→ The fuel pump stops.
2. Switch off the system from the main switch Fig. 4 (10).
3. Close the ball valves at the inlet and outlet of the system.
4. Check system pressure and reduce it if necessary via the drain.
Page 25
• Shut down the system, see Chapter 7.4 Taking the system out of service.
• Secure the system from being switched on without authorisation.
Page 26
The maintenance schedule depends on the specific use case. Check with Filtration
Group GmbH for details.
The dirt trap on the pump may only be replaced with the system is at a complete
stop.
Page 27
3. Loosen the four bolts 1 on the cover of the dirt trap and remove the cover.
4. Remove and clean the now accessible strainer from the dirt trap.
5. Insert the strainer into the dirt trap again and re-tighten the four bolts 1.
The filter/coalescer element may only be replaced when the system is at a complete
stop.
Page 28
3. Unscrew the nuts 2 on the tank cover. Remove the nuts, bolts 3 and washers and remove the
tank cover.
4. Remove the cover seal Fig. 13 (1) . The filter/coalescer element is now accessible.
5. Check the seal surfaces on the tank and cover and clean if necessary.
6. Remove the fixing nuts 4, sealing washers 8 and end plates 6 from the element.
Page 29
9 Troubleshooting
Major malfunctions are indicated by the indicator lamps on the system's control cabinet (see Chap-
ter 4.1 Controls and indicator lamps on the control cabinet).
• If an alarm message appears, find the components causing the malfunction and remedy it.
• Note (write) down the malfunction and specifically check during subsequent inspections
• If the cause of the malfunction cannot be found and/or it cannot be remedied, contact Filtration
Group GmbH.
Page 30
10 Technical data
Flow rate max. 800 l/h max. 2200 l/h max. 4400 l/h max. 8000 l/h
Operating temperature min. 2 °C to max. 45 °C
Ambient temperature max. 55 °C
Pre-alarm: 1,8 bar; Main alarm: 2,0 bar (see 4.3 Settings (facto-
Differential pressure alarm value
ry settings) for electrical components 4.3)
Maximum permissible operating pressure 6 bar
Minimum operating pressure 0.7 bar
Pressure loss Max. 2.7 bar
Electrical connection 400 V / 50 Hz or 440 V / 60 Hz
Control voltage 24 VAC
Pressure tank:
Design operating pressure 6 bar
Test pressure 9 bar
Materials:
Frame Sandblasted 2½, coated
Piping Sandblasted 2½, coated
Tank exterior Sandblasted 2½, coated
Tank interior Sandblasted SA 2½
Pump:
Flow rate ca. 670 l/h ca. 2000 l/h ca. 4400 l/h ca. 8000 l/h
Vacuum head max. 2 m
Discharge head min. 3 m
Overflow valve opening pressure 3 bar
Page 31
Page 32