SPEC-0221 - 1000 kVA (PT ADIJAYA)

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Address. Jl. Hayam Wuruk 4 FX, Jakarta 10120 To. PT ADIJAYA TEKNINDO Date.

7 FEBRUARI 2022
Phone. (62-21) 385 0703, 386 1865, 351 7113, 345 1384
Fax. (62-21) 385 0702, 386 1865 Spec No. 0221 / SP / 02 / 2022
Email. [email protected] ; [email protected]
www.trafoindonesia.com
Address. Jl. Siliwangi, Tangerang (Factory I, II, III & IV) 7. ACCESSORIES : The transformer will be furnished with all necessary accessories as follow :

GENERAL ACCESSORIES SPECIAL ACCESSORIES


SPECIFICATION FOR TRANSFORMER √ HV Porcelain Bushing on Cover - Plug in Bushing mm2 c/w straight connector on cover
√ LV Porcelain Bushing on Cover √ Integrated Safety Device c/w Contact
1. TYPE ONAN : self cooled / in / out door use / step-up / step-down / hermetically sealed distribution transformer - Oil Level Indicator w/o Contact - Oil Level Indicator c/w Alarm Contact
- Oil Temperature Indicator w/o Contact - Oil Temperature Indicator c/w Alarm & Trip Contact
2. SERVICE CONDITION : The transformer will be installed at the altitudes below 1,000 meters - Pressure Relief Valve w/o Contact - Pressure Relief Device c/w Alarm Contact
and the maximum ambient temperature does not exceed 40 o
C √ Name Plate - Winding Temperature Indicator c/w Alarm & Trip Contact
√ Earth Terminal - CT for Winding Temperature Indicator
3. STANDARD : The transformer is designed, manufactured tested and tolerance in accordance with : √ Manual Off-Load Tap Changer - Sudden Pressure Rise Relay + Seal in Relay c/w Alarm & Trip Contact
IEC 60076 - Voltage Change Over Board - Buchholz Relay c/w Alarm & Trip Contact
√ Radiator - Conservator c/w Sampling Valve
4. RATING √ Lifting Lug - Breather c/w Silicagel
4-1 Number of Phase : 3 phase 4-2 Frequency : 50 Hz √ Oil Filter Valve - Valve for Buchholz Relay
4-3 Primary Voltage : 11 kV 4-4 Secondary Voltage : 400 Volt √ Drain Valve - Pressure Vacuum Gauge c/w Bleeder
4-5 Rated Primary Current : 52.49 A 4-6 Rated Secondary Current : 1443.38 A √ Roller - N2 Filling Valve
Winding Connection : DELTA Winding Connection : WYE - Skid Base (Pad Mounted) - Air-filled LV Junction Box
4-7 Rated Capacity (total) : 1,000 kVA - Jacking Lug - HV/LV Cable Box
Incase of double primary voltage, Capacity will be : - Sampling Valve - Terminal Control Box
at : - kV Rated Capacity : - kVA - Ladder - Radiator Fans
at : - kV Rated Capacity : - kVA - Radiator Valves
Incase of double secondary voltage, Capacity will be : - Neutral CT
at : - V Rated Capacity : - kVA - Thermometer Pocket
at : - V Rated Capacity : - kVA
4-8 Additional Taps on High Voltage : +/- 2.5 % & +/- 5 % ( 5 Taps )
No. Routine Test
5. POLARITY AND PHASOR RELATIONSHIP : The transformer will be subtractive polarity and phasor relationship will be : Dyn-5 1 Breakdown voltage oil
2 Transformer Turn Ratio, Polarity & Vector group test
6. ELECTRIC PERFORMANCE : 3 Measurement of No load loss and Exciting current
Primary Voltage Secondary Voltage 4 Measurement of impedance and load loss
6-1 Highest System Voltage : 12 kV : 1.1 kV 5 Separate source voltage withstand test (Applied potential test)
6-2 Impulse Test Voltage : 75 kV : - kV 6 Induced potential test
6-3 Applied Test Voltage During 1 Minute : 28 kV : 3 kV 7 Insulation resistance test
6-4 Induced Voltage Test : Apply 2 times of the rate voltage at 200 cycles per second for 30 second 8 Winding resistance measurement
o
6-5 Temperature Rise : The winding temperature rise measured by resistance method will not exceed 65 C
o
and the oil temperature rise will not exceed 60 C * Painting System Stoving Min. 70 Micron
6-6 Losses at Rated Voltage Primary Side : 11 kV Secondary Side : 0.4 kV * Painting Color RAL 7023 (Concrete Grey)
No Load Losses : 1,900 Watt
Load Losses ( at 75 °C ) : 13,000 Watt
Total Losses : 14,900 Watt Note : - Winding Al - Al
6-7 Efficiency at % Rated Capacity : 100 75 50 25 %
at P.F. = 1.0 : 98.53 98.79 98.98 98.93 %
at P.F. = 0.8 : 98.17 98.49 98.73 98.66 %
6-8 Exciting Current / Off load Current at Nominal Voltage : 2.00 %
6-9 Percent Impedance : 5.00 %
6 - 10 Voltage Regulation at P.F. = 1.0 : 1.42 %
Voltage Regulation at P.F. = 0.8 : 3.98 % Date of Approval :
PROPOSER :

hp

TP/V.11-03/19 (Rev./ Tgl. Form : 0/29-07-2019)