Technical Specification-Npc
Technical Specification-Npc
FOR
18/30kV Underwater cables
1
www.npcelectric.com
1. GENERAL
This specification covers the structure and performance of the offered ‘18/30kV TR-XLPE Insulation 1C ×
70sq.mm. cable’ as manufactured by NPC ELECTRIC.
2. REFERENCE STANDARDS
The cable which NPC offered shall be designed, manufactured and tested according to standards as follows.
ISO 9001:2015 Quality Management Systems
ISO 14001:2015 Environmental Management Systems
OHSAS 18001:2007 Occupational health and safety management system
IEC 60228:2004 Conductors of insulated cables
Power cables with extruded insulation and their accessories for rated
IEC 60502-1: 2009 voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV)-Part 1: Cables for
rated voltage of 1kV(Um=1.2kV) and 3kV(Um=3.6kV)
Power cables with extruded insulation and their accessories for rated
IEC 60502-2:2014 voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 2: Cables
for rated voltages from 6 kV (Um = 7,2 kV) and up to 30 kV (Um = 36 kV)
Tests on electric cables under fire conditions – Part 1:Test on a single vertical
IEC 60332-1: 2004
insulated wire or cable
IEC 60332-3-24: Tests on electric cables under fire conditions-Part 3-24: Test for vertical flame
2009 spread of vertically-mounted bunched wires or cables –Category C
Measurement of smoke density of cables burning under defined
IEC 61034-2: 2005
conditions-Part 2: Test procedure and requirements
Test on gases evolved during combustion of electric cables – Part 1:
IEC 60754-1: 2011
Determination of the halogen acid gas content
Low-voltage electrical installations – Part 5-54: Selection and erection of
IEC 60364-5-54:2011
electrical equipment- Earthing arrangements and protective conductors
UL 2556 Wire and Cable Test Methods. Section 9.3: FT1 (Vertical-Specimen) Flame Test
IEC 60684-2 Flexible insulating sleeving - Part 2: Methods of test.
IEC 60754-1 Test on gases evolved during combustion of materials from cables - Part 1:
Determination of the halogen acid gas content.
IEC 61034-2 Measurement of smoke density of cables burning under defined conditions
ICEA S-93-639 5-46kV Shielded Power Cable for Use in the Transmission and Distribution of
Electric Energy. Section 9.4.2: Oil Immersion Test
ICEA S-66-524 Cross linked thermosetting polyethlene insulated wire and cable for the
transmission and distribution energy
ASTMB 400 Standard Specification for Compact Round Concentric-Lay-Stranded Aluminum
1350 Conductors
2
www.npcelectric.com
3. Cable Structure Single Core 18/30 kV cable - 70 mm²-aluminum:
TECHNICAL PARTICULARS
No. ITEMS UNIT
1*70 mm2
2 Rated Voltage kV 18/30
3 Number of Cores No. 1
4 Conductor
-- Cross sectional area mm2 70
-- Material Aluminum wires(water block conductor)
-- Type of conductor Circular compacted
-- Max. D.C. conductor resistance at 20’C Ω/km ≤0.443
-- Diameter of conductor mm 10.0
5 Conductor screen
-- Material Semi-conductive conductor screen
-- Nominal thickness mm 0.7
-- Diameter mm 11.4
6 Insulation
-- Material TR-XLPE
-- Nominal thickness mm 8.0
-- Diameter mm 7.4
7 Insulation screen
-- Material Semi-conductive insulation screen
-- Nominal thickness mm 0.7
-- Daimeter mm 28.8
8 Screen
-- Material Water blocking tape+Copper tape screen
-- Thicknes of the waterl blocking tape 0.3
-- Nominal thickness of copper tape mm 0.12
-- Thicknes of the waterl blocking tape mm 0.3
-- Diameter mm 30.7
3
www.npcelectric.com
9 Longitudinal water blocking layer
-- Material Aluminum/polyester tape
-- Thickness of Aluminium tape 0.25
10 Inner sheath
-- Material HDPE
-- Nominal thickness mm 2.10
-- Diameter mm 35.4
11 Armored
-- Material Aluminium wires+water blocking tape
-- OD of Aluminium wires mm 5.0
-- Number of the armor wires mm 23±4
-- Armor binder (synthetic tape) mm 0.2
-- Diameter mm 46.3
12 Outer sheath
-- Material HDPE
-- Nominal thickness mm 3.0
13 OD of the finished cable (Approx.) mm 52.3
14 Weight of the finished cable (Approx.) kg/km 3058.3
15 Min. bending radius at laying in terms of
D 15XD
cable diameter
16 Marking
18/30kV 1C×70SQM AL/TR-XLPE/CTS/HDPE/LAS/AWA/HDPE
IEC 605002-2 NPC ELECTRIC 001m .......
4
www.npcelectric.com
4. PERFORMANCE PARAMETER
Electrical Performance Parameter
Design voltage U(kV), insulation level 36.0
Frequency (Hz) 60
Max operation temperature of power conductor(℃) 90
Min. temperature for nominal operation(°C) -40
Max short circuit temperature of power conductor(℃) 250
Power conductor resistance @DC 20℃(Ω/km) 0.443
The Short circuit current of conductor 1s(Single Phase ) 6.8kA
Aluminum tape shield 1s short circuit current 2.8kA
Conductor AC resistance @ 90℃(Ω/km) 0.568
Reactancia Inductiva a 60 Hz (Ohm/km) 0.568
Capacidad Nominal (µF/km) 0.149
5
www.npcelectric.com
5. ROUTINE TEST AND SAMPLE TEST FOR INSULATED 18/30kV Underground water cable
18/30kV underground water cable shall be accordance with applicable standard of 18/30kV underground
water cable and requirements of customer. The following test items shall be carried out according to
corresponding reference.
No Item Reference
1 Dimensions /
6
www.npcelectric.com
6.PACKING
The required marking shall be printed with a weather-proof material on the outsides of drum according to the
customer requirement .
18/30kV 1C×70SQM 4200 3500 1600 2000 1800 800 13647.5 Steel Drums
7