Unidad Paquete ZF120C00
Unidad Paquete ZF120C00
Unidad Paquete ZF120C00
®
®
ZF12-1/2 TON
Table of Contents
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Capacity Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Sound Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Typical Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Economizer Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Component Location
Cooling With Gas Heat
Second model
nameplate Slide-out motor and
inside hinged blower assembly for
access panel easy adjustment
and service
Dual stage Belt-drive
cooling for blower motor
maximum
comfort VFD Location (optional)
Power ventor motor
Compressor #2
access (high- 20-gauge alumi-
efficiency nized steel tubular
compressor heat exchanger for
w/crankcase long life (stainless
heater) steel option)
Two-stage gas
Base rails w/forklift heating to maintain
slots (three sides) warm, comfortable
and lifting holes Slide-out drain pan temperature
with 3/4” NPT,
Roof curbs in eight- and female connection Intelligent control
fourteen-inch heights. Roof board for safe and
curbs for transitioning from efficient operation
Side entry power Compressor #1 access
York Sunline™ footprint to Toolless (high-efficiency compressor
the ZF Series footprints and control wiring
door latch knockouts w/crankcase heater)
are also available (field
installed accessory)
Nomenclature
N10 = 100 MBH Output Aluminized Steel Variable Air Volume, VFD Ready (for customer-provided, field-installed drive)
N15 = 150 MBH Output Aluminized Steel Variable Air Volume, VFD Ready with Simplicity®LINC
N20 = 200 MBH Output Aluminized Steel (for customer-provided, field-installed drive)
S10 = 100 MBH Output Stainless Steel 2" Pleated filters
S15 = 150 MBH Output Stainless Steel
S20 = 200 MBH Output Stainless Steel 4" Pleated filters
BAS Ready Economizer (2-10 V.D.C. Actuator without a Controller)
Electric Heat Options Shipping Bag
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned
E09 = 9 KW
E18 = 18 KW
Product Generation
E24 = 24 KW
E36 = 36 KW
E54 = 54 KW 5 = Fifth Generation
Additional Options
Airflow
AA = None AG = Coil Guard & Dirty Filter Switch
AB = Phase Monitor AH = Phase Monitor, Coil Guard & Dirty Filter Switch
A = Std. Motor
AC = Coil Guard RC = Coil Guard, Shipping Bag & American Flag
B = Std. Motor/Econo./Barometric Relief (Downflow
AD = Dirty Filter Switch TA = Technicoat Condenser Coil
Only)
AE = Phase Monitor & Coil Guard TJ = Technicoat Evaporator Coil
C = Std. Motor/Econo./Power Exhaust (Downflow Only)
AF = Phase Monitor & Dirty Filter Switch TS = Technicoat Evaporator & Condenser Coils
D = Std. Motor/Motorized Damper (Downflow Only)
E = Std. Motor/Horizontal Economizer (No Baro.)
F = Std. Motor/Slab Econo./Power Exhaust ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be
(Downflow Only) located in digits 15-18.
G = Std. Motor/Slab Econo./Barometric Relief
(Downflow Only)
N = Hi Static Installation Options
P = Hi Static/Econo./Barometric Relief
(Downflow Only) A = No Options Installed
Q = Hi Static/Econo./Power Exhaust B = Option 1
(Downflow Only) C = Option 2
R = Hi Static/Motorized Damper (Downflow Only) D = Options 1 & 2
S = Hi Static/Horizontal Economizer (No Baro.) E = Option 3
T = Hi Static/Slab Econo./Power Exhaust F = Option 4
(Downflow Only) G = Options 1 & 3
U = Hi Static/Slab Econo./Barometric Relief H = Options 1 & 4
(Downflow only) J = Options 1, 2 & 3
K = Options 1, 2, & 4
L = Options 1,3 & 4
M = Options 1, 2, 3, & 4
Voltage N = Options 2 & 3
P = Options 2 & 4
2 = 208/230-3-60 Q = Options 2, 3, & 4
4 = 460-3-60 R = Options 3 & 4
5 = 575-3-60 S = Option 5
T = Options 1 & 5
U = Options 1, 3, & 5
V = Options 1, 4, & 5
W = Options 1, 3, 4, & 5
X = Options 3 & 5
Y = Options 4 & 5
Z = Options 3, 4 & 5
Options
1 = Disconnect
2 = Non-Pwr'd Conv. Outlet
3 = Smoke Detector S.A.
4 = Smoke Detector R.A.
5 = Pwr'd Conv. Outlet
Features and Benefits • System Protection - Suction line freezestats are supplied
on all units to protect against loss of charge and coil frosting
Standard Features when the economizer operates at low outdoor air
• High Efficiency – High efficiency units reach as high as temperatures while the compressors are running. Every unit
11.2 EER. Gas/electric units have electronic spark ignition has solid-core liquid line filter-driers and high and low-
and power vented combustion with steady state efficiencies pressure switches. Internal compressor protection is
of 80%. These efficiencies exceed all legislated minimum standard on all compressors. Crankcase heaters are
levels and provide low operating costs. standard on reciprocating compressors. Scroll compressors
do not require crankcase heaters. Phase Monitors are
• Service Friendly – The Predator® incorporates a number
standard on units with scroll compressors. This accessory
of enhancements which improve serviceability.
monitors the incoming power to the unit and protects the
The motor and blower slide out of the unit as a common unit from phase loss and reversed phase rotation.
assembly. This facilitates greater access to all the indoor
• Advanced Controls - Simplicity® control boards have
airflow components, thus simplifying maintenance and
standardized a number of features previously available
adjustment.
only as options or by utilizing additional controls.
Service time is reduced through the use of hinged,
toolless panels. Such panels provide access to frequently • Low Ambient - An integrated low-ambient control
inspected components and areas, including the control allows all units to operate in the cooling mode down to
box, compressors, filters, indoor motor & blower, and the 0F outdoor ambient without additional assistance.
heating section. The panels are screwed in place at the Optionally, the control board can be programmed to
factory to prevent access by children or other lockout the compressors when the outdoor air temper-
unauthorized persons. It is recommended that the panels ature is low or when free cooling is available.
be secured with screws once service is complete.
Service windows have been placed in both condenser
section walls. Rotation of the cover allows easy access to
the condenser coils for cleaning or inspection.
Both the unit control board and ignition control board utilize The Simplicity® control board used in this product
flash codes to aid in diagnosis of unit malfunctions. Unique will effectively operate the cooling system down to
alarm codes quickly identify the source of the unit alarm. 0°F when this product is applied in a comfort cooling
application for people. An economizer is typically
All units use the same standard filter size. This
included in this type of application. When applying
standardization removes any confusion on which filter
this product for process cooling applications (com-
sizes are needed for replacement.
puter rooms, switchgear, etc.), please reference
The non-corrosive drain pan slides out of the unit to permit applications bulletin AE-011-07 or call the applica-
easy cleaning. The drain pan is accessed by removing the tions department for Unitary Products @ 1-877-
drain pan cover plate on the rear of the unit. Once the plate is UPG-SERV for guidance. Additional accessories
removed, the drain pan slides out through the rear of the unit. may be needed for stable operation at temperatures
All Predator® units have a second model nameplate below 30° F.
located inside the control access door. This is to prevent
deterioration of the nameplate through weathering. • Anti-Short Cycle Protection - To aid compressor life,
• Coil Technology – ZF condensers utilize Micro-Channel an anti-short cycle delay is incorporated into the stan-
“all aluminum” condensers which provide improved heat dard controls. Compressor reliability is further ensured
transfer capabilities and reduced charge volumes. by programmable minimum run times. For testing, the
anti-short cycle delay can be temporarily overridden
• Environmentally Aware – For improved Indoor Air
with the push of a button.
Quality, a combination of foil faced and elastometric
rubber insulation is used exclusively throughout the units. • Fan Delays - Fan on and fan off delays are fully pro-
• Balanced Heating – The Predator® offers “Ultimate grammable. Furthermore, the heating and cooling fan
Heating Comfort” with a balance between 1st and 2nd stage delay times are independent of one another. All units
gas heating. The first stage of a gas heat Predator® unit are programmed with default values based upon their
provides 60% of the heating capacity. Balanced heating configuration of cooling and heat.
allows the unit to better maintain desired temperatures. • Safety Monitoring - The control board monitors the
• Convertible Airflow Design – The side duct openings high and low-pressure switches, the freezestats, the
are covered when they leave the factory. If a side supply/ gas valve, if applicable, and the temperature limit
return is desired, the installer simply removes the two side switch on gas and electric heat units. The unit control
duct covers from the outside of the unit and installs them board will alarm on ignition failures, compressor lock-
over the down shot openings. No panel cutting is required. outs and repeated limit switch trips.
Convertible airflow design allows maximum field flexibility
• Nuisance Trip Protection and Strikes - To prevent
and minimum inventory.
nuisance trouble calls, the control board uses a “three
times, you’re out” philosophy. The high and low-pres-
sure switches and the freezestats must trip three times • Warranty - All models include a 1-year limited warranty
within two hours before the unit control board will lock on the complete unit. Compressors and electric heater
out the associated compressor. elements each carry a 5-year warranty. Aluminized steel
and stainless steel tubular heat exchangers carry a 10-
• On Board Diagnostics - Each alarm will energize a
year warranty.
trouble light on the thermostat, if so equipped, and
flash an alarm code on the control board LED. Each Factory Installed Options
high and low-pressure switch alarm as well as each
YORK® offers several equipment options factory installed, for
freezestat alarm has its own flash code. The control
the Predator®line.
board saves the five most recent alarms in memory,
and these alarms can be reviewed at any time. • Optional Factory Installed Economizers - Predator units
Alarms and programmed values are retained through offer a variety of optional factory installed economizers
the loss of power. with low leak dampers. The outdoor air enthalpy sensor
enables economizer operation if the outdoor enthalpy is
• Reliable – From the beginning – All units undergo less than the setpoint of the economizer logic module. See
computer automated testing before they leave the factory. economizer options section to determine the correct
Units are tested for refrigerant charge and pressure, unit economizer for your application.
amperage, and 100% functionality. For the long term – All
• Downflow Economizer - (With barometric relief) -
Predator® units are painted with a long lasting, powder
The economizer is provided with a single enthalpy input.
paint that stands up over the life of the unit. The paint
The economizer is 2% low leakage type, and is shipped
used has been proven by a 1000 hour salt spray test.
installed and wired. The installer needs only to
• Flexible Placement – All models and configurations assemble and mount the outdoor air hood (Provided).
share the same cabinet/footprint and thus the same roof The economizer has spring return, fully modulating
curb. You have the flexibility to set one curb and choose damper actuators and is capable of introducing up to
the correct tonnage size and heating option after the 100% outdoor air. As the outdoor air intake dampers
internal loads have been determined. open, the return air dampers close. The changeover
To further simplify planning and installation, Predator® ZF from mechanical refrigeration to economizer operation is
cabinets are designed to fit your roof. With the optional regulated by the standard single enthalpy input. There is
roof curb, the unit ductwork is designed to fit around 24” an optional input dual dry bulb available. To meet
on-center joists or between 48” on-center joists. regulated air standards, the economizer control accepts
The drain pan can be rotated to drain to either the front or an optional CO2 input for demand ventilation. With
the rear of the unit. Additionally, the drain pan can be single enthalpy input, the economizer control monitors
fitted to drain through the roof curb. As it is sometimes outdoor air. The dual enthalpy kit provides a second
difficult to have a level installation, the drain pan features input used to monitor the return air. With a dual input kit
a generous slope to ensure proper drainage. installed, the economizer control compares the values of
• Full Perimeter Base Rails – The permanently attached the two enthalpy or temperature inputs and positions the
base rails provide a solid foundation for the entire unit and dampers to provide the maximum efficiency possible.
protect the unit during shipment. The rails offer forklift • Horizontal Economizer - (Without barometric relief) -
access from 3 sides, and rigging holes are available so that All features of the downflow economizer exist except you
an overhead crane can be used to place the units on a roof. must order the duct mount barometric relief separately.
• Easy Installation – Gas and electric utility knockouts are You must order a 1EH0408 if you are installing a
supplied in the unit underside as well as the side of the unit. power exhaust. You can order a 1RD0411 Barometric
A clearly identified location is provided to mount a field Relief for horizontal flow economizers only.
supplied electrical disconnect switch. Utility connections can • BAS Ready Economizer -(With barometric relief) -
be made quickly and with a minimum amount of field labor. The economizer is provided with an actuator that
All units are shipped with 2” throw-away filters installed. requires a 2-10V DC input from an external source (i.e.,
field installed building automation system controller).
• Wide Range of Indoor Airflows – All indoor fan motors
Power exhaust options are available. The economizer is
are belt-drive type providing maximum flexibility to handle
2% low leakage type with spring return and fully
most airflow requirements. For high static applications,
modulating dampers capable of introducing up to 100%
factory installed alternate indoor fan motors are available.
outside air. Also include 2” pleated filters. BAS Ready
With the optional indoor fan motor, all units can supply
actuators have an adjustable auxiliary end-switch for
nominal airflow at a minimum of 1.5” ESP.
optional power exhaust control.
A variable air volume (VAV) option using a variable
For units with optional VAV or Simplicity® Intelli-
frequency drive is available on 6-1/2 through 12-1/2 ton,
Comfort™ control, a factory-installed, dry bulb sensor
ZF models for applications requiring a constant supply
determines if outdoor air temperature is low enough to
duct pressure. A differential pressure transducer is used
provide free-cooling operation. (Field-installed humidity
to monitor supply duct static pressure while a VAV control
sensors for either outdoor air or outdoor & return air
board provides a speed reference signal to the VFD to
streams are available for single enthalpy and differential
control the output of the indoor blower motor.
enthalpy configurations respectively).
•Slab Economizer for Energy Recovery Ventilators- If the drive will not fit in the allotted space, then it will have
(With barometric relief and Fresh Air Hood) - The to be mounted elsewhere; either within the building on a
economizer is provided with a single enthalpy input. The perpendicular wall which is not subjected to excessive
economizer is 2% low leakage type, and is shipped temperature, vibration, humidity, dust, corrosive gas,
installed and wired. The economizer has spring return, explosive gas, etc., or within an appropriate enclosure
fully modulating damper actuators and is capable of rated for outside installation to safeguard against
introducing up to 100% outdoor air. As the outdoor air moisture, dust and excessive heat. A terminal block
intake dampers open, the return air dampers close. The located in the control box is provided for field connection
changeover from mechanical refrigeration to economizer of the VFD controls.
operation is regulated by the standard single enthalpy • Aluminized Steel Gas Heat Exchanger - For
input. There is an optional input dual dry bulb available. applications in non-corrosive environments.
To meet regulated air standards, the economizer control
• Stainless Steel Gas Heat Exchanger - For applications
accepts an optional CO2 input for demand
in corrosive environments, this option provides a full
ventilation.With single enthalpy input, the economizer
stainless steel heat exchanger assembly.
control monitors outdoor air. The dual enthalpy kit
provides a second input used to monitor the return air. • Stainless Steel Drain Pan - An optional rust-proof
With a dual input kit installed, the economizer control stainless steel drain pan is available to provide years of
compares the values of the two enthalpy or temperature trouble-free operation in corrosive environments.
inputs and positions the dampers to provide the • Electric Heaters - The electric heaters range from 9kW to
maximum efficiency possible. 54kW and are available in all the voltage options of the
• Power Exhaust (Downflow only) - This accessory base units. All heaters are dual staged. All heaters are
installs in the unit with a down flow economizer. intended for single point power supply.
• Motorized Outdoor Air Damper - The motorized outdoor • Disconnect Switch - For gas heat units and cooling units
air damper includes a slide-in/plug-in damper assembly with electric heat, a HACR breaker sized to the unit is
with an outdoor air hood and filters. The outdoor air provided. For cooling only units, a switch sized to the
dampers open to the preset position when the indoor fan largest electric heat available for the particular unit is
motor is energized. The damper has a range of 0% to provided. Factory installed option only.
100% outdoor air entry. Factory installed option or field • Convenience Outlet - (Non-Powered/Powered) - This
installed accessory. option locates a 120V single-phase GFCI outlet with cover,
• Alternate Indoor Blower Motor - For applications with on the corner of the unit housing adjacent to the
high static restrictions, units are offered with optional compressors. The “Non-powered” option requires the
indoor motors that provide higher static output and/or installer to provide the 120V single-phase power source and
higher airflow, depending upon the installer’s needs. wiring. The “Powered” option is powered by a stepdown
transformer in the unit. Factory installed option only.
• Variable Air Volume (VAV); 6-1/2 through 12-1/2 ton -
A factory-installed variable frequency drive (VFD), • Smoke Detectors - The smoke detectors stop operation
mounted in the Blower Access compartment, is used to of the unit by interrupting power to the control board if
control the speed of the indoor blower motor in order to smoke is detected within the air compartment. Available
maintain a constant static pressure in the supply duct. A for both the supply and/or return air configurations.
pressure transducer and VAV control board are mounted • Filters – 2” Pleated MERV 7 or 4” Pleated MERV 13 are
inside the control box. The drive comes completely wired available to meet LEED requirements. A 2” Throwaway is
and preprogrammed from the factory. shipped as standard.
An optional, factory-installed manual bypass switch
available with factory-installed VFD can be found in the
Blower Motor Access compartment. The switch can be
used to either route power to the VFD for modulating
control of the blower motor, to bypass the drive and Factory-installed smoke detectors may be subjected to
operate the motor at full speed, or to power the drive (and extreme temperatures during "off" times due to outside air
not the motor) for diagnostic purposes. infiltration. These smoke detectors have an operational
range of -4 °F to 158°F. Smoke detectors installed in areas
Due to space limitations, VAV is not available with any of
that could be outside this range will have to be relocated to
the factory-installed BAS options, but is available with
prevent false alarms.
‘BAS-ready’ models. Terminal blocks are provided in the
control box for field wiring of the customer-installed BAS • Phase Monitors - Designed to prevent unit damage. The
A ‘VFD-ready’ option provides the provisions for a phase monitor will shut the unit down in an out-of phase
customer-installed drive. The unit comes with a mounting condition. (Standard on units with Scroll Compressors.)
bracket installed in the Blower Access compartment which • Coil Guard - Customers can purchase a coil guard kit to
may accommodate other vendor’s drives depending on protect the condenser coil from damage. Additionally, this
their size. In order to utilize the unit’s mounting bracket, kit stops animals and foreign objects from entering the
the maximum recommended drive dimensions are limited space between the inner condenser coil and the main
to approximately 9” H x 5” W x 7.5” D. cabinet. This is not a hail guard kit.
• Dirty Filter Switch - This kit includes a differential factory installed. Includes supply air sensor, return air
pressure switch that energizes the fault light on the unit sensor, dirty filter indicator switch, and air proving switch.
thermostat, indicating that there is an abnormally high • CPC BAS Control - The Computer Process Controls
pressure drop across the filters. Factory installed option or Model 810-3060 ARTC Advanced Rooftop building
field installed accessory. automation system controller is factory installed. Includes
• Technicoat Condenser Coils - The condenser coils are supply air sensor, return air sensor, dirty filter indicator
coated with a phenolic coating for protection against switch and air proving switch.
corrosion due to harsh environments. • Honeywell BAS Control - The Honeywell W7750C
• Technicoat Evaporator Coil - The evaporator coils are building automation system controller is factory installed.
coated with a phenolic coating for protection against Includes air supply sensor, return air sensor, dirty filter
corrosion due to harsh environments. indicator switch, and air proving switch.
• Hot Gas Bypass - Allows operation during low load • York Commercial Comfort System (YCCS) - Provides
conditions while avoiding coil frosting and damage to rooftop system integration for YCCS single zone and
compressor. When suction pressure falls below valve change-over bypass systems (Not offered on ZR units.).
setpoint, the valve modulates hot gas to the inlet of the
evaporator. Field Installed Accessories
HGBP is standard on all units with VAV, and optional with YORK® offers several equipment accessories for field
constant-volume units. installation, for the Predator® line.
• Downflow Economizer - (With barometric relief) - The
Control Options economizer is provided with a single enthalpy input. The
• BAS - Building Automation System Controls Simplicity® economizer is 2% low leakage type. The economizer has
INTELLI-Comfort™ Control - The York® Simplicity® spring return, fully modulating damper actuators and is
INTELLI-Comfort™ control is factory installed. It includes a capable of introducing up to 100% outdoor air. As the
supply air sensor, a return air sensor, and an outside air outdoor air intake dampers open, the return air dampers
sensor. There are provisions for a field installed dirty filter close. The changeover from mechanical refrigeration to
indicator switch, an air-proving switch, an Outside Air economizer operation is regulated by the standard single
Humidity sensor, a Return Air Humidity sensor, an Inside enthalpy input. There is an optional input dual dry bulb
IAQ sensor, and an Outside Air IAQ sensor. Construction available. To meet regulated air standards, the economizer
mode operation, 365-day real time clock with 7 day control accepts an optional CO2 input for demand
programming plus holiday scheduling is built-in. Two ventilation. With single enthalpy input, the economizer
different modes of demand ventilation are achieved through control monitors outdoor air. The dual enthalpy kit provides a
the INTELLI-Comfort™ using CO2 sensors. It uses an second input used to monitor the return air. With a dual input
inside CO2 sensor to perform Demand Ventilation. It can kit installed, the economizer control compares the values of
also use an Outside CO2 sensor to perform Differential the two enthalpy or temperature inputs and positions the
Demand Ventilation. It uses a Patented Comfort Ventilation dampers to provide the maximum efficiency possible.
algorithm to provide comfortable ventilation air • Horizontal Economizer - (Without barometric relief) -
temperature. The patented economizer-loading algorithm All features of the downflow economizer exist except you
will protect the equipment when harsh operating conditions must order the duct mount barometric relief separately.
exist. Humidity in the occupied space or return duct can be You must order a 1EH0408 if you are installing a
monitored and controlled via humidity sensors and the on- power exhaust. You can order a 1RD0411 Barometric
board connection for hot gas re-heat system. It uses the Relief for horizontal flow economizer.
INTELLI-Start™ algorithm to maximize energy savings by • Slab Economizer for Energy Recovery Ventilator-
recovering the building from the Unoccupied Setpoints to (Without barometric relief or Fresh Air Hood) - The
the Occupied Setpoints just in time for the Occupied Time economizer is provided with a single enthalpy input. The
Period to begin. The Simplicity® INTELLI-Comfort™ economizer is 2% low leakage type. The economizer has
balances space temperature, ventilation air temperature, spring return, fully modulating damper actuators and is
CO2 and humidity for ultimate comfort. capable of introducing up to 100% outdoor air. As the
• Simplicity® INTELLI-Comfort™ with Simplicity®LINC outdoor air intake dampers open, the return air dampers
Control - The York® Simplicity® INTELLI-Comfort™ with close. The changeover from mechanical refrigeration to
Simplicity®LINC control is factory installed. It includes all economizer operation is regulated by the standard single
the features of the INTELLI-Comfort™ control with an enthalpy input. There is an optional input dual dry bulb
additional control to translate communications from available. To meet regulated air standards, the economizer
MODBUS to the BACnet MSTP protocol. control accepts an optional CO2 input for demand
• Novar® BAS Control - The Novar® building automation ventilation.With single enthalpy input, the economizer control
system controller is factory installed. Incudes supply air monitors outdoor air. The dual enthalpy kit provides a
sensor, return air sensor, dirty filter indicator switch, and second input used to monitor the return air. With a dual input
air proving switch. kit installed, the economizer control compares the values of
• Johnson Controls BAS Control - The Johnson Control the two enthalpy or temperature inputs and positions the
YK-UNT-1126 building automation system controller is dampers to provide the maximum efficiency possible.
You can order 1EH0409 Barometric Relief/FA Hood for valve and controls will continue to function properly at
field installations without an ERV. extremely low temperatures.
• Dual Enthalpy Control, Accessory - This kit contains • Gas Heat High Altitude Kit - This kit converts a gas heat
the required components to convert a single enthalpy unit to operate at high altitudes, 2,000 to 6,000 feet.
economizer to dual enthalpy. Conversion kits are available for natural gas and propane.
• Barometric Relief Damper - Zero to 100% capacity • Gas Heat Propane Conversion Kit - This kit converts a
barometric relief dampers for use with horizontal flow, or gas-fired heater from natural gas to propane. It contains the
field installed slab economizers. main burner orifices and gas valve replacement springs.
• Power Exhaust - This accessory installs in the unit with a • Gas Piping Kit - Contains pipe nipples, fittings and gas cock
down flow economizer. Power exhaust plugs into the required for gas supply connection with external shut off.
connector in the unit bulkhead. You must purchase • Electric Heaters - The electric heaters range from 9 kW
1EH0408 barometric relief when applying to a to 54kW and are available in all the voltage options of the
horizontal flow application. base units. The 54kW/208-240 volt, Field-installed heater
• Manual Outdoor Air Damper - Like the motorized outdoor kit is not available with VAV units due to a lack of space to
air damper, each manual outdoor air damper includes a accommodate the heater’s fuse block accessory.
slide-in damper assembly with an outdoor air hood and All heaters are dual staged. Cooling units include an
filters. Customers have a choice of dampers with ranges of adapter panel for easy installation of the electric heaters.
0% to 100% or 0% to 35% outdoor air entry. Necessary hardware and connectors are included with the
• Motorized Outdoor Air Damper - The motorized outdoor heaters. All heaters are intended for single point power
air damper includes a slide-in/plug-in damper assembly with supply.
an outdoor air hood and filters. The outdoor air dampers • Low Limit / Compressor Lockout Kit
open to the preset position when the indoor fan motor is
• Compressor Lockout (CLO): To prevent mechanical
energized. The damper has a range of 0% to 100% outdoor
(compressorized) operation of the unit during cold
air entry. Factory installed option or field installed accessory.
outdoor conditions where there is a risk of returning
• Smoke Detectors - The smoke detectors stop operation liquid refrigerant back to the compressors.
of the unit by interrupting power to the control board if
• Low Limit Control (LLC): To prevent the supply air
smoke is detected within the air compartment.
from dropping below a specified setpoint by utilizing the
• CO2 Sensor - Senses CO2 levels and automatically units first stage heating means when there is a demand
overrides the economizer when levels rise above the for cooling during cold outside conditions.
preset limits.
• Metal Frame Filter Kit - Metal frame with polyester filter
• Dirty Filter Switch - This kit includes a differential medium.
pressure switch that energizes the fault light on the unit
• Permanent Filters - Permanent filters are available.
thermostat, indicating that there is an abnormally high
pressure drop across the filters. • Roof Curbs - The roof curbs have insulated decks and are
• Coil Guard - Field installed decorative wire coil guard. shipped disassembled The roof curbs are available in 8” and
14” heights. For applications with security concerns, burglar
• Hail Guard - This kit includes a sloped hood which installs
bars are available for the duct openings of the roof curbs.
over the outside condenser coil and prevents damage to
the coil fins from hail strikes. Field installed accessory only. • Roof Curb Transition - Single Piece Adapter (10” High) -
Roof curbs for transitioning from Sunline™ units to
• Flue Exhaust Extension Kit - In locations with wind or
Predator® units. Fits 7.5 to 12.5 Sunline™ roof curbs only.
weather conditions which may interfere with proper
exhausting of furnace combustion products, this kit can be • Burglar Bars - Mount in the supply and return openings
installed to prevent the flue exhaust from entering nearby to prevent entry into the duct work.
fresh air intakes. • Thermostat - The units are designed to operate with 24-
• -60°F Gas Heat Kit - For installations which require gas volt electronic and electro-mechanical thermostats. All
heat units to perform in low ambient temperatures, a gas units (with or without an economizer) operate with two-
section heating kit is available. This kit provides electric stage heat/two-stage cool or two-stage cooling only
heat in the gas heat controls section to ensure the gas thermostats, depending upon unit configuration.
Accessories
Field Installed Acessories - Non-Electrical
MODEL VOLTAGE DESCRIPTION WHERE USED
1BD0408 All Burglar Bars, Downflow All Cabinets
1CG0419 All Coil Guard (Electric / Electric Models), 50” Tall Standard Cabinets
1CG0420 All Coil Guard (Gas / Electric Models), 50" Tall Standard Cabinets
1CG0427 All Coil Guard (Electric / Electric Models), 42” Tall Cabinets
1CG0428 All Coil Guard (Gas / Electric Models), 42" Tall Cabinets
All Tall (50") Standard Cabinets, (Excludes 12.5T "V"
1HG0411 All Hail Guard Kit cabinets)
1HG0415 All Hail Guard Kit All Short (42") Standard Cabinets
1FE0411 All Flue Exhaust Extension Kit All Cabinets
1FF0414 All 2" only Metal Filter Frame Kit All Tall 50" Cabinets
1FF0415 All 2" only Metal Filter Frame Kit All Tall 42" Cabinets
1FL0402 All Permanent 2" only Filter Kit Includes (4) Four Filters) All Tall 50" Cabinets
1FL0423 All Permanent 2" only Filter Kit (Includes (4) four Filters) All Tall 42" Cabinets
1GP0405 All Gas Piping Kit All Cabinets
1HA0442 All High Altitude Kit for Natural Gas All 6 - 12T Cabinets
1HA0443 All High Altitude Kit for Propane All 6 - 12T Cabinets
1NP0442 All Propane Conversion Kit All 6 - 12T Cabinets
1RC0470 All Roof Curb, 8" Height All Cabinets
1RC0471 All Roof Curb, 14" Height All Cabinets
Roof Curb, Transition (7.5 T thru 12.5T Sunline to
1RC0472 All Predator 3- 12T) All Cabinets
Wooden Crate for extra protection during shipping and Standard Cabinets Only (not applicable to units 119" in
1WC0412 All handling length)
Accessories (Continued)
Field Installed Acessories - Fresh Air
MODEL VOLTAGE DESCRIPTION WHERE USED
Barometric Relief Kit for Power Exhaust, Downflow
All
1EH0407 Application (Includes Hood) All Cabinets
Barometric Relief Kit for Power Exhaust, Horizontal
1EH0408 All Application All Cabinets
Barometric Relief/Hood Kit - Required for field installed
1EH0409 All slab economizer without ERV All Cabinets
1FA0413 All Manual Outside Air Damper 0-35%, Downflow All Cabinets
1FA0414 All Manual Outside Air Damper 0-100%, Downflow All Cabinets
1RD0411 All Barometric Relief Kit for Horizontal Applications All Cabinets
2EC04700924 All Dual Enthalpy Control All Cabinets
Downflow Economizer, Slab type for ERV, (no
2EE04705724 All Barometric Relief or FA hood) All 50" Cabinets
Downflow Economizer, Slab type for ERV, (no
2EE04705824 All Barometric Relief or FA hood) All 42" Cabinets
2EE04705924 All Downflow Economizer with Barometric Relief All Cabinets
2EE04706024 All Horizontal Economizer without Barometric Relief All Cabinets
2MD04703224 All Motorized Damper, Downflow without Barometric Relief All Cabinets
2MD04703724 All Motorized Damper, Horizontal All Cabinets
2PE04703225* 230 Power Exhaust 230V Downflow or Horizontal All Cabinets
2PE04703246* 460 Power Exhaust 460V Downflow or Horizontal All Cabinets
2PE04703258* 575 Power Exhaust 575V Downflow or Horizontal All Cabinets
* Must be installed in return Duct on Horizontal Applications and a 1EH0408 is required.
GAS HEATING SECTION (IF EQUIPPED) intake dampers shall not exceed 2% when dampers are
fully closed and operating against a pressure differential
Heat exchanger and exhaust system shall be constructed of of 0.5 IWG. A unit-mounted potentiometer shall be
aluminized steel and shall be designed with induced draft com- provided to adjust the outdoor and return air damper
bustion with post purge logic, energy saving direct spark igni- assembly to take in outdoor air to meet the minimum
tion, and redundant main gas valve. The heat exchanger shall ventilation requirement of the conditioned space during
be of the tubular type, constructed of T1-40 aluminized steel for normal operation. During economizer operation, a mixed-
corrosion resistance and allowing minimum mixed air entering air temperature control shall modulate the outdoor and
temperature of 40 ºF. Burners shall be of the in-shot type, con- return air damper assembly to prevent the supply air
structed of aluminum-coated steel. All gas piping shall enter the temperature from dropping below 55 ºF. Changeover from
unit cabinet at a single location, through either the side or bot- compressor to economizer operation shall be provided by
tom, without any field modifications. An integrated control board an integral electronic enthalpy control that feeds input into
shall provide timed control of evaporator fan functioning and the basic module. The outdoor intake opening shall be
burner ignition. Heating section shall be provided with the fol- covered with a rain hood that matches the exterior of the
lowing minimum protection: unit. Water eliminator/filters shall be provided.
a. Primary and auxiliary high-temperature limit switches. Simultaneous economizer/compressor operation is also
possible. Dampers shall fully close on power loss.
b. Induced draft pressure sensor. Available with barometric relief or power exhaust.
c. Flame roll out switch (manual reset). • MOTORIZED OUTDOOR AIR DAMPERS – Outdoor and
return air dampers that are interlocked and positioned by
d. Flame proving controls.
a 2-position, spring-return damper actuator. The
e. All two stage units shall have two independent stages of maximum leakage rate for the outdoor air intake dampers
capacity (60% 1st stage, 100% 2nd stage). shall not exceed 2% when dampers are fully closed and
operating against a pressure differential of 0.5 IWG. A
ELECTRIC HEATING SECTION (IF EQUIPPED) unit-mounted potentiometer shall be provided to adjust
the outdoor and return air damper assembly to take in the
An electric heating section, with nickel chromium elements,
design CFM of outdoor air to meet the ventilation
shall be provided in a range of 9 thru 54 KW, offering two states
requirements of the conditioned space during normal
of capacity all sizes. The heating section shall have a primary
operation. Whenever the indoor fan motor is energized,
limit control(s) (automatic reset) to prevent the heating element
the dampers open up to one of two pre-selected positions
system from operating at an excessive temperature. The Heat-
– regardless of the outdoor air enthalpy. Dampers return
ing Section assembly shall slide out of the unit for easy mainte-
to the fully closed position when the indoor fan motor is
nance and service. Units with Electric Heating Sections shall be
de-energized. Dampers shall fully close on power loss.
wired for a single point power supply with branch circuit fusing
(where required). ADDITIONAL FACTORY INSTALLED OPTIONS
UNIT OPERATING CHARACTERISTICS • ALTERNATE INDOOR BLOWER MOTOR – For
applications with high restrictions, units are available with
Unit shall be capable of starting and running at 125 ºF outdoor
optional indoor blower motors that provide higher static
temperature, exceeding maximum load criteria of ARI Standard
output and/or higher airflow.
340/360. The compressor, with standard controls, shall be
capable of operation down to 0 ºF outdoor temperature. Unit • Variable Air Volume (VAV) – The VAV option using a
shall be provided with fan time delay to prevent cold air delivery varible frequency drive (VFD) shall be available on 6-1/2
before heat exchanger warms up. (Gas heat only) through 12-1/2 ton, models for applications requiring a
constant supply-duct static pressure. Unts equipped for
ELECTRICAL REQUIREMENTS - All unit power wiring shall VAV shall be controlled by a duct pressure transducer
enter unit cabinet at a single factory provided location and be with a 0 - 5” WC pressure range. The pressure transducer
capable of side or bottom entry to minimize roof penetrations shall provide a 0 - 5 VDC output signal to a VAV control
and avoid unit field modifications. Separate side and bottom board which, in turn shall provide a 2 - 10 VDC speed
openings shall be provided for the control wiring. reference signal to the VFD. The VAV control board shall
operate using factory-installed Supply Air, Return Air and
STANDARD LIMITED WARRANTIES - Compressor – 5 Years,
Outside Air Temperature Sensors with a nominal
Heat Exchanger – 10 Years, Elect. Heat Elem. – 5 Years,
resistance of 10,000 Ohms. Units equipped with VFD’s
Parts – 1 Year
shall have factory-installed manual bypass as an option.
FACTORY INSTALLED OPTIONAL OUTDOOR AIR (Shall be • CONVENIENCE OUTLET (POWERED/NON-POWERED)–
made available by either/or): Unit can be provided with an optional 120VAC GFCI outlet
• ELECTRONIC ENTHALPY AUTOMATIC ECONOMIZER with cover on the corner of the unit housing the compressors.
– Outdoor and return air dampers that are interlocked and • ELECTRIC HEAT - Electric Heaters range from 9 kW to
positioned by a fully-modulating, spring-return damper 54 kW and are available in all the voltage options of the
actuator. The maximum leakage rate for the outdoor air base unit.
• PHASE MONITOR - Designed to prevent damage in out- OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
of-phase condition.
• ROOF CURB - 14” and 8” high, full perimeter knockdown
• COIL GUARD - Designed to prevent condenser coil
curb, with hinged design for quick assembly.
damage.
• BAROMETRIC RELIEF DAMPER – (Unit mounted –
• BAS CONTROLS - Include supply air sensor, return air
Downflow, Duct Mounted – Horizontal) – Contains a rain
sensor, dirty filter indicator and air proving switch.
hood, air inlet screen, exhaust damper and mounting
• DIRTY FILTER SWITCH – This kit includes a differential hardware. Used to relieve internal air pressure through
pressure switch that energizes the fault light on the unit the unit during economizer operation.
thermostat, indicating that there is an abnormally high-
• PROPANE CONVERSION KIT – Contains new orifices
pressure drop across the filters.
and gas valve springs to convert from natural to L.P. gas.
• BREAKER – An HACR breaker can be factory installed
• 60ºF GAS HEAT KIT – Provides an electric heat kit for the
on gas heat units or cooling units with electric heat.
gas compartment for use in extreme low ambient
• DISCONNECT SWITCH - A disconnect can be factory conditions.
installed on a cooling only units sized for the largest
• ECONOMIZER (Downflow and Horizontal flow)
electric heat available.
• POWER EXHAUST – (Unit mount – Downflow, Duct
• STAINLESS STEEL HEAT EXCHANGER – For
mount – Horizontal flow)
applications in a corrosive environment, this option
provides a full stainless steel heat exchanger assembly. • DUAL ENTHALPY KIT - Provides a second input to
economizer to monitor return air.
• SMOKE DETECTOR – A smoke detector can be factory
mounted and wired in the supply and/or return air
compartments.
Physical Data
Capacity Performance
ZF078-150 Cooling Capacities
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Airflow Performance
ZF078-150 Side Duct Application
RPM Selection
Size Max Motor Blower 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn Fully
Model HP
(Tons) BHP Sheave Sheave Open Open Open Open Open Open Closed
078 1.5 1.73 1VM50 AK74 N/A 887 936 986 1035 1084 1134
ZF
(6.5) 2 2.30 1VM50 AK64 N/A 1039 1094 1150 1207 1256 1308
090 1.5 1.73 1VM50 AK74 N/A 887 936 986 1035 1084 1134
ZF
(7.5) 3 3.45 1VM50 AK61 N/A 1088 1147 1205 1265 1312 1365
102 2 2.30 1VM50 AK94 N/A 690 728 767 805 843 882
ZF
(8.5) 3 3.45 1VM50 AK74 N/A 887 936 986 1035 1084 1134
120 2 2.30 1VM50 AK84 N/A 776 819 863 906 949 992
ZF
(10) 3 3.45 1VM50 AK74 N/A 887 936 986 1035 1084 1134
150 3 3.45 1VM50 AK74 N/A 887 936 986 1035 1084 1134
ZF
(12.5) 5 5.75 1VP56 BK77 1052 1095 1136 1175 1216 1272 N/A
Drive Selection
1. 2600 CFM
2. 1.6 iwg
3. Using the supply air blower performance table below, the following data point was located: 1268 RPM & 1.95 BHP.
4. Using the RPM selection table below, Size X and Model Y is found.
5. 1.95 BHP exceeds the maximum continuous BHP rating of the 1.5 HP motor. The 2 HP motor is required.
6. 1268 RPM is within the range of the 2 HP drives.
7. Using the 2 HP motor and drive, .5 turns open will achieve 1268 RPM.
Airflow Performance
1.100
1.050
1.000
Sea Level
0.950
Correction Factor
1000 ft
0.900 2000 ft
3000 ft
0.850
4000 ft
0.800 5000 ft
6000 ft
0.750 7000 ft
8000 ft
0.700
9000 ft
10000 ft
0.650
0.600
40 50 60 70 80 90 100
Air Temperature (ºF)
Sound Performance
Indoor Sound Power Levels
Sound Power, dB (10-12) Watts
Size ESP Blower
Model CFM Sound Rating1 Octave Band Centerline Frequency (Hz)
(Tons) (IWG)
RPM BHP dB (A) 63 125 250 500 1000 2000 4000 8000
078
ZF 2600 0.6 812 1.14 74 71 73 73 71 69 65 65 60
(6.5)
090
ZF 3000 0.6 854 1.47 77 74 76 76 74 72 68 68 63
(7.5)
102
ZF 3400 0.6 872 1.65 80 77 79 79 77 75 71 71 66
(8.5)
120
ZF 4000 0.6 959 2.29 83 80 82 82 80 78 74 74 69
(10)
150
ZF 5000 0.6 1132 3.74 87 84 86 86 84 82 78 78 73
(12.5)
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric/free field. The dBA values
provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way
of knowing the details of each system. This constitutes an exception to any specification or guarantee requiring a dBA value of sound data
in any other form than sound power level ratings.
Electrical Data
Typical ZF078-120 Cooling Unit with Gas Heat 460/575 Volt Wiring Diagram
Typical ZF150 Cooling Unit with Gas Heat 230 Volt Wiring Diagram
Typical ZF150 Cooling Unit with Gas Heat 460/575 Volt Wiring Diagram
Typical ZF078-150 Factory Installed VFD and Manual Bypass with CCS Control (Option)
Typical ZF078-150 BAS Ready Unit with Factory Installed VFD (Option)
Typical ZF078-150 BAS Ready Unit with Factory Installed VFD and Manual Bypass (Option)
FRONT
FRONT
LEFT LEFT
B C C D
A B
A
E
D F
Y
X
FRONT
LEFT
Size Weight (lbs.) Center of Gravity 4 Point Load Location (lbs.) 6 Point Load Location (lbs.)
Model
(Tons) Shipping Operating X Y A B C D A B C D E F
078
ZF 865 860 38 24 200 149 218 292 140 114 95 138 167 205
(6.5)
090
ZF 885 860 38 24 205 153 223 299 144 117 97 142 171 210
(7.5)
102
ZF 1025 1020 38 24 238 177 258 347 167 136 113 164 198 243
(8.5)
120
ZF 1065 1060 38 24 247 184 268 360 173 141 117 171 206 253
(10)
150
ZF 1258 1253 47 25 251 280 381 341 164 176 190 259 240 223
(12.5)
29.69
15.25
15.38
59.00
15.38
C
D
E
11 3/8
F
LEFT 4 3/16
FRONT
59 27 5/16 21 3/16
89
ZF150
29.95 30.11
45.64
14.92
14.92
58.09
14.92
B
See detail A for gas inlet
C
D
E
11 3/8
F
Detail A
3.184
3.184
Ø 3.126 Ø 3.126
17.541
14.594
7.705 7.715
4.727 4.737
Detail B
5-3/8
3/4” FPT
89
32 11/16
6 13/16
6 13/16
RETURN SUPPLY
AIR AIR
24
27 1/2
LEFT 18 21 RIGHT
20 1/8 19 1/8
17 1/8
12 5/16
18 1/16 FRONT
TOP VIEW
3X Ø 0.875
Ø 2.469
Convenience Outlet
Power Entry Ø 7/8
FRONT
Return A
Air
Supply Air
2-31/32
5-5/32
C
31-11/16
D
B
5-5/32 2-7/8
C 31-5/8
30-3/8
4-5/16
RIGHT
20
SUPPLY
20 6
RETURN
2 TYP.
30
50-1/2 INSULATED DECK UNDER
COMPRESSOR SECTION
FRONT
8 or 14
2 TYP
23 4
50-1/2 30-1/2
26 80-5/8
RETURN
SUPPLY
10
76-5/8
94 59-1/4
FRONT RIGHT
64-1/4
58 1/4
88 1/4
39 1/2
or
47 1/2
Outside Air
Intake Hood
35 3/4
26 25 3/4
26 30 1/4
Economizer Options
Economizer Usage
Application Cabinet Height Description Model
Bottom Return All Downflow economizer with barometric relief 2EE04705924
Side Return All Horizontal economizer without barometric relief 2EE047060241
42" Slab Economizer, 42” tall cabinet 2EE047058242
ERV or End Return
50" Slab Economizer, 50” tall cabinet 2EE047057242
2EE04706024
Return Air Damper
Field Installed
Duct Work
2EE04706024
Fresh Air Damper
2PE047032XX
Power Exhaust 1EH0408 1EH0408 2EE04706024
Barometric Barometric Fresh Air Hood
Relief Damper Relief Hood
1EH0409
Fresh Air Hood
2EE04705X24
Slab Economizer 2PE047032XX
Power Exhaust
1EH0409 Barometric 1EH0409 Barometric
Relief Damper Relief Hood
1EH0409
Fresh Air Hood
Field Installed
Duct Work
2EE04705X24
Slab Economizer
1EH0409
Barometric Relief Hood
2PE047032XX
1EH0409 Power Exhaust
Barometric Relief Damper