Bichena Substation
Bichena Substation
ELECTRICAL SUBSTATION
Now days the demand of electrical power is increasing very rapidly. For fulfilling these huge power
demands the modern time requires creation of bigger and bigger power generating stations. These
power generating stations may be hydro – electric, thermal or atomic. Depending upon the availability of
resources these stations are constructed different places. These places may not be nearer to load centers
where the actual consumption of power takes place. So it is necessary to transmit these huge power
blocks from generating station to their load centers. Long and high Voltage transmission networks are
needed for this purpose. Power is generated comparatively in low voltage level. It is economical to
transmit power at high voltage level. Distribution of electrical power is done at lower voltage levels
as specified by consumers. For maintaining these voltage levels and for providing greater stability a
number of transformation and switching stations have to be created in between generating
station and consumer ends.These transformation and switching stations are generally known as
electrical substations. Depending upon the purposes, the substations may be classified as
Step Up Substation
Step up substations are associated with generating stations. Generation of power is limited to low voltage
levels due to limitations of the rotating alternatr. These generating voltages must be stepped up for
economical transmission of power over long distance. So there must be a step up substation associated
with generating station.
Step Down Substation
The stepped up voltages must be stepped down at load centers, to different voltage levels for different
purposes. Bichena substaion is one of the Step Down Substation established near to the twon bichena.The feeder
of these substation comes from Debre Markos substation through 66kv Transmission line.So, this 66kv
input processed is step downs to 33/15 and 15KV via 6.5MVA and 12.5MVA power transformer.Now,
the substation gives power for different woreda towns and some factories. The substation mainly has 7
outgoing feeders. From these5 feeders i.e bichena,dejen,debrewerk,midrok and kuy are
66kv/15kv.and two of the feders are i.e tik and telma are 66kv/33kv
Table1.1 the substation with the corresponding feeders
Bichena 66/15kv
Dejen 66/15kv
kuy 66/15kv
Debrewerk 66/15kv
Telma 66/33kv
Tik 66/33kv
BUS BAR
Bus bars are used to carry large current and to distribute current to multiple circuits within
switchgear or equipment. Bus bar is a line in which the incoming feeder come in to and get in to the
instruments for further step up or step down. There are a single bus bar and a single bus bar, but in this
substation only single bus bar is available. In electrical power distribution substation,a busbar is a strip of
copper or aluminum that conducts electricity within a switch board, distribution board, substation or
other electrical apparatus.
POWERTRANSFORMERS
Power transformers are consists of two or more windings for each phase and these windings are
usually wound around an iron core. The iron core improves the efficiency of the transformer by
concentrating the magnetic field and reduces transformer losses. The high-voltage and low-voltage
windings have a unique number of coil turns.Specifically in Bichena substation, there are two step-down
transformers. These are:-66/33 kv and 6/33/15 kv step down transfrmer.
The 66/15 Transformer step downs the incoming 66 kV to 15kv, while the 66/33/15 transformer
step downs the incoming 66 kv to33 kv and15 kv.
INSTRUMENT TRANSFORMERS
Instrument transformers are used for measuring voltage and current in electrical power systems, and for
power system protection and control. Where a voltage or current is too large to be conveniently used by an
instrument, it can be scaled down to a standardizedlow value. Instrument transformers isolate measurement,
protection and control circuitry from the high currents or voltages present on the circuits being measured
or controlled.
Current transformer is a measurement device designed to provide a current in its secondary coil
proportional to the current flowing in its primary. Current transformers can perform circuit control,
measure current for power measurement and control, and perform roles for safety protection and
current limiting. They can also cause circuit events to occur when the current reaches a specified level.
Lightening Arrester
Lightening arresters are the instrument that are used in the incoming feeders so that prevent the high
voltage entering the main stations or in other words lightening arresters are devices for
limiting surge voltages due to lightning strikes or equipment faults or other events, to prevent damage
to equipment and distribution of service. Also called surge arresters. The lightning arresters are
grounded to the earth so that it can pull the lightening to the ground. Lightning Arresters
are installed on many different pieces of equipment such as power poles and towers power
transformers, circuit breakers , bus structures, and steel super structures in substations.
Surge Counter
Surge counters are connected in series with the surge arresters to count the action times of the
arrester.Structure and Working principle of Surge Counter The surge counter is mainly composed of:-
Valve
Silicon bridge rectifier
Capacitor and
Electromagnetic counter
The surge current and power frequency current pass through the surge arresters are used to fetch voltage
from the valve which is actually nonlinear resistor. Then, the capacitor is unidirectional charged
through the silicon bridge rectifier. After wards, the capacitor discharges to the coils of the
electromagnetic counter in dc and thus moves the counter to realize the record of action times.
In electrical engineering, a disconnector or isolator switch is used to make sure that an electrical
circuit can be completely de-energized for service or maintenance. Such switches are often found
in electrical distribution and industrial applications where machinery must have its source of driving
power removed for adjustment or repair. Highm voltage isolation switches are used in electrical substations
to allow isolation of apparatus such as circuit breakers and transformers, and transmission lines, for
maintenance. In some designs the isolator switch has the additional ability to earth the isolated
circuit thereby providing additional safety. Such an arrangement would apply to circuits which inter-
connect power distribution systems where both end of the circuit need to be isolated. The major
difference between an isolator and a circuit breaker is that an isolator is an off-load device intended to be
opened only after current has been interrupted by some other control device.
Figure .disconnector
Dc Battery
Batteries are essential components in a substation. They provide the (tripping) current by which
protective relays can trip high-voltage circuit breakers in the event of a fault.Generally all control
systems in the substation uses a Dc power supply.
Reclosers address this problem by further dividing up the network into smaller sections. For instance,
the city grid example above might be equipped with reclosers at every branch point on the network.
Reclosers, because of their position in the network, handle much less power than the breakers at the
feeder stations, and therefore can be set to trip at much lower power levels. This means that a single
event on the grid will cut off only the section handled by the single recloser, long before the feeder
station would notice a problem. A normal breaker could also be used for this role, but, because they
are distributed geographically throughout the grid, as opposed to being centralized at feeder stations,
resetting a breaker might take considerable time. For this reason, reclosers are used to automatically re-
connect after a brief interval. There is a strong likelihood that the fault will be gone when the
power is restored. If the fault is still present, the recloser opens again.
The control system for a recloser allows a selected number of attempts to restore service after adjustable
time delays. For example a recloser may have 2 or 3 "fast" reclose operations with a few seconds delay,
then a longer delay and one reclose; if the last attempt is not successful, the recloser will lock out and
require human intervention to reset. If the fault is a permanent fault (downed wires, tree limbs lying
on the wires, etc.) the autorecloser will exhaust its pre - programmed attempts to re-energize the
line and remain tripped off until manually commanded to try again. About 80-90% of faults on
overhead power lines are transient and can be cured by autoreclosing.The result is increased availability
of supply.
Autoreclosers are made in single-phase and three-phase versions, and use either oil, vacuum,
interrupters. Controls for the reclosers range from the original electromechanical systems to digital
electronics with metering and SCADA functions. The ratings of reclosers run from 2.4– 3.8 kV for
load currents from 10–1200 A and fault currents from 1–16 kA.