Marine Fire and Gas Dampers: Type JFD
Marine Fire and Gas Dampers: Type JFD
Marine Fire and Gas Dampers: Type JFD
2/2/EN/ 2
Description 2 Accessories 6
Construction; Materials; Standard Sizes 3 Order Details 7
Product Range; Performance data 5
TROX Type ‘JFD’ Damper is a Multi-leaf Fire and The damper is also certified for use in Zone 1 and
Gas Damper, designed for marine and offshore 2 hazardous areas and complies with EU Directive
applications. The damper is certified by Lloyd’s 94/9/EG (ATEX 95), Appendix 1 and is classified
Register and ABS for the compliance with IMO under equipment group II, category 2G. In accor-
Fire Test Procedures Code, Annex 1; Part 3. The dance with EU Directive 99/92/EC (ATEX 137),
damper is also certified by Lloyd’s Register for the damper can be used in potentially explosive
compliance with the essential Fire protection environment where gas Groups IIA, IIB and IIC,
requirements of the EU Marine Equipment Direc- and flammable materials at temperature classes
tive (MED) 96/98/EC. The damper is certified for T1 to T6 are present.
horizontal or vertical mounting in ‘A-0’ divisions,
and ‘A-15’, ‘A-30’ and ‘A-60’ divisions when The maximum recommended operating pressure
suitably insulated. for this damper is 3000 Pa.
2
Construction · Materials · Standard Sizes
3
General Details
Minimum and Maximum Damper Size
11 Insulation 60 kg/m
Rockwool
12 Landing angle GMS or
stainless steel
2
50 50
300
8
4 @ 150
7
“H” MAX=1250/”H” MIN=200
6
“H” + (50mm x 2)
112
5
4 @ 150
4
Product Range · Performance Data
Pressure drop across JFD Damper with blades in fully open position
80
70
60
Pressure drop (Pa)
50
40
30
20
10
0
1 Air Velocity (m/s) 10 20 30
5
Accessories
6
Order Details
Note: If the order codes below are incomplete, then it is assumed that standard damper construction is required.
E1
E2
E3
Make: TROX
G2 – 50 Flange (Standard Supply) Type: JFD– G-FL2-3-F4-0-0 / 600x600 /12 /R /V /Z01 /A1-5-6-8
Others - Special Quantity: 12 nos
The Type JFD is certified by the Lloyd s Register and ABS in accordance with the IMO Fire Test Procedures Code,
Annex1, Part 3, and it is suitable for both marine and offshore applications.