Calculations and Modelling
Calculations and Modelling
Calculations and Modelling
Data Input
Location Songco, Lantapan, Bukidnon
Length Parallel to Wind (L) 30 m
Length Perpendicular to Wind (B) 23 m
First Storey Height 3m
Second Storey Heigth 3.5 m
Roof Heigth 1.5 m
z 6.5 m
h 7.25 m
By Interpolation
Kz (6.5) = 0.914
Kh (7.25) = 0.933
qz = 0.8269
qh = 0.844
6) External Pressure Coefficient (Cp or Cn)
For Walls
L = 30 m
B = 23 m
L/B = 1.304347826 or 1
Windward Wall Cp = 0.8
Leeward Wall Cp = -0.5
Side Wall Cp = -0.7
For Roof
h/L = 0.241666667
θ = 10
Winward Roof Cp = -0.7
Leeward Roof Cp = -0.3
For Wall
Windward Wall
Load (+) kPa (-) kPa
P (0-4.5) 0.0587 0.9872
P (6) 0.0894 1.0180
P (6.5) 0.0980 1.0266
Leeward Wall
Load (+) kPa (-) kPa
P -0.8230 0.1055
Side Wall
Load (+) kPa (-) kPa
P -0.9665 -0.0380
For Roof
Windward Roof
Load (+) kPa (-) kPa
P -0.9665 -0.0380
Leeward Roof
Load (+) kPa (-) kPa
P -0.6795 0.2490
b. Building Weights
Upper Roof
Area of plan 660 sq.m
0.7(Area of Plan) 462 kN
4. Concrete Slab
(upper storey)
Area of Plan 739 sq.m
Thickness (h) 0.2 m
Unit Wt. 23.56 kN/cu.m
Weight 3482.168 kN
5. Wall Loading
c. Seismic Load
d. Roof Live Loads
STRUCTURAL ELEMENTS DEAD LOAD
ROOF
Slab Type 1
150-mm thick concrete fill 3.45 kPa
0.023 * 150
Electrical and Plumbing Materials 0.3 kPa
TOTAL SLAB TYPE 1 3.75 kPa
Roof Beam
250 mm X 400 mm, reinforced stone concrete 2.36 kN/m
0.25 * 0.40 * 23.6
SECOND FLOOR
Slab Type 1
200-mm thick concrete fill 4.6 kPa
0.023 * 200
Electrical and Plumbing Materials 0.3 kPa
TOTAL SLAB TYPE 1 4.9 kPa
Beam
250 mm X 400 mm, reinforced stone concrete 2.36 kN/m
0.25 * 0.40 * 23.6
Walls and Partitions
200-mm CHB, fully grouted using 19.6 kN/m3 density of unit, 34.88kN/m
plastered in both sides, 8 m high (interior and exterior)
[3.88 + 2(0.24)] * 8
Columns
300 mm X 300 mm reinforced stone concrete columns,
8 m high 16.992 kN
0.300 * 0.300 * 8 * 23.6
When wind interacts with a building, both positive and negative (i.e., suction)
pressures occur simultaneously. A building must have sufficient strength to resist the
applied loads in order to prevent wind-induced building failure. The magnitude of the
pressures is a function of the many primary factors as defined in the introduction of
this subject.
The computed wind load parameters are as follows:
Kd = 0.85
Exposure = C
Kzt = 1.0
Gust effect = 0.85
GCpi = 0.55
Surface Roughness C
Building Low Rise, Partiallly enclosed
z Kz qz (kPa) qh (kPa)
qz = 0.8269 0 - 4.5 0.85 0.7690 0.7690
qh = 0.8441 6 0.9 0.8143 0.8143
6.5 0.914 0.8269 0.8269
7.25 0.933 0.8441
7.5 0.94 0.8505 0.8505
L = 30 m
B = 23 m
L/B = 1.304347826 or 1
For Roof
h/L = 0.2416666667
θ = 10
As we have seen in figure below, the wind pressure in the windward wall varies
and is a function of height z.
B. SEISMIC LOAD
Ct = RCMRF 0.0731
Height of frame from footing, hn = 6
T = 0.2802404
Total Building Weight, W = 8807.1995