MV PFC - Metal Enclosed - Eaton
MV PFC - Metal Enclosed - Eaton
MV PFC - Metal Enclosed - Eaton
Advantages
Eaton’s purchase of the Commonwealth Sprague capacitor systems
business, with its over 70 years of market experience, provides a
combination that allows the end user to obtain a world-class solution
to fill their power factor needs. Quality and reliability are of paramount
importance to not only the Eaton engineering team, but are also the
backbone of all Eaton products and services. This commitment to
quality means the customer can have a great deal of confidence with
the medium voltage capacitor or harmonic filter solution from Eaton’s
electrical business.
Benefits
Ease of Installation
Eaton makes installation easy. All systems are completely assembled
in the factory, with all equipment pre-wired and pre-tested for easy
on-site installation. Only shipping splits must be connected in the
Safety and Aesthetics are Just Two Compelling Reasons to Utilize Metal- field. Splice kits connect bus systems, and control wiring is easily
Enclosed PFC Systems connected at each enclosure. Current limiting fuses, contactor
assemblies, and the incoming switch assembly can be removed from
the enclosure if needed. Line terminals are completely accessible
Application Description from the front of the system.
Utility Customers Personnel Safety
Metal-enclosed power factor correction systems are fully assembled, Positive mechanical isolating switch with visible disconnect com-
tested and ready for installation. Very little field assembly is required. pletely grounds and isolates the unit from the line connectors. A
Installation and maintenance costs for metal-enclosed systems are screened barrier protects personnel from live parts. All medium volt-
low compared to pole and rack mounted capacitor banks. Metal- age doors are mechanically interlocked with the disconnect switch.
enclosed systems and harmonic filters are less vulnerable to wildlife Key interlocks are provided standard on all enclosure doors, and can
and airborne contaminants that can cause tracking and faults. In addi- be coordinated with upstream disconnect devices. The low voltage
tion, metal-enclosed systems significantly reduce the risks and the control section has a separate door-in-door design, and is segregated
associated liability involving untrained personnel. All live parts are from the medium voltage sections so that an operator can work in
contained in a grounded, key interlocked enclosure and no internal that section safely.
hardware is accessible. Metal-enclosed systems are aesthetically
pleasing due to their low profile, and can be painted to match the Ease of Maintenance
surrounding architecture. These are just some of the reasons more
and more utilities are utilizing metal-enclosed capacitor and harmonic All components are front-accessible, facilitating routine inspection or
filter systems. parts replacement. A viewing window is standard on all compartment
doors.
Industrial Customers
Flexibility
Large industrial power users can utilize the benefits associated with
medium voltage power factor correction and harmonic filtering. Systems are expandable. The customer can add stages in the future
Medium voltage solutions usually support the scale and scope of by connecting the phase bus in the field via splice kits. Structures can
larger services. Medium voltage applications can be found in the fol- be bolted together in the field.
lowing types of industries as examples: automotives, pulp and paper,
plastics, petrochemical, and heavy manufacturing. Individual fixed
capacitors provide power factor correction directly at the cause of the
problem, such as a large horsepower MV motor. Medium voltage sys-
tems allow large industrials to correct power factor at or close to the
point of common coupling (PCC), where the utility electrical system
meets theirs. This allows correction for an entire facility, instead of
having to correct at multiple locations. The Cutler-Hammer NEMAT
3R design also allows the system to be placed outdoors, saving valu-
able manufacturing floor space. The savings can be enormous, in
materials, installation costs and floor space. In short, medium voltage
solutions provide a cost-effective alternative to many local low volt-
age power factor correction units, while protecting the customer’s
entire electrical distribution system.
Commercial Customers
Many commercial customers are purchasing power from their utility
at higher voltages today (2.4 kV – 15 kV), and can also take advantage
of medium voltage power factor correction systems. These solutions
can meet the needs of large office complexes, hospitals and universi-
Insulated Splice Kits Allow for Simple Interconnection in the Field
ties, among others. The benefits of safety (key interlocking, no
exposed live parts, etc.), and aesthetics (low profile, can be painted to
match environment) both meet the needs of these applications
where there are large numbers of untrained personnel in proximity of
electrical equipment.
2 EATON CORPORATION PF Correction and Harmonic Filter Systems Technical Data TD02607011E Effective: November 2008
TD02607011E.fm Page 3 Wednesday, November 12, 2008 4:35 PM
Application Description
● Large motors.
● Motor control centers.
● Branch circuits.
● Service entrances.
EATON CORPORATION PF Correction and Harmonic Filter Systems Technical Data TD02607011E ©Copyright 2008 3
TD02607011E.fm Page 4 Wednesday, November 12, 2008 4:35 PM
Technical Data
TABLE 2. TWO-PHASE FUSED
4 EATON CORPORATION PF Correction and Harmonic Filter Systems Technical Data TD02607011E Effective: November 2008
TD02607011E.fm Page 5 Wednesday, November 12, 2008 4:35 PM
EATON CORPORATION PF Correction and Harmonic Filter Systems Technical Data TD02607011E ©Copyright 2008 5
TD02607011E.fm Page 6 Wednesday, November 12, 2008 4:35 PM
Dimensions
FIGURE 1. FIGURE 3.
FIGURE 2.
6 EATON CORPORATION PF Correction and Harmonic Filter Systems Technical Data TD02607011E Effective: November 2008
TD02607011E.fm Page 7 Wednesday, November 12, 2008 4:35 PM
Application Description
● Large motors.
● Motor control centers.
● Branch circuits.
● Service entrances.
EATON CORPORATION PF Correction and Harmonic Filter Systems Technical Data TD02607011E ©Copyright 2008 7
TD02607011E.fm Page 8 Wednesday, November 12, 2008 4:35 PM
Technical Data
TABLE 5. STANDARD 3 FUSES (6600 — 13,800 VOLTS)
APPROX.
STANDARD 3 FUSES DIMENSIONS WEIGHT
(A) (B) (C) (D)
INCHES INCHES INCHES INCHES FIGURE STANDARD
KVAR 6600 VOLT 7200 VOLT 12,470 VOLT 13,800 VOLT (MM) (MM) (MM) (MM) LBS (KG) N0. DWG NO.
50 50663FKED3 50723FKED3 50123FKED3 50133FKED3 4.25 (108) 45.50 (1156) 14.46 (367) 0.25 (6) 198 (90) 4 5D10243
100 100663FKED3 100723FKED3 100123FKED3 100133FKED3 4.25 (108) 45.50 (1156) 14.46 (367) 0.25 (6) 198 (90) 4 5D10243
150 150663FKED3 150723FKED3 150123FKED3 150133FKED3 4.25 (108) 45.50 (1156) 14.46 (367) 0.25 (6) 198 (90) 4 5D10243
200 200663FKED3 200723FKED3 200123FKED3 200133FKED3 5.62 (143) 45.50 (1156) 14.46 (367) 0.25 (6) 220 (100) 4 5D10243
250 250FKY66323 250FKY2323 250FKY12323 250FKY13323 5.62 (143) 48.50 (1232) 17.46 (443) 0.25 (6) 246 (112) 4 5D10243
300 300FKY66323 300FKY2323 300FKY12323 300FKY13323 5.62 (143) 53.50 (1359) 17.46 (443) 0.25 (6) 246 (112) 4 5D10243
350 350FKY66323 350FKY2323 350FKY12323 350FKY13323 5.62 (143) 53.50 (1359) 17.46 (443) 0.25 (6) 246 (112) 4 5D10243
400 400FKY66323 400FKY2323 400FKY12323 400FKY13323 5.62 (143) 57.25 (1454) 22.46 (570) 0.25 (6) 281 (128) 4 5D10243
450 — — 450FKY12323 450FKY13323 5.62 (143) 57.25 (1454) 22.46 (570) 0.25 (6) 281 (128) 4 5D10243
500 — — 500FKY12323 500FKY13323 5.62 (143) 57.25 (1454) 26.21 (666) 0.25 (6) 336 (153) 4 5D10243
Dimensions
Removable
Top Cover .250-20
Grd. Scr.
16.42 34.00
Barriers
Solderless Conn.
for A #10 Solid
to A #4 Str'd. Conn.
B
(2).500 x .625
Slots [13 x 16]
C
D
24.12
A 25.08
8 EATON CORPORATION PF Correction and Harmonic Filter Systems Technical Data TD02607011E Effective: November 2008
TD02607011E.fm Page 9 Wednesday, November 12, 2008 4:35 PM
Product Description
The Autovar medium voltage automatic power factor capacitor sys-
tems are designed for power factor correction in applications where
plant power factor can be constant or changing, and an engineered
solution is required. These systems can be a fixed amount of capaci-
tance with a disconnect, a number of switched capacitance stages, or
a combination of both. The Autovar medium voltage capacitor Medium Voltage PFC Enclosure
system can switch stages of capacitance in and out automatically
based on information collected by the power factor controller on
the door-in-door control panel.
EATON CORPORATION PF Correction and Harmonic Filter Systems Technical Data TD02607011E ©Copyright 2008 9
TD02607011E.fm Page 10 Wednesday, November 12, 2008 4:35 PM
Vacuum Switches
On multi-stage capacitor systems, each stage is controlled by low
maintenance vacuum contactors (2.4 – 7.2 kV) or vacuum switches
(7.2 – 15 kV) depending on the application (see below).
Environmental Controls
● Exhaust fans: Exhaust fans are provided for forced air ventilation
of all enclosures as standard.
● Thermal controls: Thermostats are included as standard to help
maintain an acceptable internal environment for all components.
● Space heaters: Space heaters are provided to control moisture and
humidity inside all enclosures.
● Each compartment has individual thermostats for fan and space
heater controls.
10 EATON CORPORATION PF Correction and Harmonic Filter Systems Technical Data TD02607011E Effective: November 2008
TD02607011E.fm Page 11 Wednesday, November 12, 2008 4:35 PM
CPT and TVSS Provide Power and Protection for Control Section
Control Panel
A door-in-door NEMA 3R swing-out control panel is provided on the
main incoming structure as standard. This unit includes a viewing
window so that all controls and information can be viewed without
opening the panel. All low voltage controls and logic are accessible
from the front of the system, and are isolated from the medium
voltage section.
Included:
● PFC controller.
● Ammeter with switch (for maintenance and diagnostic purposes).
● Stage ON/OFF pilot lights.
● Manual stage operation switches.
● Any special controls requested by the customer.
EATON CORPORATION PF Correction and Harmonic Filter Systems Technical Data TD02607011E ©Copyright 2008 11
TD02607011E.fm Page 12 Wednesday, November 12, 2008 4:35 PM
Solid-State Controller
Automatic metal-enclosed capacitors and harmonic filter systems
come equipped with an automatic controller that switches each
capacitor stage based upon power factor. The customer simply
programs in the target PF to meet. The controller analyzes current PF,
the size of each stage, and turns on and off stages to meet the cus-
tomer’s programmed target. The controller has alarms such as power
factor out of range, high harmonic voltage content and loss of power.
Up to 12 steps of capacitance can be designed into any system.
Customers can note this feature when designing for future
expansions.
Communications
Communications of power factor data via RS-485. ModbusT is avail-
able as an option. Communicated information from the controllers:
● Voltage.
● Current.
● Target power factor. Phase Bus
● Current power factor. Continuous 1/4” x 1” silver-plated copper ground bus rated 300 A is
● Active power. provided throughout the line-up for easy interconnection, field instal-
lation and future expansion. Ground studs are available in all
● Apparent power.
structures for customer connection.
● Reactive power.
● Number of steps in the circuit.
● All alarm status.
● All counters.
● Time and date.
Inrush Reactors
Inrush reactors are provided as standard on all switched (non-
harmonic filtered) capacitor systems for protection against transients
from back-to-back switching. Reactors in harmonic filtered
applications provide this same protection.
12 EATON CORPORATION PF Correction and Harmonic Filter Systems Technical Data TD02607011E Effective: November 2008
TD02607011E.fm Page 13 Wednesday, November 12, 2008 4:35 PM
Optional Features
Harmonic Filter Reactors
Iron core reactors provide the necessary reactance to tune the IQ Analyzer 6600
capacitor system to a desired frequency. Standard tuning is the 4.7th
harmonic. Other tuning frequencies, as well as multi-tuned systems, Enclosure Options
are also available. Iron core reactors are 100% copper windings, NEMA 3R stainless steel construction for highly caustic
115°C rise with 220°C insulation VPI varnish. environments.
Alarm Strobe
Strobe light can be provided for visual indication of faults and alarms.
Unbalance Protection
Neutral PT or CT-based unbalance protection for wye ungrounded
capacitor configuration.
Harmonic Filter
Lightning Arresters
Optional heavy-duty distribution class/intermediate/station lightning
arresters protect the capacitor system from lightning and switching
transients.
EATON CORPORATION PF Correction and Harmonic Filter Systems Technical Data TD02607011E ©Copyright 2008 13
TD02607011E.fm Page 14 Wednesday, November 12, 2008 4:35 PM
Technical Data
Top Power
Cable Entry
Lifting Eyes
Shipping Split
Incoming Main Section
Main Switch
92.56 22.80
K1 (2351.0) (579.1)
Control
Panel 1740
CAUTION CAUTION CAUTION
Customer (442.0)
DANGER DANGER DANGER
Cable
Ground Switch
Termination
Danger Danger Danger Danger (Approximate
High Voltage High Voltage High Voltage
Keep Out Keep Out Keep Out Location, See
Actual Unit
for Exact
Dimensions)
D2 D3 D2 90.33 Gourd Bus
1/4-inch x 1-inch
Base Channel
180.80 Bottom Power
(4592.3) Cable Entry
8 Tieddown Points 45.00 49.10
per Enclosure Front Elevation 1.50
(1143.0) (1247.1)
Front and Rear (38.1)
13.50 15.00 13.50
for 1/2 Inch Hardware Rear Access Doors Optional (Typ) (342.9) (381.0) (342.9) Rigth Side Elevation
Base Channel
18.00 21.79
40-Inches High
(457.2) (553.5)
48.27
Bottom Entry 18.00 (1226.1)
Cover Plate
(457.2)
5.09 9.07
(129.3) (230.4)
Floor Plan
Top
19.00
Entry (482.6)
MV
Top Entry Conduit 16.00
Control Area (406.4)
Conduit
4.00 x 4.00 15.00 13.00
(381.0) (330.2)
FIGURE 5. TYPICAL ENGINEERED METAL-ENCLOSED POWER FACTOR CORRECTION SYSTEM DIMENSIONAL DATA
14 EATON CORPORATION PF Correction and Harmonic Filter Systems Technical Data TD02607011E Effective: November 2008
TD02607011E.fm Page 15 Wednesday, November 12, 2008 4:35 PM
Utility Line
Utility
Transformer
Main Breaker
CT
A-Phase 1
Feeder Breaker K0
Plant Loads
K-K Interlock
Fuse
S1
Enclosure
Door
C1
Vacuum
Contactor
Reactor
FIGURE 6. TYPICAL MEDIUM VOLTAGE AUTOMATIC POWER FACTOR CORRECTION SINGLE-LINE DRAWING
EATON CORPORATION PF Correction and Harmonic Filter Systems Technical Data TD02607011E ©Copyright 2008 15
TD02607011E.fm Page 16 Wednesday, November 12, 2008 4:35 PM
16 EATON CORPORATION PF Correction and Harmonic Filter Systems Technical Data TD02607011E Effective: November 2008
TD02607011E.fm Page 17 Wednesday, November 12, 2008 4:35 PM
f. Copper bus shall be provided and properly sized to handle 3. Capacitor Section
continuous current rating of capacitor bank as well as a a. Capacitors shall be low loss, 2 bushing (or 3 bushing if
minimum of 25% (if future expansion required, specify) specified, Internally Delta connected), properly sized and
future expansion. connected per the specification.
g. Inrush reactors shall be air core, copper windings and 40uH b. Each capacitor cell shall Internal discharge resistors to drain
minimum for each stage. Reactors shall be sized per the voltage to 50 volts or less in five minutes.
capacitor stage kvar sizes.
c. Capacitor shall be suitable for operation at 110% of rated volt-
h. Contactors shall be rated for switching of capacitors by the age, and 135% of rated current minimum.
contactor manufacturer.
d. Capacitors shall be rated [60 kV/ 75 kV/95 kV] BIL.
i. The automatic harmonic filter equipment shall be warranted
by the manufacturer of the capacitor bank. e. Capacitors shall be configured in [delta/wye] arrangement.
j. The capacitor bank shall be modular design for ease of future f. A current limiting capacitor fuse with current and voltage
expansion. ratings appropriate for the capacitor shall protect stage and
capacitors.
k. Capacitor bank shall have a 4-inch base channel.
g. Capacitors for harmonic filter applications shall be heavy duty,
l. Each section shall have a viewing window. 55°C temperature rating, 125% continuous over-voltage capa-
m. The main bus and ground bus shall be silver plated copper. bility, 15 kA fault handling capability, 100 kA transient current
withstand capability, and meet IEEE std 18, NEMA and IEC
n. The bus support insulators shall be 95kV BIL.
standards.
o. Each stage of the capacitor bank shall be installed in an
h. Vacuum contactors shall be rated for capacitive switching.
individual compartment isolated by steel sheets from
Vacuum contactors shall be rated 7.2 kV, 3-pole for 5 kV
other stages.
systems and 15 kV,1-pole for 15 kV systems.
p. All Fuses shall be rated 50kAIR, full rated for the system
i. Each capacitor case shall be grounded to the enclosure
voltage class, current limiting type.
ground bus.
q. The equipment shall be modular design with maximum
j. Each vacuum contactor shall be grounded to the enclosure
90”wide x 49”deep sections.
ground bus.
r. The equipment shall be shipped on wood pallets for ease
4. Control Section
of handling and installation.
a. This section shall include a digital power factor controller with
s. Each shipping section shall have removable lifting eyes.
a digital power factor meter.
t. Each section door shall have warning labels, Danger High
b. Programmable set points for all functions.
Voltage, Section #, and Caution labels.
c. Stage anti-cycling timers programmable to not less than
u. The enclosure steel shall be fabricated at the same mfg.
5 minutes.
facility where the capacitor bank is assembled.
d. Power Factor “Out-of-Range” alarm.
v. The doors shall have gaskets, heavy-duty hinges, pad lockable
and keyed heavy-duty handles. The doors shall be latched at e. High harmonic content (>5% THD voltage) alarm.
three points. Doors shall have welded grounding studs and f. Manual-Off-Auto toggle switches shall be provided for
shall be bonded to the equipment ground bus. operation of the switched steps.
w. The roof shall be sloped to the rear. There shall be a drip g. “Power On” and “Unit Alarm” indicating lights.
shield provided over each door. h. Capacitor "Stage On" indicating lights shall be provided.
2. Incoming Section i. Each stage shall have Manual-Off-Auto switches, stage on
a. Unit shall have an integrally mounted, assembled isolation indicator, and counter. The control scheme shall be such that
disconnect (if specified) with current limiting fuses (if speci- when switching from “Manual” position to “OFF” to
fied), and grounding switch (if specified) OR Incoming “AUTO” or “MAN” position on any stage, that the corre-
section shall have NEMA termination pads with main sponding stage will not be energized in less than 5 minutes.
fuses (or without main fuses). An interposing timing relay shall be provided to prevent
energization of the capacitor stage in less than 5 minutes.
b. [Distribution/Intermediate class arresters shall be provided
for lightning protection. Specify MCOV required.] j. A digital multifunction meter/relay shall be included with
amps and phase current unbalance functions.
c. [Current limiting line fuses shall be provided for equipment
short circuit protection sized a minimum of 135% of required k. Power factor controller shall have the following alarm options
amperage.] which can be programmed by the Customer: over/under
compensation, no current signal, step fault, step warning,
d. (If specified) Main switch and ground switch shall have 20X switching time outside limit, voltage harmonic limit,
externally operable handles with padlocking provisions. current harmonic limit, and voltage outside tolerance.
e. Control power transformer shall be provided in each l. Power factor controller shall have password protection.
incoming section.
m. Power factor controller shall have field adjustable phase
f. Current transformer shall be provided for each phase to compensation so that the user can connect the current and
monitor capacitor bank current. Current transformers shall be voltage measurement signals in any phase orientation so that
multi-ratio with 10 ratio taps so that the ratio can be adjusted the user does not have to physically rotate the power cable
for future expansion. and/or CT leads to achieve a particular phasing between
g. Incoming section shall be designed for top, bottom and current and voltage.
rear side Customer power cable entry. For bottom entry n. Power factor controller shall have individual discharge time
a removable bolted cover plate shall be provided. programmable for each step.
h. The incoming section shall have adequate power cable o. Control panel shall be designed for future addition for ___
bending radius space for Customer’s cables. stages (If future expansion required, specify).
i. The incoming section shall have cable supports for p. Not used.
Customer’s power cables.
q. Controller shall have control halt and control sleep on/off
settings for each control alarm.
r. Controller shall have a digital relay output in addition to the
alarm output.
EATON CORPORATION PF Correction and Harmonic Filter Systems Technical Data TD02607011E ©Copyright 2008 17
TD02607011E.fm Page 18 Wednesday, November 12, 2008 4:35 PM
s. Controller shall have programmable switch cycle balancing, PART 3 TESTING AND DOCUMENTATION
step exchange and control sensitivity settings.
t. Control panel shall have 120 V circuit breaker for disconnect- 3.01 FACTORY TESTING
ing and over-current protection of control wiring. A. All capacitors shall be tested in compliance with NEMA, and
u. Space heater circuit shall be such that the Customer can bring ANSI requirements for capacitance, dissipation factor, terminal
external power source if needed to power space heaters to terminal and terminal to case dielectric strength, and oil
during storage. leaks. All capacitor cells shall be traceable through construction
and testing.
v. The control shall have on delay timers as protection against
upstream utility reclosers opening and closing to clear B. The automatic power factor capacitor correction unit shall be
distribution line faults. The start timer shall be adjustable. tested for proper operation prior to leaving the factory. The
certified record of these tests shall become part of the perma-
w. All timers and settings shall be field adjustable.
nent documentation package that travels with the automatic
x. All control wiring shall be minimum #14 AWG, 600 V. capacitor bank. The following checks, measurements, and
5. Key Interlock System operations must be confirmed and recorded for each stage.
a. Unit main disconnect shall have key lock that, when switch 1. Wire connections
is open, key is removable to unlock opened position on 2. Torque connections
ground switch.
3. Phase to Phase resistance checks
b. The ground switch can then be closed and shall have key
interlocks that can be removed in closed position to allow 4. Phase to Phase capacitance checks
for unlocking doors. 5. Controller operation, manual operation
c. The ground switch cannot close unless the disconnect switch 6. Controller operation, automatic operation
is locked open. The ground switch cannot open unless all the
capacitor section doors have been locked closed. 7. Megger
6. Bank Protection 8. Hi-pot
a. Unit shall have a weatherproof alarm strobe light and dry 9. Test meter and controller with secondary current injection
contacts for customer remote alarm. C. Capacitor bank assembly shall be engineered, manufactured
b. Power factor controller shall have the following and tested under the supervision of a Registered Professional
programmable alarms and setpoints: Electrical Engineer.
1. No current input 3.02 DOCUMENTATION
2. Step fault A. Supplier to provide test reports for capacitors, reactors, and
3. Step warning capacitor bank assembly.
4. 20 X switching time outside limit B. Supplier to provide handling and installation instructions.
5. Voltage Harmonics overload C. Supplier to provide inspection and maintenance schedule.
6. Current Harmonics overload D. Supplier to provide ISO-9001 certificate for the facility where
the capacitor bank will be manufactured.
7. Control voltage out of tolerance
E. Supplier to provide facilities Quality System Manual.
8. Overcurrent
F. Supplier to provide approval/construction/as-built schematic,
9. Over/under compensation outline, settings, and wiring drawings.
c. Capacitors shall be protected with current limiting full voltage
rated fuses with blown fuse indication. Fuses shall be 50 kAIR
rated for the full system voltage class.
2.03 NAMEPLATES
A. Each unit will have a rating nameplate. The lettering shall be
black 3/16-inch high, on a silver background.
B. The main incoming section shall have a rating nameplate located
on the inside door in addition to the external nameplate.
2.04 FINISH
A. Metal-Enclosed capacitor equipment enclosures shall be
provided with a powder coat paint finish. Exterior color shall
be ANSI 61.
18 EATON CORPORATION PF Correction and Harmonic Filter Systems Technical Data TD02607011E Effective: November 2008
TD02607011E.fm Page 19 Wednesday, November 12, 2008 4:35 PM
EATON CORPORATION PF Correction and Harmonic Filter Systems Technical Data TD02607011E ©Copyright 2008 19
TD02607011E.fm Page 20 Wednesday, November 12, 2008 4:35 PM
20 EATON CORPORATION PF Correction and Harmonic Filter Systems Technical Data TD02607011E Effective: November 2008
TD02607011E.fm Page 21 Wednesday, November 12, 2008 4:35 PM
EATON CORPORATION PF Correction and Harmonic Filter Systems Technical Data TD02607011E ©Copyright 2008 21
TD02607011E.fm Page 22 Wednesday, November 12, 2008 4:35 PM
22 EATON CORPORATION PF Correction and Harmonic Filter Systems Technical Data TD02607011E Effective: November 2008
TD02607011E.fm Page 23 Wednesday, November 12, 2008 4:35 PM
EATON CORPORATION PF Correction and Harmonic Filter Systems Technical Data TD02607011E ©Copyright 2008 23
TD02607011E.fm Page 24 Wednesday, November 12, 2008 4:35 PM