Applied DC Voltage (V) Reference Resistance ( ) R - (YB Earth) Y - (RB Earth) B - (RY Earth)

This document provides a test report for a hipot cable. It describes the cable's nameplate details, insulation resistance measurements before and after hipot testing, and the hipot testing procedure. The hipot testing procedure involves connecting the cable to a high voltage diode, slowly increasing the applied voltage while monitoring leakage current, and discharging the cable after testing. Insulation resistance measurements are taken to verify the insulating materials are performing correctly both before and after hipot testing. The document provides applied voltage values, resistance measurements, and test statuses.

Uploaded by

Melkin NP
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
121 views3 pages

Applied DC Voltage (V) Reference Resistance ( ) R - (YB Earth) Y - (RB Earth) B - (RY Earth)

This document provides a test report for a hipot cable. It describes the cable's nameplate details, insulation resistance measurements before and after hipot testing, and the hipot testing procedure. The hipot testing procedure involves connecting the cable to a high voltage diode, slowly increasing the applied voltage while monitoring leakage current, and discharging the cable after testing. Insulation resistance measurements are taken to verify the insulating materials are performing correctly both before and after hipot testing. The document provides applied voltage values, resistance measurements, and test statuses.

Uploaded by

Melkin NP
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 3

CLIENT IP / TR / F /

TR NO / IPSE / BLR /
CUSTOMER
(Job No)
LOCATION SHEET OF

TEST REPORT FOR HIPOT CABLE


DATE OF TESTING:
1. NAME PLATE DETAILS:
Location :
Voltage Rating :
Make :
No.of core :

2. INSULATION RESISTANCE (Before HIPOT):

PROCEDURE:-
1. Cable Insulation resistance testing, Cable incoming and outgoing must be disconnect.
2. If not disconnected the test measurement will also include the characteristics of connected
circuit.
3. Insulation Resistance testing verifies that the insulating material, which makes up the
Insulating material (XLPE/PVC) are performing correctly.
4. A Insulation Resistance measuring instrument applies a known DC Voltage (as per IEC
standard). The DC voltage applies for 1 minute with different combination as requires (as per
below mentioned circuit).

Applied DC Resistance
Reference
Voltage ( Ω)
(V)
R - (YB Earth)
Y- (RB Earth)
B - (RY Earth)

3. HIPOT TEST:

M/S. INEL PSE M/S. INEL PSE M/S


References
Tested By Verified By Witnessed By

Name NIRMAL KUMAR


Signature
Designation TESTING ENGINEER MANAGER TECHNICAL
CLIENT IP / TR / F /
TR NO / IPSE / BLR /
CUSTOMER
(Job No)
LOCATION SHEET OF

PROCEDURE:

1. Connect the HV terminal from HV Diode to the cable.


2. While doing HIPOT test, there should be ENOUGH clearance between Cable, HV
terminal and Ground surface Contact.
3. Check earthling and connection of HI-POT Kit before starts test.
4. Start the apply the voltage increase the voltage slowly (500V per sec)
5. As per IEEE 95, the DC HIPOT only 70% of Power Frequency withstand voltage
should be apply for old Cables (There is a Depreciation factor).
6. Measure the leakage current by using leakage ammeter in the HIPOT kit or ensure
with external leakage clamp meter.
7. After the completion, the tested cable must be discharge with the earth rod.

Applied DC
Leakage Current
Voltage Reference Withstand Status
( mA)
(V) for 1 minute
R - (YBEarth)
Y- (RBEarth)
B - (RYEarth)

4. INSULATION RESISTANCE (After HIPOT):

M/S. INEL PSE M/S. INEL PSE M/S


References
Tested By Verified By Witnessed By

Name NIRMAL KUMAR


Signature
Designation TESTING ENGINEER MANAGER TECHNICAL
CLIENT IP / TR / F /
TR NO / IPSE / BLR /
CUSTOMER
(Job No)
LOCATION SHEET OF

PROCEDURE:-
1. for individual breaker resistance testing, Breaker incoming and outgoing must be
disconnect.
2. If not disconnected the test measurement will also include the characteristics of connected
circuit.
3. Insulation Resistance testing verifies that the insulating material, which makes up the
Insulating material (XLPE/PVC) are performing correctly.
4. A Insulation Resistance measuring instrument applies a known DC Voltage (as per IEC
standard). The DC voltage applies for 1 minute with different combination as requires (as per
below mentioned circuit).

Applied DC Resistance
Reference
Voltage ( Ω)
(V)
R - (YB Earth)
Y- (RB Earth)
B - (RY Earth)

Note:

# Cable must be open at both sending and receiving end.

# Cable core must be identify before testing from the both end.

M/S. INEL PSE M/S. INEL PSE M/S


References
Tested By Verified By Witnessed By

Name NIRMAL KUMAR


Signature
Designation TESTING ENGINEER MANAGER TECHNICAL