Instrument Connections

Download as pdf or txt
Download as pdf or txt
You are on page 1of 91

Chapter 8

Instrument connections

All instruments connect to their respective processes and to each other by means of pipe, tube, and/or
wires. Improper installation of these connective lines can make the difference between success or
failure in an installation. Safety is also impacted by improper connections between instruments and
the process, and from instrument to instrument.

8.1 Pipe and pipe fittings


Pipe is a hollow structure designed to provide an enclosed pathway for fluids to flow, usually
manufactured from cast metal (although plastic is a common pipe material for many industrial
applications). This section discusses some of the more common methods for joining pipes together
(and joining pipe ends to equipment such as pressure instruments).

563
564 CHAPTER 8. INSTRUMENT CONNECTIONS

8.1.1 Flanged pipe fittings


In the United States of America, most large industrial pipes are joined together by flanges. A pipe
“flange” is a ring of metal, usually welded to the end of a pipe, with holes drilled in it parallel to
the pipe centerline to accept several bolts:

Side view End view

Pipe

Flange

Two flanged pipes


joined together

Flange joints are made pressure-tight by inserting a donut-shaped gasket between the flange
pairs prior to tightening the bolts. Gaskets are manufactured from materials softer than the flange
material. When sandwiched between a pair of flanges, the gasket will be “crushed” between them
to seal all potential leak paths.
In instrument diagrams such as P&IDs, flanges are denoted by two short parallel lines, both
perpendicular to the pipe. The pipe size of the flange is often written near the flange symbol, as is
the case with this 8-inch flange symbol shown below:

Flange
Pipe Pipe

8"
8.1. PIPE AND PIPE FITTINGS 565

A photograph showing a Rosemount magnetic flowmeter installed with 4-bolt flange fittings
appears here:

If you examine the flanged connections closely, you can see the gap between the flange faces
created by the thickness of the gasket material “sandwiched” between the flange pairs.
566 CHAPTER 8. INSTRUMENT CONNECTIONS

In this next photograph, we see a pair of large pipe flange connections on either end of a relatively
short “spool” pipe section. The large number of studs holding each flange set together gives you
some indication of the pressure of the fluid within, in this case upwards of 1000 PSI!

Like the flowmeter flanges shown previously, gaps between the flange ring faces reveal the space
occupied by the gasket sealing those flange surfaces together to form a pressure-tight seal.
8.1. PIPE AND PIPE FITTINGS 567

A common method of installing such a flange gasket is to first install only half of the bolts (in
the holes lower than the centerline of the pipe), drop the gasket between the flanges, insert the
remaining bolts, then proceed to tighten all bolts to the proper torques:

(All views shown end-wise)

Step 1: Step 2: Step 3:


Insert lower bolts Insert gasket Insert upper bolts

Flanges differ with regard to their sealing design and required gasket type. In the United States,
one of the most common flange “face” designs is the raised-face (RF) flange, designed to seal against
a gasket by means of a set of concentric grooves machined on the face of the flange. These grooves
form a sealing surface with far greater leakage path length than if the faces were smooth, thus
discouraging leakage of process fluid under pressure.
Another flange face design is called ring-type joint (RTJ). In this design, a special metal ring
sits inside a groove machined into the faces of both mating flanges, crushing and filling that
groove when the flanges are properly tightened together. RTJ flanges are typically found on high-
pressure applications where leakage control is more challenging. The grooves in RTJ flanges must
be completely free of foreign material, and well-formed (not distorted) in order to achieve proper
sealing.

In the United States, flanges are often rated according to a system of “pressure classes” defined
in the ANSI (American National Standards Institute) standard 16.5. These pressure classes are
designated by numerical values followed by “pound”, “lb”, or “#”. Common ANSI ratings include
the 150#, 300#, 400#, 600#, 900#, 1500#, and 2500# pressure classes. It should be noted that
these class numbers do not refer directly to pressure ratings in units of PSI, but that they do scale
with pressure (i.e. a 600# flange will have a greater pressure rating than a 300# flange, all other
factors being equal). Pressure ratings not only vary with the “class” of the flange, but also with
operating temperature, as metals tend to weaken at elevated temperature.
Originally, the ANSI class designations were based on the ratings of these flanges in steam line
service. A 250# flange, for instance, was rated such because it was designed to be used in piping
service where the fluid was saturated steam at 250 PSI (and 400 degrees Fahrenheit). As metallurgy
advanced, these flanges became capable of handling higher pressures at higher temperatures, but
the original “pound” rating remained1 . This state of affairs is not unlike the “tonnage” rating
of American light trucks: a “one-ton” truck is actually capable of hauling far more than 2000
pounds of cargo. The “one-ton” designation refers to a particular design which used to be rated for
1 EBAA Iron Sales, Inc published a two-page report in 1994 (“Connections” FL-01 2-94) summarizing the history

of flange “pound” ratings, from the ASME/ANSI B16 standards.


568 CHAPTER 8. INSTRUMENT CONNECTIONS

approximately 2000 pounds, but through advances in metallurgy and manufacturing is now able to
carry well over that rating.
Piping flanges and components must have matching flange ratings and sizes in order to properly
function. For example, a control valve with a flanged body rated as a 4-inch ANSI class 300# can
only be properly joined to another 4-inch ANSI class 300# pipe flange. The physical integrity of
the piping system will be jeopardized if mis-matched pressure-class flanges are connected together.
Proper gasket types must also be selected to coordinate with the pressure class of the mating flanges.
Thus, each and every flanged joint must be considered a complete system, with integrity ensured
only if all components comprising that system are designed to work together.
A very important procedure to observe when tightening the bolts holding two flanges together
is to evenly distribute the bolt pressure, so that no single region of the flange receives significantly
more bolt pressure than any other region. In an ideal world, you would tighten all bolts to the
same torque limit simultaneously. However, since this is impossible with just a single wrench, the
best alternative is to tighten the bolts in alternating sequence, in stages of increasing torque. An
illustrative torque sequence is shown in the following diagram (the numbers indicate the order in
which the bolts should be tightened):

1
8 6

3 4

5 7
2
With one wrench, you would tighten each bolt to a preliminary torque in the sequence shown.
Then, you would repeat the tightening sequence with additional torque for a more cycles until all
bolts had been tightened to the recommended torque value. Note how the torque sequence alternates
between four quadrants of the flange, ensuring the flanges are evenly compressed together as all bolts
are gradually tightened. This technique of alternating quadrants around the circle is often referred
to as cross-torquing.
Special wrenches called torque wrenches exist for the purpose of measuring applied torque during
the tightening process. In critical, high-pressure applications, the actual stretch of each flange bolt
is measured as a direct indication of bolting force. A special bolt sold under the brand name of
Rotabolt contains it own built-in strain indicator, letting the mechanic know when the bolt has been
sufficiently tightened regardless of the tool used to tighten it.

Another important procedure to observe when working with flanged pipe connections is to loosen
the bolts on the far side of the flange before loosening the bolts on the side of the flange nearest
you. This is strictly a precautionary measure against the spraying of process fluid toward your face
or body in the event of stored pressure inside of a flanged pipe. By reaching over the pipe to first
loosen flange bolts on the far side, if any pressure happens to be inside the pipe, it should leak there
first, venting the pressure in a direction away from you.
8.1. PIPE AND PIPE FITTINGS 569

A special provision of flanged pipe connections is the ability to install a blank metal plate called
a blind over or between flange faces, thereby preventing flow. This is useful when a pipe must be
blocked in a semi-permanent fashion, for example if that section of pipe has been decommissioned,
or if the section of pipe must be sealed for reasons of safety during maintenance operations.
In order to install a blind, the flange joint must first be broken, then the flanges pried apart to
provide the necessary space for the blind. After installing new gaskets along with the blind, the
flanged bolts may then be re-installed and torqued to specification. A photograph of a stainless-steel
blind (not installed on a pipe) appears here, two welded lifting tabs being clearly seen to facilitate
handling this heavy piece of hardware:

In applications where “blinding” is frequent, a permanent form of blind called a spectacle blind
may be installed to simplify the task. A spectacle blind is comprised of a regular blind plate attached
to an equal-diameter ring by a short tab, the outline of which resembles a pair of spectacles:

Spectacle blind Spectacle blind


(physical appearance) (P&ID symbol)

Ring Plate

Since the spectacle blind’s ring is exactly the same thickness as its blind plate, the piping system
may be designed and built with the blind’s thickness in mind, the flange-to-flange gap remaining
constant for the “open” and “blinded” states. This is especially helpful in very large piping systems,
where the force required to separate formerly mated flange faces may be very large.
570 CHAPTER 8. INSTRUMENT CONNECTIONS

A spectacle blind may be seen in this next photograph, where the blind is installed in such a
way that the yellow-painted “blind” half is exposed and the “open” half is sandwiched between the
pipe flanges to allow flow through that pipe:

This next photograph shows a spectacle blind installed the other way, where the “open” half is
exposed and the “blind” half is blocking any fluid from moving through the pipe:
8.1. PIPE AND PIPE FITTINGS 571

8.1.2 Tapered thread pipe fittings


For smaller pipe sizes, threaded fittings are more commonly used to create connections between pipes
and between pipes and equipment (including some instruments). A very common design of threaded
pipe fitting is the tapered pipe thread design. The intent of a tapered thread is to allow the pipe
and fitting to “wedge” together when engaged, creating a joint that is both mechanically rugged
and leak-free.
When male and female tapered pie threads are first engaged, they form a loose junction:

Threads loosely engaged

Fitting wall
Pipe wall

Pipe wall
Fitting wall

After tightening, however, the tapered profile of the threads acts to wedge both male and female
pieces tightly together as such:

Threads fully engaged -- pressure-tight seal established

Fitting wall
Pipe wall

Pipe wall
Fitting wall

Several different standards exist for tapered-thread pipe fittings. For each standard, the angle of
the thread is fixed, as is the angle of taper. Thread pitch (the number of threads per unit length)
572 CHAPTER 8. INSTRUMENT CONNECTIONS

varies with the diameter of the pipe fitting2 .

In the United States, the most common tapered thread standard for general-purpose piping is
the NPT, or National Pipe Taper design. NPT threads have an angle of 60o and a taper of 1o 47’
(1.7833o ):

1o 47’
Tape
r

Pipe wall

NPT -- National Pipe Tapered Open end of pipe

Pipe wall

60o

NPT pipe threads must have some form of sealant applied prior to assembly to ensure pressure-
tight sealing between the threads. Teflon tape and various liquid pipe “dope” compounds work well
for this purpose. Sealants are necessary with NPT threads for two reasons: to lubricate the male
and female pieces (to guard against galling the metal surfaces), and also to fill the spiral gap formed
between the root of the female thread and the crest of the male thread (and vice-versa).
NPTF (National Pipe Thread) pipe threads are engineered with the same thread angle and pitch
as NPT threads, but carefully machined to avoid the spiral leak path inherent to NPT threads.
This design – at least in theory – avoids the need to use sealant with NPTF threads to achieve
a pressure-tight seal between male and female pieces, which is why NPTF threads are commonly
referred to as dryseal. However, in practice it is still recommended that some form of sealant be
used (or at the very least some form of thread lubricant) in order to achieve reliable sealing.
ANPT (Aeronautical National Pipe Tapered) is identical to NPT, except with a greater level of
precision and quality for its intended use in aerospace and military applications.

2 For example, 1/8 inch NPT pipe fittings have a thread pitch of 27 threads per inch. 1/4 inch and 3/8 inch NPT

fittings are 18 threads per inch, 1/2 inch and 3/4 inch NPT fittings are 14 threads per inch, and 1 inch through 2
inch NPT fittings are 11.5 threads per inch.
8.1. PIPE AND PIPE FITTINGS 573

Another tapered-thread standard is the BSPT, or British Standard Pipe Tapered. BSPT threads
have a narrower thread angle than NPT threads (55o instead of 60o ) but the same taper of 1o 47’
(1.7833o ):

1o 47’
Tape
r

Pipe wall

BSPT -- British Standard Pipe Tapered Open end of pipe

Pipe wall

55o
574 CHAPTER 8. INSTRUMENT CONNECTIONS

8.1.3 Parallel thread pipe fittings


An alternative to tapered threads in pipe joints is the use of parallel threads, similar to the threads
of machine screws and bolts. Since parallel threads are incapable of forming a pressure-tight seal
on their own, the sealing action of a parallel thread pipe fitting must be achieved some other way.
This function is usually met with an O-ring or gasket.
In the United States, a common design of parallel-thread pipe fitting is the SAE straight thread,
named after the Society of Automotive Engineers:

O-ring

Pipe wall

SAE straight thread Open end of pipe

Pipe wall 55o

Sealing is accomplished as the O-ring is compressed against the shoulder of the female fitting.
The threads serve only to provide force (not fluid sealing), much like the threads of a fastener.

Another parallel-thread pipe standard is the BSPP, or British Standard Pipe Parallel. Like the
BSPT (tapered) standard, the thread angle of BSPP is 55o . Like the SAE parallel-thread standard,
sealing is accomplished by means of an O-ring which compresses against the shoulder of the matching
female fitting:

O-ring

Pipe wall

BSPP -- British Standard Parallel Pipe Open end of pipe

Pipe wall 55o


8.1. PIPE AND PIPE FITTINGS 575

8.1.4 Sanitary pipe fittings


Food processing, pharmaceuticals manufacturing, and biological research processes are naturally
sensitive to the presence of micro-organisms such as bacteria, fungi, and algae. It is important in
these processes to ensure the absence of harmful micro-organisms, for reasons of both human health
and quality control. For this reason, the process piping and vessels in these industries is designed
first and foremost to be thoroughly cleaned without the need for disassembly. Regular cleaning and
sterilization cycles are planned and executed between production schedules (batches) to ensure no
colonies of harmful micro-organisms can grow.
A common Clean-In-Place (CIP) protocol consists of draining all process piping and vessels of
process liquid, then flushing them with a sequence of rinse water, detergent solution, caustic solution,
and sometimes an acid solution, followed by a final water rinse. For increased sanitization, a Steam-
In-Place (SIP) cycle may be incorporated as well, sterilizing all process pipes and vessels with hot
steam to ensure the destruction of any micro-organisms.
An important design feature of any sanitary process is the elimination of any “dead ends” (often
called dead legs in the industry), crevices, or voids where fluid may collect and stagnate. This includes
any instruments contacting the process fluids. It would be unsafe, for example, to connect something
as simple as a bourdon-tube pressure gauge to a pipe carrying biologically sensitive fluid(s), since
the interior volume of the bourdon tube will act as a stagnant refuge for colonies of micro-organisms
to grow:

Bourdon
tube

Pinion gear
Sector gear
Bourdon tube
pressure gauge
k
Lin

Pointer

Pipe

(process fluid)
576 CHAPTER 8. INSTRUMENT CONNECTIONS

Instead, any pressure gauge must use an isolating diaphragm, where the process fluid pressure
is transferred to the gauge mechanism through a sterile “fill fluid” that never contacts the process
fluid:

Bourdon
tube

Pinion gear
Sector gear
Bourdon tube
pressure gauge

k
Lin
with isolating diaphragm

Fill fluid
Pointer

Pipe Isolating diaphragm

(process fluid)

With the isolating diaphragm in place, there are no stagnant places for process fluid to collect
and avoid flushing by CIP or SIP cycles.
8.1. PIPE AND PIPE FITTINGS 577

Standard pipe fittings are problematic in sanitary systems, as tiny voids between the mating
threads of male and female pipe fittings may provide refuge for micro-organisms. To avoid this
problem, special sanitary fittings are used instead. These fittings consist of a matched pair of
flanges, held together by an external clamp. An array of sanitary fittings on an instrument test
bench appear in the following photograph:

The next photograph shows the installation of a pressure transmitter on an ultra-pure water line
using one of these sanitary fittings. The external clamp holding the two flanges together is clearly
visible in this photograph:
578 CHAPTER 8. INSTRUMENT CONNECTIONS

Sanitary pipe fittings are not limited to instrument connections, either. Here are two photographs
of process equipment (a ball valve on the left, and a pump on the right) connected to process pipes
using sanitary fittings:
8.2. TUBE AND TUBE FITTINGS 579

8.2 Tube and tube fittings


Tube, like pipe, is a hollow structure designed to provide an enclosed pathway for fluids to flow. In
the case of tubing, it is usually manufactured from rolled or extruded metal (although plastic is a
common tube material for many industrial applications). This section discusses some of the more
common methods for joining tubes together (and joining tube ends to equipment such as pressure
instruments).
One of the fundamental differences between tube and pipe is that tube is never threaded at the
end to form a connection. Instead, a device called a tube fitting must be used to couple a section of
tube to another tube, or to a section of pipe, or to a piece of equipment (such as an instrument).
Unlike pipes which are thick-walled by nature, tubes are thin-walled structures. The wall thickness
of a typical tube is simply too thin to support threads.
Tubes are generally favored over pipe for small-diameter applications. The ability for skilled
workers to readily cut and bend tube with simple hand tools, as well as the ability to repeatedly
break and re-make tube connections without compromising the integrity of the seals, makes tube the
preferred choice for connecting instruments to process piping. When used as the connecting units
between an instrument and a process pipe or vessel, the tube is commonly referred to as an impulse
tube or impulse line 3 .

3 Impulse lines are alternatively called gauge lines or sensing lines.


580 CHAPTER 8. INSTRUMENT CONNECTIONS

8.2.1 Compression tube fittings


By far the most common type of tube fitting for instrument impulse lines is the compression-style
fitting, which uses a compressible ferrule to perform the task of sealing fluid pressure. The essential
components of a compression tube fitting are the body, the ferrule, and the nut. The ferrule and
body parts have matching conical profiles designed to tightly fit together, forming a pressure-tight
metal-to-metal seal. Some compression fitting designs use a two-piece ferrule assembly, such as this
tube fitting shown here4 (prior to full assembly):

Just prior to assembly, we see how the nut will cover the ferrule components and push them into
the conical entrance of the fitting body:

After properly tightening the nut, the ferrule(s) will compress onto the outside circumference of
the tube, slightly crimping the tube in the process and thereby locking the ferrules in place:

4 This happens to be a Swagelok brass instrument tube fitting being installed on a 3/8 inch copper tube.
8.2. TUBE AND TUBE FITTINGS 581

When initially assembling compression-style tube fittings, you should always precisely follow the
manufacturer’s instructions to ensure correct compression. For Swagelok-brand instrument tube
fittings 1 inch in size and smaller, the general procedure to “swage” a new connector to a tube is
to tighten the nut 1-1/4 turns past finger-tight. Insufficient turning of the nut will fail to properly
compress the ferrule around the tube, and excessive turning will over-compress the ferrule, resulting
in leakage. After this initial “swaging,” the connector may be separated by loosening the nut until
it no longer engages with the body, then the connection may be re-made by threading the nut back
on the body until finger-tight and then gently tightening with a wrench until snug (no additional
1-1/4 turns!!!).
Swagelok provides special gauges which may be used to measure proper ferrule compression
during the assembly process. The design of the gauge is such that its thickness will fit between
the nut and fitting shoulder if the nut is insufficiently tightened, but will not fit if it is sufficiently
tightened. Thus the gauge has the ability to reveal an under-tightened fitting, but not an over-
tightened fitting. These gauges fit easily in the palm of one’s hand:

Such gauges are referred to in the industry as no-go gap gauges, because their inability to fit
between the nut and body shoulder of a tube fitting indicates a properly-tightened fitting. In other
words, the gauge fit will be “no-go” if the tube fitting has been properly assembled.
582 CHAPTER 8. INSTRUMENT CONNECTIONS

Photographs showing one of these gauges testing a properly-tightened fitting (left) versus an
under-tightened fitting (right) appear here:

Parker is another major manufacturer5 of instrument tube fittings, and their product line uses
a single-piece ferrule instead of the two-piece design preferred by Swagelok. Like Swagelok fittings,
Parker instrument fitting sized 1/4 inch to 1 inch require 1-1/4 turns past hand tight to properly
compress the ferrule around the circumference of the tube. Parker also sells gauges which may be
used to precisely determine when the proper amount of ferrule compression is achieved.

5 So is Gyrolok, Hoke, and a host of others. It is not my intent to advertise for different manufacturers in this

textbook, but merely to point out some of the more common brands an industrial instrument technician might
encounter on the job.
8.2. TUBE AND TUBE FITTINGS 583

What a gap gauge will not indicate is over-tightening. Over-tightening of a compression fitting
is just as bad as under-tightening, as the fitting cannot form a robust seal once the ferrule and tube
have been deformed. An example of an over-tightened Swagelok two-piece ferrule (left) on a plastic
tube appears in the following photograph, next to a properly swaged ferrule (right):

Note the lack of a substantial gap between the two ferrule pieces in the over-tightened example.
Note also the steeper cone taper of the over-tightened front ferrule, as a result of being pushed too
deep inside the fitting body.
584 CHAPTER 8. INSTRUMENT CONNECTIONS

Regardless of the brand, compression-style instrument tube fittings are incredibly strong and
versatile. Unlike pipe fittings, tube fittings may be disconnected and reconnected with ease. No
special procedures are required to “re-make” a disassembled instrument fitting connection: merely
tighten the nut “snug” to maintain adequate force holding the ferrule to the fitting body, but not
so tight that the ferrule compresses further around the tube than it did during initial assembly.
A very graphic illustration of the strength of a typical instrument tube fitting is shown in the
following photograph, where a short section of 3/8 inch stainless steel instrument tube was exposed
to high liquid pressure until it ruptured. Neither compression fitting on either side of the tube leaked
during the test, despite the liquid pressure reaching a peak of 23000 PSI before rupturing the tube6 :

6 It should be noted that the fitting nuts became seized onto the tube due to the tube’s swelling. The tube fittings

may not have leaked during the test, but their constituent components are now damaged and should never be placed
into service again.
8.2. TUBE AND TUBE FITTINGS 585

8.2.2 Common tube fitting types and names


Tube fittings designed to connect a tube to pipe threads are called connectors. Tube fittings designed
to connect one tube to another are called unions:

Male connector Female connector Union


Tube Tube Tube

Pipe (male) Pipe (female) Tube

If a tube union joins together different tube sizes rather than tubes of the same size, it is called
a reducing union.
A variation on the theme of tube connectors and unions is the bulkhead fitting. Bulkhead fittings
are designed to fit through holes drilled in panels or enclosures to provide a way for a fluid line to
pass through the wall of the panel or enclosure. In essence, the only difference between a bulkhead
fitting and a normal fitting is the additional length of the fitting “barrel” and a special nut used
to lock the fitting into place in the hole. The following illustration shows three types of bulkhead
fittings:

Bulkhead male Bulkhead female Bulkhead union


Tube Tube Tube

Nut Nut Nut

Pipe (male) Pipe (female) Tube


586 CHAPTER 8. INSTRUMENT CONNECTIONS

Tubing elbows are tube connectors with a bend. These are useful for making turns in tube runs
without having to bend the tubing itself. Like standard connectors, they may terminate in male
pipe thread, female pipe threads, or in another tube end:

Male elbow Female elbow Union elbow


Tube Tube Tube

Pipe (male) Pipe (female) Tube

These elbows shown in the above illustration are all 90o , but this is not the only angle available.
45o elbows are also common.
Tee fittings join three fluid lines together. Tees may have one pipe end and two tube ends (branch
tees and run tees), or three tube ends (union tees). The only difference between a branch tee and
a run tee is the orientation of the pipe end with regard to the two tube ends:

Male branch tee Male run tee Union tee

Tube Tube Tube Tube Tube

Pipe
(male)
Tube Tube
Pipe (male)
8.2. TUBE AND TUBE FITTINGS 587

Of course, branch and run tee fittings also come in female pipe thread versions as well. A
variation of the theme of union tees is the cross, joining four tubes together:

Cross

Tube
Tube

Tube
Tube

Special tube fittings are made to terminate tube connections, so they are sealed up instead of
open. A piece designed to seal off the open end of a tube fitting is called a plug, while a piece
designed to seal off the end of an open tube is called a cap:

Cap Plug
Tube
588 CHAPTER 8. INSTRUMENT CONNECTIONS

8.2.3 Bending instrument tubing


Tube bending is something of an art, especially when done with stainless steel tubing. It is truly
magnificent to see a professionally-crafted array of stainless steel instrument tubes, all bends perfectly
made, all terminations square, all tubes parallel when laid side by side and perfectly perpendicular
when crossing.
If possible, a goal in tube bending is to eliminate as many connections as possible. Connections
invite leaks, and leaks are problematic. Long runs of instrument tubing made from standard 20 foot
tube sections, however, require junctions be made somewhere, usually in the form of tube unions.
When multiple tube unions must be placed in parallel tube runs, it is advisable to offset the unions
so it is easier to get a wrench around the tube nuts to turn them. The philosophy here, as always, is
to build the tubing system with future work in mind. A photograph of several tube junctions shows
one way to do this:
8.2. TUBE AND TUBE FITTINGS 589

If an instrument tube must connect between a stationary object and a vibrating object, a straight
(square) run of tube is actually not desirable, since it will not have much flexibility to absorb the
vibration. Instead, a vibration loop should be made in the tube, giving it the necessary elasticity to
tolerate the vibrational stresses. An example of a vibration loop placed in the air supply tube going
to a control valve appears in this photograph:

When bending such a loop, it is helpful to use the circumference of a large pipe as a mandrel to
form the tube rather than attempt to form a loop purely by hand.
590 CHAPTER 8. INSTRUMENT CONNECTIONS

8.2.4 Special tubing tools


A variety of specialized tools exist to help tubing installers work with compression-style tube fittings.
One of these special devices is an electronic power tool manufactured by American Power Tool
expressly for use with instrument tube fittings:

The Aeroswage SX-1 has a microprocessor-controlled electric motor programmed to rotate a tube
fitting’s nut to a precise angular dimension, in order to properly swage the fitting. The tool comes
complete with a holding jig to engage the body of the tube fitting, in order that all tightening torque
is borne by the tool and not imposed on the person operating the tool:

Not only does this feature reduce the amount of stress placed on the tube fitter’s hand and
wrist, but it also enables the tool to be used in the demanding environment of zero gravity, for
example aboard a space station. In such an environment, torque applied to the tool operator could
be disastrous, as the human operator has no weight to stabilize herself.
8.2. TUBE AND TUBE FITTINGS 591

This next pair of photos shows how the tool is able to support itself on a piece of stiff ( 21 inch
stainless steel) tubing, and indeed may even be operated hands-free:

The amount of rotation is programmable, enabling the tool to be used with different kinds of
fittings. For standard industrial Swagelok compression fitting sizes ( 14 inch, 38 inch, and 12 inch), the
recommended swaging rotation of 1-1/4 turns may be entered into the tool as a tightening angle of
450 degrees:

Being a microprocessor-controlled device, the SX-1 has the ability to digitally record all actions.
This is useful in high-reliability production environments (e.g. aerospace tube installation) where
individual tube fitting data are archived for safety and quality control purposes. This data may be
downloaded to a personal computer through a serial port connection on the side of the tool. Here
you can see the tool’s digital display showing the recorded action number, tightening angle, date,
and time:

For large instrument compression fittings, hydraulic swaging tools are also available to provide the
force necessary to properly compress the ferrule(s) onto the tube. Instrument tube manufacturers
will provide specific recommendations for the installation of non-standard tube types, sizes, and
materials, and also recommend particular swaging tools to use with their fittings.
592 CHAPTER 8. INSTRUMENT CONNECTIONS

8.3 Electrical signal and control wiring


There is much to be said for neatness of assembly in electrical signal wiring. Even though the
electrons don’t “care” how neatly the wires are laid in place, human beings who must maintain the
system certainly do. Not only are neat installations easier to navigate and troubleshoot, but they
tend to inspire a similar standard of neatness when alterations are made7 .
The following photographs illustrate excellent wiring practice. Study them carefully, and strive
to emulate the same level of professionalism in your own work.

Here we see 120 volt AC power distribution wiring. Note how the hoop-shaped “jumper” wires
are all cut to (nearly) the same length, and how each of the wire labels is oriented such that the
printing is easy to read:

7 No one wants to become known as the person who “messed up” someone else’s neat wiring job!
8.3. ELECTRICAL SIGNAL AND CONTROL WIRING 593

This next photograph shows a great way to terminate multi-conductor signal cable to terminal
blocks. Each of the pairs was twisted together using a hand drill set to very slow speed. Note how
the end of the cable is wrapped in a short section of heat-shrink tubing for a neat appearance:

Beyond esthetic preferences for instrument signal wiring are several practices based on sound
electrical theory. The following subsections describe and explain these wiring practices.

8.3.1 Connections and wire terminations


Many different techniques exist for connecting electrical conductors together: twisting, soldering,
crimping (using compression connectors), and clamping (either by the tension of a spring or under
the compression of a screw) are popular examples. Most industrial field wiring connections utilize
a combination of compression-style crimp “lugs” (often referred to as ferrules or compression
terminals) and screw clamps to attach wires to instruments and to other wires.
594 CHAPTER 8. INSTRUMENT CONNECTIONS

The following photograph shows a typical terminal strip or terminal block array whereby twisted-
pair signal cables connect to other twisted-pair signal cables. Metal bars inside each plastic terminal
section form connections horizontally, so that wires fastened to the left side are connected to wires
fastened to the right side:

If you look closely at this photograph, you can see the bases of crimp-style ferrules at the ends of
the wires, just where they insert into the terminal block modules. These terminal blocks use screws
to apply force which holds the wires in close electrical contact with a metal bar inside each block,
but metal ferrules have been crimped on the end of each wire to provide a more rugged tip for the
terminal block screw to hold to. A close-up view shows what one of these ferrules looks like on the
end of a wire:

Also evident in this photograph is the dual-level connection points on the left-hand side of each
terminal block. Two pairs of twisted signal conductors connect on the left-hand side of each terminal
block pair, where only one twisted pair of wires connects on the right-hand side. This also explains
why each terminal block section has two screw holes on the left but only one screw hole on the right.
8.3. ELECTRICAL SIGNAL AND CONTROL WIRING 595

A close-up photograph of a single terminal block section shows how the screw-clamp system
works. Into the right-hand side of this block a single wire (tipped with a straight compression
ferrule) is clamped securely. No wire is inserted into the left-hand side:

If another wire were secured by the screw clamp on the left-hand side of this terminal block, it
would be made electrically common with the wire on the right-hand side by virtue of the metal bar
joining both sides.
596 CHAPTER 8. INSTRUMENT CONNECTIONS

Some terminal blocks are screwless, using a spring clip to make firm mechanical and electrical
contact with the wire’s end:

In order to extract or insert a wire end from or to a “screwless” terminal block, you must insert
a narrow screwdriver into a hole in the block near the insertion point, then pivot the screwdriver
(like a lever) to exert force on the spring clip. Screwless terminal blocks are generally faster to
terminate and un-terminate than screw type terminal blocks, and the pushing action of the release
tool is gentler on the body8 than the twisting action required to loosen and tighten screws.

8 An occupational hazard for technicians performing work on screw terminations is carpal tunnel syndrome, where

repetitive wrist motion (such as the motions required to loosen and tighten screw terminals) damages portions of the
wrist where tendons pass.
8.3. ELECTRICAL SIGNAL AND CONTROL WIRING 597

Many different styles of modular terminal blocks are manufactured to suit different wiring needs.
Some terminal block modules, for example, have multiple “levels” instead of just one. The following
photograph shows a two-level terminal block with screwless wire clamps:

The next photograph shows a three-level terminal block with screw type clamps:

Some multi-level terminal blocks provide the option of internal jumpers to connect two or more
levels together so they will be electrically common instead of electrically isolated. This use of a
multi-level terminal block is preferable to the practice of inserting multiple wires into the same
terminal, when wires need to be made common to each other.
598 CHAPTER 8. INSTRUMENT CONNECTIONS

Other modular terminal blocks include such features as LED indicator lamps, switches, fuses,
and even resettable circuit breakers in their narrow width, allowing the placement of actual circuit
components near connection points. The following photograph shows a swing-open fused terminal
block module, in the open position:

Modular terminal blocks are useful for making connections with both solid-core and stranded
metal wires. The clamping force applied to the wire’s tip by the screw mechanism inside one of
these blocks is direct, with no sliding or other motions involved. Some terminal blocks, however, are
less sophisticated in design. This next photograph shows a pair of “isothermal” terminals designed
to connect thermocouple wires together. Here you can see how the bare tip of the screw applies
pressure to the wire inserted into the block:

The rotary force applied to each wire’s tip by these screws necessitates the use of solid wire.
Stranded wire would become frayed by this combination of forces.
8.3. ELECTRICAL SIGNAL AND CONTROL WIRING 599

Many field instruments, however, do not possess “block” style connection points at all. Instead,
they are equipped with pan-head machine screws designed to compress the wire tips directly between
the heads of the screws and a metal plate below.
Solid wires may be adequately joined to such a screw-head connection point by partially wrapping
the bare wire end around the screw’s circumference and tightening the head on top of the wire, as
is the case with the two short wire stubs terminated on this instrument:

The problem with directly compressing a wire tip beneath the head of a screw is that the tip is
subjected to both compressive and shear forces. As a result, the wire’s tip tends to become mangled
with repeated connections. Furthermore, tension on the wire will tend to turn the screw, potentially
loosening it over time.
This termination technique is wholly unsuitable for stranded wire9 , because the shearing forces
caused by the screw head’s rotation tends to “fray” the individual strands. The best way to
attach a stranded wire tip directly to a screw-style connection point is to first crimp a compression-
style terminal to the wire. The flat metal “lug” (ferrule) portion of the terminal is then inserted
underneath the screw head, where it can easily tolerate the shearing and compressive forces exerted
by the head.

9 An exception is when the screw is equipped with a square washer underneath the head, designed to compress the

end of a stranded wire with no shear forces. Many industrial instruments have termination points like this, for the
express purpose of convenient termination to either solid or stranded wire ends.
600 CHAPTER 8. INSTRUMENT CONNECTIONS

This next photograph shows five such stranded-copper wires connected to screw-style connection
points on a field instrument using compression-style terminals:

Compression-style terminals come in two basic varieties: fork and ring. An illustration of each
type is shown here:

Fork terminal Ring terminal

Fork terminals are easier to install and remove, since they merely require loosening of the
connector screw rather than removal of the screw. Ring terminals are more secure, since they
cannot “fall off” the connection point if the screw ever accidently loosens.
Just as direct termination underneath a screw head is wholly unsuitable for stranded wires,
compression-style terminals are wholly unsuitable for solid wire. Although the initial crimp may feel
secure, compression terminals lose their tension rapidly on solid wire, especially when there is any
motion or vibration stressing the connection. Compression wire terminals should only be crimped
to stranded wire!
8.3. ELECTRICAL SIGNAL AND CONTROL WIRING 601

Properly installing a compression-type terminal on a wire end requires the use of a special
crimping tool. The next photograph shows one of these tools in use:

Note the different places on the crimping tool, labeled for different wire sizes (gauges). One
location is used for 16 gauge to 10 gauge wire, while the location being used in the photograph is
for wire gauges 22 through 18 (the wire inside of the crimped terminal happens to be 18 gauge).
This particular version of a “crimping” tool performs most of the compression on the underside
of the terminal barrel, leaving the top portion undisturbed. The final crimped terminal looks like
this when viewed from the top:
602 CHAPTER 8. INSTRUMENT CONNECTIONS

8.3.2 DIN rail


An industry-standard structure for attaching terminal blocks and small electrical components to
flat metal panels is something called a DIN rail. This is a narrow channel of metal – made of bent
sheet steel or extruded aluminum – with edges designed for plastic components to “clip” on. The
following photograph shows terminal blocks, relay sockets, fuses, and more terminal blocks mounted
to a horizontal length of DIN rail in a control system enclosure:

Two photographs of a terminal block cluster clipped onto a length of DIN rail – one from above
and one from below – shows how specially-formed arms on each terminal block module fit the edges
of the DIN rail for a secure attachment:

The DIN rail itself mounts on to any flat surface by means of screws inserted through the slots
in its base. In most cases, the flat surface in question is the metal subpanel of an electrical enclosure
to which all electrical components in that enclosure are attached.
An obvious advantage of using DIN rail to secure electrical components versus individually
attaching those components to a subpanel with their own sets of screws is convenience: much less
labor is required to mount and unmount a DIN rail-attached component than a component attached
with its own set of dedicated screws. This convenience significantly eases the task of altering a panel’s
configuration. With so many different devices manufactured for DIN rail mounting, it is easy to
8.3. ELECTRICAL SIGNAL AND CONTROL WIRING 603

upgrade or alter a panel layout simply by unclipping components, sliding them to new locations on
the rail, or replacing them with other types or styles of components.
This next photograph shows some of the diversity available in DIN rail mount components. From
left to right we see four relays, a power supply, and three HART protocol converters, all clipped to
the same extruded aluminum DIN rail:

As previously mentioned, DIN rail is available in both stamped sheet-steel and extruded
aluminum forms. A comparison of the two materials is shown here, with sheet steel on the left
and aluminum on the right:

The form of DIN rail shown in all photographs so far is known as “top hat” DIN rail. A variation
in DIN rail design is the so-called “G” rail, with a markedly different shape:
604 CHAPTER 8. INSTRUMENT CONNECTIONS

Fortunately, many modular terminal blocks are formed with the ability to clip to either style of
DIN rail, such as these two specialty blocks, the left-hand example being a terminal block with a
built-in disconnect switch, and the right-hand example being a “grounding” terminal block whose
termination points are electrically common to the DIN rail itself:

If you examine the bottom structure of each block, you will see formations designed to clip either
to the edges of a standard (“top hat”) DIN rail or to a “G” shaped DIN rail.
Smaller DIN rail standards also exist, although they are far less common than the standard
35mm size:
8.3. ELECTRICAL SIGNAL AND CONTROL WIRING 605

A nice feature of many DIN rail type terminal blocks is the ability to attach pre-printed terminal
numbers. This makes documentation of wiring much easier, with each terminal connection having
its own unique identification number:

8.3.3 Cable routing


In the interest of safety and longevity, one cannot simply route electrical power and signal cables
randomly between different locations. Electrical cables must be properly supported to relieve
mechanical stresses on the conductors, and protected from harsh conditions such as abrasion which
might degrade the insulation.
A traditional and rugged technique for cable routing is conduit, either metal or plastic (PVC).
Conduit resembles piping used to convey fluids, except that it is much thinner-walled than fluid pipe
and is not rated to withstand internal pressure as pipe is. In fact, threaded conduit uses the same
thread pitch and diameter standards as NPT (National Pipe Taper) fluid pipe connections.
Metal conduit naturally forms a continuously-grounded enclosure for conductors which not only
provides a measure of protection against electrical shock (all enclosures and devices attached to
the conduit become safely grounded through the conduit) but also shields against electrostatic
interference. This is especially important for power wiring to and from devices such as rectifiers and
variable-frequency motor drive (VFD) units, which have a tendency to broadcast large amounts of
electromagnetic noise.
Plastic conduit, of course, provides no electrical grounding or shielding because plastic is a non-
conductor of electricity. However, it is superior to metal conduit with regard to chemical corrosion
resistance, which is why it is used to route wires in areas containing water, acids, caustics, and other
wet chemicals.
606 CHAPTER 8. INSTRUMENT CONNECTIONS

Thin-wall conduit is made with metal so thin that threads cannot be cut into it. Instead, special
connectors are used to join “sticks” of thin-wall conduit together, and to join thin-wall conduit to
electrical enclosures. Several runs of thin-wall conduit appear in this next photograph. Two of those
conduit runs have been severed following a wiring change, exposing the conductors inside:

Installing cable into an electrical conduit is a task referred to as cable pulling, and it is something
of an art. Cable “pulls” may be especially challenging if the conduit run contains many bends,
and/or is close to capacity in terms of the number and size of conductors it already holds. A good
practice is to always leave a length of nylon pull string inside each length of conduit, ready to use
for pulling a new wire or cable through. When performing a wire “pull,” a new length of nylon
pull string is pulled into the conduit along with the new wires, to replace the old pull string as it
is pulled out of the conduit. Special lubricating “grease” formulated for electrical wiring may be
applied to conductors pulled into a conduit, to reduce friction between those new conductors and
the conductors already inside the conduit.
8.3. ELECTRICAL SIGNAL AND CONTROL WIRING 607

When connecting electrical conduit to end-point devices, it is common to use flexible liquid-
tight conduit as a connector between the rigid metal (or plastic) conduit and the final device. This
provides some stress relief to the conduit in the event the device moves or vibrates, and also allows
more freedom in positioning the device with respect to the conduit. Here, we see a motor-operated
control valve with two runs of liquid-tight conduit routing conductors to it:

Liquid-tight conduit comes in two general varieties: metallic and non-metallic. The metallic kind
contains a spiraled metal sheath just underneath the plastic outer coating to provide a continuously-
608 CHAPTER 8. INSTRUMENT CONNECTIONS

grounded shield much the same way that rigid metal conduit does. Non-metallic liquid-tight conduit
is nothing more than plastic hose, providing physical protection against liquid exposure and abrasion,
but no electrical grounding or shielding ability.

Another technique for cable routing is the use of cable tray. Trays may be made of solid steel
wire for light-duty applications such as instrument signal cabling or computer network cabling,
or they may be made of steel or aluminum channel for heavy-duty applications such as electrical
power wiring. Unlike conduit, cable trays are open, leaving the cables exposed to the environment.
This often necessitates special cable insulation rated for exposure to ultraviolet light, moisture, and
other environmental wear factors. A decided advantage of cable trays is ease of cable installation,
especially when compared to electrical conduit.
While cable tray does provide a continuously-grounded surface for electrical safety the same as
metal conduit, cable tray does not naturally provide shielding for the conductors because it does
not completely enclose the conductors the way metal conduit does.
An example of light-duty cable tray appears here, used to support Ethernet cabling near the
ceiling of a room at a college campus. The cable tray is made of solid steel wire, bent to form a
“basket” to support dozens of yellow Ethernet cables:
8.3. ELECTRICAL SIGNAL AND CONTROL WIRING 609

Heavy-duty cable tray appears throughout this next photograph, supporting large-gauge power
conductors for electric generators at a gas turbine power plant. Here, the cable tray has the
appearance of an aluminum ladder, with extruded metal rails and rungs providing physical support
for the cables:
610 CHAPTER 8. INSTRUMENT CONNECTIONS

Similar cables trays appear in the next photograph, supporting feeder cables from a stationary
transformer and switchgear cabinets:
8.3. ELECTRICAL SIGNAL AND CONTROL WIRING 611

A special form of wiring often seen in industrial facilities for power distribution is busway, also
known as bus duct. These are rectangular sheet-metal tubes containing pre-fabricated copper busbars
for the conduction of three-phase AC power. Special junction boxes, “tees,” and tap boxes allow
busways to extend and branch to other busways and/or standard conductor wiring.
Busways are used in indoor applications, often in motor control center (MCC) and power
distribution center rooms to route electrical power to and from large disconnect switches, fuses,
and circuit breakers. In this photograph, we see busway used to distribute power along the ceiling
of an MCC room, alongside regular rigid conduit:

As useful and neat in appearance as busways are, they are definitely limited in purpose. Busways
are only used for electrical power distribution; not for instrumentation, control, or signaling purposes.

Two materials useful for neatly routing power, signal, and instrumentation conductors inside an
enclosure are wire duct and wire loom. Wire duct is a plastic channel with slotted sides, designed
to be attached to the subpanel of an enclosure along with all electrical devices inside that enclosure.
Wires pass from the devices to the duct through the slots (gaps) in the sides of the duct, and are
enclosed by a removable plastic cover that snaps onto the top of the duct. A common brand name
of wire duct in the industry is Panduit and so you will often hear people refer to wire duct as
“Panduit” whether or not that particular brand is the one being used10 . Wire loom is a loose spiral
10 This is similar to people referring to adhesive bandages as “Band-Aids” or tongue-and-groove joint pliers as
612 CHAPTER 8. INSTRUMENT CONNECTIONS

tube made of plastic, used to hold a group of individual wires together into a neat bundle. Wire
loom is frequently used when a group of conductors must periodically flex, as is the case of a wire
bundle joining devices inside a panel to other devices mounted on the hinging door of that panel.
A photograph showing both wire duct and wire loom inside an instrumentation panel appears
here. The wire duct is the grey-colored rectangular plastic channel set vertically and horizontally
inside the panel, while the loom is a grey-colored plastic spiral surrounding the bundle of wires near
the door hinge:

“Channelocks,” because those particular brands have become popular enough to represent an entire class.
8.3. ELECTRICAL SIGNAL AND CONTROL WIRING 613

8.3.4 Signal coupling and cable separation


If sets of wires lie too close to one another, electrical signals may “couple” from one wire (or set
of wires) to the other(s). This can be especially detrimental to signal integrity when the coupling
occurs between AC power conductors and low-level instrument signal wiring such as thermocouple
or pH sensor cables.
Two mechanisms of electrical “coupling” exist: capacitive and inductive. Capacitance is a
property intrinsic to any pair of conductors separated by a dielectric (an insulating substance),
whereby energy is stored in the electric field formed by voltage between the wires. The natural
capacitance existing between mutually insulated wires forms a “bridge” for AC signals to cross
between those wires, the strength of that “bridge” inversely proportional to the capacitive reactance
(XC = 2πf1 C ). Inductance is a property intrinsic to any conductor, whereby energy is stored in the
magnetic field formed by current through the wire. Mutual inductance existing between parallel
wires forms another “bridge” whereby an AC current through one wire is able to induce an AC
voltage along the length of another wire.
Capacitive coupling between an AC power conductor and a DC sensor signal conductor is shown
in the following diagram:

Load Power
source
Capacitance
Vdifference through the air
Potentiometric sensor
Rsensor Receiving instrument

Vsensor +
− Some AC "noise" will Rinput
be seen at the receiving
instrument’s input

If the voltage-generating sensor happens to be a thermocouple and the receiving instrument a


temperature indicator, the result of this capacitive coupling will be a “noisy” temperature signal
interpreted by the instrument. This noise will be proportional to both the voltage and the frequency
of the AC power.
614 CHAPTER 8. INSTRUMENT CONNECTIONS

Inductive coupling between an AC power conductor and a DC sensor signal conductor is shown
in the following diagram:

Magnetic field

Current
Load Power
source

Potentiometric sensor
Rsensor Receiving instrument
Induced current

Vsensor +
− Some AC "noise" will Rinput
be seen at the receiving
instrument’s input

Whereas the amount of noise induced into a low-level signal via capacitive coupling was a function
of voltage and frequency, the amount of noise induced into a signal via inductive coupling is a function
of current and frequency11 .

A good way to minimize signal coupling is to simply separate conductors carrying incompatible
signals. This is why electrical power conductors and instrument signal cables are almost never found
in the same conduit or in the same ductwork together. Separation decreases capacitance between the
conductors (recall that C = A" d where d is the distance between the conductive surfaces). Separation
also decreases the coupling
√ coefficient between inductors, which in turn decreases mutual inductance
(recall that M = k L1 L2 where k is the coupling coefficient and M is the mutual inductance
between two inductances L1 and L2 ). In control panel wiring, it is customary to route AC power
wires in such a way that they do not lay parallel to low-level signal wires, so that both forms of
coupling may be reduced.
11 The principle at work here is the strength of the field generated by the noise-broadcasting conductor: electric

field strength (involved with capacitive coupling) is directly proportional to voltage, while magnetic field strength
(involved with inductive coupling) is directly proportional to current.
8.3. ELECTRICAL SIGNAL AND CONTROL WIRING 615

If conductors carrying incompatible signals must cross paths, it is advisable to orient the
conductors perpendicular to each other rather than parallel, like this:

Signal conductors

90o
Power conductors

Perpendicular conductor orientation reduces both inter-conductor capacitance and mutual


inductance by two mechanisms. Capacitance between conductors is reduced by means of minimizing
overlapping area (A) resulting from the perpendicular crossing. Mutual inductance is reduced by
decreasing the coupling coefficient (k) to nearly zero since the magnetic field generated perpendicular
to the current-carrying wire will be parallel and not perpendicular to the “receiving” wire. Since
the vector for induced voltage is perpendicular to the magnetic field (i.e. parallel with the current
vector in the “primary” wire) there will be no voltage induced along the length of the “receiving”
wire.

The problem of power-to-signal line coupling is most severe when the signal in question is analog
rather than digital. In analog signaling, even the smallest amount of coupled “noise” corrupts the
signal. A digital signal, by comparison, will become corrupted only if the coupled noise is so great
that it pushes the signal level above or below a detection threshold it should not cross. This disparity
is best described through illustration.
616 CHAPTER 8. INSTRUMENT CONNECTIONS

Two signals are shown here, coupled with equal amounts of noise voltage:

Analog signal with noise


URV

LRV

Digital signal with noise

High threshold

Low threshold

Corrupted bit!

The peak-to-peak amplitude of the noise on the analog signal is almost 20% of the entire
signal range (the distance between the lower- and upper-range values), representing a substantial
degradation of signal integrity. Analog signals have infinite resolution, which means any change in
signal amplitude has meaning. Therefore, any noise whatsoever introduced into an analog signal
will be interpreted as variations in the quantity that signal is supposed to represent.
That same amount of noise imposed on a digital signal, however, causes no degradation of the
signal except for one point in time where the signal attempts to reach a “low” state but fails to cross
the threshold due to the noise. Other than that one incident represented in the pulse waveform, the
rest of the signal is completely unaffected by the noise, because digital signals only have meaning
above the “high” state threshold and below the “low” state threshold. Changes in signal voltage level
caused by induced noise will not affect the meaning of digital data unless and until the amplitude
of that noise becomes severe enough to prevent the signal’s crossing through a threshold (when it
should cross), or causes the signal to cross a threshold (when it should not).
From what we have seen here, digital signals are far more tolerant of induced noise than analog
signals, all other factors being equal. If ever you find yourself in a position where you must route
a signal wire near AC power conductors, and you happen to have the choice whether it will be an
analog signal (e.g. 4-20 mA, 0-10 V) or a digital signal (e.g. EIA/TIA-485, Ethernet), your best
option is to choose the digital signal to coexist alongside the AC power wires.
8.3. ELECTRICAL SIGNAL AND CONTROL WIRING 617

8.3.5 Electric field (capacitive) de-coupling


The fundamental principle invoked in shielding signal conductor(s) from external electric fields is
that no substantial electric field can exist within a solid conductor. Electric fields exist due to
imbalances of electric charge. If such an imbalance of charge ever were to exist within a conductor,
charge carriers (typically electrons) in that conductor would quickly move to equalize the imbalance,
thus eliminating the electric field. Another way of saying this is to state that electric fields only
exist between points of different potential, and therefore cannot exist between equipotential points.
Thus, electric flux lines may be found only in the dielectric (insulating media) between conductors,
not within a solid conductor:

Electric field lines

Metal Solid
plate metal
sphere

This also means electric flux lines cannot span the diameter of a hollow conductor:

Electric field lines

Metal Hollow
plate metal
sphere

Note: no electric
field lines inside
the hollow sphere!

The electrical conductivity of the hollow sphere’s wall ensures that all points on the circumference
of the sphere are equipotential to each other. This in turn prohibits the formation of any electric
flux lines within the interior air space of the hollow sphere. Thus, all points within the hollow sphere
are shielded from any electric fields originating outside of the sphere.
618 CHAPTER 8. INSTRUMENT CONNECTIONS

The only way to allow an external electric field to penetrate a hollow conductor from the outside
is if that conductive shell is left “floating” with respect to another conductor placed within the shell.
In this case the lines of electric flux do not exist between different points on the conductive sphere,
but rather between the shell of the sphere and the conductor at the center of the sphere because
those are the points between which a potential difference (voltage) exists. To illustrate:

Electric field lines


Radial electric
field lines

Metal
plate

However, if we make the hollow shell electrically common to the negative side of the high-voltage
source, the flux lines inside the sphere vanish, since there is no potential difference between the
internal conductor and the conductive shell:

Electric field lines


No electric
field lines!

Metal
plate
8.3. ELECTRICAL SIGNAL AND CONTROL WIRING 619

If the conductor within the hollow sphere is elevated to a potential different from that of the
high-voltage source’s negative terminal, electric flux lines will once again exist inside the sphere, but
they will reflect this second potential and not the potential of the original high-voltage source. In
other words, an electric field will exist inside the hollow sphere, but it will be completely isolated
from the electric field outside the sphere. Once again, the conductor inside is shielded from external
electrostatic interference:

Electric field lines from high-voltage source

Radial electric
field lines
from Vsignal
Metal
plate

Vsignal

If conductors located inside the hollow shell are thus shielded from external electric fields, it means
there cannot exist any capacitance between external conductors and internal (shielded) conductors.
If there is no capacitance between conductors, there will never be capacitive coupling of signals
between those conductors, which is what we want for industrial signal cables to protect those signals
from external interference12 .

12 Incidentally, cable shielding likewise guards against strong electric fields within the cable from capacitively coupling

with conductors outside the cable. This means we may elect to shield “noisy” power cables instead of (or in addition
to) shielding low-level signal cables. Either way, good shielding will prevent capacitive coupling between conductors
on either side of a shield.
620 CHAPTER 8. INSTRUMENT CONNECTIONS

All this discussion of hollow metal spheres is just an introduction to a discussion of shielded cable,
where electrical cables are constructed with a conductive metal foil wrapping or conductive metal
braid surrounding the interior conductors. Thus, the foil or braid creates a conductive tube which
may be connected to ground potential (the “common” point between external and internal voltage
sources) to prevent capacitive coupling between any external voltage sources and the conductors
within the cable:

Load Power
source
Capacitance
through the air
Potentiometric sensor
Shielded cable Receiving instrument
Rsensor

Vsensor +

Rinput

No AC "noise" will
be seen at the receiving
instrument’s input
8.3. ELECTRICAL SIGNAL AND CONTROL WIRING 621

The following photograph shows a set of signal cables with braided shield conductors all connected
to a common copper “ground bus.” This particular application happens to be in the control panel
of a 500 kV circuit breaker, located at a large electrical power substation where strong electric fields
abound:

This next photograph shows a four-conductor USB cable stripped at one end, revealing a metal-
foil shield as well as silver-colored wire strands in direct contact with the foil, all wrapped around
the four colored power and signal conductors:

At the terminating end we typically twist the loose shield conductor strands together to form a
wire which is then attached to a ground point to fix the cable’s shield at Earth potential.
622 CHAPTER 8. INSTRUMENT CONNECTIONS

It is very important to ground only one end of a cable’s shield, or else you will create the
possibility for a ground loop: a path for current to flow through the cable’s shield resulting from
differences in Earth potential at the cable ends. Not only can ground loops induce noise in a cable’s
conductor(s), but in severe cases it can even overheat the cable and thus present a fire hazard:

A ground loop: something to definitely avoid!

Shielded cable


+
Potential between different
earth-ground locations

An important characteristic of capacitively-coupled noise voltage is that it is common-mode in


nature: the noise appears equally on every conductor within a cable because those conductors lie
so close to each other (i.e. because the amount of capacitance existing between each conductor and
the noise source is the same). One way we may exploit this characteristic in order to help escape
the unwanted effects of capacitive coupling is to use differential signaling. Instead of referencing
our signal voltage to ground, we let the signal voltage “float.” The following schematic diagram
illustrates how this works:

Load Power
source
Capacitance
through the air
Potentiometric sensor
Rsensor Receiving instrument

Rinput
Vsensor +
− Noise voltage will appear between
either signal wire and ground, but
not between the signal wires

The lack of a ground connection in the DC signal circuit prevents capacitive coupling with the
AC voltage from corrupting the measurement signal “seen” by the instrument. Noise voltage will
still appear between either signal wire and ground as a common-mode voltage, but noise voltage
will not appear between the two signal wires where our signal of interest exists. In other words, we
8.3. ELECTRICAL SIGNAL AND CONTROL WIRING 623

side-step the problem of common-mode noise voltage by making common-mode voltage irrelevant
to the sensor and to the signal receiver.
Some industrial data communications standards such as EIA/TIA-485 (RS-485) use this
technique to minimize the corrupting effects of electrical noise. To see a practical example of how
this works in a data communications circuit, refer to the illustration in section 15.6.2 beginning on
page 1057 of this book.

8.3.6 Magnetic field (inductive) de-coupling


Magnetic fields, unlike electric fields, are exceedingly difficult to completely shield. Magnetic flux
lines do not terminate, but rather loop. Thus, one cannot “stop” a magnetic field, only re-direct
its path. A common method for magnetically shielding a sensitive instrument is to encapsulate
it in an enclosure made of some material having an extremely high magnetic permeability (µ): a
shell offering much easier passage of magnetic flux lines than air. A material often used for this
application is mu-metal, or µ-metal, so named for its excellent magnetic permeability:

µ-metal
shield
N

Magnet Sensitive
device

This sort of shielding is impractical for protecting signal cables from inductive coupling, as mu-
metal is rather expensive and must be layered relatively thick in order to provide a sufficiently
low-reluctance path to shunt most of the external magnetic flux lines.
The most practical method of granting magnetic field immunity to a signal cable follows the
differential signaling method discussed in the electric field de-coupling section, with a twist (literally).
If we twist a pair of wires rather than allow them to lie along parallel straight lines, the effects of
electromagnetic induction are vastly minimized.
624 CHAPTER 8. INSTRUMENT CONNECTIONS

The reason this works is best illustrated by drawing a differential signal circuit with two thick
wires, drawn first with no twist at all. Suppose the magnetic field shown here (with three flux lines
entering the wire loop) happens to be increasing in strength at the moment in time captured by the
illustration:

AC magnetic
field Receiving instrument
Rinput

Induced current


+

Vsensor
Potentiometric sensor

According to Lenz’s Law, a current will be induced in the wire loop in such a polarity as to
oppose the increase in external field strength. In other words, the induced current tries to “fight”
the imposed field to maintain zero net change. According to the right-hand rule of electromagnetism
(tracing current in conventional flow notation), the induced current must travel in a counter-clockwise
direction as viewed from above the wire loop in order to generate a magnetic field opposing the rise
of the external magnetic field. This induced current works against the DC current produced by the
sensor, detracting from the signal received at the instrument.
When the external magnetic field strength diminishes, then builds in the opposite direction, the
induced current will reverse. Thus, as the AC magnetic field oscillates, the induced current will also
oscillate in the circuit, causing AC “noise” voltage to appear at the measuring instrument. This is
precisely the effect we wish to mitigate.
Immediately we see a remarkable difference between noise voltage induced by a magnetic field
versus noise voltage induced by an electric field: whereas capacitively-coupled noise was always
common-mode, here we see inductively-coupled noise as differential 13 .
13 This is not to say magnetic fields cannot induce common-mode noise voltage: on the contrary, magnetic fields are
8.3. ELECTRICAL SIGNAL AND CONTROL WIRING 625

If we twist the wires so as to create a series of loops instead of one large loop, we will see that
the inductive effects of the external magnetic field tend to cancel:

AC magnetic
field Receiving instrument
Rinput

Induced current
opposed!

Induced current

+

Vsensor
Potentiometric sensor

Not all the lines of flux go through the same loop. Each loop represents a reversal of direction
for current in the instrument signal circuit, and so the direction of magnetically-induced current in
one loop directly opposes the direction of magnetically-induced current in the next. So long as the
loops are sufficient in number and spaced close together, the net effect will be complete and total
opposition between all induced currents, with the result of no net induced current and therefore no
AC “noise” voltage appearing at the instrument.
In order to enjoy the benefits of magnetic and electric field rejection, instrument cables are
generally manufactured as twisted, shielded pairs. The twists guard against magnetic (inductive)
interference, while the grounded shield guards against electric (capacitive) interference. If multiple
wire pairs are twisted within the same cable, the twist rates of each pair may be made different so
as to avoid magnetic coupling from pair to pair14 .

capable of inducing voltage in any electrically-conductive loop. For this reason, both differential and ground-referenced
signals are susceptible to interference by magnetic fields.
14 An example of this is the UTP (Unshielded, Twisted Pair) cabling used for Ethernet digital networks, where four

pairs of wires having different twist rates are enclosed within the same cable sheath.
626 CHAPTER 8. INSTRUMENT CONNECTIONS

8.3.7 High-frequency signal cables


Electronic signals used in traditional instrumentation circuits are either DC or low-frequency AC
in nature. Measurement and control values are represented in analog form by these signals, usually
by the magnitude of the electronic signal (how many volts, how many milliamps, etc.). Modern
electronic instruments, however, often communicate process and control data in digital rather than
analog form. This digital data takes the form of high-frequency voltage and/or current pulses along
the instrument conductors. The most capable fieldbus instruments do away with analog signaling
entirely, communicating all data in digital form at relatively high speeds.
If the time period of a voltage or current pulse is less than the time required for the signal
to travel down the length of the cable (at nearly the speed of light!), very interesting effects may
occur. When a pulse propagates down a two-wire cable and reaches the end of that cable, the energy
contained by that pulse must be absorbed by the receiving circuit or else be reflected back down the
cable. To be honest, this happens in all circuits no matter how long or brief the pulses may be, but
the effects of a “reflected” pulse only become apparent when the pulse time is short compared to
the signal propagation time. In such short-pulse applications, it is customary to refer to the cable as
a transmission line 15 , and to regard it as a circuit component with its own characteristics (namely,
a continuous impedance as “seen” by the traveling pulse). For more detail on this subject, refer to
section 5.10 beginning on page 475.
This problem has a familiar analogy: an “echo” in a room. If you step into a large room with
hard wall, floor, and ceiling surfaces, you will immediately notice echoes resulting from any sound
you make. Holding a conversation in such a room can be quite difficult, as the echoed sounds
superimpose upon the most recently-spoken sounds, making it difficult to discern what is being said.
The larger the room, the longer the echo delay, and the greater the conversational confusion.
Echoes happen in small rooms, too, but they are generally too short to be of any concern. If
the reflected sound(s) return quickly enough after being spoken, the time delay between the spoken
(incident) sound and the echo (reflected) sound will be too short to notice, and conversation will
proceed unhindered.
We may address the “echo” problem in two entirely different ways. One way is to eliminate the
echoes entirely by adding sound-deadening coverings (carpet, acoustic ceiling tiles) and/or objects
(sofas, chairs, pillows) to the room. Another way to address the problem of echoes interrupting a
conversation is to slow down the rate of speech. If the words are spoken slowly enough, the time delay
of the echoes will be relatively short compared to the period of each spoken sound, and conversation
may proceed without interference16 (albeit at a reduced speed).
Both the problem of and the solutions for reflected signals in electrical cables follow the same
patterns as the problem of and solutions for sonic echoes in a hard-surfaced room. If an electronic
circuit receiving pulses sent along a cable receives both the incident pulse and an echo (reflected
pulse) with a significant time delay separating those two pulses, the digital “conversation” will be
impeded in the same manner that a verbal conversation between two or more people is impeded by
echoes in a room. We may address this problem either by eliminating the reflected pulses entirely
(by ensuring all the pulse energy is absorbed by an appropriate load placed at the cable’s end) or
15 This use of the term is entirely different from the same term’s use in the electric power industry, where a

“transmission line” is a set of conductors used to send large amounts of electrical energy over long distances.
16 A student of mine once noted that he has been doing this out of habit whenever he has a conversation with anyone

in a racquetball court. All the hard surfaces (floor, walls) in a racquetball court create severe echoes, forcing players
to speak slower in order to avoid confusion from the echoes.
8.3. ELECTRICAL SIGNAL AND CONTROL WIRING 627

by slowing down the data transfer rate (i.e. longer pulses, lower frequencies) so that the reflected
and incident pulse signals virtually overlap one another at the receiver.
High-speed “fieldbus” instrument networks apply the former solution (eliminate reflections)
while the legacy HART instrument signal standard apply the latter (slow data rate). Reflections
are eliminated in high-speed data networks by ensuring the two furthest cable ends are both
“terminated” by a resistance value of the proper size (matching the characteristic impedance of
the cable). The designers of the HART analog-digital hybrid standard chose to use slow data
rates instead, so their instruments would function adequately on legacy signal cables where the
characteristic impedance is not standardized.

The potential for reflected pulses in high-speed fieldbus cabling is a cause for concern among
instrument technicians, because it represents a new phenomenon capable of creating faults in an
instrument system. No longer is it sufficient to have tight connections, clean wire ends, good
insulation, and proper shielding for a signal cable to faithfully convey a 4-20 mA DC instrument
signal from one device to another. Now the technician must ensure proper termination and the
absence of any discontinuities17 (sharp bends or crimps) along the cable’s entire length, in addition
to all the traditional criteria, in order to faithfully convey a digital fieldbus signal from one device
to another.
Signal reflection problems may be investigated using a diagnostic instrument known as a time-
domain reflectometer, or TDR. These devices are a combination of pulse generator and digital-storage
oscilloscope, generating brief electrical pulses and analyzing the returned (echoed) signals at one end
of a cable. If a TDR is used to record the pulse “signature” of a newly-installed cable, that data
may be compared to future TDR measurements on the same cable to detect cable degradation or
wiring changes.

17 The characteristic, or “surge,” impedance of a cable is a function of its conductor geometry (wire diameter and

spacing) and dielectric value of the insulation between the conductors. Any time a signal reaches an abrupt change
in impedance, some (or all) of its energy is reflected in the reverse direction. This is why reflections happen at the
unterminated end of a cable: an “open” is an infinite impedance, which is a huge shift from the finite impedance
“seen” by the signal as it travels along the cable. This also means any sudden change in cable geometry such as a
crimp, nick, twist, or sharp bend is capable of reflecting part of the signal. Thus, high-speed digital data cables must
be installed more carefully than low-frequency or DC analog signal cables.
628 CHAPTER 8. INSTRUMENT CONNECTIONS

8.4 Fiber optics


Light has long18 been used as a long-range signaling medium. While communication by light through
open air is still possible using modern technology, it is far more practical in most cases to channel
the light signals through a special strand of optically transparent material called an optical fiber.
When packaged in a protective sheath, it is known as a fiber optic cable.
The transmission of light through a “light pipe” was demonstrated as early as 1842 by Daniel
Colladon and Jacques Babinet in Paris, using a running stream of water to guide a beam of light.
Many modern houses in the United States are equipped with light-pipes19 directing natural sunlight
into rooms for illumination, without the use of “skylight” ceiling windows. Modern fiber optic
cables apply similar optical principles to very small-diameter fibers of transparent material (usually
ultra-pure glass), able to convey optical energy and optically-encoded information.

18 Smoke signals are an ancient form of light-based communication!


19 These are thin plastic or sheet metal tubes with mirrored internal surfaces, extending from a collector dome (made
of glass or plastic) outside the dwelling to a diffusion lens inside the dwelling.
8.4. FIBER OPTICS 629

8.4.1 Fiber optic data communication


Simply put, an optical fiber is a “pipe” through which light flows. This is, of course, merely an
analogy for how an optical fiber works, but it conveys the basic idea. The interface between a
piece of electronic equipment and an optical fiber consists of an optical source (typically an LED
or a semiconductor laser) to generate light signals from electrical signals, and an optical detector
(typically a photodiode or phototransistor) to generate electrical signals from received light signals.
The predominant use of optical fiber in modern industry is as a data communication medium
between digital electronic devices, replacing copper-wire signal and network cabling. An illustration
showing two digital electronic devices communicating over a pair of optical fibers appears here,
each fiber “conducting” pulses of light (representing serial digital data) from an LED source to a
photodiode detector:

Duplex serial fiber-optic communication

Digital electronic device Signal Digital electronic device


Optical fiber
TD RD
... ...
LED Photodiode

Signal
Optical fiber
RD TD
... ...
Photodiode LED

The following photograph shows a serial converter (the black rectangular plastic box with a blue
label) used to convert optical data pulses entering and exiting through orange-jacketed optical cables
(on the left) into EIA/TIA-232 compliant electrical signals through a DB-9 connector (on the right)
and vice-versa, allowing the electronic serial data device on the right-hand side of the photograph
to communicate via fiber optic cabling:

Note how the two optical fiber ports on the converter body are labeled “R” and “T” for Receive
and Transmit, respectively. Serial devices with built-in electronic/optical converters will similarly
label their optical ports.
630 CHAPTER 8. INSTRUMENT CONNECTIONS

For this device, connection to each of the optical fibers is made using an “ST” style connector,
with a quarter-turn locking ring holding each one in place (much like the quarter-turn barrel body of
a “BNC” style electrical connector). The next photograph shows a pair of optical fibers terminated
with ST-style connectors. White plastic caps cover the connector tips, keeping the glass fiber ends
protected from dust and abrasion:

As a data pathway, optical fiber enjoys certain advantages over electrical cable, including:

• Much greater bandwidth (data-carrying capacity), estimated to be in the terahertz range


• Much less equivalent signal power loss per unit cable length (less than 1 dB per kilometer
compared with 25 dB per kilometer for coaxial cable)
• Complete immunity to external “noise” sources
• No radiation of energy or data from the cable, thus will not create interference nor be liable
to eavesdropping
• No electrical conductivity, allowing safe routing of cables near high voltage conductors
• Total galvanic isolation (i.e. no electrically conductive connection) between data devices,
allowing operation at different electrical potentials
• Safe for use in areas with explosive vapors, dust, and/or fibers

These advantages deserve some elaboration. The superior bandwidth of fiber-optic cable is
so dramatic that the present-day (2015) limitation on data transfer rates for most fiber-optic
installations is the electronic devices at each end, and not the optical fiber itself! This, combined
with the low inherent power loss of optical fiber, makes it an ideal medium for long-range data
communication such as telephone and internet. Thousands of miles of optical fiber cable have
8.4. FIBER OPTICS 631

been buried in underground trenches, laid down on sea floors, strung as overhead lines, and used as
“patch” cables in room-scale applications since the advent of affordable optical cabling in the 1980’s.
The “tech boom” of the 1990’s saw an impressive amount of trans-continental and inter-continental
optical fiber installation, paving the way for the global expansion of internet services into the 21st
century. The limitations of electronics at each end of these long fibers means we have not yet begun to
tap their full data-carrying capacity, either. Conveying data in photonic – as opposed to electronic
– form means there is absolutely no such thing as capacitive or inductive coupling with external
systems as there is with conductive wire cable, which not only means optical fiber communication
is immune to external interference but also that the optical signals cannot create interference for
any other system. Since optical fibers are customarily manufactured from glass which is electrically
non-conductive, it is possible to route optical fibers alongside high-voltage power lines, and also
connecting together devices at vastly different electrical potentials from each other, with no risk of
bridging those differing potentials. Finally, the low power levels associated with optical fiber signals
also makes this technology completely safe in areas where explosive compounds in the atmosphere
might otherwise be ignited by faults in electrical communications cable.

Optical fibers also suffer from some unique limitations when compared against electrical cable,
including:

• Need to avoid tight bend radii for optical cables


• Connections need to be extremely clean

• Specialized tools and skills necessary for installation and maintenance

• Expensive testing equipment

While electrical “transmission line” signal cables must also avoid sharp bends and other
discontinuities caused by cramped installations, this need is especially pronounced for optical fiber
(for reasons which will be explained later in this section). Since fiber-to-fiber connections consist
of glass pressed against glass, the presence of even microscopic contaminants such as dust particles
may damage fiber optic connectors if they aren’t cleaned20 prior to insertion. Cutting, preparing,
and terminating optical fiber cables requires its own set of specialized tools and skills, and is not
without unique hazards21 . Lastly, the test equipment necessary to check the integrity of an optical
pathway is similarly specialized and typically quite expensive.

20 Technicians working with optical fiber typically carry pressurized cans of dust-blowing air or other gas to clean

connectors and sockets prior to joining the two.


21 Chief of which is the potential to get optical fibers embedded in the body, where such transparent “slivers” are

nearly impossible to find and extract.


632 CHAPTER 8. INSTRUMENT CONNECTIONS

8.4.2 Fiber optic sensing applications


Optical fibers find applications beyond electronic data cable replacement, though, which means they
will be a growing presence in the field of industrial instrumentation above and beyond their use as
serial data communication cables. Some industrial process transmitters use optical fibers to send and
receive light between the transmitter electronics and an optically-based primary sensing element.
This may be as simple as a non-contact proximity switch using light to sense the presence of an
object within a gap between the two fibers’ ends, or as sophisticated as a chemical analyzer relying
on the absorption of specific light wavelengths to detect the presence of a chemical substance in a
solution.
8.4. FIBER OPTICS 633

Turbine flowmeter sensing


One example of a specialized application for optical fibers is shown in this photograph of a
paddlewheel-style liquid flowmeter using a pair of optical fibers to convey light to and from the
paddlewheel assembly, where the spinning paddlewheel serves to “chop” the light beam and thereby
represent liquid flow rate as a frequency of pulsing light:

An end-view of the two optical fibers is shown in the next photograph. When installed as a
working system, these two fibers will plug into a flow transmitter device sending a continuous beam
of light through one fiber and sensing the pulsed light signal coming back from the paddlewheel
through the other fiber:
634 CHAPTER 8. INSTRUMENT CONNECTIONS

Fabry-Perot interferometry temperature measurement


Another example of a specialized application for optical fibers is measurement of high temperatures
using the Fabry-Perot interferometry method. This technology utilizes a small, thin disk of sapphire
as a temperature sensor. The thickness of this disk as well as the speed of light through the sapphire
are both temperature-dependent, which means a photon22 of light shot at the face of the disk will
reflect off the back face of the disk and return to the source at different times depending on the
temperature of the disk. In a Fabry-Perot interferometer instrument, the “optical thickness” of the
sapphire disk is measured by sending a continuous beam of white light to the disk and receiving the
reflected light from the disk through a single optical fiber, the optical interference resulting from
the incident and reflected light beams representing the disk’s temperature. This novel method of
temperature measurement shows promise for certain challenging industrial process applications such
as high-temperature measurement inside slagging coal gasifiers used to efficiently extract energy and
chemical feedstocks from coal:

Sapphire disk

Fabry-Perot interferometry
temperature transmitter
Incident light Reflected light
(with interference
patterns as a function
Process vessel
of temperature)

Light source and


interferometry Optical fiber
pattern analyzer

Temperature signal

22 A “photon” is a quantity of light energy represented as a particle, along the same scale as an electron. It isn’t

entirely fair to characterize light as either consisting of waves or as consisting of particles, because light tends to
manifest properties of both. Actually, this may be said of any sub-atomic particle (such as an electron) as well: under
certain conditions these particles act like clumps of matter, and under different conditions they tend to act as waves of
electromagnetic energy. This particle-wave duality lies at the heart of quantum physics, and continues to be something
of a philosophical mystery simply because the behavior defies the macroscopic constructs we are accustomed to using
when modeling the natural world.
8.4. FIBER OPTICS 635

Dissolved oxygen measurement


Yet another example of a specialized application for optical fibers is the measurement of dissolved
oxygen in aqueous solutions using the dynamic luminescence quenching or fluorescence quenching
method. This technology uses a thin layer of solid material containing molecules known to fluoresce23
with red light when exposed to visible light of a shorter wavelength (typically green or blue). Oxygen
molecules present in the liquid solution tend to bond with the fluorescing molecules in the sensor and
inhibit that fluorescence, thus providing a means of measuring oxygen concentration near the sensor:
the less O2 dissolved in solution, the stronger the fluorescence (i.e. more red light received, for a
longer duration); the more O2 , the less fluorescence. Optical fibers convey both the incident (green
or blue) and returned (red) light between the wet sensing element and the interpreting electronics.

Dynamic luminescence quenching


dissolved oxygen transmitter

Optical fiber
Light source and Incident light
(green or blue)
detector
Fluorescent light
(red)
Probe containing
optically active
substances

Dissolved O2 concentration
signal

Process liquid

In both the Fabry-Perot interferometry and the fluorescence quenching sensors, the function of
the fiber optic cable is to physically separate the sensing element from the sophisticated and fragile
electronic transmitter needed to interpret the optical signal as a process variable measurement.

23 Fluorescence is the phenomenon of a substance emitting a long-wavelength (low-energy) photon when “excited” by

a short-wavelength (high-energy) photon. Perhaps the most familiar example of fluorescence is when certain materials
emit visible light when exposed to ultraviolet light which is invisible to the human eye. The example of fluorescence
discussed here with dissolved oxygen sensing happens to use two different colors (wavelengths) of visible light, but
the basic principle is the same.
636 CHAPTER 8. INSTRUMENT CONNECTIONS

Arc flash detection


There is at least one application where the optical fiber itself is the sensing element: arc flash
detection within high-voltage switchgear cabinets. “Arc flash” is the phenomenon of intense heat and
light developed at a high-current electrical arc, especially a phase-to-phase arc between electric power
conductors where there is little circuit resistance to limit fault current. High-voltage switchgear is
constructed in such a way as to extinguish the arc normally developed at the contacts during
each “opening” cycle, but certain faults within a piece of switchgear may inhibit this extinguishing
function. In such cases the potential for equipment damage and threat to human health and life is
severe.
If a bare (unjacketed) optical fiber is properly arranged within a piece of switchgear, an arc flash
event will inject enough light through the fiber that some of it will be detected at the far end where
it meets a light-sensitive receiver. Since the fiber itself is not electrically conductive, there is no risk
of conducting a high-voltage arc back to this receiver. The receiver, meanwhile, serves the purpose of
commanding any “upstream” switchgear to trip open in the event of a detected arc fault. The early
detection of arc flash by optical means rather than the time-delayed detection of the same fault by
overcurrent or current-imbalance detection results in much faster clearing of the faulted switchgear
from the power grid, both limiting equipment damage and limiting the potential for injury or death.
8.4. FIBER OPTICS 637

8.4.3 Fiber optic cable construction


Communication-grade optical fibers are manufactured from fused silica (SiO2 ) glass of exceptional
purity24 . A single strand of optical fiber made from this glass called the “core” serves as a waveguide
for the light. The core is surrounded by another layer of glass called the “cladding” which has a
different index of refraction25 necessary to “channel” the majority of the optical energy through the
core and inhibit “leakage” of optical power from the cable. Additional layers of plastic and other
materials around the core/cladding center provide coloring (for fiber identification in multi-fiber
cables), protection against abrasion, and tensile strength so the cable will not suffer damage when
pulled through conduit.
The purpose of building a fiber optic cable with a core and a cladding having different refractive
indices (i.e. different speeds of light) is to exploit a phenomenon called total internal reflection,
whereby rays of light reflect off the interface between core and cladding to prevent its unintentional
escape from the core at any point along the length of the fiber.
When light crosses an interface between two materials having different speeds, the light beam
will become refracted as a function of those two speeds as described by Snell’s Law :

Incident θ1
light beam

v1 = Speed of light in first material

v2 = Speed of light in second material

Refracted
sin θ1 < sin θ2 θ2 light beam
because
v1 < v2

Snell’s Law relates the sine of the incident angle to the sine of the refracted angle as a ratio to
each material’s speed of light, the material possessing the greatest speed of light (i.e. the lowest
refractive index value) exhibiting the greatest angle as measured from perpendicular to the interface:
sin θ1 sin θ2
=
v1 v2

24 Impurities such as metals and water are held to values less than 1 part per billion (ppb) in modern optical

fiber-grade glass.
25 The “index of refraction” (n) for any substance is the ratio of the speed of light through a vacuum (c) compared

to the speed of light through that substance (v): n = vc . For all substances this value will be greater than one (i.e.
the speed of light will always be greatest through a vacuum, at 299792458 meters per second or 186282.4 miles per
second). Thus, the refractive index for an optically transparent substance is analogous to the reciprocal of the velocity
factor of an electrical transmission line, where the permittivity and permeability of the cable materials act to slow
down the propagation of electric and magnetic fields through the cable.
638 CHAPTER 8. INSTRUMENT CONNECTIONS

According to Snell’s Law, there will be a critical angle at which the incident light ray will
refract to being parallel to the interface. Beyond this critical angle, the light ray ideally reflects
off the interface and never enters the second material at all. This is the condition of total internal
reflection, and it is what we desire in an optical fiber where the core is the first material and the
cladding is the second material:

Total internal reflection

Incident θ1
light beam
Reflected
v1 = Speed of light in first material light beam

v2 = Speed of light in second material

θ2 = 90o

Optical fiber

Core

Cladding

Both the core and cladding of an optical fiber are manufactured from the same base material of
ultra-pure fused silica, but “doped” with specific impurities designed to alter the refractive index
of each one (raising the refractive index of the core to decrease its optical velocity and lowering the
refractive index of the cladding to increase its optical velocity).

The diameter of core and cladding vary with the type of optical fiber, but several standard sizes
have emerged in the industry, each one specified by the diameter of the core followed by the diameter
of the cladding expressed in microns (millionths of a meter). A common optical fiber standard in the
United States is 62.5/125 (62.5 micron core diameter, 125 micron cladding diameter), and 50/125
in Europe. Some less common standard core/cladding diameters26 include 85/125 and 100/140.
26 All of these sizes refer to glass fibers. Plastic-based optical fibers are also manufactured, with much larger core

diameters to offset the much greater optical losses through plastic compared to through ultra-pure glass. A typical
plastic optical fiber (POF) standard is specified at a core diameter of 980 microns and a cladding diameter of 1000
8.4. FIBER OPTICS 639

To give some perspective on the physical size of an optical fiber core, the following photograph
shows the end-view of an “ST” style fiber optic connector for a 50/125 micron cable, held by my
hand. A green LED light source is shining into the other end of this cable, the tiny green dot visible
at the center of the ST connector revealing the diameter of the 50 micron core:

Several other layers of material must be placed over the core and cladding to form a rugged
optical fiber. A plastic jacket with a typical diameter of 250 microns (0.25 mm) covers the cladding,
and provides a base for color-coding the fiber. This three-layer construction of core, cladding, and
jacket is known in the industry as Primary Coated Optical Fiber, or PCOF.
PCOF is still too fragile for end-user applications, and so another layer of plastic is typically
added (900 microns in diameter) to make the fiber Secondary Coated Optical Fiber, or SCOF. When
wrapped with fiberglass or Kevlar fibers around the secondary jacket for tensile strength, and a
protective PVC plastic outer layer to protect against abrasion, the cable becomes suitable for indoor
use. Cables suitable for outdoor, direct burial, and undersea applications usually take the form
of groups of PCOF fibers packaged within an extremely rugged encasement with metal strands
for tensile strength. Sometimes a gel material helps cushion the fibers from each other within the
confines of the cable sheath.

microns (1 millimeter)!
640 CHAPTER 8. INSTRUMENT CONNECTIONS

8.4.4 Multi-mode and single-mode optical fibers


In any sort of waveguide – optical, electrical, or even acoustical (sound) – the signal energy may be
able to propagate down the waveguide in different orientations. This is true for optical fibers where
the core diameter is relatively large27 compared to the wavelength of the light: there will be many
alternative pathways for light to travel along the length of a fiber’s core. Optical fibers with core
diameters of 50 microns or more are referred to as multi-mode fibers, because multiple independent
pathways, or “modes”, of light are possible within the core’s width.
If an optical fiber’s core is manufactured to be small enough, relative to the wavelength of the
light used, the fiber will only support one “mode” or pathway down its core. Such fiber is called
single-mode. Single-mode fiber cores typically range from 4 to 10 microns in diameter, with 8 micron
being typical.
The purpose of single-mode optical fiber is to avoid a problem called modal dispersion. When
multiple “modes” of light propagate down the length of an optical fiber, they don’t all have the
same length. That is to say, some modes actually take a straighter (and more direct) path down the
fiber’s core than others. The reason this is a problem is that this phenomenon corrupts the integrity
of high-speed (i.e. short-period) pulses. An exaggerated illustration of this problem appears here,
showing the relative path lengths of three different light rays, each one entering the fiber core at a
slightly different angle. The light ray closest to parallel with the core’s centerline finds the shortest
“mode” to the fiber’s end, and arrives in the least amount of time:

Multi-mode optical fiber

Incident light pulse Received light pulse

Time Time

With different “modes” of light arriving at different times from the same incident pulse, the
received light pulse at the exiting end of the fiber will no longer possess a crisp “square-wave”
shape. Instead, the pulse will be “smeared” over time, occupying a larger time span. This poses
a bandwidth limit on the fiber, as there will be some maximum pulse frequency at which adjacent
pulses will begin to merge together and become indistinguishable. The longer the length of optical
fiber, the more pronounced this dispersion will be. This problem is most evident in applications
where the fiber length is very long (hundreds of miles) and the data rate is very high (hundreds of
megahertz). Thus, it is a significant problem for long-distance data trunk cables such as those used
for transcontinental and intercontinental internet traffic.

27 A common core size for “multi-mode” optical fiber is 50 microns, or 50 micro-meters. If a wavelength of 1310
50
nanometers (1.31 microns) is used, the core’s diameter will be 1.31 or over 38 times the wavelength.
8.4. FIBER OPTICS 641

Single-mode optical fiber completely averts this problem by eliminating28 multiple modes within
the fiber core. When there is only one mode (pathway) for light to travel, there will be exactly one
distance for light to travel from one end of the fiber to the other. Therefore, all portions of the
incident light pulse experience the same travel time, and the light pulse arrives at the far end of the
cable suffering no modal dispersion:

Single-mode optical fiber

Incident light pulse Received light pulse

Time Time

As you can imagine, single-mode fiber is more challenging to splice than multi-mode fiber, as the
smaller core diameter provides less room for alignment error.

A compromise solution to the problem of modal dispersion in multi-mode fibers is to manufacture


the core glass with a graded index of refraction rather than a homogeneous index of refraction. This
means the concentration of doping material in the glass varies from the center of the core to the
outer diameter of the core where it interfaces with the cladding. The result of this graded dispersion
is that modes traveling closest to the core’s centerline will experience a slower speed of light (i.e.
greater index of refraction) than modes near the edge of the core, which means the difference in
travel time from one mode to the next will be less pronounced than within normal “step-index”
fibers. Of course, this also means graded-index optical fiber is more costly to manufacture than
step-index optical fiber.

28 The most straight-forward way to make an optical fiber single-mode is to manufacture it with a skinnier core.

However, this is also possible to achieve by increasing the wavelength of the light used! Remember that what makes a
single-mode optical fiber only have one mode is the diameter of its core relative to the wavelength of the light. For any
optical fiber there is a cutoff wavelength above which it will operate as single-mode and below which it will operate
as multi-mode. However, there are practical limits to how long of a wavelength we can make the light before we run
into other problems, and so single-mode optical fiber is made for standard light wavelengths by manufacturing the
cable with an exceptionally small core diameter.
642 CHAPTER 8. INSTRUMENT CONNECTIONS

8.4.5 Fiber optic cable connectors, routing, and safety


One of the most popular styles of single-fiber connector is the so-called “ST” style, which uses a
quarter-turn locking barrel to secure the connector into its matching socket:

Communication patch cables such as the one shown above come in pairs of fibers, one for
receiving and one for transmitting. Note how the plastic strain-relief grips between the metal barrel
of each connector and each orange-jacketed cable are color-coded (one white, one black) for easy
identification at each end of the cable.
An older style of connector based on the type used to connect small coaxial cables together is the
“SMA” style, which used a threaded barrel to lock each fiber in place. The SMA-style connectors
were very secure, but laborious to engage and disengage due to the fine pitch of the barrel’s threads
and the subsequent need to turn the barrel multiple rotations (versus one-quarter turn of the barrel
for an ST connector).
Given that communication patch cables typically have two fibers (one for each direction of data
flow), connector styles have emerged to accommodate fiber pairs. One such style is the so-called
“SC” connector, with a pair of side-by-side plugs accommodating twin optical fibers.

Terminating a bare cable of fibers with individual connectors is a time-consuming process,


requiring the technician to unbundle the individual fibers, strip the jacketing off of each one to
reveal the core and cladding, cleave each glass fiber to give it a flat end, and finally insert and
secure each fiber into its respective connector. Typical fiber connectors use either a “hot-melt” or a
chemical epoxy system of attachment, where the glue adheres to the strain-relief fibers of the cable
for tensile strength, while the central glass fiber protrudes through a small hole in the center of the
connector tip. This protruding glass fiber must be carefully cut and polished to produce a flat end
suitable for engagement with another optical fiber aligned to its center.

Optical fibers may be spliced mid-way in a cable run, although this practice should be avoided
whenever possible. If the fibers are multi-mode, the splicing may be done using “butt” connectors
8.4. FIBER OPTICS 643

but the power losses may be unacceptable. Alternatively, stripped fibers may be inserted into both
ends of a small-diameter tube filled with gel having the same index of refraction as the core glass,
to “conduct” light with as little loss as possible from one fiber core to the other.
A very good technique often applied to single-mode fiber is that of fusion splicing, where two
single-mode fiber ends are literally melted together using an electric arc so that they form one
seamless glass fiber. The alignment of fibers prior to fusion is done under the view of a microscope,
and often with the aid of a light source on one end and an optical power meter on the other end to
give a quantitative measurement of alignment accuracy. When the two fibers are aligned as close
as possible, the electric arc is fired to melt the two fibers together, creating a single fiber. Fusion
splicing is the method of choice for long-distance runs of single-mode fiber, where low power loss
and high integrity of the splice are paramount factors.

When laying optical fiber in wire trays, pulling through rigid conduit, or arranging it in connection
panels, an important physical consideration is to maintain a minimum bend radius29 at all points
along the fiber’s length. This is important because sharp bends will cause light to “leak” out of the
fiber core and into the cladding where it may then escape the cable altogether. A sharp bend in an
optical fiber will cause the angle between the light ray and the core/cladding interface to reach the
critical point where total internal reflection no longer occurs:

Critical angle exceeded

Lost light

The light leakage from an optical fiber may be dramatic if the bend is sharp enough. On an
indoor cable, using visible laser light, you can actually see the light “leak” through to the PVC outer
coating on the outside of the cable!
Junction boxes and connection panels where excess lengths of fiber optic cabling may be coiled
will typically provide plastic forms over which those loops of cable may be bent, the radius of that
plastic form exceeding the manufacturer’s specification for minimum bend radius.
A common way in which the minimum bend radius requirement is violated is when a cable tie
is used to anchor a fiber optic cable to some sturdy surface such as a wiretray or a cabinet post.
The sharp bend created by the tension of a tightened cable tie on the fiber optic cable will easily
exceed the minimum bend radius for that cable, creating light leakage and subsequent performance
problems. Therefore, a good installation practice for fiber optic cables is to always leave cable ties
loose enough that they do not tightly grip the cable.

29 Typically a few inches for multi-mode fiber.


644 CHAPTER 8. INSTRUMENT CONNECTIONS

There are multiple safety concerns when working with optical fibers, both when installing them
and when doing maintenance-type work. Installation hazards center around dangers of the glass
fiber itself, while maintenance hazards center around the light sources used to “power” the optical
fibers.

Installation of fiber optic cable requires that individual glass fibers be separated from each other
in a multi-fiber cable and each one terminated with a connector, and this requires at some point that
the technician strip each fiber down to its glass core and cladding. Both the core and the cladding are
extremely small in diameter, and are made of ultra-pure glass. If a piece of core/cladding breaks off
the fiber and penetrates the skin, the resulting “sliver” will be nearly invisible due to its exceptional
transparency. Its outer surface is also very smooth, making extraction difficult. Unextracted pieces
of an optical fiber, if left in the body, can actually migrate through the victim’s flesh and become
buried even deeper to the point where they can cause serious health problems.
Technicians working with optical fiber typically lay a length of adhesive tape, sticky-side up, on
whatever workbench or table they are using to prepare the cable, as a tool to catch any loose fiber
ends they cut off. At the conclusion of the job, this length of tape is carefully rolled up and then
disposed of in the same manner that “sharps” may be disposed of in a medical environment.

Maintenance technicians working with functioning fiber optic systems need to be careful when
disconnecting “hot” fibers, due to the intensity of the light used in some systems. This is especially
true of long-distance telecommunication fibers using laser sources rather than regular LEDs, which
may have power levels reaching a half watt or so. One-half of a watt doesn’t sound like very much
power, but when you consider this power level is concentrated over a circular area with a diameter less
than 10 microns (for single-mode fiber), the watt-per-square-meter value is actually large enough
to cause significant temperature increases wherever the light beam happens to fall. In fact, you
can actually damage a fiber-optic connector on such a system by disconnecting the fiber with the
fiber “powered”, the laser light being intense enough to burn and pit the aluminum ferrule of the
connector!
Even standard LED light sources may pose a hazard if a technician directly views the end of the
cable with his or her eyes, due to the focused nature of the light beam. The retina of your eye is
extremely sensitive to light, and may easily be damaged by viewing such an intensely focused beam
coming out of an optical fiber, where the entire LED’s light output is channeled into a core just a
fraction of a millimeter in diameter. The optical hazard is even greater when infra-red light sources
are used, because there is no visible indication of the light’s presence. A technician won’t even be
able to see the light coming out, yet it could still be intense enough to damage their retina(s).
Laser-sourced fibers should never be unplugged from the equipment. One should treat a laser-
sourced fiber with the same respect as a “live” electrical circuit, and use the same lockout/tagout
procedures to ensure personnel safety. In systems using visible light wavelengths, a safe way to view
the light coming out the end of an optical fiber is to point the fiber end at a piece of paper and look
for the colored dot falling on the paper. The paper’s rough surface scatters the light so that it is no
longer a focused beam.
The only time it is truly safe to view the end of an optical fiber to check for light is when the
light source is something diffuse such as natural sunlight or a flashlight. It is common for technicians
to use a flashlight to identify fibers from one end of a multi-fiber cable to the other, one technician
shining the flashlight at the end of one fiber while another technician views all the fibers at the other
end of the cable to see which one is lit.
8.4. FIBER OPTICS 645

Some optical communications equipment come equipped with a feature called an Open Fiber
Control (OFC) safety system, which turns off all light sources on a channel whenever an interruption
of light is detected at the receiver port. Since most duplex (two-way) optical fiber channels consist
of two fibers (one for each direction of light), a break in any one fiber will darken one receiver,
which then commands the transmitter port on that equipment to darken as well to prevent anyone
getting injured from the light. It also completely disrupts communication in that channel, requiring
a re-initialization of the channel after the fiber is plugged back in.

8.4.6 Fiber optic cable testing


Optical fibers, like electrical communications cable, may need to be tested to measure certain
performance characteristics. Such testing is commonplace for new installations of fiber optic cabling
to ensure all installed cable lengths and connectors are functioning properly. Repeated tests over
time, compared with the initial installation test, quantifies any degradation of cables or connectors.
Another common testing procedure, called acceptance testing, tests the optical cable while it is still
on the spool prior to installation.
Two basic types of optical fiber tests are presented here: one where the power level of light is
measured at the far end of the fiber from a source of known optical power, and another where a
pulse of light is sent down a fiber and the light received at the same end of the fiber is analyzed.
The former test is simply a measurement of optical power, while the latter test is a sophisticated
analysis of light over very brief periods of time (time domain reflectometry).
646 CHAPTER 8. INSTRUMENT CONNECTIONS

Optical power loss testing


Perhaps the simplest quantitative test of an optical fiber consists of shining a light source of known
optical power at one end of a fiber and monitoring the amount of optical power received at the other
end of the fiber. This type of test is typically performed with two pieces of equipment: the source
and the power meter.
First, the optical power meter and light source are short-coupled together using a pair of patch
cables and a single “butt” connector:

"Butt" connector

Light source
dB
Patch cable Patch cable

Optical power
meter

Press this button to Zero


establish a 0 dB reference

Once light is received by the optical power meter, the technician presses the “zero” button to set
the baseline or reference point for all future power measurements. Although some light will be lost
in the two patch cables and connector, this amount of loss will also be present in the final test and
so it must be ignored.
8.4. FIBER OPTICS 647

After “zeroing” the optical power meter, the actual fiber to be tested is connected between the
light source and the power meter. Any additional light lost within the tested fiber30 will register at
the power meter as a negative decibel figure:

"Butt" connector "Butt" connector

Light source
dB
Patch cable Patch cable

Optical power
meter

Fiber under test


Zero

Recall that the definition of a “decibel” is 10 times the common logarithm of the power ratio
between output and input for any system:
! "
Pout
dB = 10 log
Pin
Thus, the power loss of −0.6 dB shown in the illustration represents 87.1% of the optical source
power received by the optical power meter. Decibels are very commonly used as an expression
of power gain and loss in communication system testing, because dB figures directly add when
components are connected in series with each other. For example, if we knew that a certain type of
“butt” connector for optical fiber exhibited a typical power loss of −1.2 dB and that three of these
connectors would be used to join a single run of fiber, we would know to expect a total connector
loss of −3.6 dB (i.e. 3 × −1.2 dB).

30 Not just light lost along the length of the fiber, but also at each connector on the fiber, since placing the test

fiber within the optical path between the light source and optical power meter necessarily introduces another pair of
connectors where light may be lost.
648 CHAPTER 8. INSTRUMENT CONNECTIONS

Excessive optical power losses may be caused by a number of different factors, including:

• Poor alignment between fibers in a connector


→ Connector flaw causing fibers to be mis-aligned (e.g. angular misalignment)
→ Fiber flaw causing mis-alignment in a good connector (e.g. cores not concentric)

• Mismatched fiber sizes (e.g. 62.5 micron core sending light into a 50 micron core)

• Oil or debris on the end of a connector

• Rough (improperly polished) end on one or more fibers

• Minimum bend radius violated at any point along the fiber’s length

• Cracked fiber core

Unfortunately, a power meter test will not indicate what kind of flaw is causing excessive power
loss, nor where that flaw might be located. If the cable in question has removable connectors mid-
way in its length, the power meter and/or source may be relocated to test portions of the cable to
determine which section contributes more to the power loss, but an end-to-end power test cannot
pinpoint the location or the type of fault.
8.4. FIBER OPTICS 649

OTDR testing
An Optical Time-Domain Reflectometer or OTDR is a sophisticated test instrument used to probe
the characteristics of long optical fibers. They work by injecting a very brief pulse of light into one
end of a long optical fiber, then monitoring any light received at that same end of the fiber. As
the light pulse travels down the length of the fiber, it continuously loses some of its magnitude due
to scattering in the glass. Some of this scattered light returns back to the source-end of the fiber,
presenting a sort of “continuous echo” of the moving pulse. This continuous echo is analogous to
the noise heard from an object moving away from the listener. As the light pulse encounters flaws
and other discontinuities in the fiber and/or connectors along its length, the echoed signal changes
in magnitude. This received signal is displayed as a time-domain plot on the OTDR viewing screen,
and will look something like this:

"Butt" connector

...

OTDR

"Launch" cable
Signal
(dB)

Time
Fiber under test

The “trace” shown on the display screen of an OTDR is a plot of the received optical signal
strength over time. A large “spike” at the left-hand side of this trace marks the incident pulse of
light injected into the optical fiber by the OTDR from the traveling pulse as it propagates down
the length of the fiber. All signals after that (to the right of that initial “spike”) represent light
received from that same end of the optical fiber. In a completely uniform fiber the resulting “echo”
would trace a downward-sloping straight line as the traveling light pulse gradually weakens. In an
imperfect fiber, any discontinuities such as splices, connector joints, sharp bends, cracks, etc. will
cause the traveling light pulse to lose more photons than usual at the location of the discontinuity:
sometimes returning a strong echo back toward the OTDR and other times not. A discontinuity
such as a mis-aligned fiber connector will tend to return a strong echo as part of the traveling light
pulse reflects off the mis-aligned connector end and returns to the OTDR. A discontinuity such as
a mal-formed fusion splice merely scatters a greater-than-normal amount of light out through the
fiber’s cladding, in which case there is no echo “pulse” received by the OTDR but rather just a
further weakening of the echo signal.
650 CHAPTER 8. INSTRUMENT CONNECTIONS

The OTDR trace shown in the previous illustration demands further explanation. Shown here
is a magnified view of it, complete with numbers to identify each noteworthy event:

2
Signal
(dB) 3
5
4

Time
Legend:
1. Incident pulse output by the OTDR, and injected into the launch fiber
2. Reflection off the face of the near-end connection between the launch fiber and the fiber under
test
3. Loss of light due to a non-reflective discontinuity (e.g. sharp bend, splice)
4. Loss of light due to a reflective discontinuity (e.g. mis-aligned connector)
5. Reflection off the face of the far-end connection at the end of the fiber under test
6. The “noise floor”
As you can see, an OTDR trace provides much more information about the performance of an
optical fiber than a simple power test. Each flaw in the cable or its associated connectors appears
as a deviation from the normal downward-sloped line of the trace, the location in time revealing
the distance between the OTDR and the flaw. Thus, an OTDR not only indicates the nature of
each flaw, and the amount of optical power lost at each flaw, but also the location 31 of each flaw
along the fiber’s length. One important caveat exists for this distance calculation, and that is the
fact that the length of a fiber in a multi-fiber cable will always be somewhat longer than the length
of the cable itself, since individual fibers inside a cable are often “wound” in a spiral configuration
or otherwise deviating from the straight centerline of the cable. “Loose tube” cables, for example,
often exhibit fiber lengths 5% to 10% greater than the physical length of the cable itself.
31 Since distance along any path is simply the product of speed and time (x = vt), and the speed of light through

an optical fiber is a well-defined quantity (v = nc where n is the core’s index of refraction), the distance between the
OTDR and the flaw is trivial to calculate.
8.5. REVIEW OF FUNDAMENTAL PRINCIPLES 651

8.5 Review of fundamental principles


Shown here is a partial listing of principles applied in the subject matter of this chapter, given for
the purpose of expanding the reader’s view of this chapter’s concepts and of their general inter-
relationships with concepts elsewhere in the book. Your abilities as a problem-solver and as a
life-long learner will be greatly enhanced by mastering the applications of these principles to a wide
variety of topics, the more varied the better.

• Sanitary applications: In processes where bacterial growth cannot be tolerated, there must
never be stagnant pockets in piping systems for cultures to reside.
• Fluid seals: accomplished by maintaining tight contact between solid surfaces. The shapes
of these surfaces are generally conical (e.g. tapered pipe threads, tubing ferrules).
• Electrical connection integrity: the integrity of electrical connections is absolutely essential
to system reliability. Maintaining firm, clean contact between mating conductor surfaces is
necessary to ensure this.
• Analog vs. digital signals: analog signals have infinite resolution but are susceptible to
corruption by noise. Digital signals have limited resolution but are tolerant of any noise
measuring less than the difference in thresholds between the high and low states.
• Electromagnetic induction: occurs only when magnetic fields are perpendicular to the
conductor. Relevant to signal coupling in cables, mitigated by twisting cable conductors to
form opposing loops from the perspective of an external magnetic field.
• Electrostatic coupling: occurs when electric fields bridge between conductors, and cannot
occur “behind” a grounded conductor. Relevant to signal coupling in cables, mitigated by
building cables with shield conductors and grounding the shield at one cable end.
• Lenz’s Law: any magnetic field arising from electromagnetic induction opposes the inducing
field. Relevant to determining the directions of induced current in a twisted-pair cable exposed
to an AC magnetic field.
• Capacitance: C = "A d , capacitance being proportional to the area of two overlapping
conductors (A), the permittivity of the insulating (dielectric) substance between them ("),
and the distance (d) separating the conductors. Relevant to electrostatic coupling, where the
degree of coupling between two electrical conductors is directly proportional to the overlapping
area and inversely proportional to the distance between the conductors.
• Transmission lines: short-duration (pulsed) electrical signals travel along a cable at nearly
the speed of light, reflecting off the end of that cable if not properly terminated. Relevant to
signal cables carrying high-frequency signals.
• Decibels: used to express the ratio of one power to another in logarithmic form, such that the
sum of component dB values is equivalent to the product of those same component gain/loss
ratios. Decibels may also be used to express a power quantity relative to some reference power
value such as 1 milliwatt (dBm) or 1 watt (dBW). Decibels are an example of a mathematical
transform function, whereby one type of mathematical problem (multiplication/division) is
transformed into an easier type of problem (addition/subtraction).
652 CHAPTER 8. INSTRUMENT CONNECTIONS

• Time-Domain Reflectometry: the analytical technique of sending a pulse signal down a


transmission line or waveguide and analyzing the characteristics of that transmission line or
waveguide by the reflected signal. Relevant to the testing of electrical cables as well as optical
fibers.

• Snell’s Law: relates the angle of a refracted light ray at the interface of two transparent
substances to the relative speeds of light through those two substances. Relevant to the core
and cladding materials of an optical fiber, the speeds of light for those two substances altered
in such a way as to produce total internal reflection of the light rays within the core. This
keeps the light in the fiber, inhibiting leakage and subsequent signal loss.
8.5. REVIEW OF FUNDAMENTAL PRINCIPLES 653

References
“An Overview of Fiber Optic Technology” whitepaper BB-WP13-r0-0305, B&B Electronics
Manufacturing Company.

Austin, George T., Shreve’s Chemical Process Industries, McGraw-Hill Book Company, New York,
NY, 1984.

“Connections” report FL-01 2-94, EBAA Iron Sales, Inc., 1994.

“CPIT M Tube Fittings”, catalog 4230, Parker Hannifin Corporation, Cleveland, OH, 2000.

Croft, Terrell and Summers, Wilford I., American Electrician’s Handbook, Eleventh Edition,
McGraw-Hill Book Company, New York, NY, 1987.

Dutton, Harry J.R., Understanding Optical Communications, First Edition, document SG24-5230-
00, International Business Machines Corporation, September 1998.

“Fitting Installation Manual”, Hoke Incorporated, Spartanburg, SC, 1999.

“Gaugeable Tube Fittings and Adapter Fittings”, document MS-01-140, revision 7, Swagelok
Company, MI, 2004.

Graves, W.V., The Pipe Fitters Blue Book, W.V. Graves Publisher, Webster, TX, 1973.

“Industrial Pipe Fittings and Adapters”, catalog 4300, Parker Hannifin Corporation, Columbus,
OH, 2000.

Ivanov, Georgi, Fabry-Perot Sapphire Temperature Sensor for use in Coal Gasification, Master of
Science thesis paper in Electrical Engineering, Blacksburg, VA, 3 May 2011.

Morrison, Ralph, Grounding and Shielding Techniques in Instrumentation, John Wiley and Sons,
Inc., NY, 1967.

“Oxymax COS61D dissolved oxygen sensor with Memosens protocol operating instructions”,
BA00460C/07/EN13.12, Endress+Hauser.

“Pipe Fittings”, document MS-01-147, revision 3, Swagelok Company, MI, 2002.

“Piping Joints Handbook”, document D/UTG/054/00, BP Amoco, 2000.

“Thread and End Connection Identification Guide”, document MS-13-77, revision 3, Swagelok
Company, 2005.

You might also like