NETA - 21 Remote Monitoring Tool - UM - E - A4

This document provides a user manual for the NETA-21 remote monitoring tool. It discusses safety considerations for installation, mechanical and electrical installation instructions, and start-up procedures. The manual describes the features and functionality of the NETA-21 tool, including its front page interface, communication protocols, and how to initialize communication with monitored drives. It provides guidance on basic configuration settings for the NETA-21 device.

Uploaded by

Sanu Yo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
187 views196 pages

NETA - 21 Remote Monitoring Tool - UM - E - A4

This document provides a user manual for the NETA-21 remote monitoring tool. It discusses safety considerations for installation, mechanical and electrical installation instructions, and start-up procedures. The manual describes the features and functionality of the NETA-21 tool, including its front page interface, communication protocols, and how to initialize communication with monitored drives. It provides guidance on basic configuration settings for the NETA-21 device.

Uploaded by

Sanu Yo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 196

Remote monitoring options for ABB drives, converters and inverters

User’s manual
NETA-21 remote monitoring tool
User’s manual
NETA-21 remote monitoring tool

Table of contents

1. Safety

4. Mechanical installation

5. Electrical installation

6. Start-up

 2017 ABB Oy. All Rights Reserved. 3AUA0000096939 Rev E


EN
EFFECTIVE: 2017-06-12
5

Table of contents

1. Safety
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Use of warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Safety in installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

2. Introduction to the manual


What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Applicability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Target audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Purpose of the manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Before you start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Terms and abbreviations used in this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

3. Overview
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
NETA-21 remote monitoring tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
NETA-21-specific features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Layout of the NETA-21 and the NEXA-21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Hardware and software requirements of the PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

4. Mechanical installation
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Unpacking and examining the delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Installing NEXA-21 to NETA-21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Installing the NETA-21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

5. Electrical installation
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
General cabling instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Power connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Communication connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Data link connections –
Drive with the ACS-AP-x panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Connection over the Ethernet tool network with an Ethernet adapter module . . . . . . 27
Data link connections –
Drive with the RDCU control unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Connection via the EIA-485 port with a Modbus/RTU adapter module . . . . . . . . . . . 30
Connecting the NETA-21 to the RS-485 network . . . . . . . . . . . . . . . . . . . . . . . . . 30
Switching on the bus termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
6

6. Start-up
Contents of this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
First access to the user interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Connecting a local PC to the NETA-21 in the DHCP server mode . . . . . . . . . . . . . . 34
Logging on to the NETA-21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Basic settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Updating the NETA-21 firmware via ABB web pages . . . . . . . . . . . . . . . . . . . . . . . . 36
Changing the password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Adding users . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Setting date and time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Setting the language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Setting the location of the NETA-21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Defining the Ethernet network settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Initializing the communication between the NETA-21 and drives online . . . . . . . . . . . . 41
Initializing the communication between the NETA-21 and
ACS800 drives (or other drives with the RDCU control unit) . . . . . . . . . . . . . . . . . . 41

7. Program features
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
FTP/FTPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
HTTP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
HTTPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
HTTPS certificate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Modbus/TCP gateway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Ethernet PC tool gateway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
TCP and UDP service ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
In-bound network services on the NETA-21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Out-bound network services on the NETA-21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Safe deployment of NETA-21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Cybersecurity Disclaimer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

8. Front page
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Parts and components of the portal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
All devices portlet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Version information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Application toolbar and navigation bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Status icons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Content area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

9. Users
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
My details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
User management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Users tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
User properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
User roles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Tool admin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Drive expert . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Network admin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
7

Firmware admin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
User . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Guest . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
FTP user account . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
External account . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
User interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66

10. Devices
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Devices tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Device front page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Device control buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Parameter browser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Parameter properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Export of parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Import of parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Device data logger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Data logger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Opening a data logger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Setting up a data logger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Device interface settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Device interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
DDCS tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Ethernet tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Modbus monitoring tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Modbus templates tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Add Modbus templates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Edit Modbus templates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Modbus/TCP gateway tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Panel bus tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Interface settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Ethernet settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Modbus settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
DDCS settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Panel bus settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100

11. Networks
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Network interfaces view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Test interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Ethernet panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Network status panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Network services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Test SMTP settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Services/firewall settings panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Services settings panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Proxy settings panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Mail servers (outgoing) panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
DHCP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
HTTP/HTTPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Starting up the SMTP configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
FTP/FTPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
8

Dynamic DNS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110


Using the Dynamic DNS service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Dial-up function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Using a mobile broadband connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112

12. Events
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Universal event list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Contents of the non-universal event list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Filtering settings by columns . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Filtering settings through the Event filter panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119

13. Reporting
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Introduction to reporting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Configuring the NETA-21 for reporting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Creating an email report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Format of the email report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Creating an SD card report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Format of an SD card report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
CSV-formatted reports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
DB-formatted reports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Creating an FTP report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Format of an FTP report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Creating SMS report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Setting the report trigger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Setting the reported data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Changing the reporting name . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Changing the default naming of signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Parameter logging interval templates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Changing the continuous monitor interval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Using scripting for email reports (custom report) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Using scripting for SMS reports (custom report) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
Description of the tabs under Reports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Settings tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Devices tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Parameter history logging tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
Report events data tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
Configuration events tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149

14. Tools
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
Tool firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
Factory tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
IP address after a factory reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
Packages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
Using ABB IP Configuration Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155

15. Backup and restore


What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
9

Backing up the NETA-21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157


Restoring the NETA-21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159

16. Security
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
Applicability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
Advantages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
Protocol level implementation for RADIUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
Enabling RADIUS authentication in NETA-21 web UI . . . . . . . . . . . . . . . . . . . . . . . . . 163
Enable RADIUS authentication method in security settings . . . . . . . . . . . . . . . . . . . 163
Add RADIUS user account with External account user role . . . . . . . . . . . . . . . . . . . 164
Steps: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
User permissions mapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171

17. Memory card


What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
Using the memory card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
Memory card status tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
File browser tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
Autoinst tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
Backup tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
Report tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
Restore tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175

18. Frequently asked questions


What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
How to update the NETA-21 firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
Before you start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 178
Updating the NETA-21 firmware over a remote web connection . . . . . . . . . . . . . . . 178
Updating the NETA-21 firmware locally with SD card(s) . . . . . . . . . . . . . . . . . . . . . 180
Copying the FMZAAvrr.NTU file to memory card . . . . . . . . . . . . . . . . . . . . . . . . 180
Updating the firmware locally with an SD card . . . . . . . . . . . . . . . . . . . . . . . . . . 180
How to reset the factory settings /
What if I forget my password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
How to replace the SD memory card safely . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
How to configure the logging of drive data to the SD card . . . . . . . . . . . . . . . . . . . . . . 182
How much logged data fits into an SD/SDHC card? . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
How to interpret the logged data from the SD card . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
How to create an FTP account . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
How to re-enable reports if time & date have been shifted backwards . . . . . . . . . . . . . 183

19. Diagnostics and troubleshooting


What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
LED indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
LED indications of the NETA-21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 186
LED indications of the NEXA-21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188
10

20. Technical data


What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192
Enclosure of the NETA-21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192
Enclosure of the NETA-21 with the NEXA-21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192
Technical data of the NETA-21 and the NEXA-21 . . . . . . . . . . . . . . . . . . . . . . . . . 193

Further information
Product and service inquiries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
Product training . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
Providing feedback on ABB Drives manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
Document library on the Internet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
Safety 11

1
Safety

What this chapter contains


The chapter contains the warning symbols used in this manual and the safety instructions
which you must obey when you install or connect an optional module to a drive, converter
or inverter. If you ignore the safety instructions, injury, death or damage can occur. Read
this chapter before you start the installation.

Use of warnings
Warnings tell you about conditions which can cause injury or death, or damage to the
equipment. They also tell you how to prevent the danger. The manual uses these warning
symbols:

Electricity warning tells you about hazards from electricity which can cause
injury or death, or damage to the equipment.

General warning tells you about conditions, other than those caused by
electricity, which can cause injury or death, or damage to the equipment.
12 Safety

Safety in installation
These warnings are intended for all who install or connect an optional module to a drive,
converter or inverter, and need to open its front cover or door to perform the work.

WARNING! Obey these instructions. If you ignore them, injury or death, or


damage to the equipment can occur.

• If you are not a qualified electrician, do not do installation or maintenance work.


• Disconnect the drive, converter or inverter from all possible power sources. After you
have disconnected the drive, converter or inverter, always wait for 5 minutes to let the
intermediate circuit capacitors discharge before you continue.
• Disconnect all dangerous voltages connected to any control signal connectors in
reach. For example, it is possible that 230 V AC is connected from outside to a relay
output of the drive, converter or inverter.
• Always use a multimeter to make sure that there are no parts under voltage in reach.
The impedance of the multimeter must be at least 1 Mohm.
Introduction to the manual 13

2
Introduction to the manual

What this chapter contains


This chapter introduces this manual.

Applicability
This manual applies to the NETA-21 remote monitoring tool and the NEXA-21 extension
unit for DDCS, SW version 2.31 or later.

Compatibility
The NETA-21 remote monitoring tool is compatible with various types of ABB drives, wind
turbine converters and solar inverters. The ABB drives compatible with NETA 21 are
shown in the below table:

Drive Type Connection type

ACS310 Modbus (/RTU and /TCP)

ACS320 Modbus (/RTU and /TCP)

ACS355 solar pump Modbus (/RTU and /TCP)

ACS380 Panel bus, Modbus (/RTU and /TCP)

ACS550 Modbus (/RTU and /TCP)

ACx580 Panel bus, Modbus (/RTU and /TCP)

ACSM1 Modbus/TCP

ACSM1 solar pump Modbus/TCP

ACx400 DDCS with NEXA-21 extension


14 Introduction to the manual

Drive Type Connection type

ACS600 DDCS with NEXA-21 extension

ACS800 DDCS with NEXA-21 extension

ACQ810 Modbus (/RTU and /TCP)

ACS850 Modbus (/RTU and /TCP)

ACS880 Panel bus, Modbus, Ethernet tool network

DCS600 DDCS with NEXA-21 extension

DCS800 DDCS with NEXA-21 extension

ACS1000 DDCS with NEXA-21 extension

ACS2000 DDCS with NEXA-21 extension

ACS5000 DDCS with NEXA-21 extension

ACS6000 DDCS with NEXA-21 extension

PVS800 (solar inverter) DDCS with NEXA-21 extension

ACH550 Modbus (/RTU and /TCP)

ACS560 Panel bus, Modbus (/RTU and /TCP)

ACS860 Panel bus, Modbus (/RTU and /TCP)

ACS580MV Panel bus, Ethernet tool network

Note: Later in this manual, term drive substitutes for string drive/converter/inverter.

Target audience
The reader is expected to have basic knowledge of electrical fundamentals, electrical
wiring practices and how to operate the drive.

Purpose of the manual


The manual provides information on installing, commissioning and using the NETA-21.
Introduction to the manual 15

Before you start


It is assumed that the drive is installed and ready to operate before starting the installation
of the NETA-21.
In addition to conventional installation tools, have the drive manuals available during the
installation as they contain important information not included in this manual.

Contents
The manual consists of the following chapters:
• Safety presents the safety instructions which you must follow when installing a NETA-
21.
• Introduction to the manual introduces this manual.
• Overview contains a short description of the NETA-21.
• Mechanical installation contains a delivery checklist and instructions on installing the
NETA-21.
• Electrical installation contains the cabling and connection instructions of the NETA-21.
• Start-up contains instructions on how to start up the NETA-21.
• Program features contains feature descriptions in more detail.
• Users describes the user management.
• Devices describes how to manage device parameters and use data loggers.
• Networks explains how to set up and configure Ethernet network interfaces of the
NETA-21.
• Events describes how to observe and filter events.
• Reporting describes how to make reporting and trend logging settings for configuring
which time levels and event categories are sent out by a reporting plug-in to be
monitored.
• Tools explains how to manage NETA-21 firmware, factory settings and software
packages.
• Backup and restore describes the backup and restore functions of the NETA-21.
• Memory card describes the tabs under Memory card.
• Frequently asked questions contains how-to instructions for various tasks.
• Diagnostics and troubleshooting explains how to trace faults with the status LEDs on
the NETA-21 and the NEXA-21.
• Technical data contains the technical data of the NETA-21 and the NEXA-21.
16 Introduction to the manual

Terms and abbreviations used in this manual


 Terms
Term Explanation

Assistant control panel Assistant control panel with an USB connector enabling a PC tool connection
for common architecture drives. Assistant control panel is a generic name for
ACS-AP-I and ACS-AP-S panels.

Data log File produced by a data logger. Can be sent and stored as a report
attachment.

Data logger Data logger inside a monitored device

DDNS Dynamic domain name system

Device Device connected to the NETA-21 for remote monitoring and data access. In
the UI devices are classified as generic devices, drives, converters or
inverters. See Device type.

Device interface Software component that enables access to certain types of devices

Device type Attribute for a device that is auto-detected or set by the user. Defines the
main category of the device, eg, if the device represents a rotating machine
or if it just converts electrical power from one form to another.

Drive Term drive is used instead of string drive/converter/inverter

Modbus/TCP gateway Modbus/TCP server that relays data read requests to any device interface.
Feature allows an external Modbus/TCP client to read data through the
NETA-21 from any connected device.

NETA-21 remote Hardware product for accessing drives remotely – typically off-site access
monitoring tool over public Internet, local/private Ethernet or modem connection.

Network interface Any defined interface to the connected data network

Network service Any inbound or outbound data connection provider in the NETA-21. NTP
time service and email (SMTP) are examples of outbound network services.

Parameter Operating instruction for the drive. Parameters are typically adjusted with a
control panel or a PC tool. Parameter browsing, monitoring and writing can
be done also with the NETA-21.

PC tool autodiscovery Network service which allows automatic detection of other Ethernet-based
ABB products (eg, the FENA-11) in a local network. In addition, enables
finding the NETA-21 in the network where the PC tool has been connected.

Portlet Panel for text and controls within a page or tab. Some portlets can be moved
around, added and removed, eg, on the front page.

Trend logging = parameter Refers to low time resolution, long-term data logging performed by the
history logging NETA-21. Trend logging is a functionality within the NETA-21 while data
loggers are part of the drive functionality and merely configured with the
NETA-21.

User account A user name that in combination with a password can be used to access the
NETA-21 web user interface or some other services of the NETA-21.

Web UI Web-based user interface of the NETA-21


Introduction to the manual 17

 Abbreviations
Abbreviation Explanation

DDCS Distributed Drives Communication System, an optical fiber device access


method for drives and inverters (for example, ACS800 and PVS800)

DDNS Dynamic Domain Name System

DHCP Dynamic Host Configuration Protocol, a protocol for configuring servers in a


network

FTP File Transfer Protocol provides an unsecure way to access files in a network

FTPS File Transfer Protocol Secure provides a secure way to access files in a net-
work

HTTP Hypertext Transfer Protocol is an application protocol used between data cli-
ents and web servers

HTTPS Hypertext Transfer Protocol Secure is a combination of the HTTP and


SSL/TLS protocols. Provides secure communication with web servers.

NBT NS NBT NS is a daemon for the NetBIOS name discovery. Allows finding com-
puters from a local network by using the NetBIOS host name.

NTP Network Time Protocol is a protocol for synchronizing computer clocks over
a network

SD Secure Digital memory card

SDHC Secure Digital High Capacity memory card

SMTP Simple Mail Transfer Protocol is a protocol for sending emails

SSH Secure Shell, a protocol for a secure remote access.

SSL/TLS Transport Layer Security (previously Secure Sockets Layer) protocol is used
to encrypt data between clients and servers

TCP Transmission Control Protocol, used together with Internet Protocol (IP) as
the transport protocol for the Internet

UI User interface

UTC Coordinated Universal Time is the most often used time in the world. Time
zones are presented with positive or negative offsets.
18 Introduction to the manual
Overview 19

3
Overview

What this chapter contains


This chapter contains a short description of the NETA-21.

NETA-21 remote monitoring tool


The NETA-21 remote monitoring tool is used for browser-based remote monitoring of ABB
drives via Ethernet. Multiple drives can be connected to the network by using a panel bus
or through the fiber optic channel of the NEXA-21 extension unit.
Through the NETA-21, you can:
• monitor drives
• read and adjust drive parameter values
• read status information and actual values from drives
• set up and monitor the data logger and save its content to a file
• read the contents of the fault log from monitored devices and save it to the memory
• send email messages on events
• use email for continuous monitoring of drives
• reset a fault on drives
• use an SD card for continuous monitoring of drives
• use an SD card to store all events
• use the FTP server for storing drive parameters and events
• create custom events
• create custom reports: email reports, SD card reports and FTP reports.
20 Overview

The NETA-21 is not intended for controlling or commissioning the drive. The NETA-21
provides stand-alone logging without a PC and automated data reporting to external data
systems. The user interface can be accessed with any web browser including mobile
devices, without the need to install any special software.

NETA-21-specific features
• Two network connections
• Internal (factory line)
• External (Internet access)
• Automatic or fixed IP configuration
• Easy point-to-point access to the NETA-21 with a PC (no need to change the IP
address of the PC)
• Email reporting of events and parameter history logs
• FTP reporting of events and parameter history logs to an external FTP server
• Storing of events and history log files to a SD memory card
• FTP and FTPS file access to an SD/SDHC memory card
• Browsing an SD/SDHC memory card via the web UI
• Different access rights for different users
• NETA-21 software upgrade locally or remotely
• Importation of the NETA-21 settings from the USB memory
• Time synchronization via an NTP server
• Full or selected backup/restore of the software
• Dynamic DNS support
• Support devices connected via:
• Panel bus (ACSx80 series)
• Ethernet PC tool communication (ACSx80 series)
• DDCS with a fiber optic cable (eg, ACS800, ACS600)
• Modbus/RTU via RS485
• Support for a USB modem
• Online monitoring with a history
• Automatic discovery the connected device
• Automatic log changes in the connected device
Overview 21

 Layout of the NETA-21 and the NEXA-21


The following figures describe the front and bottom layout of the NETA-21 and the NEXA-
21.

NETA-21 NETA-21 and NEXA-21

4 4

5
3

11

5
8

7 10
6a

6b 12

9 13

1 Front panel labeled with a black sticker and equipped with indicator LEDs

2 PWR, STAT, MON – power, status and monitoring indicators, see LED indications

3 SD – SD/SDHC memory card slot

4 USB – USB host connector for third party extensions

5 PNL 1/PNL 2 – connector providing an interface for a panel bus that can be used for communication
with certain drive types

6a PC ETH 1 – connector providing an Ethernet connection for a locally connected PC

6b ETH 2 – connector providing an Ethernet connection for an external Ethernet network

7 Connector for the NEXA-21 unit

8 SD RJ45 – SD button is used for removing the SD/SDHC card safely and activating a DHCP server
for the first access to the user interface

9 Reset button is used for rebooting the NETA-21

10 NEXA-21 provides a DDCS fiber optics connection, secondary power input and one extra USB
connector

11 PWR, STAT, RX, TX – power, status and RX/TX indicators, see LED indications

12 Fiber optic transmitter DDCS

13 Fiber optic receiver DDCS


22 Overview

NETA-21 NETA-21 and NEXA-21

1
5

1 X1 10…30 V DC – power supply input

2 X2 EIA-232 connector (in reserve)

3 X3 EIA-485 connector for a Modbus network

4 Termination jumpers for the link connected to X3

5 X11 AC/DC 24V – secondary power supply input

Hardware and software requirements of the PC


The NETA-21 can be configured and used with a normal PC with:
• Ethernet network adapter
• Windows XP/Vista/7/8, Linux, MAC OS
• Internet Explorer 9+, Firefox 3.6+ (PC, Mac), Safari 5+, Chrome 10+ or Opera 11+
(PC, Mac).
Note: Firmware versions until 2.21 have been tested with Internet Explorer 8.
Firmware versions 2.22 and beyond have been tested only with Internet Explorer 9
and later.
Most mobile phone and tablet browsers are also capable of showing the NETA-21 web
pages, but displayed elements are not fully optimized for the touch screen use.
Javascript and cookies must be enabled in the web browser settings before you can use
the NETA-21 web interface. The NETA-21 does not require external plug-ins, such as Java
or Flash.
Mechanical installation 23

4
Mechanical installation

What this chapter contains


This chapter contains a delivery checklist and instructions on mounting the NETA-21.

WARNING! Follow the safety instructions given in this manual and the drive
documentation.

Unpacking and examining the delivery


The option package for the NETA-21 contains:
• remote monitoring tool, type NETA-21
• NETA-21 remote monitoring tool installation and start-up guide (3AUA0000096881
[English]).
The option package for the NEXA-21 contains:
• extension unit, type NEXA-21
• NEXA-21 installation instructions sheet.
1. Open the option package.
2. Make sure the package contains all items listed above.
3. Make sure that there are no signs of damage.
24 Mechanical installation

Installing NEXA-21 to NETA-21


1. Remove the plastic cap from the connector in the NETA-21.
2. Press the NEXA-21 against the NETA-21.
3. Tighten the grounding screw.
Do not use excessive force.

Installing the NETA-21


1. Protect the devices from the drilling dust.
2. Drill the holes for the fastening screws of the mounting rail.
3. Fasten the mounting rail.

4. Snap the NETA-21 onto the rail.

DIN rail grounding clip

See the grounding instructions in section Grounding.


Electrical installation 25

5
Electrical installation

What this chapter contains


This chapter contains:
• general cabling instructions
• grounding instructions
• instructions on setting the IP address
• instructions on connecting the NETA-21 to the drive and to the Ethernet network.

WARNING! Only qualified electricians are allowed to carry out the work described
in this chapter. Follow the instructions in section Safety in installation. Ignoring the
safety instructions can cause physical injury or death.

General cabling instructions


• Arrange the cables as far away from the power cables as possible.
• Avoid parallel runs with the power cables.
See chapter Technical data for information on cable types.
26 Electrical installation

Grounding
Use a grounding clip to connect the ground of the NETA-21 to the mounting rail. Make sure
that he mounting rail is grounded to a noiseless ground. If the rail is not mounted on a
properly grounded base, use a separate grounding conductor. The conductor must be as
short as possible and its cross-sectional area must be 6 mm2 at least.
Do not use any solid copper conductor (only stranded wire is allowed).

Power connections
Connect the power supply to connector X1 of the NETA-21. The NETA-21 supplies also
the NEXA-21. For information on the connector type, voltage and power specification, see
Technical data of the NETA-21 and the NEXA-21.
Note: In the NEXA-21, there is an alternative power supply input (X11), which you can use
for supplying power to the NEXA-21 and the NETA-21.

Communication connections
 Data link connections –
Drive with the ACS-AP-x panel

Termination switch of Termination switch of


the bus the bus
NETA-21

PNL1

PNL2

PC
ETH1

ETH2
ABB drive, ABB drive, ABB drive, ABB drive,
converter or converter or converter or converter or
inverter inverter inverter inverter

PC Link to Ethernet networks

Note: The RJ45 connectors of the control panel are located in the “ceiling” of the control panel housing.
Beside the left-hand side RJ45 connector in the control panel housing there is a switch that must be pushed
upwards in the last drive of the chain to terminate the bus.

The maximum number of devices per panel port bus is 32.


Set a unique ID to each node on the panel bus. See the appropriate drive manual.
Electrical installation 27

In the BCU-01/02/12/22 control unit, use connector X13 for the panel bus connection.

X13
NETA-21

PNL1

PNL2

PC
ETH1

ETH2
BCU Public IP address or
VPN tunnel needed

BCU PC

 Connection over the Ethernet tool network with an Ethernet adapter


module
In the Ethernet tool network, each drive/unit is connected to the network through a FENA-
11/21 Ethernet adapter module.
Note: The Ethernet tool network is available only for ACS880 and ACS860 drive series.

NETA-21 ABB drive ABB drive ABB drive


or unit or unit or unit
with the with the with the
FENA-11/21 FENA-11/21 FENA-11/21

PC
ETH1

ETH2

Ethernet switch

The NETA-21 detects nearby adapter modules (max. 32 pcs over Ethernet) in a local
network. The automatic detection is enabled by default only via the ETH2 port. To change
the settings of the automatic detection, go to Settings –> Device interfaces –> Ethernet
–> Settings –> Background scan.
Note: If the ETH1 and ETH2 ports of the NETA-21 are connected, they must be configured
to use different sub-nets (different IP addresses under non-overlapping netmasks).
28 Electrical installation

 Data link connections –


Drive with the RDCU control unit
The figures below show the data connections in a ring and star topology when a fiber optic
link is used.

ABB drive, ABB drive, ABB drive,


converter or converter or converter or
inverter inverter inverter

NETA-21

NEXA-21
RDCU RDCU NDCU

RDCO RDCO

T R TT R T
T R

PC
ETH1

Tx

ETH2
Rx

PC
Link to Ethernet networks

The maximum number of devices per fiber optic link is 10.


Connect the NEXA-21 primarily to fiber optic channel ch3 on the RDCO connector unit.
You can connect the NEXA-21 also to ch0 if the maximum speed of the DDCS
communication does not increase above 1 Mbit/s.
The default NETA-21 settings for a DDCS network are ring topology and 1 Mbit/s
communication speed. With these settings, the NETA-21 can normally auto-detect drives
connected to an NDBU branching unit. The NETA-21 auto-detects connected devices
when the fiber is connected for the first time. If reconfiguration is needed afterwards, it can
be done in the web user interface.
Note: If there are NDCU control units, use channel 4 or 3 (titled Remote diagnostics and
PC channel).
Electrical installation 29

Note: Use the same speed setting in the NETA-21, NDBU branching unit and drives.

ABB drive, ABB drive,


converter or converter or
inverter inverter

RDCU RDCU

RDCO RDCO
NETA-21 NDBU-x5
NEXA-21

T R T R

V106
PC CH1
V105
ETH1
V104
CH0
V103
Tx
V102
MSTR
ETH2 V101
Rx

Drive/converter/inverter 1 to CH0 … drive/converter/inverter 9 to CH8

Link to Ethernet networks

PC
30 Electrical installation

 Connection via the EIA-485 port with a Modbus/RTU adapter


module
A maximum of 32 monitored Modbus/RTU devices can be connected to the same EIA-485
network. The following figure is an example of an allowable topology:

NETA-21 ABB drive with Other slave ABB drive with


an FSCA-01 device an FSCA-01
or with an or with an
embedded embedded
EIA-485 port EIA-485 port

Other slave ABB drive with Other slave ABB drive with
device an FSCA-01 device an FSCA-01
or with an or with an
embedded embedded
EIA-485 port EIA-485 port

T = Termination

The X3 EIA-485 connector for a Modbus network is located at the bottom of the NETA-21.
See the bottom layout in section Layout of the NETA-21 and the NEXA-21. The EIA-485
(RS-485) cabling requires a shielded dual twisted pair cable. The nominal impedance of
the cable must between 100…150 ohm.

Connecting the NETA-21 to the RS-485 network


Connect the bus cable to connector X3 on the NETA-21.
The pin allocation of the X3 connector is shown below.
1 2 3 4

X1 Description
1 SHLD Bus cable shield. Connected internally to a ground clip via an RC filter. Depending on
the installation environment, the shielding is connected to this pin on the NETA-21 or
on another location on the EIA-485 network.
2 DATA_B Data positive
3 DATA_A Data negative
4 GND_B Isolated signal ground

Signals DATA_A, DATA_B and GND_B must always be connected to all communication
modules and to the NETA-21.
Electrical installation 31

Switching on the bus termination


To avoid signal reflection, add 120-ohm termination to the last devices at each end of the
bus line.

J2 J2 J2 J2

Termination Termination Termination Termination


activated deactivated deactivated activated

EIA-485 device EIA-485 device EIA-485 device EIA-485 device

Term. Term. Term. Term.


ON OFF OFF ON

You can use the internal resistor of RS-485/EIA-485 adapters or an external passive
termination resistor. The internal termination switch activates also the pull-up and pull-
down resistors.
32 Electrical installation
Start-up 33

6
Start-up

Contents of this chapter


This chapter tells you how to start the NETA-21.

First access to the user interface


This section tells you how to get access to the user interface. The NETA-21 can be used
as a DHCP server for a local PC when the PC is connected to the PC ETH 1 terminal.
When the DHCP server mode is activated, the NETA-21 provides an IP address to the PC
for an easy connection.
The NETA-21 uses dynamic IP addressing by default. After it starts, the NETA-21 tries to
get a dynamic IP address from the local Ethernet network if there is a DHCP server
available. If there is no local DHCP server in the connected network, then the NETA-21
assigns itself a Zero Configuration networking address in the range of
169.254.1.0…169.254.254.255. The technology of the automatic IP address configuration
is called either Link-local address assignment (RFC 3927) or Automatic Private IP
addressing (APIPA).
When a local PC is connected to the PC ETH 1 connector, you can set the NETA-21 as the
DHCP server in the Ethernet 1 link.
34 Start-up

 Connecting a local PC to the NETA-21 in the DHCP server mode


Note: If another device operates in the DHCP server mode, you cannot use the NETA-21
in the DHCP mode via the local Ethernet 1 network.
1. Start the NETA-21.
2. Wait until the set-up completes and the STAT LED is green.
3. Push the SD RJ45 button for 5 seconds or until the PC ETH 1 LED starts to flash
green.
The NETA-21 operates as a DHCP server via the PC ETH 1 connector.
4. Connect the PC to the PC ETH 1 connector.
The PC gets a dynamic IP from the NETA-21.
The PC ETH 1 LED shows that there is a connection (green blink = waiting, green =
connected).
Note: If after one minute there is no connection between the PC and the NETA-21, the
DHCP server mode in the NETA-21 is set off.
5. Go to http://192.168.230.1.
Note: If the Ethernet cable is connected to the NETA-21 before you push the SD RJ45
button, the PC does not automatically get an IP address.

 Logging on to the NETA-21


1. With the web browser of you PC, navigate to http://192.168.230.1.
2. When you log on to the NETA-21 for the first time, use the default user
name/password.
Type “admin” both to the Username and Password text boxes.
The UI recommends that you use the secure HTTPS login. If you click the link, you get
a notification on a possible warning message concerning an invalid certificate.

3. Click Login.
You are redirected to the front page.
Start-up 35

If the authentication does not succeed and you are redirected back to the Login dialog
box, the following error messages may appear:
• Authentication failed. Contact system administrator for more information.
• You have logged out from the remote monitoring tool!
• Session expired; you were automatically logged out because of idle time was
exceeded.
• Server (remote tool) does not respond to authorization request.
• The server was rebooted.
By clicking the Information... button you can get information on, for example, the
serial number and MAC addresses of the Ethernet interfaces. To customize the data,
go to Settings –> User interface.
4. Change the password (recommended).

You can keep the default password by clicking the Don’t change button.
Note: We recommend that you change the default password when you log on to the
NETA-21 for the first time.
The front page of the user interface is shown. See chapter Front page.
You are now logged on as a tool administrator (Tool admin). See section User roles.
36 Start-up

Basic settings
 Updating the NETA-21 firmware via ABB web pages
1. Go to the front page.
2. Click the Software update button.

The NETA-21 searches the pages for a new version of firmware or any of the installed
extra packages and shows a list of available updates.

3. Select the updates you want to install and click the Update button.
You get the following Update message.

When the selected updates have been downloaded, the NETA-21 reboots.
There is an alternative way to look for available updates: Go to Settings –> Tool settings
–> Tool firmware and click the Check updates button.
Start-up 37

 Changing the password


1. To change your password, go to Settings –> My details –> Change password.

2. Type the old password to the Old password text box.


3. Type the new password to the New password text box.
4. Type the new password again to the Confirm new password text box.
5. Click Save.
38 Start-up

 Adding users
Note: You can add users only if you have the access rights of Network admin or Tool
admin.
1. To add a user, go to Settings –> Users –> Add user.
The User properties panel appears on the right-hand side of the tab.

The components of the tab are described in section User management.


2. Fill in the text boxes.
The name typed into the Full name text box is shown in the upper right-hand side
corner of the window. The user name (login name) is created under the User &
password sub-panel in step 4.
3. Expand the User & password sub-panel by clicking the heading.
4. Fill in the text boxes.
See section User roles.
5. Click Create user.
Start-up 39

 Setting date and time


Note: You can change the locale settings, if you have the access rights of Drive expert,
Network admin or Tool admin.
1. To set date and time, go to Settings –> Locale –> Date and time.
Note: If the NETA-21 does not have the correct date and time, the stored data will also
be logged with incorrect date and time stamp.

2. In the Time source drop-down list, select one of the following values:
• Automatic
• NTP (Network Time Protocol)
• Manual
If you select Manual, define the time from the Current time drop-down list and
select the date from the calendar in the Current date box.
• External
The external software synchronizes time with NETA-21 periodically. Hence,
enable External option when you use remote monitoring services.
Note: In the Automatic mode the NETA-21 tries to fetch time and date over NTP,
contacting server pool.ntp.org by default.
3. Fill in other appropriate boxes.

 Setting the language


Note: You can change the locale settings, if you have the access rights of Drive expert,
Network admin or Tool admin. Currently only English language is available for the web UI.
To customize the date format, time format, decimal separator and the first day of the week,
go to Settings –> Locale –> Language.
40 Start-up

Note: The language selected on the Language tab is used only in the web UI of the
NETA-21. Monitored devices can have their own independent language selectors.

 Setting the location of the NETA-21


Note: You can change the locale settings, if you have the access rights of Drive expert,
Network admin or Tool admin.
To set the location of the NETA-21, go to Settings –> Locale –> Location.

 Defining the Ethernet network settings


1. Go to Settings –> Network interface and enable the Obtain DNS server
automatically function.
The NETA-21 adjusts the communication settings automatically. Individual attributes
can be set separately.
Enable the function both for local Ethernet 1 connected to the PC ETH 1 connector
and external Ethernet 2 connected to the ETH 2 connector.
Note: From firmware version 2.12 onwards, the Ethernet settings are taken into use
directly after the settings have been saved. The NETA-21 shows a warning explaining
that connection can be lost if the IP address of the currently active connection is
changed.

2. From the DHCP server mode drop-down list, select the desired DHCP server mode.
The available options are:
• Disabled always
• Enable with button
• Enable during next reboot
• Enable always
3. Check the LAN settings of your PC.
Activate the following functions: Obtain an IP address automatically and Obtain
DNS server address automatically.
Start-up 41

Initializing the communication between the NETA-21 and


drives online

WARNING! Follow the instructions in section Safety in installation.

 Initializing the communication between the NETA-21 and


ACS800 drives (or other drives with the RDCU control unit)
1. Switch the drives on.
2. In the first drive, change the node address of channel 3 (CH3) to 1 (example: ACS800
standard control 70.02 CHANNEL 3 ADDR = 1).
3. In the second drive, change the node address of channel 3 (CH3) to 2 (example:
ACS800 standards control 70.02 CHANNEL 3 ADDR = 2).
4. Give the rest of the drives a unique ID as well.
See the appropriate drive manuals.
5. Switch the drives off to set the channel address settings.
6. Switch the NETA-21 off or disconnect the fiber optic cable from the NEXA-21 for more
than 1 minute.
7. Connect the drives to the NEXA-21. See section Communication connections. Use
either the ring or star topology.
8. Switch the drives, NETA-21 and NEXA-21 on.
9. Wait until the PWR and STAT LEDs of the NEXA-21 go green.
Tx and Rx LEDs are yellow indicating that there is data transmission between the
NETA-21 and monitored devices.
10. Log on to the UI when the STAT LED of the NEXA-21 is blinking green.
The UI recognizes the monitored device automatically and the drive is shown in the
user interface.

Note: If the NETA-21 does not detect all drives automatically, go to Settings –>
Device interfaces –> DDCS –> Rescan devices.
11. Click Save.
42 Start-up
Program features 43

7
Program features

What this chapter contains


This chapter describes some of the features listed in section NETA-21-specific features in
more detail.

FTP/FTPS
FTP (File Transfer Protocol) is a simple protocol designed for transferring files.
FTP allows you to browse folders in a remote device. All normal operations are supported,
eg, you can create or delete folders, and move, delete or rename files.
The main purpose of using FTP is to upload or download files between the local and
remote device.
The NETA-21 supports both unencrypted and encrypted (FTPS) connection.
The unencrypted connection s disabled by default and works on port 21.
The encrypted connection supports only explicit Transport Layer Security (TLS) encryption
and works on port 990.
You can enable or disable these services as well as change the default port through the
Network services panel.
44 Program features

HTTP
The HTTP (Hypertext Transfer Protocol) is used to serve web pages using the HTML
(Hypertext Markup Language) and Javascript. To use the NETA-21 web interface you
need a browser supporting Javascript and cookies (see Hardware and software
requirements of the PC). External plug-ins, such as Java or Flash, are not required.
It is recommended to use HTTP only with a direct cable connection to the NETA-21. For all
other purposes it is recommended to use the secure HTTPS. To switch from HTTP to
HTTPS edit the address from http://192.168.230.1 to https://192.168.230.1. You can also
do this by checking the Prefer HTTPS check box in Network services.
HTTPS URLs use port 443 by default, whereas HTTP URLs use port 80 by default.

HTTPS
The Hypertext Transfer Protocol Secure (HTTPS) is a combination of the HTTP with an
added encryption layer of SSL/TLS protocols to create a secure channel over an insecure
network, provided that adequate cipher suites are used and that the server certificate is
verified and trusted. The HTTPS is supported by all popular browsers.
Note: Although the HTTPS encrypts everything, including the URL, an eavesdropper can
still observe the host name and port of the URL because they are part of TCP/IP packets
to establish and maintain the connection. This means that an eavesdropper or attacker
can know that a connection is taking place between the two parties, get the domain name
and IP addresses, through which he can see the sites the host is connect to, the amount of
time spend using a site, and the amount of information uploaded or downloaded on the
particular site.

 HTTPS certificate
The NETA-21 HTTPS uses a self-signed certificate which is uniquely generated per each
NETA-21 tool. The factory reset of the NETA-21 can also reset the self-signed certificate
and generate a new one (while, eg, a firmware update keeps the certificate unchanged).
Most browsers display a warning if they receive an invalid or a self-signed certificate.
When you connect an older browser to a site with an invalid certificate the browser shows
you a dialog box asking if you want to continue. Newer browsers display a warning across
the entire window and also prominently display the site's security information in the
address bar. Extended validation certificates turn the address bar green in newer
browsers. Most browsers also display a warning when you visit a site that contains a
mixture of encrypted and unencrypted content.
From the NETA-21 firmware version 2.13 onwards you can install a customized HTTPS
site certificate to each NETA-21. The installation requires than an Apache 2 compatible
apache.pem certificate file is generated on the PC and saved to folder "cert” in the SD
memory card. Create a “cert” folder, if the “cert” folder does not exist. The customized
certificate will be taken to use after a reboot or power-up of the NETA-21. A valid certificate
is taken into use and removed from the memory card for security reasons.
Program features 45

Modbus/TCP gateway
The NETA-21 supports a subset of the Modbus/TCP protocol specification v1.1b. This
allows to use a normal TCP/IP connection to access the parameters of drives.
The supported functions are:
• 03 (0x03) Read Holding Registers
• 06 (0x06) Write Single Register
• 16 (0x10) Write Multiple registers
• 23 (0x17) Read/Write Multiple registers
• 43 (0x2B) Encapsulated Interface Transport
To enable the service for selected network interfaces (by unlocking it in the NETA-21
internal firewall), go to Settings –> Network services –> Services.
With a normal PC and a program that supports the Modbus/TCP protocol in the same
network to which the NETA-21 is connected, you can query values of parameters from the
connected devices. The Modbus/TCP client configuration requires you only to specify the
IP of the NETA-21 and port 502.
The Modbus protocol supports up to 247 devices. Each device is identified with an ID, a
number from 1 to 247.
ID range Protocol

1…32 DDCS fiber optics

33…64 Panel bus 1 (port PNL1)

65…96 Panel bus 2 (port PNL2)

97…128 Modbus/RTU

129…160 Ethernet tool network

161…247 Reserved

The ID used by a specific device can be determined with its internal name (shown in the
Modbus/TCP gateway panel under Device interfaces). This name always ends with a
number that represents the index inside the range of the IDs of the specific protocol. For
example, a slave device connected through the Modbus/RTU protocol with station address
3 (device node ID mb_3) is accessible by Modbus/TCP gateway station address 99 (97+3-
1).
To access a specific parameter of a given group and index, you must specify an address
by calculating it according to one of the following formulas:
16-bit address = (4)0000 + 100 × group + index
46 Program features

32-bit address = (4)20000 + 200 x group + 2 x index

Device
Modbus PC
mb_3
Modbus device, parameter 01.15
ID: 99
NETA-21 Switch Address: 115
Panel bus (port PNL2) device ID 1,
parameter 03.10 using 32-bit addressing
Device ID: 65
Panel bus {2} {1} Address: 420000 + 200 x 3 + 2 x 10 =
pnl2_01 420620

By default, the Modbus protocol returns the internal raw 16-bit value and does not specify
any information about sign and scaling. Therefore, you must apply the correct ones for the
specified parameter.
Note: Most Modbus/TCP master applications omit the 40000 (or 400000) from the
beginning of the register numbering.
The Modbus function code 03 Read Holding Registers is supported over the Modbus/TCP
gateway of the NETA-21. In firmware 2.23 you can configure the settings of the
Modbus/TCP gateway. Go to Settings –> Device interfaces. Firmware 2.23 and above
supports a read/write option. In addition, firmware 2.24 and above supports dataset
access.
If any user tries to access read protected, write protected, or 'string' type drive parameters
via Modbus/TCP Gateway, the error 0x02 - Illegal Data Address is sent to the master.
Note: For security reasons, Modbus/TCP gateway connections must be used only inside a
trusted network.

 Ethernet PC tool gateway


Drive Composer establishes Ethernet communication only with recognized devices such
as FENA-11 and FENA-21 Ethernet fieldbus adapters.
The PC tool friendly mode should be enabled in NETA-2 if NETA-21 and Drive Composer
are used at the same time through Ethernet. To enable PC tool friendly mode, go to
Settings –> Device interfaces –>Ethernet/Settings –> PC tool friendly mode.
Drive Window PC tool can connect to UDP port 61332 on NETA-21 and access connected
drives through the DDCS Ethernet gateway. When a connection is active, normal DDCS
communication from NETA-21 web user interface to the drive is suspended.
Note: For cybersecurity reasons, all Ethernet PC tool gateway connections (DDCS and
Panel bus) must be used only inside a trusted network.
Program features 47

TCP and UDP service ports


There are multiple in-bound and out-bound network services running on the NETA-21.

 In-bound network services on the NETA-21


Port Service Purpose

21 / TCP FTP File transfer service. Enabled by default, but FTP user accounts need to be
990 / TCP specified in the web UI (Settings –> Users) before the FTP login becomes
possible.
Port 990 provides a file transfer service with an SSL security layer. You can
use the same user accounts as for the FTP service. Explicit TLS encryption
must be used in a FTPS client. (SFTP protocol is not supported).
To modify the FTP and FTPS service availability, go to
Settings –> Network services.

22 / TCP SSH SSH console for support and diagnostics. Each NETA-21 contains a factory
user account with a random password. SSH access is not provided for
NETA-21 end users. To disable the SSH service, go to Settings –> Tool
settings –> Factory tools and deselect Enable factory login (factory
support account).

80 / TCP HTTP Web server provides the UI over the HTTP protocol. HTTP protocol access
is always enabled. Recommendation to use HTTPS is shown in the tool
login box.

443 / TCP HTTPS Secure version of the HTTP pages. To modify the HTTPS port, go to Set-
tings –> Network services.

502 / TCP Modbus/TCP Modbus/TCP Gateway is listening on port 502. Gateway forwards Mod-
bus/TCP data requests to any connected drive (either as DDCS fiber optics,
RJ45 Panel bus or as EIA485 Modbus/RTU traffic). To modify the service
availability, go to Settings –> Network services.

(optional) / HTTP To specify an extra HTTP port (any higher TCP port than 1024) or a default
TCP HTTPs port, go to Settings –> Network services. Extra port is disabled by
default.

67,68 / UDP DHCP DHCP client functionality is used in both Ethernet ports by default as speci-
(client and fied in RFC 3927 (Dynamic Configuration of IPv4 Link-Local Addresses).
server) DHCP server can be activated only on the ETH1 port.

137 / UDP NBT NS Netbios (NBT) Name Service allows a name resolution from Windows XP /
Windows 7 PC by typing http://neta-21 to the address bar of the web
browser (if a firewall is disabled in Windows).
NBT NS service is active only on the ETH1 port by default. To modify the
service availability, go to Settings –> Network services.

24576 / ABB Autodiscovery protocol used by ControlBuilder plus (IP Configuration tool)
UDP Netconfig and Drive composer pro and DriveWindow 2.40 PC tools to discover ABB-
specific Ethernet devices in a local network segment, by listening to and
responding to UDP broadcasts. This service is also in the out-bound ser-
vices list.

61332 / Ethernet gateway service is disabled by default. When enabled, the DDCS
UDP Ethernet GW Ethernet gateway starts to wait for DriveWindow PC tool connections on
this port. To enable the service, go to Settings –> Device interfaces –>
DDCS –> Settings –> Ethernet GW.

8888/TCP Panel bus Ethernet gateway service is disabled by default. When enabled, the Panel
Ethernet GW bus Ethernet gateway starts to wait for Drive Composer PC tool connec-
tions on this port. To enable the service, go to Settings –> Device inter-
faces –> Panel bus –> Settings –> Ethernet GW.
48 Program features

 Out-bound network services on the NETA-21


Port Service Purpose

21 FTP File Transfer Protocol. Reporting option for sending CSV files over the FTP
protocol to any external server. Not in use until configured.

25 / TCP SMTP(S) Simple Mail Transfer Protocol, outgoing e-mail. Also secure version
(or another SMTPS is supported (typically TCP port 587 or 465). NETA-21 can send
configured email out if the SMTP(S) server settings and email reporting are configured.
port) By default, the service is not in use.
Two SMTP servers are supported (primary and secondary server). Server
names and outgoing port numbers can be configured in the web UI (Set-
tings –> Network services). To enable the email plug-in, go to Reports –>
Settings –> Add and select E-mail reporting.

80, 443 HTTP, Used for reporting data to external portal services. Not in use until config-
HTTPS ured.

80 HTTP HTTP protocol is used for the Ethernet tool network slave device access, to
access FENA-11/-21 fieldbus modules and BCU-xx control boards over the
Ethernet tool network (typical use case in a local/private network only).
Connection to supported devices established if supported devices are dis-
covered.

123 / UDP NTP Network Time Service.


NETA-21 sends outgoing NTP service packets to “pool.ntp.org” by default
every hour. To configure the setting, go to Settings –> Locale –> Date and
time. If no NTP server is found, the NETA-21 defaults to a manually config-
ured clock setting.

24576 / ABB Autodiscovery protocol. By default the NETA-21 sends discovery broad-
UDP Netconfig casts over the ETH2 interface every minute to discover other ABB devices
(eg, FENA-11 or BCU-xx) in a local network segment. To modify the back-
ground scan setting, go to Settings –> Device interfaces –> Ethernet –>
Settings.

 Safe deployment of NETA-21


The NETA-21 firmware includes many extra services as follows:
• NBT NS discovery
• ABB Netconfig
• FTP
• FTPS
• HTTP
• Modbus/TCP gateway
• PC tool gateway
• NTP
Before deployment of NETA-21 cybersecurity features, you should disable all unwanted
services. By default, the following services are disabled:
• PC tool gateway
• Modbus/TCP gateway
• FTP
• Modbus/TCP master (By default, no slaves are configured)
Program features 49

The services can be disabled as follows:

Service Navigation Action

ABB Netconfig Setting –> Network services –> Services –> Firewall Clear the check box of the
settings desired network interface.

FTP Setting –> Network services –> Services –> Firewall Clear the check box of the
settings desired network interface.

FTPS Setting –> Network services –> Services –> Firewall Clear the check box of the
settings desired network interface

HTTP Setting –> Network services –> Services –> Firewall Clear the check box of the
settings desired network interface
Note: HTTP protocol can
be disabled only if HTTPS
port setting has the default
value 443.

Modbus/TCP Setting –> Network services –> Services –> Firewall Clear the check box of the
gateway settings desired network interface.

PC tool gateway Settings –> Device interfaces –> Panel bus –> Settings Set Ethernet GW to
Disable.

NTP Settings –> Locale –> Date and time Set Time source to Manual
or External.

Network Time protocol settings Replace public NTP server


address with a local server
address.

Cybersecurity Disclaimer
This product is designed to be connected to and to communicate information and data via
a network interface. It is Customer's sole responsibility to provide and continuously ensure
a secure connection between the product and Customer network or any other network (as
the case may be). Customer shall establish and maintain any appropriate measures (such
as but not limited to the installation of firewalls, application of authentication measures,
encryption of data, installation of anti-virus programs, etc) to protect the product, the
network, its system and the interface against any kind of security breaches, unauthorized
access, interference, intrusion, leakage and/or theft of data or information. ABB and its
affiliates are not liable for damages and/or losses related to such security breaches, any
unauthorized access, interference, intrusion, leakage and/or theft of data or information.
50 Program features
Front page 51

8
Front page

What this chapter contains


This chapter describes the front page of the web UI.

Parts and components of the portal


The front page consists of the following parts:
• application-specific toolbar (1)
• navigation bar (2)
• content area (3).

2
3
52 Front page

The front page is a portal where you can change the contents by adding, removing or
moving around the portlets. The figure below shows a modified front page.

The front page contains the following components:


• Refresh button updates the contents of the front page.
• Add content button adds new portlets to the front page. The portlet can be selected
from a pop-up menu. If a portlet is already selected, the corresponding menu item is
disabled in the pop-up menu.

• Save layout button stores the current layout to be loaded when the front page is
opened again.
• Welcome instructions portlet contains instructions for the new user. To change the
instruction text, go to Settings –> User interface.
• Tool description portlet contains a description of the NETA-21. The description text
can be changed from the settings.
• Favorite parameters portlet contains the parameters that are marked with a blue star
on the Parameter browser tab. To refresh the values of the parameters, click the
Refresh button on the title bar.
Front page 53

To group the parameters by drive, click the button on the title bar.
• Unconfigured settings portlet shows the settings categories that have not been
configured or that are misconfigured. By clicking the category button you are
redirected to the corresponding settings view.

All devices portlet


The All devices portlet shows all devices connected to the NETA-21. To navigate to the
front page of a device, double-click the device in the list.

All portlets can be minimized or closed by clicking the icons in the right corner of the portlet
title bar.

Version information
To find out the version information of the NETA-21, click About in the navigation bar of the
user interface or the corresponding icon in the application-specific toolbar.

• Features tab shows the versions of the internal software components.


• License tab contains the software license agreement.
• 3rd party licenses tab lists the third-party software licenses in this product. The third-
party licenses include open source software licenses.
54 Front page

 Application toolbar and navigation bar


The application-specific toolbar is visible in every view (excluding the login page) on the
top of the user interface. The toolbar provides a quick access to the views that are used
most frequently. The toolbar contains the following components:
• Tool ID field shows the identifier of the NETA-21 (default: NETA-21 <serialno>).
• Time field shows the current time and time zone of the NETA-21.
• Location field shows the location of the NETA-21.
• User name field in the upper right hand corner shows the name of the user that has
logged on.
• Logout link logs the currently logged-on user out. The user is redirected to the login
page.
• Help button opens the following dialog box.
Note: The ABB library access requires a connection to the Internet.

• Home button opens the front page of the user.


• Reports button opens the reporting view.
• Settings button opens the main settings view.
• Devices button opens a view showing all the devices connected to the NETA-21.
• Top bar can be shrunk to a smaller size by clicking the double arrow button at the
bottom right corner of the gray box.

The navigation bar contains the above-mentioned navigational items and also the sub-
items for the Settings and Devices items.
Front page 55

The navigation bar can be hidden/unhidden by clicking the small arrow between the
navigation bar and the content area or the double arrow within the Navigation title bar.

Status icons
In the navigation bar and application toolbar the statuses of the devices are indicated with
small icons. The following device statuses are supported:
disconnected
busy
warning
fault.
If the device is connected and functioning normally, the device is shown without any status
icon.
The Devices button in the application toolbar can have a maximum of three different
status icons simultaneously. For example, if there are two devices that are disconnected,
only one icon indicating a disconnected device is shown in the Devices button. If there is
one disconnected device and one busy device, both icons are shown in the Devices
button. If all four statuses occur at the same time, the icons indicating the fault,
disconnected and warning statuses are shown in the Devices button. If the status of the
device is missing or cannot be read, the device is shown with the busy icon.

 Content area
The application-specific tabs are shown in the content area. The view in the content area
changes as soon as you have selected another application since the UI does not have to
load a new HTML file from the server. However, you may have to refresh the view if the
data gets out of date.
56 Front page
Users 57

9
Users

What this chapter contains


This chapter describes the user management.

My details
To see the settings of a current user, go to Settings –> My details. On the admin tab, you
can change your email address, phone number, language and password. You cannot
change your user name or role, even if you had an administrator role.
58 Users

The admin tab contains the following components:


• Save button saves the modified settings to the server.
• Reset button cancels the changes in the settings.
• Full name text box shows the full name of the current user.
• User name text box shows the user name of the current user.
• User role text box shows the user role of the current user.
• E-mail address text box shows the email address of the current user.
• Phone number text box shows the phone number of the current user.
• Login key expires shows the login key expiry time.
• Language drop-down list shows the selected language of the user interface.
• When the language is changed, the change takes place in the user interfaces as
the next view is loaded from the server.
Note: Currently, only English language is supported.
• Old password text box is empty by default.
• If you want to set a new password, the old password must be written for
verification purposes.
• New password text box empty by default.
• The minimum requirement for the valid password is two different characters.
• Confirm new password text box is empty by default.
• You are notified if both passwords do not match or the old password is wrong or
missing.

User management
You can restrict the access rights of users by choosing different roles for them. The names
of the roles are descriptive, for example, Guest has the lowest level access to the NETA-
21 and Tool admin can change everything in it.
Note: The NETA-21 includes a factory account for the web UI. This account is not shown
in the users list. To disable the factory account, go to Tool settings –> Factory tools (see
Factory tools).

 Users tab
On the Users tab you can add, remove and modify users.
Users 59

The Users tab contains the following buttons:


• Add user button inserts a new user in the list with default settings. The new user is not
added to the UI until you have clicked the Create user button in the User properties
panel.
• Remove user button removes the selected user from the UI. This button is disabled if
no users are selected from the user list, or if the user selects itself.
• Generate key button creates a hash key which can be used to securely log into the
tool without providing the user password.
• Logged in users shows the total number of active users.
User list contains existing users, which can be sorted according to different columns.
When a user is selected from the list, the User properties panel appears on the right side
of the tab.

The user list contains the following columns:


• User name shows the name which is used for logging on to the UI.
• Full name shows the full name of the user.
• E-mail address shows the email address of the user.
• Phone number shows the phone number of the user.
• Language shows the used language when the user is logged on.
• Login count shows the total number of logins performed by the user.
60 Users

User properties
The User properties panel contains modifiable settings for the selected user. This panel is
visible only if a user is selected from the user list. The User properties panel consists of
two sub-panels: User details and User & password.
The User details sub-panel inside the User properties panel contains the following
components:
• Full name text box defines the full name of the user. When you are creating a new
user, the user name in the User & password sub-panel is generated based on the full
name if you have not already modified the login name.
• User role drop-down list contains all the roles that can be selected for the user: See
User roles. Guest is selected by default. The user cannot change his/her own role.
• E-mail address text box defines the email address of the user (optional).
• Phone number text box defines the phone number of the user (optional).
• Language drop-down list contains all possible languages in the UI. This defines the
language used when the user logs on.
• Comment text box provides the administrators with an area for writing a comment on
the currently selected user. The comment is not visible for the selected user (unless
the user has administrator privileges).
The User & password sub-panel inside the User properties panel contains the
authentication details of the user:
• User name text box defines the name of the user.
• Password text box defines the password for the user name. The password is not
shown in plain text. The minimum length for a password is 2 symbols.
• Confirm Password text box is used for checking that the password has been typed
correctly. The password is not shown in plain text.
Users 61

In the lower part of the User properties panel there are two buttons, whose names
change by the context. When you are creating a new user, there are the following buttons:
• Create user for saving the new user settings
• Cancel for canceling the creation and removing new_user (default name) from list.
When you are modifying an existing user, there are the following buttons:
• Apply changes for saving the modifications
• Restore defaults for resetting the values to a previously saved user setting.
When the new user logs on to the UI for the first time, he/she is prompted to change the
password.

User roles
The user roles to be selected from the User role drop-down list on page 38 are the
following:
• FW admin
• Tool admin
• Network admin
• Drive expert
• User
• Guest
• FTP user account.
• External account

 Tool admin
With the Tool admin role you have the full access rights to the NETA-21. In addition to the
access rights listed for Drive expert and Network admin, the Tool admin role allows you to:
• add and remove NETA-21 user accounts (and modify permissions of other users)
• perform the firmware update of the NETA-21 through the SD card or PC
• back up and restore the NETA-21 firmware and NETA-21 settings to/from the SD card
• enable or disable the factory login (factory support account)
• reset the tool settings to the default settings (restore the factory settings)
• add and remove extra software packages
• change report settings.
62 Users

If you log on to the UI as Tool admin, the front page appears as follows:

 Drive expert
The Drive expert role includes the access rights of Guest and User supplemented with
rights allowing you to:
• reset and rescan drives
• view network interface settings
• change locale settings
• view and change device interface settings.
If you log on to the UI as Drive expert, the front page appears as follows:
Users 63

 Network admin
The Network admin role includes almost all the access rights of the Drive expert role plus
supplemental rights allowing you to:
• change network interface settings
• view and change network service settings
• change descriptions and prompts for the UI
• change the web server session time-out
• view the memory card status and reports folder on the SD card
• monitor the IP addresses of the logged-on users through events.
As Network admin you cannot:
• view and manage user settings
• view and change NETA-21 settings
• restore settings to factory default values (software option)
• see the installed software type and version of the NETA-21
• reboot the NETA-21 (software option)
• view and change user interface settings
• back up and restore tool parameters to the internal memory or SD card
• rescan device parameters or reset an active fault
• view and change device interface settings
• write device parameters
• select parameters for trend logging
• configure and control data loggers embedded in some monitored devices
• export or import device parameters to/from a file.
If you log on to the UI as Network admin, the front page appears as follows:
64 Users

 Firmware admin
The Firmware admin (FW Admin) role includes the access rights of the User role in
addition with rights allowing you to:
• reset and rescan drives
• change locale settings
• view and change device interface settings
• back up and restore the NETA-21 firmware and NETA-21 settings to/from the SD card
• update the firmware of NETA-21 connected drives.
If you log on to the UI as FM Admin, the front page appears as follows:

 User
With the User role you have the access rights of the Guest role supplemented with rights
allowing you to:
• write drive parameters
• select parameters for trend logging
• access data logger views
• view report settings
• view locale settings
• view the memory card and its contents
• export all drive parameters to the Events tab and save them to a PC
• import drive parameters from the PC file to a device.
Users 65

If you log on to the UI as User, the front page appears as follows:

 Guest
With the Guest role you have the lowest level access rights. As Guest you can only:
• change My details settings
• view events
• read drive parameters and see the statuses of the devices.
If you log on to the UI as Guest, the front page appears as follows:

 FTP user account


The FTP user account does not give access to log on to the web UI. The account can be
defined to allow an FTP or FTPS access to the memory card.
Note: The unsecured FTP protocol is disabled by default from firmware 2.22 onwards
(FTPS is enabled). To enable the FTP service go to Settings –> Network services –>
Services.

 External account
For information on External account, see chapter Security on page 161.
66 Users

User interface
The User interface tab is found under Settings. The text boxes on the tab can contain
embedded environment variables, in other words, the value of the environment variable is
shown in the text. The text may contain '{VARIABLE}' where VARIABLE means the name
of environment variable on the server. If text contains two braces ('{{' or '}}'), only one brace
is shown in the UI.
Users 67

The User interface tab contains the following components:


• Save button saves the modified settings to the NETA-21.
• Reset button discards all changes in the settings.
• Export button exports the UI settings to a local file.
• Import button imports the UI settings from a file to the UI.
• Help button opens a dialog box informing you about the embedded environment
variables in the UI.
• Tool name text box shows the name of the NETA-21 (the default is the same as the
tool type). This box may contain embedded environment variables. When you make
changes in this box, the following places will be affected:
• Web browser title shows the tool name.
• Application toolbar shows the tool name.
• Welcome instructions text box contains the welcome instructions for the UI. The
welcome instructions are shown on the front page after the first login. This box may
contain embedded environment variables.
• Tool description text box contains the NETA-21 description. This text is shown on the
front page after the login. This box may contain embedded environment variables.
• Login prompt information text box contains the information visible for all users in the
login dialog box. This box may contain embedded environment variables.
• Web session timeout drop-down list defines the time (in minutes) when the user is
logged out if there is no activity in the UI. The default value is 15 minutes. The
following values can be selected:
• 15 minutes
• 30 minutes
• 60 minutes
• 2 hours
• 6 hours
• 12 hours
• 14 hours
• indefinite.
Note: The web session expires in less than 5 minutes if the web browser is closed or
the connection to the NETA-21 is lost. The Web session timeout setting has effect
only if the web browser window is open. The time-out calculation is reset every time
when the user browses around in the UI.
68 Users
Devices 69

10
Devices

What this chapter contains


This chapter describes how to manage device parameters and use data loggers.

Devices tab

There are two tab pages under Devices:


• Devices tab lists all devices that are connected to the NETA-21.
• Events tab lists events for all detected devices.
The Devices tab contains the following components:
• All button shows all devices.
• Refresh button updates the device list. When the view is updated, the Refresh button
is disabled and the icon spins indicating that the updating is in progress.
70 Devices

• Navigate button opens the front page of a selected device. This button is disabled if
no device has been selected. If you click the arrow on the button and select
Parameters or Events, you can go directly to the Parameter browser tab or the
Event tab of the selected device.

• Device list shows all detected devices. Double-click a device to open the front page of
the device. The list contains the following columns:
• Name column contains the name and icon of the device.
After the device name there are two numbers in curly brackets. The first number
depends on the connection type:
0 = DDCS connection
1 or 2 = PNL connection
3 = Modbus connection
Ethernet connection = IP of the device without dots.
The second number is an ID that indicates different devices of the same
connection.
• Category column contains the category of the device.
• Type column contains the type of the device.
• Status column contains the connection status of the device and the corresponding
icon describing the status. The status can be, for example, one of the following:
Normal, Disconnected, Warning, Fault.
• Connection type column contains the connection type of the device. The following
connection types are available:
DDCS
ETH scan, ETH manual (Ethernet connection, either automatically scanned or
manually connected)
MB (Modbus)
Panel bus.
Devices 71

 Device front page


Every device has its own front page which can be customized by the administrator. Every
user has the same layout. The front pages are portals where the user can move, add and
remove the contents.
• Example of a device front page:

The toolbar of the front page contains the following buttons:


• Refresh button refreshes the contents of the view. When the view is updated, the
Refresh button is disabled and the icon spins to indicate that the updating is in
progress.
• Add content button adds a new portlet to the portal. If you click the arrow on the
button, you get a drop-down list containing the following portlets:
• System info
• Device control
• Events
• Favorite parameters.
72 Devices

• Save layout button saves the layout. This button is visible only to device super users
and administrators that have permissions to modify the layout.
The front page contains the following portlets:
• System info portlet shows read-only information about the device.
• Device control portlet contains means to control the device. Every option contains a
title, icon and description. See section Device control buttons.
• Events portlet shows the latest events for the device. The event list contains the
following columns: Name, Timestamp and Severity. The list can be sorted.
• Favorite parameters portlet contains the parameters that are marked with a yellow
star on the Parameter browser tab. You can refresh the values of the parameters by
clicking the Refresh button of the front page.

Device control buttons


There are three device control buttons in the Device control portlet.When you click the
icon, the icon is disabled until the action has completed. If the action fails, a light-blue
warning message is shown under the description. The panel may contain the following
actions (the options may vary between devices):

• Rescan parameters button


The button is enabled when the associated drive is connected and parameter
scanning is not active on any of the drives handled by the same device interface (eg,
DDCS, panel bus, Ethernet, Modbus). In any other case the button is disabled.
The automatic parameter scanning starts if all connected devices per interface (or
panel port) become disconnected. Some interfaces such as Ethernet tool network may
scan for nearby devices continuously in the background.
There are situations when the parameter list of a drive and the content of the
Parameter browser tab become unsynchronized, for example, when the parameters
of a drive have been modified while it has been disconnected shortly from the NETA-
21. When you reconnect the NETA-21 to the drive, use this button to resynchronize
the parameters shown in the Parameter browser tab with the actual parameters of
the drive.
When you click the button, a dialog box appears. Click Yes to confirm rescan:

• Reset fault button


The button is enabled when the associated drive is connected, there is an active fault
on a drive, or when a drive has an unacknowledged fault which has already ended.
Devices 73

In any other case the button is disabled.


If the cause of the fault has been handled, you can reset the fault by clicking this
button. If a fault condition is active or a device has a permanent fault, the fault cannot
be reset via interferes.
• Remove button
The button is enabled when the associated drive has been disconnected from the
NETA-21. Use the button to permanently delete the drive from the drive list of a device
interface, for example, when the configuration of the system has changed.
The button is disabled when the drive has been reconnected to the NETA-21.

 Parameter browser
Every device has one or more parameter browser tabs that list the parameter groups and
parameters of the device. You can mark favorite parameters with yellow and blue stars.
Parameters marked with a yellow star are shown in the Favorite parameters portlet on
the device front page. Parameters marked with a blue star are shown in the Favorite
parameters portlet on the My frontpage tab.

The toolbar of the Parameter browser tab contains the following components:
• Filter parameters… is a text box for finding parameters from the parameter list. The
parameter list is updated automatically when you type search criteria to this box.
• Parameter status is a check box for showing or hiding the parameter status bar of the
parameter view at the bottom of the window. The status bar is visible by default.
• Refresh values button updates the parameter values visible in the parameter list.
When the view is updated, the refresh button is disabled and the icon spins to indicate
that the refreshing is in progress.
The NETA-21 has a cached list of parameter groups and parameter names. The
Refresh values button does not necessarily update all group names on the list, since
that would take too much time. Some of the parameter data will be updated after a
delay when you start browsing into the parameter groups. If it is uncertain that the
parameter list is up to date or if there are strange access errors when you try to open
parameter lists, the errors can be solved by reloading all device-specific data. To
74 Devices

reload all device-specific data, click the Rescan parameters control button on the
device front page.
• Expand all button shows all parameters of all groups.
• Collapse all button hides all parameters and shows only the group list.
• Export button exports parameters to a file.
• Import button imports parameters to the device.
The status bar provides the following information:
• Parameters updated field shows how much time has gone since the parameter
structures have been updated from the device to the NETA-21. The NETA-21 keeps a
cached list of parameter structures, and someone else (a local user with a control
panel, a PC tool user, or the monitored device itself) may have changed parameters
after the last update. The elapsed time is shown as follows:
• Parameters updated X days ago
• Parameters updated X hours ago
• Parameters updated X minutes ago
• On-going operation field shows what the device is currently doing. The operation is
indicated with an icon and, for example, the following texts:
• Parameter list is up to date
• Refreshing parameters
• Device is disconnected
• Device is offline.
The parameter list is not sortable. The list contains the following columns:
• Name column shows the name of a parameter.
• Value column shows the value of a parameter. For parameters that have a decimal
value, the value is shown in the hex, decimal or binary format depending on the
selection made in the Parameter properties panel.
• Minimum, maximum and default value columns are hidden by default.
To add columns, click the arrow on the right-hand side of an existing column:

• Unit column shows the unit of the parameter value. This field may be empty for some
parameters.
• Internal type shows the data type of the parameter, either a device-specific type (eg,
float2 for a float number with two decimals) or a generic type (eg, "number" or "string").
When you select a parameter from the list, an edit panel titled Parameter properties
appears in the right-hand side of the tab.
Devices 75

Parameter properties
Open the Parameter properties panel by clicking a parameter in the Name column. The
panel has two sub-panels that are visible one at a time.
• Modify panel has controls to modify the parameter value.
• Logging panel contains logging-specific settings and lists.
With the Modify sub-panel you can modify the parameter value.

The Modify sub-panel contains the following components:


• Value check box: There can be two value boxes to choose from depending on the
data type of the parameter. If there are two value boxes, only one of them can be
selected at a time, and the other is collapsed.
The box may be a spin box, check box grid, drop-down list, text editor or a parameter
selection control (parameter pointer or bit pointer). If there is the Parameter check
box, click the list to open a pop-up window where you can choose a parameter or the
bit of a parameter value.
76 Devices

Spin-boxes use the minimum and maximum value limits received from the device. You
cannot type the value.
• Format is a drop-down list for specifying the format of a parameter value. The format
can be Decimal, Hex or Binary.
• Export button exports the parameter in a text-based file.
• Apply changes button saves the parameter changes to the device.
The icon of the Refresh button is spinning while the changes are applied to the NETA-
21.
• Restore defaults button asks the device to restore the default value to a parameter.
This button is disabled if the parameter has no default value.
Notes:
• You cannot modify the value or format of read-only parameters.
• Read-protected parameters cannot be read and appear as an empty value field.
The Logging sub-panel contains logging-specific settings and lists:

The Logging sub-panel contains the following components:


• Signal name defines the name of the parameter that is used in reporting and trend
logging. The default name depends of the style selected in Reports –> Settings –>
Signal names –> Settings –> Default signal name. You can restore the default
signal name with the Restore default button or by storing an empty signal name.
• Interval drop-down list is used for selecting the logging interval for the current
parameter. You can select from the following values: Minute, 5 Minutes, Hour, Day,
None or Continuous monitor. To save the value, click the Apply changes button.
• Log only when changed check box is used for selecting values to be logged only
when the parameter value changes. If this check box is not selected, the parameter
value is logged at every interval.
Devices 77

• Open parameter logging history in a new tab button


• Refresh button updates the log list/chart if new values have been logged.
• Export the event attachment button creates a log report file to be exported.
• Toggle between chart and list view button changes the view in which the
logged values are displayed.
• Logging history shows all the logged values for the parameter in the current
segment.
• Apply changes button saves the parameter log changes.
• Restore default button replaces all changes in the settings with default values.

Export of parameters
When you click the Export button in the toolbar the following progress pop-up window
appears:

The progress pop-up window has a Cancel button which stops the exporting process.
With the Hide button you can hide the exporting pop-up window. The pop-up window is
shown again when you click the Export button.

Note: Only one parameter export can be ongoing at a time. If another user has started a
parameter export before you started a new export, your export may fail. In addition, you
cannot start an export, if drive parameters are being scanned in background.
Note: The parameter export format depends on the device type and device interface. The
parameter export is not available for all device interfaces.
78 Devices

Import of parameters
When you click the Import button you are asked for an import file.

The file is sent to the NETA-21 and the progress dialog box is shown. The NETA-21
supports the NETA-21, NETA-01 and DriveWindow parameter export files for importing.
Note: The format of the parameter import file is compatible with the NETA-21 parameter
export files, NETA-01 parameter export files and DriveWindow 2.x parameter export .txt
files (but not with DriveWindow parameter .dwp save files).
Make sure that you import/export parameters only between identical drives and device
software versions.
It may be necessary to power cycle the drive and reload the device interface in the NETA-
21 to see all effects of parameter changes, especially if monitored devices change their
device interface node ID.
Note: The parameter import does not open a parameter lock or handle all dependencies
between parameters. Sometimes it helps when you import a parameter file multiple times.
Note: For the ACS800 firmware, the parameter import restores ID run parameters if those
are included in the parameter file. In addition, only visible parameters are restored.

WARNING! Make sure that you can start the drive safely before using the
parameter import function. Imported parameter settings must to be compatible
with the specific drive. When you import specific parameter configurations you
can cause the drive to start during or after the parameter import. (Control words or signals
in groups <10 are not written to a drive during the parameter import).
Devices 79

Device data logger


 Data logger
The drives connected through a DDCS protocol have a data logger or data loggers that
can record data from various signals of the drive when there is no external logging
mechanism active. This can be used for troubleshooting or diagnostics. Data collecting
can be stopped by either a specific stop command or automatically by a triggering
condition becoming true in the drive. After the data collecting has been stopped, the
collected data can be read and studied.
The data logger tabs contains all uploaded data logs from the drive. One drive can have
multiple data loggers configured. All data loggers have an identical user interface.

The data logger tabs contain the following components:


• Refresh button refreshes the data logger view.
• Control button is a menu button that can be used to control the data logger with the
following actions:
• Start - starts the data logger.
• Stop - stops the data logger.
• Reset - restarts the data logger.
• Trigger - triggers the data logger manually.
• Settings toggle button shows the data logger settings in the editor panel.
80 Devices

• Triggers toggle button shows the data logger trigger settings in the editor panel.
• Export… button shows a drop-down list of two options: Events and Settings.

• Events option exports all collected recent data log files to a compressed .zip file
that can be opened with a PC.
• Settings option exports the currently opened data logger Settings and Triggers
panel configurations to a file that can be loaded to a PC.
• Import settings button allows you to import the previously saved data logger settings
and triggers from a file on a PC to a data logger in a monitored device.
• State defines the current state of the data logger with the following states:
• Not initialized
• Stopped – the data logger is not running/collecting data.
• Started – the data logger is running/collecting data.
• Filled – data logger upload is complete and data logger is not running/collecting
data.
The State is updated automatically every couple of seconds.
The Datalogger tabs show all uploaded data logs from the drive.

You can see the content of an entry by double-clicking the entry in the data logger list or by
clicking the plus sign beside it. You can close the content of an entry by double-clicking the
open entry in the data logger list or by clicking the minus sign.
The tabs contain the following columns:
• Name column shows the event name.
• Local time column shows when the event occurred. You can use the following filters
Before, After or On.
• Relative time column shows how much time has passed since the event occurred.
• Category column defines whether the event contains a device-produced data log file
(category: device generated datalog) or whether the event indicates a change in a
data logger state (category: device datalogger control).
Devices 81

• Source column shows the source of the event. You can filter this field with a free text
box.
• Severity column defines the severity (or type) of the event (Detail, Notification,
Warning, Fault, Severe). You can filter this field to show only the wanted event types.
The columns can be sorted, hidden or filtered by clicking the header arrow, which appears
when the cursor is over the header.

The data logger records data before and after the triggering event, depending on its
settings.
For more information on the functionality of data loggers, see the drive-specific firmware
manual.

 Opening a data logger


1. Log on as a user with roles other than Guest or Net Admin.
2. Click Devices.
3. Select the device to be monitored with a data logger.
Note: All monitored devices do not provide data loggers. Data loggers are supported if
there is one Datalogger tab or more Datalogger tabs on the device-specific page.
4. Click the Datalogger 1 or Datalogger 2 tab to view the system data logs.
82 Devices

 Setting up a data logger


1. Open Datalogger 1 or Datalogger 2 (see above).
2. Click the Settings button to open the Settings sub-panel of the Datalogger
configuration panel in the right-hand side of the tab.

3. From the Datalogger auto control drop-down list select Only automatic upload
(data logger stops after it has finished collecting data) or Keep continuously running
(data logger is started whenever the logger is initialized or filled, even if the logger was
not initially running).
4. In the Channels box click the parameter you want to add and then click the Change
selected channel icon.
5. In the pop-up window select the new parameter you want to add to the list and click
OK.
Devices 83

To leave the Channel box as it is, click Cancel.

6. Remove the unnecessary monitoring parameters by selecting them and clicking the
Remove selected channel icon.
84 Devices

7. Open the Triggers sub-panel.

In this panel you can adjust:


• Time step (ms): sampling rate of the data logger in the device.
• Trigger conditions: multiple choices depending on the monitored device.
• Trigger variable (parameter selection), Trigger level and Trigger hysteresis, if
the selected trigger condition requires the values. For example, a limit check
requires that the parameter and trigger level limit are specified.
• Pre-trigger count: number of the samples recorded in each data log before the
triggered event occurred.
Note: The number of available ranges and trigger options vary depending on the
monitored device. If the selected settings are not accepted by the monitored device
when you click the Apply changes button, the UI restores the original settings from
the monitored device to the Triggers panel.
8. From the Time step spin box select the time interval (in milliseconds) between data
readings.

9. From the Trigger conditions list select what device conditions will trigger the data
logger to send in the collected data.
An additional parameter value set in Trigger variable can be used to trigger the data
logger. Use the Trigger hysteresis spin box to set the signal value hysteresis.
10. In the Pre-trigger count spin box select the number of data entries that will predate
the trigger event.
Devices 85

11. Click Apply changes.


12. Click Control and select Start to start the data logger or change the Only automatic
upload mode to the Keep continuously running mode in the Settings panel.

The State changes to Started indicating that data logger is running.

Device interface settings


 Device interfaces
The Device interfaces view is meant for device expert users who want to configure the
access to the monitored devices in fine detail. Device interface specific settings lets you
configure communication parameters as well as fine tune device specific settings.
Normally the NETA-21 configures device interfaces automatically and auto-discovers
connected monitored devices. Sometimes it is necessary to rebuild the device interface to
refresh the list of monitored devices. Devices in the selected interface are presented in a
generic fashion since new interfaces can be added to this view dynamically as new device
interfaces.
Every connection type has its own tab.

Note: The selection of available device interfaces depends on the installed firmware
version and extra packages.
The toolbars of the tabs differ but all of them have the following buttons:
• Settings button opens an Interface settings dialog box that contains settings for the
selected device interface. The settings vary for every interface.
• Refresh button refreshes the device list in the current interface.
• Rescan devices button rescans a specific device interface to add/remove devices.
This button is not available for every device interface. The rescanning of devices is run
in the background for every device interface while no devices are connected, or when
all connected devices become disconnected. Some interfaces such as Ethernet may
be able to rescan for added devices in the background continuously.
• Restore defaults button restores the default values for settings and re-initiates the
scanning of devices within the selected interface. Previously connected devices may
be lost.
86 Devices

The device list on each tab has the following columns:


• Device column shows the name of device.
• Node ID column shows the node ID of the device interface.
• Category column shows the category of the device.
• Connection type column shows the connection type of the device.
When you select a device from the list, the Device parameters panel appears in the right-
hand side of the tab. The content of the Device parameters panel is specific for each
connection type, but the following components can be found in all of them:
• Device name box sets a custom name for the device.
• Apply changes button saves the modified device settings.
• Restore defaults button discards the changes made before the Apply changes
command was given.

 DDCS tab
The DDCS tab contains all the devices which use the DDCS protocol and which are
connected to the NETA-21 through fiber cables (via the NEXA-21).

Click a device in the list to open the Device parameters panel where you can change the
value of the Main status word to Not set, Dataset 2 or Dataset 11.
Note: The Main status word dataset is normally auto-detected during the device detection.
If a wrong value is selected, the device fault and warning statuses are not indicated
correctly.
Devices 87

 Ethernet tab
The Ethernet tab contains all the devices that the NETA-21 finds in its Ethernet tool
network.

Note: If there is an ACS880 or ACS860 drive equipped with a FENA-11/21 adapter


module in the Ethernet network, the NETA-21 and the Drive composer PC tool cannot
access the FENA-11/21 at the same time. The FENA-11/21 can have only one PC tool
connection at a time. The FENA-11/21 connection can be released for a PC tool by
removing the specific Ethernet device from the NETA-21 device interfaces view (or by
clicking the Remove button on a specific Ethernet device front page).
The toolbar of the ETH tab contains the following two extra buttons:
• Add button allows you to add a device to the list by specifying its IP address.
• Remove button removes the selected device from the list.
By default, the NETA-21 discovers devices automatically via the Ethernet tool
communication connected to port ETH2. To modify the background scan settings click the
Settings button.
88 Devices

 Modbus monitoring tab


The Modbus monitoring tab contains all the devices which use the Modbus/RTU protocol
and which are connected to the NETA-21 through serial port.

The toolbar of the Modbus monitoring tab contains the following extra buttons:
• Add button allows you to add a device to the list by specifying the following properties:
• Device Name is a text box for the custom name of the device.
• Modbus/TCP host (empty for RTU) is a text box for the IP address of the
Modbus/TCP host. No value should be provided when the used protocol is
Modbus/RTU.
• Modbus node ID is a spin box for the node ID configured in the monitored device.
• Drive template is a drop-down list for the template to be used with this device. A
template is a file provided by ABB that is stored under the "template" folder in the
SD card or internal memory. The template selection provides also a list of other
connected drives. You can clone parameters from another device (eg, a DDCS or
Panel bus connected device) into a Modbus device.
• Import drive template contains the name of the imported active template. Click
the Browse button to select a file.
• 32-bit registers is drop-down list for selecting 16-bit or 32-bit values of
parameters. There are three options:
As in template, 16-bit if unset
As in template, 32-bit if unset
Force all values to 32-bit
• 32-bit register word order is a drop-down list for selecting the most or least
significant word order for 32-bit values. There are three options:
Autodetect
High-low
Low-high
• Remove button removes the selected device from list.
• Rescan devices button performs a rescan that searches for all Modbus-connected
devices.
Devices 89

Note: The Modbus/RTU rescan uses a selected communication speed (defined in the
Interface Settings dialog box). The rescan runs continuously in the background if all
devices are disconnected.
Click a device in the list to open the Device parameters panel where you can change the
Modbus node ID and the 32-bit register word order.

 Modbus templates tab


The Modbus templates tab lists all the available templates from the internal memory and
the SD card of NETA-21.

The tool bar of the Modbus templates tab has the following buttons:
• Add button allows you to add more templates. You can either import a template or can
clone the parameters of a connected device. See, Add Modbus templates.
• Remove button allows you to remove a template from the list of available templates
and from the SD card. Only user defined templates can be removed.
• Refresh button updates the list of templates. This is performed after addition or
removal of a template.
• Edit button displays the Modus Template Editor dialog box and allows you to edit the
template. Before editing, templates stored in the internal memory will be saved to the
SD card. See Edit Modbus templates.

Add Modbus templates


To add new Modbus templates, perform the following:
1. Open the template directory.
Note: Create the template directory if the template directory does not exist.
2. Click the Add button and select the template file to be uploaded. To add the template
directly, copy the templates to the template directory.
90 Devices

Note: The template names should be in 8.3 format. The maximum file name length is 8
characters and the maximum file extension length is 3 characters. This is due to the SD
card’s file system limitation.

Edit Modbus templates


You can edit an existing Modbus templates or can add and edit a copy of existing default
template. To edit an existing Modbus template, perform the following:
1. From the NETA-21 UI, go to Settings -> Device interfaces -> Modbus templates
tab.
2. Select the template to be edited and click Edit. A Modbus template Editor dialog box is
displayed.
To edit a new template based on an existing default template, click Export and copy
the existing template to PC. Rename the file and Add (see Add Modbus templates) it
to the template directory as a new template.
Devices 91

Note: If you try to edit a default template, a confirmation message is displayed to copy
the template to the SD card. Click Yes to continue. Else, click No.

3. In the Modbus Template Editor, you can edit the following:


• Basic Info
• Identification rules
• States
• Events
• Parameters
4. After required modification in each section, click Apply and then Save to save the
changes.
Basic Info
Basic info includes the basic information of the templates. These are informal
metadata attributes. The Basic info tab has the following components:
• Template name - Defines the name of the template.
• Version - Defines the version of the template.

Identification rules
Identification rules are used for automatically scanned Modbus/RTU devices. It is not
used for node IDs that are added manually such as Modbus/TCP devices connected
through fixed IP address.
The Identification rules tab include the raw Modbus register and fixed value details. To
apply the template automatically during the background scan of the Modbus/RTU
devices, the register and fixed values should match.
The Identification rules tab has the following components:
• Register - Unsigned integer. Modbus register can be 16 bit (values 1...20000) or
32 bit (over 20000). For drives automatic identification, if parameter internal type is
int16 or uint16 then register is calculated as:
register = 100 × group + index
92 Devices

If parameter internal type is int32 or uint32 then register is calculated as:


20000 + 200 × group + 2 × index
• Values - Comma separated integers, parameter internal values, and comparisons
using the >, >=, <, <=, and <> operators.

Note: It is possible to list multiple registers and multiple possible identification values
for each register. However, the increase in conditions makes the identification slower
and further slows the automatic identification performance (Modbus background
scanning). Hence, it is recommended to use maximum 3 conditions.
States
States tab includes the Modbus register information that is mapped to the Modbus
template and also indicates the device status.
States tab has the following components:
• Name - Displays the device status. For example, Disconnected, fault, warning,
and so on.
• Parameter - Displays the related parameter in group.index format.
• Mask - Unsigned integer. Defines the value of bitmask for comparison
operation.The mask value is calculated as:
· askvalue = 2 0 + 2 1 + … + 2 n
m
where 0, 1.....n are the bits in a bitword.
Note: You can enter the mask values as decimal number in different formats. For
example, 123, 0x7B, 0b1111011, and so on.
• Operation - Triggered automatically if NETA - 21 cannot read any values. The
possible events and its reasons are:

Operation Reason

No response NETA-21 cannot read any values.


Value column and mask can be
empty, but the parameter must be
an existing parameter which can be
always read if the device is con-
nected (preferably main statusword
which is also used for fault and
warning states)
Devices 93

Operation Reason

Change Value is changed and is equal to


(appears as Equal specified value.
in firmware 2,27
and later)

Not equal Value not equal to specified value

Note: The operation names are not editable.


• Value - Parameter internal value (integer).

Events
Events tab provides information on the custom monitored parameters that triggers the
events.
94 Devices

Event tab has the following components:


• Severity: Displays the severity of the event.
• Parameter: Displays the related parameter that triggers the event.
• Mask - See mask field in States tab.
• Operation - See Operation in States tab.
• Value - See Value in States tab.
• Message - Displays the type of event. For example, overcurrent, overvoltage, and
so on.

Parameters
Parameters tab provides information on parameters that are mapped to the Modbus
templates. You can click Add or Remove to add or remove any parameter from the
list.
The parameters tab has following components:
• Name - Displays the parameter or group name that appears in the parameter
browser.
• Type - Displays the type of parameter listed. The possible parameter type values
are:
- Empty: Normal parameters.
- Group: Parameter groups
- List: Parameters with lists. You can edit the parameter lists using Edit list button.
Devices 95

-Bitword: Parameters with bitwords. You can edit the bit values and texts using the
Edit List button.

• Index - Displays the parameter index in group.index format. Max value is 255.255
• WP - Displays whether the parameter is write protected.
• Pointer - Allows you to enable target parameter pointer selection in web UI.
• Unit - Displays the unit that is displayed in the parameter browser.
• Internal type - Defines the parameter internal type as follows:
U16: Unassigned 16 bit integer
S16: Signed 16 bit integer
U32: Unsigned 32 bit integer
S32: Signed 32 bit integer
• Scaling: Defines the scaling value to scale the value read from the drive
• Decimals: Displays the number of decimals displayed in the parameter browser.
This is not used for any calculations.
• Format: Defines the value format. For example dec for decimal, hex for hexa
decimal, and bin for binary.

 Modbus/TCP gateway tab


The Modbus/TCP gateway tab contains a list of all connected drives which can be
accessed through the Modbus/TCP gateway.
96 Devices

On selection of a drive from the list, the Device Parameters section displays settings of
the selected drive as follows:
• Modbus node id field represents the connection specific node ID of the drive, see
chapter Modbus/TCP gateway on page 45.
• Device Name field shows the name of the drive.
• Device Node field shows the node id of the drive.
Read-write flag is a drop-down list to select the access mode, specific to the
particular drive through the gateway. There are 2 options:
- Read-only
- Read-write.
• Read-write access IP address is an edit box, where the user can specify the IP
address from where the gateway accepts connections to this particular drive.
• Read-write access netmask is an edit box, where the user can specify the
netmask of the IP address from where the gateway accepts connections to this
particular drive.
• Timeout in milliseconds is an edit box, where the user can specify the maximum
waiting time for a response after each individual request, for this specific drive.

 Panel bus tab


The Panel bus tab contains all the devices connected to the PNL connectors.

 Interface settings
To open the Interface settings dialog box, click the Settings button on the toolbar. Every
connection type has its own Interface settings dialog box. The following two buttons are
common to each connection type:
• Save button saves the modified settings.
• Close button closes the dialog box without saving the settings.
Devices 97

Modbus/TCP settings
The figure below shows the Interface settings dialog box of the Modbus/TCP gateway tab.

• 32-bit word order is a drop-down list for selecting the most or least significant word
order for 32-bit values. There are 2 options:
• Low-high
• High-low
• Auto nodes RW-flag is a drop-down list for enabling or disabling write access. There
are 2 options:
• Read-only
• Read-write
• Auto write IP address is a text box where the IP address of the Modbus/TCP master
can be specified.
• Auto write netmask is a text box where the netmask for Modbus/TCP master IP
address can be specified.
• Firewall / allowed on shows the network interfaces on which Modbus/TCP gateway
access is enabled. Changes can be done in Settings -> Network services ->
Firewall settings.
• Firewall / denied on shows the network interfaces on which Modbus/TCP gateway
access is disabled. Changes can be done in Settings -> Network services ->
Firewall settings.
• Timeout in milliseconds is a text box where the user can specify the maximum
waiting time for a response given to an individual Modbus/TCP request. If the
response hasn't arrived in the allotted time, Modbus error 0x06 - Slave Device Busy
is sent back to the master.
When the master's request contains a range of values, the timeout is applied to each value
separately.
98 Devices

Ethernet settings
The figure below shows the Interface settings dialog box of the Ethernet connection.

With the Background scan function you can define how the automatic device discovery
works. The available options are:
• Disabled: Devices are not automatically discovered.
• ETH1: Automatic discovery works only on the first Ethernet port.
• ETH2: Automatic discovery works only on the second Ethernet port.
• Both: Automatic discovery works only on both Ethernet ports.
When the PC tool friendly mode is enabled, the background scan function starts with a
30 seconds delay. This time is used by PC tool (like Drive Composer) to detect a drive and
connect to it.

Modbus settings
The figure below shows the Interface settings dialog box of the Modbus connection.

Communication Speed is a drop-down list for setting the speed of the Modbus
communication. The available speeds are the following:
• 9600 bps
• 19200 bps
• 38400 bps
• 57600 bps
• 115200 bps
• 230400 bps.
Devices 99

Communication Mode is a drop-down list for setting the serial communication mode. The
available values are the following:
• 8-N-1: 8 None 1
• 8-E-1: 8 Even 1
• 8-O-1: 8 Odd 1
• 8-N-2: 8 None 2.
Background scanning is a drop-down list for enabling or disabling the automatic device
discovery. The background scanning uses the selected communication settings. The
background scanning runs every minute if there are no connected devices, or every 4
minutes if at least one device is connected.
Modbus/TCP send timeout is a text box where the user can specify the maximum waiting
time for a response from individual drive. The timeout period is defined in milliseconds. If
the drive does not responds in specified time, a Modbus error 0x06 - Slave Device Busy is
sent back to the master. The master should retransmit the message when the slave is free.
When the master requests to read or write several registers, the timeout value is applied to
each response.

DDCS settings
The figure below shows the Interface settings dialog box of the DDCS connection.

• Optical Power is a drop-down list for defining the value from 1 (lowest) to 4 (highest).
• Communication Speed is a drop-down list for defining the value from 1 to 8 Mbit/s.
• Network Topology is a drop-down list where you can choose values Star or Ring.
• Ethernet GW is a drop-down list for enabling or disabling the Ethernet gateway for a
remote DriveWindow PC tool (2.4 or later) connection. Ethernet gateway is turned off
automatically after 10 minutes of inactivity. By default, the gateway is disabled.
Note: For security reasons, PC tool Ethernet gateway connections for DDCS must be
used only inside a trusted network.
• Dataset Access is a drop-down list where datasets can be enabled or disabled. The
options available are None, Read-only, and Read-write.
• Data logger mode is a drop-down list for selecting how drive data logger control mode
is modified. The available options are:
• Manual
• Automatic
To control data loggers efficiently, make sure that the data logger state of the
connected drives are not modified.
You can avoid modification of data logger state by performing either of the following:
• Manually set Datalogger Autostart parameter value to OFF for each drive
connected via DDCS
100 Devices

or
• Set Data logger mode to Automatic.
Note: The settings depend on the configuration required by a device interface.

Panel bus settings


The figure below shows the Interface settings dialog box of the Panel bus connection.

• Cable check is a drop-down list for enabling or disabling the function.


• When the cable check function is enabled, the NETA-21 tries to identify the
connected cable (by testing the input voltage from the drive control board). The
panel bus connection scanning runs in the background only if the cable (input
voltage) is detected on the PNL1 or PNL2 port.
• When the cable check function is disabled, panel ports are scanned continuously
even if the cable is not connected. If the input voltage is not available from the
panel bus, this option can be used for detecting panel bus devices. When the
cable check function is disabled, there is extra background CPU load in the NETA-
21. The PNL1/PNL2 LEDs are red if no panel bus device cannot be detected. See
LED indications of the NETA-21.
• Ethernet GW is a drop-down list for enabling or disabling the gateway mode. By
default, Ethernet gateway is disabled. There are four different options to enable this
feature:
• Enable - Enables the Ethernet gateway permanently. This can weaken security
and is not recommended.
• Enable while in use - Keeps the gateway open, as long as data is flowing through.
Gateway is disabled automatically after 10 seconds of inactivity.
• Enable 1 hour - Keeps the gateway open for 1 hour from the time it is enabled,
regardless of inactivity.
• Enable 24 hours - Keeps the gateway open for 1 day from the time it is enabled,
regardless of inactivity.
Note: For security reasons, PC tool Ethernet gateway connections for Panel Bus must
be used only inside a trusted network.
• Time synchronization is a drop-down list for enabling or disabling the function. When
enabled, NETA-21 will act as a clock master for the drives connected via this interface.
• Connection speed (pnl1) shows the speed for the active connection.
• Connection speed (pnl2) shows the speed for the active connection.
Networks 101

11
Networks

What this chapter contains


This chapter explains how to set up and configure Ethernet network interfaces of the
NETA-21.

Network interfaces view


The Network interfaces view (Settings –> Network interfaces) is split into two interface
specific tabs: Ethernet 1 and Ethernet 2.

In addition to the Ethernet panel and Network status panel, the Ethernet interface tabs
contain the following components:
• Save button saves the changes to the NETA-21. When you save the settings, they are
applied to use immediately. A dialog box warns that the connection to the web pages
can be lost, if the IP address of the NETA-21 is changed. You can either continue or
cancel the changes.
• Reset button discards all changes made by the user.
• Export button exports the Ethernet settings to a local file.
102 Networks

• Import button imports the Ethernet settings from a file to the UI.
• Test interface button opens a dialog which can be used for sending a ping message to
a defined address.

 Test interface
When you click the Test interface button the following dialog box appears:

The Ping server dialog box contains the following components:


• Server to ping box defines the address of the server where the ping message is sent.
• OK button sends the ping message and opens a dialog to show the result.
• Cancel button closes the dialog box.
The following Ping status dialog box appears after the ping message has been sent:

The Ping status dialog box contains the following components:


• Interface field shows the interface that was used for sending the ping message.
• Ping status field shows whether the sending of the message has failed or succeeded.
• Output field shows the console output for sending the message.
• OK button closes the dialog box.
Networks 103

 Ethernet panel

• Mode has two options for selecting either an automatically obtained or a static IP
address:
• Obtain an IP address automatically option disables the IP address, Subnet
mask and Default gateway boxes. This is the default setting. When this mode is
selected, the NETA-21 tries to retrieve its IP address from the DHCP server. If the
DHCP address retrieval fails, the NETA-21 defaults to a “zeroconf” IP address in
format 169.254.x.y where x and y are randomly selected numbers.
• Use the following IP addresses option requires you to configure the fixed static
IP address settings by filling in the following boxes: IP address, Subnet mask,
Default gateway, Preferred DNS server and Alternate DNS server.
• DHCP server mode (only on the Ethernet 1 tab from firmware 2.22 onwards) can
always be disabled or enabled, or enabled for the next boot up. Option Enable
with button is the same as by default: If you press the SD/RJ45 button for 5
seconds, you activate the DHCP server on the ETH1 port. If another DHCP server
is detected in a local network, the NETA-21 does not activate its DHCP server.
104 Networks

 Network status panel

• Disable DHCP button disables the DHCP server mode. The button is visible only
when the DHCP mode has been activated with the SD RJ45 button.
• IP address field shows the currently used IP address for the interface. If the field is
empty, no IP address has been defined. If the link status is "down", a message
indicating this is shown instead. This field cannot be modified.
• Netmask field shows the current network mask. If the field is empty, no mask has
been defined. This field cannot be modified.
• Gateway field shows the default gateway for the specific interface. This field cannot
be modified in the Network status panel.

Network services
The Network services view (Settings –> Network services) shows the connectivity of
the NETA-21 with outside world over Ethernet.

For example, time services are located in the Locale settings view. Some of the out-bound
reporting services such as email and FTP are configured in the Report view.
The Services tab contains the following components:
• Save button saves the changes to the NETA-21.
• Reset button discards all changes made by the user and restores the default settings.
• Export button exports the visible settings to a local file.
• Import button imports the settings from a file to the UI.
• Test SMTP settings button asks you for an email address. The UI uses the visible
SMTP settings to send a test email to the specified email address.
Networks 105

The Services/firewall settings panel, Services settings panel and Mail servers (outgoing)
panel are described below.

 Test SMTP settings

The Test SMTP settings dialog box contains the following components:
• From text box defines the email address of the sender.
• To text box defines the email address of the receiver.
• Subject text box defines the subject for the email message.
• Content text box defines the content for the email message.
• OK button closes this dialog box and sends an email to the receiver.
• Cancel button closes this dialog box.

 Services/firewall settings panel


The Services/firewall settings panel has one service defined in every row. You can
enable or disable the service per each interface. You can also select the service to be
enabled for all interfaces.

The list has the following columns:


• Service column has every available service listed. After the service name there is an
icon. By clicking the icon a popup dialog box or a tooltip is opened providing more
details about the service.
• Interface column has multiple sub-columns. All interfaces are below this column.
• All column is always visible and enabled. The column has a check box which is
selected if the service has been enabled for all interfaces.
• When the All check box is selected all other check boxes in the interface column
are selected as well (in the same row). The All check box disables any firewall
limits and allows the service to be reached over any network connection.
• When the All check box is not selected all other check boxes in the interface
column are unselected as well (in the same row).
• Interface X column shows what services are selected for the current interface. It is
possible that there is no interface X column since the available interfaces depend on
106 Networks

the tool configuration and type. There may be multiple interface X columns containing
a check box.

 Services settings panel

The Services settings panel contains the following components:


• Prefer HTTPS is a check box for defining that HTTPS is used when possible.
If prefer the Prefer HTTPS check box is selected, the UI login page forwards users
always to the HTTPS protocol version of the login page.
• Extra HTTP port is a text box for defining an additional HTTP port. If this box is empty,
no additional port is used.
Note: The NETA-21 provides the HTTP version of the web pages always in port 80.
• HTTPS port is a text box for defining the HTTPS port. The default value is 443.
• FTP port is a text box for defining the FTP port. The default value is 21.
• FTPs port is a text box for defining the FTPS port. The default value is 990.
Note: In the NETA-21 the FTPS client program is configured to use Explicit TLS
encryption.
• NetBios hostname is a text box for defining the host name for the NetBios service,
which facilitates the access to the NETA-21 with a local name instead of an IP address
in some local network environments. The default value is "NETA-21".

 Proxy settings panel

The Proxy settings panel contains the following components:


• A selection list to set the preferred proxy server operating mode. The options available
are:
• Automatically detect proxy
• Do not use any proxy
• Specify proxy manually
Networks 107

If the user selects to configure the proxy server manually, the desired settings can be
specified in the following fields.
• Proxy server is a text box for defining the address of the server.
• Port is a text box for defining the port of the server.
• Username is a text box for defining the user name to access the proxy server.
• Password is a text box for the password to access the proxy server.
• No proxy for is a text box to list all the IP addresses or domains which can be
accessed directly, without contacting the proxy server.

 Mail servers (outgoing) panel

The Mail servers (outgoing) panel contains the following components:


• Primary server is a text box for defining the primary server for the SMTP service.
• Secondary server is a text box for defining the secondary server for the SMTP
service.
• Port is a text box for defining the SMTP port for the SMTP service. The default value
is 25. Both primary and secondary mail servers have their own ports to be configured.
• Username is a text box for defining the user name for the SMTP service. Both primary
and secondary mail servers have their authentication settings to be configured. The
Username and Password boxes can be left empty if the SMTP server does not require
authentication.
• Password is a text box for defining the password for the SMTP service. Both primary
and secondary mail servers have their authentication settings to be configured.
• Enable SSL encryption is a check box for enabling the SSL encryption for the SMTP
service. Both primary and secondary mail servers have their encryption settings to be
configured.

DHCP
For instructions on setting up a DHCP server, see Connecting a local PC to the NETA-21
in the DHCP server mode.

HTTP/HTTPS
HTTP is the default protocol setting in the NETA-21. To switch from HTTP to HTTPS edit
the address from http://192.168.230.1 to https://192.168.230.1. This can also be done by
selecting the Prefer HTTPS check box in Network services.
108 Networks

Starting up the SMTP configuration


1. Make sure that the NETA-21 is able to access the specified SMTP server over
Ethernet.
2. Go to Settings –> Network services –> Mail servers (outgoing) and set the
appropriate server settings.

3. To check the SMTP settings, click Test SMTP settings, type the test email addresses
and click OK.

If the test succeeds, the following message is shown.

If the test fails, the following message is shown.

If the SMTP settings are correctly configured, the email reporting process is successfully
set up and it is possible to send reports with the NETA-21. See Reporting.
Networks 109

FTP/FTPS
With the NETA-21 you can access the content of the SD memory card remotely if you use
the FTP protocol either through an encrypted or an unencrypted channel.
Go to Settings –> Network services to enable FTP. You can enable either the encrypted
(FTPS) or unencrypted (FTP) connection. FTPS is enabled by default.
You have to create an FTP user account to be able to log on to the FTP connection.
You must have an FTP client to be able to connect to the NETA-21. The following
screenshots are taken from WinSCP, but you can have another client, too.

When you configure the FTP connection, you have to specify the protocol, the URL (or IP
address) of the NETA-21 and the username and password of the FTP account.
If you choose the FTP protocol with No encryption, the default port number is 21. If you
choose the FTP protocol with TLS Explicit encryption, the default port number is 990. You
can customize the ports under Network services.
When you have logged on to the FTP connection, the you see two panes listing the files on
a local computer and the content of the SD memory card.

You can move files from one pane to another with the drag and drop feature.
110 Networks

Dynamic DNS
The NETA-21 provides support for the Dynamic domain name system (DDNS).
The Dynamic DNS service is useful when you have to access the NETA-21 with a dynamic
IP, for example, when the NETA-21 is located in an isolated region where the only network
access is through a 3G modem.

 Using the Dynamic DNS service


1. Go to Settings –> Network interfaces –> Dynamic DNS.

The toolbar of the Dynamic DNS tab contains the following buttons:
• Save button saves the user configuration to the NETA-21.
No external file is generated.
• Reset button discards all changes you have made and resets the fields to default
values.
• Export button exports the DDNS settings to a local file.
• Import button imports the previously exported DDNS settings from a file to the UI.
2. Select the Enable dynamic DNS check box.
3. Fill in the following text boxes:
• Dynamic DNS service: contains a list of all DNS service providers that can be
used.
After you have registered to one of the supported Dynamic DNS service
providers, you get a host name, user name and password.
Networks 111

• Hostname: is the name assigned to the NETA-21.


Host name must be registered at the selected service provider.
• Username: defines the user name for the DDNS service.
• Password: defines the password for the DDNS service.
Now you can access the NETA-21 web interface by using the registered host name.
For example, if you have registered to the dyndns.org service with host name “my-neta-
21”, you can access the NETA-21 with address “my-neta-21.dyndns.org”.

Dial-up function
In isolated regions, the mobile broadband may be the only way to have an Internet
connection. With the dial-up function you can use a USB 3G modem for establishing an
Internet connection to the NETA-21 via the USB port (see section Layout of the NETA-21
and the NEXA-21).
Note: The NETA-21 searches for connected modems via the USB. The modems
connected to the USB port of the NEXA-21 are not detected. The modem must support
either GPRS, EDGE or 3G connections.
The following USB modem models are verified to function correctly with NETA-21:
• Huawei E153
• Huawei E3131 (non-HiLink version)
• Huawei K3715
• Telewell HSPA USB 3G modem
• Vodafone K4505.
Other modems may be detected by the NETA-21 but have not been tested for
compatibility. For example, the connection establishment may not be reliable with untested
modems. The USB modems acting as an Ethernet adapter to a PC (USB modems which
provide a web UI) are not compatible with the NETA-21.
The dial-up function is located on the Dial up tab under Network interfaces.
112 Networks

The toolbar contains the following buttons:


• Save button saves the changes to the NETA-21.
• Reset button discards all changes you have made.
• Export button exports the modem settings to a local file.
• Import button imports the modem settings from a file to the UI.
• Test interface does the ping test with a defined URL.
The Modem settings panel contains the following components:
• Select modem is a drop-down list for selecting the installed modem.
• Connection type shows the connection type of a modem.
• Search button detects the installed USB modems.
The General settings panel contains the following components:
• Pin code text box is for the PIN of a SIM card.
• Test button verifies the PIN.
• Modem info button provides additional information about the modem.
The Dial up and GPRS settings panel contains the following components:
• Enable dial up is a check box for selecting the dial-up function.
• Host to ping is a text box for the defined URL needed in a ping test.
• Ping timer is a text box for defining the PING operation delay.
• Access point name is a text box for defining the access point name of the provider to
access the Internet
• Phone number is a text box for a phone number.
• Username is a text box for the user name needed if the modem service is enabled.
• Password is a text box for the password needed if the modem service is enabled.

 Using a mobile broadband connection


1. Plug the USB 3G modem into the USB port.
2. Go to Settings –> Network interfaces –> Dial up.
3. Select the modem from the Select modem drop-down list.
Networks 113

If the modem is not already available in the list, click the Search button.

4. Select the Enable dial up check box.


5. Type all necessary information in the Dial up and GPRS settings panel.
6. Click the Save button.
7. Click the Events tab to check that the Internet connection has been established.
114 Networks
Events 115

12
Events

What this chapter contains


This chapter describes how to observe and filter events.

Universal event list


The Event tab is virtually omnipresent in the UI. The contents of the tab may vary slightly
in different views. The following figure shows the Event tab under Home. This tab shows
all events.
The past events of the monitored device are grayed out.
By default all events are sorted by the occurrence of the event. Device events, however,
are sorted by the device-specific time.
116 Events

The tab contains the following components:


• Refresh button updates the contents of the tab.
• Filter events button opens and closes the Event filter panel at the bottom of the view.
• Show local/relative/device timestamp check boxes add columns showing the
local/relative/device time for the events:
• Local time column shows all time values according to the local time of the NETA-
21
• Relative time column shows all time values in a relative format, for example 3
days 3 hours ago
• Device time shows all time values according to the time set in the device.
• Export button exports all the events and data logger data to a .ZIP file.
• Clear filtering button clears any filtering that has been performed for the event list.
This button will be disabled if no events have been filtered. Filtering is available by
clicking on event list column titles.
Note: Filtering is applied only on the web browser side and for the visible (usually 100
latest) events only. Filtering can empty the event list even if there were matched
events in the event storage of the NETA-21 (in an older event history).
Events 117

 Contents of the non-universal event list


The non-universal event lists do not show all events. For example, the Event tab under
Devices shows only device-related events.

Filtering settings by columns


The filtering criteria can be set separately for each column. In the heading row of the event
list there are arrow icons opening a menu for setting the filtering criteria for each column.
118 Events

The event list contains the following column headings:


• Event ID column shows the event ID number. The column can be sorted with a
numeric filter (less or more than or equal to the event ID number). The column is not
visible by default.
• Name column shows the event name. A balloon icon is shown if the event contains
comments. The column can be sorted with a search text box.
• Local time column shows when the event has happened. Device events are
synchronized with the NETA-21 clock.
• Relative time column shows how much time has passed since the event has
happened. You can use the following filters: Before, After or On.
• Device time column shows the event time from the device itself.
The device time can represent a run time counter for some drives. The device time is
only available for faults and warnings originating from a monitored device.
• Category column shows the event category. The column can be sorted with a search
text box.
• Source column shows the source of the event. The column can be sorted with a
search text box.
• Severity column defines the severity (or type) of the event. The menu has the
following filtering criteria: Detail, Notification, Warning, Fault and Severe.
If there is an attachment for the event, the attachment can be exported by clicking the icon
with an orange arrow.

To select the page, use the toolbar at the bottom of the Event tab.
Events 119

Filtering settings through the Event filter panel


The event list can be sorted by defining the filtering criteria with the Event filter panel.The
Event filter panel is opened by clicking the Filter events button.
Note: The Event filter panel provides more accurate search results than column filter and
search options, because it initiates a search within the web UI server. Column filters only
search within the visible data items (for example the 100 latest events).

The Event filter panel contains the following components:


• Number of events in page spin box defines the number of events shown in a single
page. The values can range from 10 to 200. The default value is 100.
• Show events after has two boxes with which the date and time can be defined for
events occurring after the selected timestamp. The boxes can be empty.
• Show events before has two boxes with which the date and time can be defined for
events occurring before the selected timestamp. The boxes can be empty.
• Sort by drop-down lists define the sorting column and sorting direction. The default
setting is Event ID in ascending order. The latest added events appear at the top of the
event list, even if the event timestamps are not in chronological order.
The first Sort by drop-down list contains the following items:
• Event ID
• Starting time
• Category
• Severity.
The second drop-down list contains the following items:
• Ascending
• Descending.
• Category box contains all available categories with check boxes. The categories have
sub-categories. The categories are selected and unselected by clicking the check
boxes. Under Settings the Category box in the Event filter panel shows only the pre-
defined categories. In general all the categories are shown and selected by default.
• Severity box contains the types of events with check boxes. The icon representing the
severity of the event is shown next to the text. By default, all types are selected except
Detail. If no type is selected, the types are not prioritized at all. The box contains the
following types:
• Detail
• Notification
• Warning
• Fault
• Severe
• Filter events button makes the query to the server. After the query has succeeded,
the Event filter panel is hidden and the list of events is updated. If events do not fit to
120 Events

a single page, the toolbar at the bottom of the Event tab can be used for changing
pages.
Reporting 121

13
Reporting

What this chapter contains


This chapter describes how to make reporting and trend logging settings for configuring
which time levels and event categories are sent out by a reporting plug-in.
The tabs under Reports are described from left to right.

Introduction to reporting
With the NETA-21, reporting means that parameter values or event data of a drive or
several drives connected to the NETA-21 are sent periodically to the users. The NETA-21
reporting provides many ways to save or send the report. The NETA-21 supports the
following reporting methods:
• Email reporting – reports are sent via email
• SD card reporting – reports are saved to an SD card
• FTP reporting - reports are transferred to an FTP server.
• SMS reporting - reports are sent as SMS messages.
The NETA-21 can be configured to send reports based on triggers. The triggers can be
time intervals, values of some parameters or drive events such as faults or warnings.
For example, it is possible to save all or some parameter values periodically to an SD card
or to upload them to an FTP server. In addition, you can configure the NETA-21 to send
emails when a drive enters a faulted state. By default the NETA-21 stores all changed
parameters and drive events to an SD card daily.
In email reporting it is possible to create a custom report format.
122 Reporting

Configuring the NETA-21 for reporting


To configure the NETA-21 for reporting, specify the logging intervals of the parameters
needed in the report:
1. Go to Reports –> Parameter history logging.

2. Click a parameter and select the interval in the Parameter properties panel.
Reporting 123

The following intervals are available:


• Day
• Hour
• 5 Minutes
• Minute
• Continuous monitor
• None (in other words, no logging)
The Continuous monitor logging interval was added in firmware 2.20.
If you want to set the intervals for several parameters simultaneously, go to
Reports –> Parameter history logging –> Parameter properties –> Interval. For
more information, see Parameter logging interval templates.
124 Reporting

Creating an email report


To be able to use the email reporting, you must configure the SMTP settings. See section
Network services.
Make sure that you have set the logging intervals for the parameters (Reports –> History
logger). If you have not set the logging intervals for the parameters, the reports will have
no data.
1. Go to Reports –> Settings and click the Add button.
2. Select E-mail reporting from the drop-down list.

Now the new report has been added to the list of reports.
3. Define the general settings of the report, such as report name and reporting trigger.
See section Setting the report trigger.
4. When you have named the report and selected the trigger, click the Reported data
sub-panel.
Here you can select the data to be reported. See Setting the reported data.
5. Click the Output settings sub-panel and define the settings.

• Enable report is a check box for enabling the email reporting.


• Report output format is a list for defining the template used in the report.
• From address is a text box for defining the sender.
Reporting 125

• To address is a tex box for defining the email recipient.


To send an email to several recipients, separate the email addresses with a
comma or semicolon.
• E-mail subject is a text box for defining the subject of the email.
• Site identifier (default: serial no. of tool) is a text box for defining the identifier
used in the reports.
6. Click the Create report button.
To check that the report has been successfully sent, go to Reports –> Report events.
If no report has been sent, check the network and email settings.

 Format of the email report


The reported data is shown in the email message body.
If you have selected an XML format, the email report looks like the following example:

If you have selected a plain text format, the email report looks like the following example:

You can create a custom format by using the report scripting section in an email report. For
more information, see section Using scripting for email reports (custom report).
126 Reporting

Creating an SD card report


The NETA-21 contains three default reports: Parameter history to SD card, Event report
to SD card and Backup all connected drive parameters to SD card monthly. These
reports update values.db and events.db databases to the SD card when new data is
logged (before firmware 2.22, .csv and .log files were stored daily by default). You can
modify or remove pre-defined reports or define additional reports to the SD card.
Make sure that you have set the logging intervals for the parameters (Reports –> History
logger). If you have not set the logging intervals for the parameters, the reports will have
no data.
1. Go to Reports –> Settings and click the Add button.
2. Select SD card reporting from the drop-down list.
Now the new report has been added to the list of reports.
3. Define the general settings of the report, such as report name and reporting trigger.
See section Setting the report trigger.
4. When you have named the report and selected the trigger, click the Reported data
sub-panel.
Here you can select the data to be reported. See Setting the reported data.
5. Click the Output settings sub-panel and define the settings.

• Enable report is a check box enabling the SD card reporting.


• Folder path is a text box for specifying the location of the reports on the SD card.
If there is no folder, it will be created automatically. The default folder path is the
serial number of the NETA-21.
• Cleaning of SD card is a list for enabling the cleaning of an SD card when the SD
card is full or, alternatively, for stopping the reporting.
Reporting 127

• Store to memory card as is a selection list for specifying the formats to save
reported data and events. The available options are:
.csv and.log files
.db database (SQLite)
6. Click the Create report button.
To check that the report has been successfully sent, go to Reports –> Report events.
Note: If the report does not appear on the SD card, check that the SD card is not full.

 Format of an SD card report


SD card reports can be stored in the CSV or SQLite format.
From firmware version 2.22 onwards, the SD card reports are in the SQLite format. SQLite
files with parameter values have extension .DB and event data reports have extension .log
(or .evt in earlier firmware revisions prior to firmware revision 2.20).
Until firmware version 2.21, the SD card reports were in the CSV format. CSV files with
parameter values have extension .CSV.

CSV-formatted reports
Each report is created in a sub-folder of the folder specified in the Output settings sub-
panel. The folder structure is: SD:/report/Folder path in Output settings/Year/Month/Day/.
The report file names on the SD card follow format <ddhhmm>[_<n>] where <ddmmss>
indicates the day of the month, hours and minutes. An optional numeric posfix "_1", "_2",
"_3" ... "10", "11" ... "99" is added if multiple log files are written during one minute.
128 Reporting

The SD card report for logged data looks like in the following example. An event report
looks similar except that there are more event-specific columns beginning with an
ampersand “&”.

DB-formatted reports
SQLite files have extension .db. You can view the content of the files with any SQLite file
viewer, for example, with SQLite Database Browser. You can also use SQLite Manager
as an extension for the Firefox web browser.
The SQLite file looks different for an events report and a parameters report.
The SQlite file of an events report is always stored to a file named events.sb and contains
the following kind of data:.

The SQLite file of a parameters report contains three tables: parameters,


sqlite_sequence and value_cache.
The parameters table contains the list of parameters stored in the report.
Reporting 129

The value_cache table contains the values read for the parameters.

Note: The timestamp column indicates time in microseconds since the 1st of January
1970 (so called Unix time except with microsecond precision).

Creating an FTP report


Make sure that you have set the logging intervals for the parameters (Reports –> History
logger). If you have not set the logging intervals for the parameters, the reports will have
no data.
1. Go to Reports –> Settings and click the Add button.
2. Select FTP reporting from the drop-down list.
Now the new report has been added to the list of reports.
3. Define the general settings of the report, such as report name and reporting trigger.
See section Setting the report trigger.
4. When you have named the report and selected the trigger, click the Reported data
sub-panel.
130 Reporting

Here you can select the data to be reported. See Setting the reported data.
5. Click the Output settings sub-panel and define the settings.

• Enable report is a check box enabling the FTP reporting.


• Create folders is check box for enabling the creation of a new folder.
• Send also empty reports is a check box to allow sending of reports even when
there hasn't been any change to report.
• Report output is a selection list which specifies content of the report. Available
options are:
Send events and attachments
Send only events
Send only attachments
• Report file name is a text box for defining file name of the report.
• Folder path is a text box for defining the path to the folder in which the report is
created.
• Server type is a selection list to specify the type of the server where the reports
will be sent. Available option are:
FTP
FTPS
• Hostname is a text box for the address of the host provider.
• Port is a list for setting the port via which the FTP connection is carried out.
• Number of retries is a list for defining the number of retries during communication
breaks.
• Username is a text box for the name of the account user.
• Password is a text box for the password needed to a verified connection.
6. Click the Create report button.
To check that the report has been successfully sent, go to Reports –> Reported data.
Reporting 131

 Format of an FTP report


The FTP reports are in the CSV format. CSV files with parameter values have extension
.CSV and event data reports have extension .log (or .evt prior to firmware revision 2.20).
Each report is created in a sub-folder of the folder specified in the Output settings sub-
panel. The folder structure is: /Folder path in Output settings/Year/Month/Day/. Each report
has a unique name with a time stamp.

Creating SMS report


Make sure that you have set the logging intervals for the parameters (Reports –> History
logger). If you have not set the logging intervals for the parameters, the reports will have
no data.
1. Go to Reports –> Settings and click the Add button.
2. Select SMS reporting from the drop-down list.
The new report is added to the list of reports.
3. Define the general settings of the report, such as report name and reporting trigger.
See section Setting the report trigger.
4. Click the Reported data sub-panel and select the data to be reported. See Setting the
reported data.
5. Click the Output settings sub-panel and define the settings.
132 Reporting

• Enable report is a check box to enable the SMS reporting.


• Report output format is a selection list which specifies the format of the report.
Available options are:
Default
Custom - Enables report scripting. For details about Report scripting, see chapter
Using scripting for SMS reports (custom report) on page 143.
• Phone number is a text box to specify the phone number to which reports needs to be
sent.
• Default SMS message is a text box to specify the format of the report message. The
default message uses certain variables from the predefined SMS report script.
• Number of messages per day is a list to define the maximum number of SMS
messages per day, which is limited to 100.
• Site identifier is a text box to define the optional name for the site. By default, the
serial number of NETA-21 is added as site identifier.
6. Click the Create report button.
To check that the report has been successfully sent, go to Reports –> Report events.
If no report has been sent, check the network and SMS settings.
Reporting 133

Setting the report trigger


1. To define the report trigger, go to Reports –> Settings –> Reports –> New report –>
General settings.

2. From the Report trigger list, select the frequency for the report generation:
• Every 5 minutes
• Every hour
• Every day
• Every week
• When new data available
Parameter has a new value or there is a new event.
• Any device state changed
Status of any of the drives has changed.

Note: You can select the statuses to be monitored.


134 Reporting

• Device state changed


Status of a particular drive has changed.

Note: You can select the drive to be monitored.


• Parameter value
Value or another parameter can be specified as a basis for comparison.
Bitmask is ANDed to the original value before comparison.

• Event
Name, category and severity of an event can be specified as a basis for
comparison.
Reporting 135

Setting the reported data


1. To define the data type for the reports, go to Reports –> Settings –> Reports –> New
report –> Reported data.
2. From the Data type drop-down list, select the desired data type.

The available Data type options are:


• Event - To report events according to severity and category.
• Logged data - To report all parameters according to the logging interval defined in
section Configuring the NETA-21 for reporting.
• Custom - To specify the custom data from the Reported custom data list.
From the Reported custom data drop-down list, select the desired Reported custom
data type:
The available options are:
• Customized report script - To report an event of a given severity with a specified
name every time the event occurs, and optionally allows you to define your own
reporting script.
• Parameter export - To report all parameters of a particular drive.
• Parameter export of all devices - To report all parameters of all connected
drives.
• Import settings -To restore the settings defined with the backup and restore
function, see chapter Backup and restore on page 157.
• APBU upload -To report the selected logger (First, Last, User) data from the
APBU logger at the given node id.
136 Reporting

3. To preview the contents of the report, click the Preview data… button.
• On selecting the data type Event, the content of the report appears as shown in
the below figure:

• On selecting the data type Logged data, the content of the report appears as
shown in below figure:
Reporting 137

Changing the reporting name


You can customize the reporting name for each connected device. The reporting name
and the optional reporting name are added as a prefix to the logged signal names, if you
have selected so (Reports –> Settings –> Signal names –> Settings, see Changing the
default naming of signals).
1. Go to Reports–> Devices and click the row of the device which you want to rename.
2. Type the new name to the Reporting name text box.
3. Click Apply changes.

To update the device list, click the Refresh button.


From firmware version 2.20 onwards, you can customize also other device-specific
reporting attributes, for example the serial number and device type. Editable attributes
depend on a specific device.
138 Reporting

Changing the default naming of signals


There are two locations where you can manually name each trend-logged parameter
value: Parameter browser tab under each monitored device and History logging tab
under Reports.
If you have not typed in any customized name for the trend-logged variables, the default
naming is used for the parameters.
1. To define how the NETA-21 names the trend-logging variables by default, go to
Reports –> Settings–> Signal names –> Settings.

2. From the Default signal name list, select one of the following options:
• Group and parameter number provides the parameter with a name such as
"03_02" (default setting prior to firmware version 2.20)
• Parameter name provides the parameter with a name such as
"main_status_word"
• Parameter group, number and name is a combination of the two options above,
for example, 03_03_main_status_word (default setting from firmware revision
2.20 onwards).
3. Optionally, define a prefix for each device reporting name in the Device reporting
name prefix text box.
4. If you select the Include device reporting name in default signal name check box,
the device reporting name set under Devices tab is prefixed to the signal name.
The example of the default name is shown in the Settings panel.
Reporting 139

Parameter logging interval templates


Use log intervals (Reports –> Settings –> Parameter logging interval templates ->
Settings –> Logging interval templates) to modify the logging intervals of multiple
parameters simultaneously instead of modifying the logging interval of parameters one by
one via the Parameter history logging tab.
With the log intervals function you can also bulk-change certain other attributes related to
parameters and reporting such as the reported parameter names and only the Log only
when changed selection on the parameter specific logging settings. All available logging
interval templates are matched to all connected monitored device parameters when the
Apply changes button is clicked. Templates are applied to newly connected devices also
when any new monitored device is connected to the NETA-21 (and after the device
interface has been reset to the default settings).

Use the Send template to tool… button to save a new template file to the NETA-21.
Under the Logging interval templates heading you can see the list of saved templates. If
you click the Run templates button, you can check some of the saved templates.
The Delete template button deletes the currently focused template file from the NETA-21.
The Run templates button runs the selected templates (all template files on the Logging
interval templates list which have been selected).
From firmware 2.22 onwards there is also a button to option Export template from
device… which shows a pop-up window with a drop-down list of all connected drives:

Select a device and click OK to export the currently selected configuration settings for the
parameter logging from the connected device into a file on a PC. The file can be edited
and imported (sent) to other NETA-21 tools.
140 Reporting

A sample content of a logging interval template file is shown below:

• device_attributes is a list of drive attributes that determine the drives to which the
template is applied.
• Possible attributes are: category for the category of the device, sw_pkg for the
SW package, sw_appl for the SW application.
• Values for these attributes are usually shown on the device front page and you
can use wild cards, for example, *(asterisk).
• If you do not specify any attributes, the template is applied to all devices.
• rules is a list of rules that define the parameters and values.
• param_id defines the index of the logged parameter, eg, "12.34
• unit defines the engineering unit of the monitored parameter, eg, "V" or "mA"
• either param_id, unit or both rules must be specified or the specific rule will not be
applied to any parameter.
• interval, signal_name and log_only_when_changed specify values that are applied
to the log interval of time, signal name and the Log only when changed selection of
the previously specified parameters.
• interval can be one of these values: “monitor”, “minute”, “5minutes”, “hour”, “day”
and “none”.
• signal_name can be any valid string.
• log_only_when_changed is true or false.
• from firmware 2.23 onwards, you can set fallback to true or false. By default the
fallback is false. If the fallback is set to true and there is a parameter that does not fit to
the primary interval (interval attribute), the NETA-21 tires to set the logging interval of
a matching parameter to the next available (lower frequency) interval during the
template run. It is possible that all intervals are fully used, in which case the parameter
is not logged at all.
• from firmware 2.23 onwards, priority can be set to 1 or 2 (default: 2) and the setting is
used to define whether the parameter interval setting overrides the intervals in other
templates.
Reporting 141

The following is an example of the logging intervals template that applies an interval of 1
minute to parameter 01.01:

The following is an example of the logging intervals template where the reported signal
name of parameter 01.01 is changed to “percentage” only when the unit of the parameter
is %:

 Changing the continuous monitor interval


In firmware 2.23 you can configure the default interval for continuously monitored
parameters (default: 5 s). You can set the value between 1 s and 30 s. To configure
the interval of Continuous monitor logging, go to Reports -> Settings -> Continuous
monitor -> Settings.
142 Reporting

Using scripting for email reports (custom report)


To see the scripting panel of email reports:
1. Go to Reports –> Settings –> Configured Reports –> New report –> Settings ->
Output settings.
2. Select Custom from the Report output format drop-down list.
3. Click Report scripting sub-panel.

The Report scripting sub-panel contains the following components:


• Preview report button displays a Preview dialog box which contains a report
generated by the currently visible script. The report is generated by using a
predefined data. If the script contains an error, an error is displayed in the preview
dialog box.
• Predefined scripts is a drop-down list with three options: Custom report, XML
report and Plain text report. If you select a predefined script from the list, the
script editing text box shows that specific predefined script.
• Script editing text box contains a script which is used for generating parameter
and event reports. If you have modified the content of a predefined script and want
to restore the predefined script, select an appropriate form from the drop-down list
and click Restore defaults.
Notes:
• JavaScript language is used to form the email output. You can modify the report
scripting code and can use the template scripts to produce XML and CSV formatted
outputs.
• Editing an invalid JavaScript code can lead to interruption in reporting. If the reporting
freezes completely as a result of an invalid script, you need to restart the NETA-21.
Before restarting the NETA-21, choose a pre-defined reporting template and save the
report settings.
• You need to use the provided code templates as detailed programming guide on the
report scripts is not available.
Reporting 143

Using scripting for SMS reports (custom report)


To see the scripting panel of SMS reports:
1. Go to Reports –> Settings –> Configured Reports –> New report –> Settings ->
Output settings.
2. Select Custom from the Report output format drop-down list.
3. Click the Report scripting sub-panel.

The Report scripting sub-panel contains the following components:


• Preview report button displays a Preview dialog box which contains a report
generated by the currently visible script. The report is generated by using a
predefined data. If the script contains an error, the error is displayed in the preview
dialog box.
• Predefined scripts is a drop-down list and includes SMS report option. On
selecting the predefined script, the script is displayed in the script editing text box.
• Script editing text box contains the script which is used for generating reports. If
you have modified the content of a predefined script and want to restore the
predefined script, select the appropriate form from the drop-down list and click
Restore defaults.
The JavaScript language is used to format the email output. You can modify the report
scripting code. Editing of an invalid JavaScript code can lead to stoppage of all reporting. If
the reporting freezes completely as a result of an invalid script, you may have to restart the
NETA-21. Before restarting the NETA-21, choose a pre-defined reporting template and
save the report settings.
Use the provided code templates, since there is no detailed programming guide on the
report scripts available.
144 Reporting

Description of the tabs under Reports


There are five tabs under Reports: Settings, Devices, Parameter history logging,
Reported data and Configuration events.

 Settings tab
You can define which reporting plug-in is used in reporting when a log segment ends. For
information on the customizable reports, see Introduction to reporting, Creating an email
report, Creating an SD card report and Creating an FTP report.

The Settings tab contains the following components:


• Refresh button refreshes the contents of the parameter list.
• Add button adds a new report to the list of reports. The button is enabled only when
the Reports folder is selected.
• Remove button removes the selected report.
• Export button downloads the saved settings of the selected report.
• Editor panel means the area appearing on the right-hand side of the Settings tab
when you have selected one of the items on the left-hand side of the Settings tab.
• Import button imports a report from a file to the NETA-21. If the imported report has
the same name as an existing report in the NETA-21, then the report in the NETA-21 is
overwritten with the file.
• Help button opens a dialog box providing information about the settings of the view.
• Tree structure shows all active reports and available settings. When an item is
selected, the Settings panel appears on the right-hand side of the Settings tab.
Reporting 145

 Devices tab
On the Devices tab, you can see all connected devices. There are the following three
columns:
• Device id: the internal name of a device.
• Device name: the name assigned to a device.
• Reporting name: the name used in reports for a device.

If you click a device, you can customize the reporting name of the device in a right-hand
side panel. From firmware version 2.20 onwards, you can customize also other device-
specific reporting attributes.
Use the Refresh button to refresh the device list.
146 Reporting

 Parameter history logging tab


The Parameter history logging tab shows the drive signals to be reported. By default all
signals are checked for changes daily. Only changes are saved and reported to the SD
card.

The tab contains the following components:


• Refresh button refreshes the contents of the parameter list.
• Interval selection drop-down list shows the logging intervals.When you select an
interval, the contents of the parameter list are updated. The following intervals are
available:
• All
• Minute
• 5 minutes
• Hour
• Day
• Continuous monitor.
• Capacity shows the number of parameters in the selected interval. The maximum
number of allowed monitored parameters per time interval are as follows:
• 1 minute – max. 100 parameters
• 5 minutes – max. 500 parameters
• 1 hour – max. 1000 parameters
• Day – max. 10000 parameters
• Continuous monitor – max. 20 parameters.
Reporting 147

• Parameter list shows all parameters in the selected interval. Multiple parameters can
be selected at the same time. If at least one parameter is selected, the parameter
properties panel is shown. The following columns exist:
• Parameter name
• Parameter group
• Device name
• Device id
• Interval.
• In the Parameter properties panel you can customize the logged signal name and
logging interval and select that logging is done either always or only when the signal
value has changed.

There are different ways to select multiple parameters:


• With the check boxes on the left of the parameters; add or remove parameters one by
one by clicking the check boxes
• To cancel the selection, click anywhere else in the row.
• With the Ctrl key; press the Ctrl key and click the rows you want to select.
• With the SHIFT key; hold down SHIFT and click the first and last rows of the selection.
To change the interval of parameters, select the parameters, choose the appropriate
interval from the drop-down list and click Apply changes. If you select multiple
parameters, you cannot edit the signal name and the signal logging history is not shown.
148 Reporting

The available intervals are:


• Minute
• 5 minutes
• Hours
• Day
• None
• Continuous monitor.
• In firmware 2.21 the logging interval for Continuous monitor is 1second. In
firmware 2.23 the logging interval is adjustable between 1 … 30 s and the default
value is 5 seconds.
The signals are logged only if their values have changed. If the Log on when changed
check box is unchecked, the values are logged even if they have not changed.

 Report events data tab


To see all sent reports and those errors that may have occurred after reports have been
created and sent, go to Reports –> Report events. The reports are sent to the email
address defined in section Creating an email report.
Reporting 149

 Configuration events tab


To see all the modifications made to reporting settings, go to Reports –> Configuration
events. The events can be filtered and sorted.
150 Reporting
Tools 151

14
Tools

What this chapter contains


This chapter explains how to manage NETA-21 firmware, factory settings and software
packages and introduces other useful tools.

Tool firmware
The Tool firmware tab (Settings –> Tool settings) shows the installed firmware version
of the NETA-21 and enables to update the firmware of the NETA-21.

Note: The NETA-21 firmware updates require an SD card with a minimum of 200 MB free
space.
The Tool firmware tab contains the following components:
• Save button saves the firmware update settings to the NETA-21.
• Reset button discards all changes made to the firmware update settings.
• Send to tool button opens a file browser for sending a firmware file to the memory
card. Firmware files to be uploaded must have the following name format:
152 Tools

FMZAAvrr.NTU, where vrr represents a 3-digit version number (letters can be in upper
or lower case).
• Check updates button connects to ABB Download Center and checks for new NETA-
21 firmware releases. If a new version is found, it is downloaded and installed to the
device.
• Reboot tool button reboots the NETA-21, which triggers the software update if new
and selected firmware upgrade exists in the memory card. You are prompted to reboot
the NETA-21 after clicking the Reboot button.
• System information panel shows tool-specific information. The panel contains the
following fields: Remote monitoring tool type, Remote monitoring tool serial number,
Installed software, Software build version, MAC1 address and MAC2 address.
• Tool firmware updates panel shows all available firmware updates on the SD card.
The changes are saved and firmware installation settings are modified when you click
the Save button. The unchecked firmware files whose version number is not greater
than the version number of the currently installed firmware file are blacklisted and not
installed during the next reboot.
• Firmware column shows the file name of the file. The column contains also a check
box for defining whether the firmware update should be installed in the next reboot (if
the file is not checked, then NETA-21 does not try to install it). The check box is
disabled if the firmware is older than the current firmware or if it is the current firmware.
• Description column shows the status of the firmware update. The following conditions
may be seen:
• Old firmware is shown if the currently installed software is newer.
• Currently installed is shown if the file version equals to the currently installed
software.
• Non-installable is shown if the running OS version is factory-loaded (FMZALvrr)
and the same version as the update package (FMZAAvrr).
• Installation failed is shown if the number of the running OS version is smaller and
updating has failed.
• Not chosen to be installed is shown if the number of the running OS version is
smaller and the file is not checked.
• Install on next reboot is shown if the number of the running OS version is smaller
than the number of the currently installed firmware version. The NETA-21 tries to
install the OS during the next reboot.
Tools 153

Factory tools
Factory tools tab provides an option to reset the NETA-21 to factory settings, and an
option to disable (or keep enabled) the factory support account.

The Factory tools tab contains the following components:


• Save button saves the settings. If the restore factory settings check box is selected,
you are prompted to reboot the NETA-21.
• Reset button discards all changes made to the settings.
• Export button exports the settings to a local file.
• Import button imports the settings from a file to the UI.
• Reboot button reboots the NETA-21.
• Enable SSH is a check box for enabling or disabling secure shell service on TCP port
22.
• Enable factory login is a check box for enabling or disabling the web UI factory
support user (user account "_factory"). Each NETA-21 has an individual factory user
account for remote service and support purposes. You can disable the factory user
account completely by unselecting this option.
Note: The factory user account can be disabled if strict security is needed, but the
deletion of the account affects the installation of extra software packages and remote
support functionalities. In addition, if this option is disabled, the IP address will not
work after a system has fully rebooted. The NETA-21 contains a factory support
account for the web UI and for SSH remote connections. Factory account passwords
are unique to each NETA-21.
• Disable extra package installation (ips) from external media (USB, SD card) is a
check box for enabling or disabling external package (*.ips) installation from external
media such as USB drives or SD card.
• Disable settings import from external media (USB, SD card) is a check box for
enabling or disabling device settings (*.baj) package installation from external media,
such as USB drives or SD card.
Note: After changing the check box status, you should restart NETA-21 for the
changes to take effect.
• Restore factory settings is a check box for removing all user data from the NETA-21
during the next reboot. To restore the factory settings, select this check box, save the
settings using the Save button and finally click the top-right corner Reboot tool
button.
154 Tools

 IP address after a factory reset


From firmware 2.22 onwards, the NETA-21 shows the following dialog box when you want
to reboot the NETA-21:

If you select Store Ethernet IP address settings to keep_ip.mod file on memory card,
the NETA-21 tries to keep any previously defined fixed IP address configuration over a
reset. The current network interface configurations are saved to a file on the SD memory
card. The freshly initiated (factory resetted) firmware should be able to read the previous
network interface configurations and take those into use. The keep_ip.mod and any
existing restore.log or restore.n21 files should be removed from the SD memory card root
folder after a factory reset to optimize the boot-up mode and to enable similar functionality
in future.

Packages
The Packages tab enables to install and uninstall packages from the NETA-21. All core
packages are filtered from the list so that you cannot uninstall any vital packages from the
NETA-21.
You must have a Tool admin role (administrator) to access this view. This tab can only be
used to install signed packages with an IPS file extension.

The Packages tab contains the following components:


• Refresh button refreshes the package list.
• Install button opens a file selector for an IPS package. After a file has been selected,
the file is sent to the NETA-21 and installed. IPS packages are signed extra software
packages provided by ABB.
• Uninstall button is enabled only if a package has been selected from the package list.
When you click the button, you are asked to confirm the uninstallation before the
NETA-21 starts uninstalling the package.
• Package list shows all installed packages in the NETA-21 excluding all packages that
are necessary to the functioning. The package list contains the following columns:
Name, Version and Installed.
Tools 155

Using ABB IP Configuration Tool


ABB IP Configuration Tool detects all the NETA-21 remote monitoring tools in the network.
The tool can be downloaded separately from www.abb.com, but it also comes bundled
with ABB Control Builder Plus, the IEC 61131-3 programming environment for ABB PLCs
and drives.
Use the tool, for an example, when you no longer know the IP address of the NETA-21 or
when you do the initial set-up.
If you have the ABB Control Builder Plus 2.3.0 build 312 or newer installed, do as follows:
1. Launch the tool from Tools –> IP-Configuration.

2. Start the scanning process by clicking the Scan button:

If no devices are found, make sure that your firewall does not interfere with the
scanning process. Disable your firewall and try again.
All devices found during the scanning process are presented in a table where each
device is in a separate row. In addition to the IP addresses of the device you can also
see the MAC address, device name, serial number and device ID information.
156 Tools

In older Control Builder Plus 2.3.0 builds (for example build 252), ABB IP Configuration
Tool is a separate program. Go to Start –> ABB –> ABB IP Configuration. However, the
older version of ABB IP Configuration Tool gives the same information:
Backup and restore 157

15
Backup and restore

What this chapter contains


The backup and restore function enables the replication of the NETA-21 settings to
another similar type of remote monitoring tool. There are two main backup types: full
system backup and backup of the selected settings only.

Backing up the NETA-21


1. Go to Settings –> Backup and restore and select the backup type.

Note: You must have an SD/SDHC card installed into the SD slot to create a backup.
The SD card must have a minimum of 200 MB free space to enable the
backup/restore functions. Backup and restore files are stored in the BACKUP folder on
the SD card.
Create backup creates a backup according to the selected backup type.
158 Backup and restore

Full system backup enables a full system backup of the NETA-21. The NETA-21 is
rebooted before the backup file can be downloaded. After the NETA-21 goes back
online, you must log on to the NETA-21. After you have logged on to the NETA-21, the
Backup tab is shown and the NETA-21 starts sending the backup file to the PC.
Settings backup enables a backup of selected data categories. You can select the
following data categories:
• Device information
• Device interface settings
• Network service settings
• Users
• Locale settings
• User interface settings
• Logging settings
• Reporting settings
2. Click the Create backup button.
The following dialog box appears.

If you have chosen the Settings backup type, the Making backup pop-up window
appears.

3. If a reboot is required after a backup has been created, log on to the NETA-21 to
enable downloading when the system is back online.
Backup and restore 159

Restoring the NETA-21


1. Go to Settings –> Backup and restore –> Restore.

The Restore file function restores a selected file. If restoring requires rebooting (full
system restore), you are prompted to reboot the system. If you choose to reboot the
NETA-21, the reboot view is shown. When the server goes back online, you are
redirected to the Login window and eventually back to the Restore tab.
To restore the files stored in the SD card, select the Select an existing file from the
memory card check box.
2. Click the Restore file button.
The following dialog box appears.

If you select Store Ethernet IP address settings to keep_ip.mod file on memory


card, the NETA-21 tries to keep any previously defined fixed IP address configuration
over a firmware restoration. The current network interface configurations are saved to
a file on the SD memory card. The freshly initiated (factory resetted) firmware should
be able to read the previous network interface configurations and take those into use,
if the restored firmware is 2.22 or later.
The keep_ip.mod and any existing restore.log or restore.n21 files should be removed
from the SD memory card root folder after a system has rebooted to optimize the boot-
up mode and to enable similar functionality in future.
160 Backup and restore

If the file is a Settings backup file, a progress dialog box appears showing the status of
the settings importation.

Note: If the restore file contains different network interface settings (for example IP
addresses for Ethernet interfaces), the connection to the web UI can be lost after the
restore function has been started. The new IP address settings depend on the file restored
to the NETA-21.
Security 161

16
Security

What this chapter contains


This chapter describes about the RADIUS (Remote authentication Dial-In User Service)
authentication feature in NETA-21.

Applicability
The central RADIUS authentication feature is available from firmware version 2.30 or later.

Advantages
On a large network each NETA-21 does not need to have user accounts and passwords
defined separately for all users. Instead, with the RADIUS authentication feature, the user
accounts and password policies can be managed centrally. This helps to increase the
cyber security of the web interface.

Features
The RADIUS authentication supports two protocol variants:
• Basic/RFC2865
• EAP-TTLS (RFC5281)
162 Security

accounts
RADIUS

User
authentication
server in
network

RADIUS-protocol
Basic (RFC2865)
EAP-TTLS (RFC581)

NETA-21 module

Username,
DataHub with
Web browser Password, HTTPS frontend
internal settings
(HTML / Javascript) Auth.method (HTTP not

RADIUS server setup,


allowed RADIUS user
and local user

Local DB (settings,
Login dialog (as plaintext) recommended)
accounts

name filter)
Over HTTPS

Notes
• The external user and password information is transmitted as plain text during
RADIUS login. Use HTTPS login as an alternative to HTTP.
• The local logins does not perform hashing of the password in external RADIUS login.
Hence, HTTPS / TLS encryption is used for password encryption.
• Local user accounts can be left active on side of the external RADIUS user accounts.
Local accounts should have strong passwords. In cases when RADIUS server is
unreachable (e.g. due to lost network connection), local login will be enabled once per
failed RADIUS login even if the local logins are disabled.

Protocol level implementation for RADIUS


On protocol level, NETA-21 sends a RADIUS access request to RADIUS server with
attributes as follows:

Attribute name Attribute ID Value

Vendor-ID 56 “ABB” (ID 100)

Vendor-Sub-Type 57 “Drives” (ID 101)


Security 163

Example of RADIUS Access-Request packet sent by NETA-21 is shown in the below


figure:

Receiving of RADIUS Access-accept leads to:


• Checking of attributes in response packet
• Mapping of attributes (in customizable Javascript code) to NETA-21 web interface
permissions
• Login as the specified external type user.

Enabling RADIUS authentication in NETA-21 web UI


You can enable RADIUS authentication as follows:
• Enable RADIUS authentication method in security settings
or
• Add RADIUS user account with External account user role

 Enable RADIUS authentication method in security settings


1. From the NETA-21 web U, navigate to Settings -> Security.
2. In the Login methods panel, enable the RADIUS Login method.
3. Choose the RADIUS login method as Default.
4. If required, modify limit of Concurrent sessions in the Login settings panel. By
default, the number of concurrent sessions is set as 10. The value can be changed to
any value between 1 and 100.
Notes:
• Factory user can use one session in the background.
• Key based authentication is not available for common use in 2.30 firmware.
5. Verify the settings on the RADIUS settings panel as follows:
Server - IP address or domain name of the RADIUS server
Port - RADIUS server port (UDP port)
Shared secret - RADIUS shared secret
164 Security

Protocol - Select one of the options:


• Basic (RFC2865) – authentication backend component implemented with pyRad.
• EAP-TTLS (RFC5281) – authentication backend is eapol-test (part of wpa-
supplicant).

 Add RADIUS user account with External account user role


This option allows you to define desired full name and external user name.

Steps:
1. Navigate to Settings -> Users, and click Add user.
2. In the User details section, complete the below details:
Full name - Enter desired name
Security 165

User role - Select External account from the drop down


Language - Select the desired language
Comment - Provide comments if required.
Notes:
• Local user accounts will be left active in addition to the external RADIUS user
accounts.
• Local accounts should have strong passwords.
• When RADIUS server is unreachable due to network unavailability or other reasons,
local login will be enabled once per failed RADIUS login even if the local logins are
disabled in Security settings.

3. In the User & password section, enter the desired user name in the User name field.
The below patterns are allowed for User name:

Pattern Login user Example

* Any valid user johdoe


[email protected]
\\JDOE

*@example.com Any user at specific [email protected]


domain

user name Only one specific user johndo


[email protected]

4. After the above changes, the Login dialog box displays the option to login with
RADIUS login method.
166 Security

 User permissions mapping


You can configure RADIUS permissions script to modify user permissions based on the
parsed RADIUS server response. For example, user level attribute or similar server
specific setting.
To configure RADIUS permissions script, perform the following:
1. Navigate to Settings -> Security -> RADIUS permissions script.
2. Configure the RADIUS permissions script (Javascript, interpreted with PyV8 inside
NETA-21).

3. If required, click Validate to validate the script and test the RADIUS login. On
validation, RADIUS permissions script gets the RADIUS Access-Accept attributes as
an input object with key/value pairs. On successful validation, the desired array of
NETA-21 permissions are generated.
If the validation fails, an error message is displayed with the reason of failure.
Security 167

Available functions in the scripts are:

Function Parameters Description

getInput() RADIUS Access-Accept attributes as an input


object with key/value pairs

getInput() Error message (any text) Debug aid for Validate function of RADIUS permis-
sion script on Security settings dialog box, to show
customized errors for recognizing specific issues in
authorization.
User-specified errors are not shown in login dialog
box of NETA-21, instead, an Authorization error is
shown.

setResultJson(obj) Array of permission Must be called at the end of the script to generate
strings valid permissions for the user (empty return results
in Authorization error).
See below for examples of different typical permis-
sion sets, which are in NETA-21 web interface hid-
den behind user “roles” such as Guest, User, Drive
expert, Tool, and admin

log(text) Message Not visible in web interface, only for command line
debugging tests
168 Security

Steps:
1. Navigate to Settings -> Security -> RADIUS permissions script.
2. Configure the RADIUS permissions script (Javascript, interpreted with PyV8 inside
NETA-21).

3. If required, click Validate to validate the script and test the RADIUS login. On
validation, RADIUS permissions script gets the RADIUS Access-Accept attributes as
an input object with key/value pairs. On successful validation, the desired array of
NETA-21 permissions are generated.
If the validation fails, an error message is displayed.

Available functions in the scripts are:

Function Parameters Description

getInput() RADIUS Access-Accept attributes as an input object


with key/value pairs
Security 169

Function Parameters Description

getInput() Error message (any text) Debug aid for Validate function of RADIUS permis-
sion script on Security settings dialog box, to show
customized errors for recognizing specific issues in
authorization.
User-specified errors are not shown in login dialog
box of NETA-21, instead, an Authorization error is
shown.

setResultJson(obj) Array of permission Must be called at the end of the script to generate
strings valid permissions for the user (empty return results in
Authorization error).
See below for examples of different typical permission
sets, which are in NETA-21 web interface hidden
behind user “roles” such as Guest, User, Drive expert,
Tool, and admin

log(text) Message Not visible in web interface, only for command line
debugging tests

If the response is successful, the RADIUS response and parsed permissions array is
returned. The permissions that affect functionalities of the NETA-21 will be available for the
logged in user.
Following are examples of available user access levels:
var accessLevelPermissions = [
// Guest
[ "webUser", "deviceViewer"
"
],
// User
[ "webUser", "settingsViewer", "moduleGuest",
"moduleUser", "deviceViewer", "deviceUser",
"fileView", "reportViewer"
],
// Drive expert
[ "webUser", "settingsViewer", "settingsManager",
"systemLogViewer", "moduleGuest", "moduleUser",
"moduleSuperUser", "networkUser", "deviceViewer",
"deviceUser", "deviceSuperUser", "deviceAdmin",
"fileView", "fileStore", "reportViewer"
],
// Drive expert
[ "webUser", "settingsViewer", "settingsManager",
"systemLogViewer", "moduleGuest", "moduleUser",
"moduleSuperUser", "networkUser", "deviceViewer",
170 Security

"deviceUser", "deviceSuperUser", "deviceAdmin",


"fileView", "fileStore", "reportViewer"
],
// Tool admin
[ "webUser", "settingsViewer", "settingsManager",
"systemLogViewer", "moduleGuest", "moduleUser",
"moduleSuperUser", "moduleAdmin", "networkUser",
"networkSuperUser", "networkAdmin", "deviceViewer",
"deviceUser", "deviceSuperUser", "deviceAdmin",
"fileView", "fileStore", "reportViewer",
"reportManager"
]
If the RADIUS request fails, one of the following errors is displayed:
• Authentication server does not respond
• Authentication server declined request
• Authorization error

• Authentication timed out


Security 171

• User name or password was incorrect This error is displayed if external user account
does not exist for the mentioned user name.

You can resolve the errors using the suggestions in Troubleshooting section.

 Troubleshooting
If an error occurs during RADIUS login, perform the following steps:

Error Message Cause What to do

User name or password was External user name filter Make sure that the user with role
incorrect did not let the user name to External account and name is created.
attempt login via RADIUS. In the login dialog box, make sure that
login method RADIUS was selected.

Authentication server does RADIUS server is not In Security settings, check the IP
not respond reached. address and availability of the RADIUS
server.

Authentication timed out High system load or long Check network access.
delays in network traffic. Retry multiple times
Note: In general, RADIUS
authentication takes 20 seconds, and
login times out after 60 seconds.

Authorization error User name or Password is Check user accounts.


wrong.
RADIUS permissions script Check the RADIUS permissions script.
failed to run or returned zero
permissions for the user
account.

Authentication server RADIUS server declined in- Check RADIUS server and firewall
declined request coming connection. settings.
172 Security
Memory card 173

17
Memory card

What this chapter contains


This chapter describes the tabs under Memory card.

Using the memory card


To observe and manage the data on the memory card, go to Settings –> Memory card.
Use the memory card for collecting, for example, log files, backup files, device manuals
and restore archives.

Memory card status tab


The Memory card status tab shows actual data about the memory card: status, access
type and space status.
174 Memory card

In general, the toolbar contains the following buttons:


• Refresh button refreshes the memory card data in the current interface.
• Add content button adds the portals: Status, Memory card control and Events.
• Save layout button stores the current layout settings to the NETA-21 memory.

File browser tab


The File browser tab shows the files in the memory card. You can see this tab only if your
role is Tool admin.

In general, the toolbar contains the following buttons:


• Refresh button refreshes the list of files in the current folder.

• Parent directory button navigates to the parent folder.


• Open button opens the selected file.
• Add… button copies a file from the PC to the memory card.
• Remove button deletes the selected file or folder (only an empty folder can be
deleted).
• Export to ZIP button collects all selected files and folders to a ZIP archive, which can
be downloaded at the end of the process.

Autoinst tab
The Autoinst tab works the same way as the File browser tab but it uses the “autoinst”
folder as a root folder in the memory card.
Memory card 175

Backup tab
The Backup tab works the same way as the File browser tab but it uses the backup
folder as a root folder in the memory card.

Report tab
The Report tab works the same way as the File browser tab but it uses the report folder
as a root folder in the memory card.

Restore tab
The Restore tab works the same way as the File browser tab but it uses the restore
folder as a root folder in the memory card.
176 Memory card
Frequently asked questions 177

18
Frequently asked questions

What this chapter contains


This chapter contains how-to instructions for various tasks.

How to update the NETA-21 firmware


The following sections show how to update the NETA-21 firmware with an SD memory
card. The NEXA-21 does not require any firmware updates.
In brief:
• With firmware 2.02 or any of the later releases:
Put the update file on the root of the SD card, and the NETA-21 applies the update (or
full system restore.n21) on the next reboot. The update takes about 5 minutes. LEDs
STAT and SD are blinking during the update.
• With firmware 2.01 and earlier releases:
Only the .NTU update mechanism over the web UI is supported. See section Updating
the NETA-21 firmware over a remote web connection on page 178.
For instructions on how to update several NETA-21 units at the same time locally with an
SD card, see section Updating the NETA-21 firmware locally with SD card(s) on page 180.
Notes:
• From firmware version 2.00 onwards, you can update all delivered NETA-21 units.
• The firmware update keeps all previous settings of the NETA-21. This means that a
remotely connected NETA-21 stays reachable after the firmware update.
• Do a factory reset after major firmware updates, especially when you upgrade the
NETA-21 firmware from version 2.11 or older releases, or when you upgrade the
NETA-21 firmware more than one minor version number The factory reset restores the
network settings.
178 Frequently asked questions

 Before you start


You must have NETA-21 update file FMZAAvrr.NTU where vrr stands for version and
subversion numbers, for example in FMZAA221.NTU firmware version 2.21.
You must have an SD memory card:
• Minimum size 512 MB, maximum size 32 GB
• Minimum of 200 MB free disk space
• Formatted with the FAT or FAT32 file system
• Read-writable (not write protected).
You can use the default SD cards included in each shipped NETA-21.
The firmware update has no effect if the existing software is already up to date. The
firmware update can be done between minor versions such as 2.12.x.y and 2.13.x.y but
not between patch versions of the same minor version such as 2.13.0.0 and 2.13.1.0.
Thus, the firmware update from 2.12.2.0 to 2.13.1.0 succeeds because the minor version
number is updated.

 Updating the NETA-21 firmware over a remote web connection


1. Log on to the NETA-21 and go to Settings –> Tool settings.
Tool firmware tab is visible. The System information panel on the Tool firmware tab
shows the currently installed software version.

2. Click the Send to tool button.


Frequently asked questions 179

The following dialog box appears.

3. Click the Browse… button.


4. Choose the FMZAA…NTU file and click the Open button.
5. Click the Send to tool button.
A process indicator shows how the uploading proceeds.
The uploading takes few minutes, depending on the network speed.
Note: If you have a slow network, we recommend you to use the FTP protocol or copy
the file manually to the SD card.
The file appears in the Tool firmware updates panel on the right-hand side of the
Tool firmware tab. The latest available version is selected.
6. Click the Reboot tool button.

Confirm that you want to reboot the tool.


The rebooting takes about 5 minutes. If the Login dialog box does not appear in 10
minutes, reopen the web browser.
Note: If you are access the NETA-21 with a local PC Ethernet connection, you must
push the SD RJ45 button and reconnect the Ethernet cable to re-enable the DHCP
server mode at this stage.
7. Log on to the web UI again.
8. To check that the update has been installed successfully, click About in the navigation
bar of the user interface or the corresponding icon in the toolbar.
180 Frequently asked questions

The About dialog box shows various software component versions. the Operating
System version number is the most interesting one.

Note: If the installation of the new firmware has failed, the firmware is unselected and
the description says "Do not install during next reboot". If the firmware update has
succeeded, the firmware file is grayed out in the Tool firmware updates list. After a
successful update, files can be cleaned up from the SD card (Settings –> Memory
card). The already installed firmware update is located in folder "autoinst". Folder
"backup" contains a full system backup image file which is automatically created
before the firmware update. The size of the system backup image file is 50 MB … 200
MB.

 Updating the NETA-21 firmware locally with SD card(s)


Use the local update method if you want to update multiple NETA-21 units in a batch or if
you do not want to spend extra time accessing the web UI before and after rebooting the
NETA-21. When the local updates are completed, we recommend you to reset the NETA-
21 to factory default settings.

Copying the FMZAAvrr.NTU file to memory card


1. Insert the SD memory card into the PC.
2. Create a folder on the SD memory card and name it "autoinst" (without the quotes).
Note: From release 2.02 onwards, you can skip this step and copy the file to the SD
card root.
3. Copy the FMZAAvrr.NTU file (eg, FMZAA213.NTU) from the PC to the “autoinst”
folder on the SD memory card.
4. Remove the card from the PC and insert it to the NETA-21.

Updating the firmware locally with an SD card


1. Make sure that NETA-21 has been switched off.
2. Insert the SD memory card with firmware update files into the SD memory card slot of
the NETA-21.
3. Switch on the NETA-21 and wait about 5 minutes.
Frequently asked questions 181

The time required by the operation depends on the speed of the SD memory card and
the amount of data in the NETA-21, because the NETA-21 takes a full system back-up
of all stored internal data to the SD memory card.
4. Do not switch off the NETA-21 or remove the SD memory card until the STAT LED on
the NETA-21 has turned green.
If power is lost during the update, the NETA-21 reverts to the previous system
configuration and blacklists the attempted update. In this case, you have to retry to
update the firmware via the web user interface or remove the blacklisted firmware
from the autoinst folder.
Do not remove the SD memory card permanently. If you do not insert the SD memory
card back, the NETA-21 can be caught in an infinite restart loop indicated by LEDs
flashing on and off every 2 minutes. If the restart loop condition does not fix itself in 10
minutes, the NETA-21 requires factory SW programming.
If the STAT LED does not turn green, restart the NETA-21. Do not remove the SD
memory card. Wait 5 minutes for the NETA-21 to restart the software update.
5. Switch off the NETA-21 when the STAT LED has been green for 1 minute.
6. Verify the update results from the log files on the SD card.
After you have updated the software, there will be some log files and backups
generated on the SD memory card. You can remove the log files and backups now or
later over a remote connection.
In folder autoinst/ on the SD memory card there are two new files per each updated
NETA-21:
• <serialno>.N21 - backup file
• <serialno>.LOG - log file
… where <serialno> is the 7-digit serial number of the NETA-21 tool, part of the same
serial number as in the barcode label. (For example, if the barcode label serial number
is B1500012WS, the log file is 1500012.LOG).
The following is an example of a successful NETA-21 SW update log file. The
timestamps at the beginning of each line specify when the operation was done
(yyyyMMddThh:mm, log level, Moreton-autoupdate: message text).
20111228T06:19:52, 2, Moreton-autoupdate: Found valid update
file, starting update.
20111228T06:19:52, 2, Moreton-autoupdate: Starting backup.
20111228T06:21:04, 2, Moreton-autoupdate: Backup done.
20111228T06:21:04, 2, Moreton-autoupdate: Starting flashing.
20111228T06:21:22, 2, Moreton-autoupdate: Flashing done.
20111228T06:21:22, 2, Moreton-updater: Rebooting.
20111228T06:21:31, 2, Moreton-autoupdate: Continuing to init
for finishing the update.
182 Frequently asked questions

How to reset the factory settings /


What if I forget my password
If you have forgotten the NETA-21 password, do as follows:
1. Name any .n21 full system backup image as a restore.n21 image or use a restore.n21
image provided by ABB.
Full system restore.n21 files are available from ABB Download Center.
2. Put the file in the SD memory card root folder.
3. Boot the NETA-21 up with the SD memory card inserted.
A full system restoration also makes a full system backup of the previous system
installation (which can be used to analyze the system afterwards).
A faster way to reset all settings to default values is to trigger a direct factory reset. This
option removes all data permanently. Do as follows:
1. When you have switched off the NETA-21 after a software update, connect a straight-
through Ethernet (Cat5 or higher) cable between the PNL1 and PNL2 ports.
Note: Crossover Ethernet cables cannot be used.
2. Switch on the NETA-21 and wait for 20…30 seconds.
3. When the PNL1 and PNL2 LEDs have turned yellow, remove the cable between the
PNL ports immediately (within a minute).
4. When you have removed the cable, the NETA-21 resets to factory defaults and
reboots.
The reset function is complete within 10…20 seconds and indicated by all LEDs
(except PWR) going off and then going on again.
5. Switch off the NETA-21.
You can switch off the NETA-21 either right after it has rebooted, or wait until the STAT
LED has become green again (factory settings have been re-initialized when the STAT
LED has turned green).

How to replace the SD memory card safely


There are two buttons on the front panel of the NETA-21:
• SD RJ45 (eject) button for ejecting the SD memory card and discovering devices
• “Reset" button (no name indicated beside the button)
To eject th SD memory card safely, press the SD RJ45 button for a minimum of 1 second
but no longer than 2 seconds. The SD LED turns from green to blinking red/green. When
the LED has stopped blinking and there is a constant yellow light, you can remove the SD
card. If you did not eject the SD card after trying for 1 minute or if a process blocked the
access to safely remove the memory card, the SD LED turns green.

How to configure the logging of drive data to the SD card


To configure the logging of specific drive parameters manually, see the description of the
Logging sub-panel in section Parameter properties or Parameter history logging tab.
By default all logged parameters and all occurred events are stored to events.db and
values.db files on the SD memory card. You can adjust the storage interval and switch to
the .csv / .log file storage, see section Creating an SD card report.
Frequently asked questions 183

How much logged data fits into an SD/SDHC card?


2 weeks to 1 year with a default SD card, up to 10 years with the largest available SD
memory card, depending on the configuration.

How to interpret the logged data from the SD card


See section Format of an SD card report for the report file syntaxes.

How to create an FTP account


Create the FTP and FTPS accounts in the same way as web UI accounts. Set the user
role to "FTP user". You can use the FTP and FTPS accounts only for accessing files on the
SD memory card.
The usage of the FTP and FTPS services may require modifications in the firewall
settings. Go to Settings –> Network services –> Services to see if the FTP/FTPS
services have been opened over the specific network interfaces.

How to re-enable reports if time & date have been shifted


backwards
If time and date of the NETA-21 have been shifted backwards, it can happen that both
logging and reporting of the previously defined reports stop, until the time again flows over
the previous point when data was sent out the last time.
To re-enable reporting and to reset the internal timestamp/pointer of the last reported data,
open the specific report for editing in the Reports view and apply changes to that report or
just save the report settings.
184 Frequently asked questions
Diagnostics and troubleshooting 185

19
Diagnostics and troubleshooting

What this chapter contains


This chapter explains how to trace faults with the status LEDs on the NETA-21 and the
NEXA-21.

LED indications
The NETA-21 is equipped with 13 bi/tricolor diagnostic LEDs. The NEXA-21 is equipped
with four bi/tricolor diagnostic LEDs. The LEDs are described below.
186 Diagnostics and troubleshooting

 LED indications of the NETA-21


Name Color Function

USB Off No USB mass storage devices attached

Green USB mass storage device attached and mounted.

Blinking green Device attached, initialization in progress

Yellow Device can be removed.

Red Unidentified error when settings are imported from an USB memory
device.

Blinking red Initialization failed.


Unsupported file system on a USB stick.
Only FAT file systems with 8.3 character filenames are supported.
Basically, NTFS-formatted USB sticks and external hard disks are not
supported.

EXT Off No NEXA-21 connected

Green NEXA-21 found and initialized

Blinking green NEXA-21 support is being initialized (when the NETA-21 boots up)

Red NEXA-21 malfunctions

Blinking red NEXA-21 not supported

SD Off No SD/SDHC card

Green Card attached and taken into use

Blinking green Card attached and initialization in progress

Yellow Card can be safely removed

Blinking yellow Card attached, removal in progress

Blinking yellow Together with the blinking red STAT LED: System waits for
confirmation of reboot operation or network override

Red Card error, for example write protection prevents from writing data to the
card

Blinking red Card initialization failed.


Unsupported card type, for example, SDXC (extra capacity) cards and
MMC cards are not supported.

PNL 1/ Off No devices (no wire) connected to the PNL port


PNL 2
Green All devices connected, identified and commissioned

Blinking green Manual or automatic discovery of devices in progress

Yellow Communication OK, but device connectivity limited.


All devices are ready to be unplugged/disconnected.

Red Communication error caused the panel port network initialization to fail.
Unknown device in the network, or something is interfering the network
and preventing proper detection of monitored devices.

Blinking red Unsupported device is found in the network, or there are too many
devices in the network to be monitored
Diagnostics and troubleshooting 187

Name Color Function

PC ETH 1 Off PC not connected.


If an Ethernet cable is connected to the PC ETH 1 port but no one uses
the NETA-21, the LED remains blank.

Green Connection set up and in operation, for example, DHCP is active and at
least one PC has got an IP-address

1/2-second • NETA-21 provides IP addresses for local devices.


blinking green Activate the DHCP server mode by pressing the SD RJ45 button for
five seconds.
• When a PC is connected and the NETA-21 has provided an IP
address for it, the LED turns steady green.
Note: The DHCP server functionality remains enabled until the NETA-21
is restarted or until the DHCP server is disabled in the web UI
(Settings –> Network interfaces –> Ethernet 1).

1-second At least one user has been logged on to the user interface
blinking green

Blinking yellow Factory-level access/operation.


Firmware update in progress.
Note: System status (STAT LED) blinks during the firmware update.

PWR Off Power off

Green Power on

Yellow Timed power off or standby.


NETA-21 can go to the standby mode as a protective measure (eg, if the
environmental temperature is too high).
To wake up the NETA-21, press the SD RJ45 button.

STAT Green System in operation, OK

Yellow System starts up, services not yet fully operational

1/4-second System waits for a confirmation of the reboot operation or network


blinking yellow override.
• If you reboot the NETA-21 by pressing the reset button for 5 seconds
when the NETA-21 is running, the STAT LED starts blinking. Confirm
the reboot operation by pressing the SC RJ45 button. If you do not
confirm the reboot operation, it stops after a 1-minute delay.
• You can override the network settings by pressing the SD RJ45 button
for 10 seconds when the NETA-21 powers up. If you keep pressing
the button for about 20 seconds, the STAT LED starts blinking, which
indicates that you can release the button. If you do not release the SD
RJ45 button within one minute (or if the button is locked to the “ON”
position), the default network settings are not restored.

1-second Firmware update in progress


blinking yellow

Blinking red Error occurred during the start-up of the NETA-21.


If the start-up fails, the NETA-21 restarts itself automatically after a few
seconds. During the reboot operation, all LEDs excluding the PWR LED
flash before the STAT LED turns yellow again.
If the yellow STAT LED and blinking red STAT LED alternate and the
STAT LED does not turn green, the start-up of the NETA-21 fails
continuously. Try resetting the NETA-21 to factory settings.

MON Blinking green NETA-21 sends data (eg, email) to an external destination.

Blinking red NETA-21 fails to send data (eg, email) to an external destination. Log on
to the web user interface and go to Reports –> Events for error details.
188 Diagnostics and troubleshooting

 LED indications of the NEXA-21


Name Color Function

PWR Off NEXA-21 not controlled by the NETA-21 or the NETA-21 boots up

Green NEXA-21 detected by the NETA-21 and the NEXA-21 turned on

STAT Green System in operation, OK.


DDCS drives commissioned.
Communication with drives OK.

Yellow System reboots, the NEXA-21 temporarily out-of-order

Blinking yellow Limited connectivity.


Devices not found.

Red Internal error.


DDCS network not physically OK, or no devices detected.

Blinking red Incompatible device in DDCS.


NEXA-21 has lost connection to a configured device.
Note: DDCS is running.

RX Off Not receiving data

Yellow Receiving data

TX Off Not transmitting data

Yellow Transmitting data

Troubleshooting
Problem Cause Solution
The STAT led of the NEXA-21 DDCS devices are not detected. Do as follows:
turns red after the NETA-21 has Check that the DDCS wiring is
been powered up. connected the right way around.
Disconnect optical fibers for over
30 seconds and then reconnect the
fibers. The 30-second
disconnection initiates the device
rescanning.
Log on to the NETA-21 web user
interface.
Go to Settings –> Device
interfaces, select the DDCS tab
and click Restore defaults.
Confirm the restoration by clicking
the same button again.
The newly connected devices do Automatic rescanning is done only EITHER: Disconnect wires for 1
not appear in the UI. if all devices per interface have minute and then reconnect.
been disconnected for 1 minute or OR: In the UI, go to Settings –>
longer. Device interfaces, select the
interface specific tab, and click
button Rescan devices.
Diagnostics and troubleshooting 189

Problem Cause Solution


The disconnected old devices Disconnected devices must to be The solution depends on the
remain in the UI and do not manually removed. An automatic device interface. Try one of the
disappear. removal would affect customized following:
device settings, such as reporting 1. Go to Settings –> Device
settings. interfaces and select the
specific device interface. Click
button Rescan devices.
2. If devices still reside in the UI,
go to the front page of the
disconnected device. Check the
Device control panel and click
the Remove device button if
such a button is available.
Web pages behave erratically or The web browser cache contains Try refreshing the whole page. Try
the login is prevented after the tool an old version of the user interface. pressing the shift key on the
firmware update. keyboard during refreshing, to
reload all script files. If that does
not help, clear all temporary
Internet files or the cached web
content using browser specific
menus, and try to log on to the
NETA-21 again.
When the web page is zoomed The content zooming with touch Zoom to the desired level and tilt
with a tablet or mobile phone only screen devices is not fully the phone/tablet screen (90
part of the screen area is usable. supported. degrees to the horizontal or vertical
position) to readjust screen frames.
190 Diagnostics and troubleshooting
Technical data 191

20
Technical data

What this chapter contains


This chapter contains the technical data of the NETA-21 and the NEXA-21.
192 Technical data

Hardware
 Enclosure of the NETA-21

98 54.2
[3.9] [2.1]

[1.5]
39
120
[4.7]

124
[4.9]

[4.5]
90
[1.3]
34

58
[2.3]

 Enclosure of the NETA-21 with the NEXA-21

98 79
[3.9] [3.1]
[1.5]
39
120
[4.7]

124
[4.9]

[4.5]
90
[2.3]
59

58
[2.3]
Technical data 193

 Technical data of the NETA-21 and the NEXA-21


Mounting On a 35-mm / 1.4-inch DIN rail
Degree of protection IP20
Ambient conditions Applicable ambient conditions specified for the drive in its manuals are in effect.
• Operating temperature: -5…+60 °C / -23…+140 °F (free air circulation)
Indicators 9 + 4 bi/tricolor LEDs
Connectors Power supply input (X1)
• Signal level: 10 … 30 V DC, max. 2 A (typical: 200mA @ 24 V / 500 mA @ 12 V)
• Connector type: Shrouded header for the wire plug, 2 pins, pitch 5.00 mm / 0.19
inch
Panel bus port 1 (PNL 1) and 2 (PNL 2)
• Bus voltage: 5 V
• Signal level: EIA-485
• Communication protocol: Panel bus over EIA-485
• Cable type: Ethernet CAT5, straight
• Connector type: Shielded 8P8C modular jack (RJ45)
• Maximum segment length: 100 m / 328 ft
Ethernet port 1 (ETH 1) and 2 (ETH 2)
• Media: 10Base-T / 100Base-TX (10 Mbit/s or 100 Mbit/s)
• Cable type: Shielded twisted pair (STP), both straight-through and crossover cables
are supported (HP Auto-MDIX).
• Connector type: Shielded 8P8C modular jack (RJ45)
• Termination: Internal
• Maximum segment length: 100 m / 328 ft
EIA-232 Port (X2)
• Physical layer: EIA-232, galvanic isolated
• Connector type: D-sub 9-pin male
EIA-485 Port (X3)
• Bus voltage: 5 V
• Medium: Shielded twisted pair cable, impedance 100…150 ohm
• Serial communication type: Asynchronous, half-duplex RS-485
• Physical layer: EIA-485, galvanic isolated
• Communication protocol: Modbus
• Connector type: Shrouded header for the wire plug, pitch 5.00 mm / 0.19 inch
• Maximum length: 1200 m / 3 937 ft
SD/SDHC connector
• Supports up to a 32-GB SD/SDHC card
USB host ports
• PHY Interface: USB2.0
• Connector type: Shielded USB Type A
Fiber optic transmitter/receiver DDCS
• Media: Fiber optic cable (max. 10 Mbit/s)
• Protocol: Distributed Drives Communication System (DDCS)
• Connectors: Dark gray – receiver; gray – transmitter
Power supply • Primary power supply input: 10…30 V DC, max. 3 A
• Secondary power supply input: AC/DC 24 V ± 10%, max. 1 A (rms). For redundant
power supplies via extension modules.
• Power supply output: 5 V, 700 mA for external option modules. Short circuit
protected.
General • Battery replacement interval: 5 years at 25 °C / 77 °F
• Complies with EMC standards IEC 61000-6-2 and IEC 61000-6-4
• All materials are UL-approved
194 Technical data
Further information
Product and service inquiries
Address any inquiries about the product to your local ABB representative, quoting the type
designation and serial number of the unit in question. A listing of ABB sales, support and
service contacts can be found by navigating to www.abb.com/searchchannels.

Product training
For information on ABB product training, navigate to new.abb.com/service/training.

Providing feedback on ABB Drives manuals


Your comments on our manuals are welcome. Navigate to
new.abb.com/drives/manuals-feedback-form.

Document library on the Internet


You can find manuals and other product documents in PDF format on the Internet at
www.abb.com/drives/documents.
Contact us

www.abb.com/drives
www.abb.com/solar
www.abb.com/windpower
www.abb.com/drivespartners

3AUA0000096939 Rev E (EN) 2017-06-12

3AUA0000096939E

You might also like