0% found this document useful (0 votes)
110 views2 pages

Power System Setting Information - TP48300B

This document contains parameter settings for a battery system including settings for over/under voltage thresholds, temperature compensation, charge parameters, rectifier settings, and temperature/humidity thresholds. The default and actual settings are shown for each parameter, with most left at the default value and some configured based on the actual battery capacity or temperature range.

Uploaded by

Lê Hữu Ái
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
110 views2 pages

Power System Setting Information - TP48300B

This document contains parameter settings for a battery system including settings for over/under voltage thresholds, temperature compensation, charge parameters, rectifier settings, and temperature/humidity thresholds. The default and actual settings are shown for each parameter, with most left at the default value and some configured based on the actual battery capacity or temperature range.

Uploaded by

Lê Hữu Ái
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 2

First parameter Second parameter Third parameter fourth parameter

Over Volt
AC setting
Under Volt
Over Volt
DC setting
Under Volt
Batt paramter Batt1 connected
Batt2 connected
Rated Capacity
LVD Setting LLVD Enable
BLVD Enable
LLVD
BLVD
Charge FC voltage
EC voltage
Curr Limit
Temp.Comp.Para TC Coefficient
Norminal Temperature
Temp.Prot.Para Very HT Prot. Mode
Very HT Prot. Volt
Battery set
HT Alarm Thres
Very HT Alarm Thres
LT Alarm Thres
Charge Parameters Auto EC Enable
FC-EC Cur. Coef
FC-EC Cur. Duration
FC-EC Cap. Percent
Sche. EC Enable
Sche. EC Interval
Sche. EC Duration
EC-FC Cur. Coef
EC-FC Cur. Duration
EC Max Duration
Main Recovery EC En
Rectifier 0V Prot. Thes
Sequential St. Int
High Rect Capacity
Low Rect Capacity
Parameter setting Max Limited Current
Defaul Output Volt
WALK-TN Enable
Power system Temp&Humi Para Amb. HT Thres
Amb. LT Thres
Default value Actual setting Remark
280V 280V Same as default
180V 180V Same as default
58V 58V Same as default
45V 45V Same as default
Yes Yes Same as default
Yes Yes Same as default
100Ah 150Ah Based on actual
Yes Yes Same as default
Yes Yes Same as default
44.0V 44.0V Same as default
43.2V 43.2V Same as default
53.5V 53.5V Same as default
56.4V 56.4V Same as default
0.15C10 0.10C10 Config
80mV/degC 80mV/degC Same as default
25 degC 51.5V Same as default
Reduce DC Voltate Reduce DC Voltate Same as default
51.5V 51.5V Same as default
50 degC 50 degC Same as default
53 degC 53 degC Same as default
-10 degC -10 degC Same as default
Yes Yes Same as default
0.05C10 0.05C10 Same as default
30 min 30 min Same as default
70% 70% Same as default
Yes Yes Same as default
30 day 30 day Same as default
9h 9h Same as default
0.01C10 0.01C10 Same as default
30 min 30 min Same as default
16h 16h Same as default
No No Same as default
59.5V 59.5V Same as default
0s 0s Same as default
5% 5% Same as default
75% 75% Same as default
121% 121% Same as default
53.5V 53.5V Same as default
No No Same as default
55 degC 55 degC Same as default
-20 degC -20 degC Same as default