Assignment Individual
Assignment Individual
UNIVERSTY
COLLEGE OF ELECTRICAL AND MECHANICAL
ENGINERRING DEPARTMENT OF ELECTRICAL AND
COMPUTER ENGINEERING
Individual assignment
By Biniyam Degemu FTP 0277/10
Answer
Harmonic distortion:-
We can understand the word harmonic like the integer which multiplies
fundamental frequencies is known as “Harmonics”. Here, harmonic is a type of
signal whose frequency is an integral multiple of the reference signal. In another
way, it can be defined as the ratio between the frequency of the signal and the
frequency of the reference signal.
Causes:
The main reasons for the harmonic-distortions are the nonlinear load and
nonlinearity characteristics of the electronic components. Nonlinear load
changes the impedance with the applied input voltage. This leads to distortions
will develop in the output signal. And the components which are using in the
circuit also show the nonlinearity characteristics. This also leads to the
development of the harmonics in the output. Because of the harmonic-distortions
circuit gets heat and output not equal to the input. This effect is harmful to any
circuit.
Causes:-
Overvoltages can be the result of load switching,
variations in the reactive compensation on the system (e.g.,
switching on a capacitor bank).
Poor system voltage regulation capabilities or controls result in
overvoltages.
Incorrect tap settings on transformers can also result in system
overvoltages.
Voltage Imbalance
Causes:-
A poor and inconsistent flow of electricity
Even nature can be the cause here. For instance, a lightning strike can
cause a surge which will cause your voltage to spike abnormally.
Faulty electrical devices might be to blame as well.
Bad wiring can also lead to voltage fluctuations.
B. voltage distortion
Voltage distortion is any deviation from the nominal sine waveform of the
AC line voltage. System harmonic voltage distortion is caused by the flow of
harmonic currents through system impedance, namely inductive reactance.
For each frequency, at which harmonic current is flowing, there is a
corresponding inductive reactance associated with system and thus a
voltage drop at that frequency. The factors that affect the system inductive
reactance are the generator, transformer, series line reactors or current
limiting reactors, and circuit conductors.
Current distortion
any distortion from the nominal sine waveform of the AC line Current.
Assuming that the source bus is a pure sinusoid, there is a nonlinear load
that draws a distorted current.
2. Calculate the reliability indices due to the power quality problems around
AASTU based on the assumed twelve outages that occur end to the customers
around AASTU in May13, 2021. The EEP has 3000 customers around AASTU
(Tulu Demtu condominium).
The summary of each interruption and its duration as given by;
follow:-
= 201.413/3000
SAIDI= 4.028min
SAIFI=0.122
= 201.413*60min/367
CAIDI=32.93min
That means on average any customer who experience an outage on 13 th was out of
service for 32.93min.
=12/367
CAIFI =0.033
So the average number of interruption for a customer who was interrupted on 13th
is 0.033.
ASAI=0.9972
ASAI=99.72%
Recommendation
C,
elements of power system circuit are predominantly inductive.so power factor
correction capacitors are commonly used in practical electrical system to offset
utility imposed power factor penalties. The combination of capacitors and and
inductive elements in the system can result either in series or parallel resonance,
or a combination of both, depending on system configuration, which can result in
an abnormal situation.
D,
Main sources
1. Arcing devices
2. Semiconductor based power supply system
3. Inverter fed A.C. drives
4. Thyristor controlled reactors
5. Phase controllers
6. A.C. regulators
Mitigation techniques
Line reactor.
K-factor transformer.
Tuned harmonic filter.
Active harmonic filter.
IGBT based fast switch harmonic filter.
Phase shift transformer.
12 and 18 pulse rectifiers
4.Mention:
a. the difference between voltage sag, swell, dip and interruption and explain how
voltage sag occur using power network schematic diagram
b. In addition try to mention the source of voltage sag and interruptions
c. the procedures to estimate voltage sag performances
Answer
Voltage sag :-short duration reduction in RMS voltage
Typical duration for instantaneous 0.5 to 30 cycles Momentary 30
cycle to 1 second temporary 3 second to 1 minute
Typical voltage magnitude in Pu 0.1 to 0.9pu typical duration.
Voltage dip:- means the amount of voltage decline from nominal
value.
Example a voltage dip of 30% is equal to voltage sag to 70%.
Voltage swell:- short duration increase in nominal supply voltage.
Typical duration for instantaneous 0.5 to 30 cycles with voltage
magnitude of 1.1 to 1.8pu
Momentary 30 cycle to 1 second with voltage magnitude of 1.1
to 1.4pu temporary 3 second to 1 minute with voltage magnitude of
1.1 to 1.2pu
Voltage interruption:- much decrease in voltage which approaches to
less than 0.1pu of nominal voltage magnitude.
Voltage sags and interruptions are generally caused by faults (short circuits) on
the utility system.
Voltage sags and interruptions are generally caused by faults (short circuits) on
the utility system. Consider a customer that is supplied from the feeder supplied
by circuit breaker 1 on the diagram shown below.
If there is a fault on the same feeder, the customer will experience a voltage sag
during the fault followed by an interruption when the breaker opens to clear the
fault. If the fault is temporary in nature, a reclosing operation on the breaker
should be successful and the interruption will only be temporary. It will usually
require about 5 or 6 cycles for the breaker to operate, during which time a
voltage sag occurs. The breaker will remain open for typically a minimum of 12
cycles up to 5 s depending on utility reclosing practices. Sensitive. Equipment
will almost surely trip during this interruption
A much more common event would be a fault on one of the other feeders from
the substation, i.e., a fault on a parallel feeder, or a fault somewhere on the
transmission system (see the fault locations shown in Fig.3.1). In either of these
cases, the customer will experience a voltage sag during the period that the fault
is actually on the system. As soon as breakers open to clear the fault, normal
voltage will be restored at the customer
To clear the fault shown on the transmission system, both breakers A and B
must operate. Transmission breakers will typically clear a fault in 5 or 6 cycles.
In this case there are two lines supplying the distribution substation and only
one has a fault. Therefore, customers supplied from the substation should
expect to see only a sag and not an interruption.
5. The radial power system supplying one of the industrial customers in Addis
Ababa with several large AC and DC adjustable-speed drives is shown below. The
DC and AC drives are fed via dedicated transformers at 100V and 380V,
respectively. System information including source impedance, feeder and
transformer data are provided in Tables below.
a. Identify Pcc points for faults on one of the 15kV, 33KV 132kV and 230kV
feeders and calculate the critical distances (Lcrit) that results in critical voltages
applying the fault at each bus at different time span.
b. Compute the critical distances (Lcrit) in table below for sag magnitudes of
10%,30%,50%,70%and90% on the 15kV,33KV,132kV and 230kV feeders.
Answer
A) in sag analysis Pcc points have to be identified first. Pcc points “point of
common coupling” means the point from which both the fault and load fed (the
load current branch off from fault current).
For any fault on one of 15KV feeders, the fault current will flow through kalit-
15KV bus, but not farther to wards the load. So the Pcc bus is kalit-15KV for
all fault within 15KV feeders. In the same way , kalit-33KV bus is the Pcc for
any of the fault within 33KV feeders. Other Pcc’s are kalit-132KV and kalit-
230KV.
To calculate the critical distance that result critical voltage sag by applying
fault on the bus for a radial power system
Vsag= Zf/(Zs+Zf) but Zf=0 since the fault happens at the bus the impedance
from the bus to the fault is zero. Now the sag magnitude becomes zero to find
the critical distance Lcrt= Zs*Vsag/(Z(1-Vsag)) in km.since Vsag=0 the
critical distance becomes zero when applying fault at the bus.
B) the critical distances (Lcrit) in table below for sag magnitudes of 10%, 30%,
50%,
70% and 90% on the 15 kV, 33 KV, 132 kV and 230 kV feeders. Using the
formula Lcrit = Zs*V/(Z(1-V)) we can get the critical distance for each buses.
For a sag magnitude of 10% on bus 15KV, Zs=70% and Z=22% from the table
given below. The critical distance becomes
If an interruption cost 100,000 Birr, then determine the total cost that utility losses
associated with the total voltage interruption and sags
Answer
When the percentage voltage interapution and sag increases the loss of money on
the utility side will increase greatly . The weighting factor increases as voltage sag
increase as shown in the table 3. The total equivalent interruption is determined
by:-
Category of events Weighting factor of each Number of Total
events for economic events per equivalent
analysis year interruptions
Interruptions 1 10 10
Sag with minimum 0.8 20 16
voltage below 50%
Sag with minimum 0.4 28 11.2
voltage between 50% and
70%
Sag with minimum 0.1 100 10
voltage between 70 % and
90%
Total 47.2
Then we can determine the total cost that utility losses associated with
the total voltage interruption and sags.
Given that the cost of an interruption is 100,000Birr, now from the table
the total equivalent interruption is 47.2.
Total cost that utility losses= total equivalent interruption * cost per
interruption = 47.2/yr * 100,000Birr
Total cost that utility losses =4.72 million Birr/yr but this interruption is
the same for the last to years. So the total cost of the 2 year becomes
Total cost that utility losses = 4.72 million birr/yr*2year
Total cost that utility losses =9.44 million birr