HD BE Parameter List & Error
HD BE Parameter List & Error
net 1
PARAMETER LIST
00 Language setting ( Turkish / English )
01 Lift type
02 Command type
03 Number of stops
04 Number of basement
05 Door type
06 Busy time
07 Lock waiting time
08 Waiting at floor time
09 High speed time
10 Low speed time
11 Max. Door time
12 Go to park time
13 Park stop
14 Fire stop
15 Direction arrow light
16 Change password
17 Cancel password
18 Maintenance done
19 Maintenance time
20 Error list
21 Digital setting
22 Special door setting
23 Rescuer (Active / Cancel
24 Dublex setting
25 Call transfer
26 Phase protection (Active / Cancel)
27 Ptc (Active / Cancel)
28 Car serial board (Active / Cancel)
29 Automatic door open time
30 Single door full automatic
31 Rp delay For roped VVVF and hydraulic elevators
32 Inspection movement type
33 Early door opener
34 Star triangle For hydraulic elevators
35 Motor valve time For hydraulic elevators
01 Ocak 2017
www.hedefsan.net 2
36 Door open leveling
37 Buttom stop
38 Early door opener way
39 Target Floor display flash
40 Display output
41 Maximum car call
42 Safety delay
43 Maximum car speed
44 Counter type
45 Go distance after JF
46 Photocell time
47 Krc (Active / Cancel)
48 Encoder divider
49 Automatic door at park
50 Position reset
51 Regulator Monitoring / Brake Monitoring
52 Floor landing correction
53 Floor ascent correction
54 Short floor way
55 Long floor way
56 Gong sound
57 First setup
58 Lcd contrast
59 UCM test
60 Interval speed
61 Kak‐sak time
62 Cabin light from card
63 Delete automatic recording
64 Input assignment
65 Factory setting
01 Ocak 2017
www.hedefsan.net 3
TECHNICAL SPECIFICATIONS
Dimensions
267× 201 × 35
Lenght × Width × Hight (mm)
Operation Temperature ±0 ‐ +60 °C
Protection Class IP20
Humidity %95
Main Control Inputs 3 x 380V, 50Hz, N
Control Feed Voltage 24 ± 5 Vdc
Power Usage Maks. 400mA 10W, for 24VDC
230Vac max. For hydraulic elevators in
Security Circuit Voltage
emergency descent 24Vdc
Control Signal Inputs 24 ± 5 Vdc
24 ± 5 Vdc
Control Signal Outputs
Short‐Circuit Protection
MAJOR FEATURES
2‐line 16‐character LCD display and 4 button keyboard
RS‐485 serial communication for group operation
RS‐485 serial communication for serial system connection with cabin
Recording the last 20 errors
Including door bridging safety circuit
Including phase sequential motor protection circuit
Including in‐ and output control of 2 automatic doors
Short circuit protected digital and signal outputs
Setting of indicator possible via menu: 7‐segment, Binary and Gray code
UPS support for emergency descent on hydraulic elevators.
01 Ocak 2017
www.hedefsan.net 4
OPENING SCREEN
When you power on, you can view the software version and serial
HD BE
number of the card on the opening screen. After a couple a seconds
Ver:1.0 SerialNo:030485 the screen changes to the MAIN SCREEN.
MAIN SCREEN
Waiting for Call… Here it shows the feed voltage (100) and the number of the floor
D:15 +25.4V where the elevator is at the present.
Waiting for Call …
If encoder is selected as counter type it looks like this.
D:15 +25.4V 65000
INSPECTION FROM BOARD
Çıkış butonuna 2 saniye basılı tutarak asansörü karttan revizyon
Inspection from Board
konumuna alabilir daha sonra yukarı ve aşağı butonları ile hareket
D:15 +24.0 V ettirebilirsiniz.
RECORDING FROM BUTTONS
Hold down both the up and the down button during one second, the
Manuel Record ==> 10
manual recording screen will appear. Select the floor number and press
D:15 +24.0 V enter. You can easely send your elevator to any floor you like.
GROUP WORKING DISPLAY
01 Ocak 2017
www.hedefsan.net 5
Group (ABCDEF) P‐A
The status of 6 panels in group operation is shown as:
D:15 +24.0 V
A‐B‐C‐D‐E‐F Is the ID name of the control panels that are defined in
group.
Indicates wether the control panel with communication
A‐a is included in the group operation. (Lowercase means
that it is excluded from the elevator group)
Indicates the ID name of the master of the control
P‐A panels.
Indicates a none existing control panel or a control panel
‐‐ without communication.
』 Shows the speed of the communication.
ENTER MENU
To enter the menu press and hold the ENTER button for 3 seconds. If
00: Language setting no password is defined for an entry permit (0000: initial password),
English then the display shows the first parameter and the text "LISAN /
LANGUAGE" will appear.
PASSWORD MENU
If you previously defined a
password, enter your
If you previously defined a password, enter your password using the
password using the UP and
UP and DOWN buttons correctly. Then press the ENTER button to
DOWN buttons correctly.
confirm the password.
Then press the ENTER button
to confirm the password.
If your password is entered correctly the first parameter will appear on
the screen. If entered incorrectly, the "INCORRECT PASSWORD!"
warning will appear and the card will return to the main screen. The
card does not block when you enter the wrong password. But you can
contact us for password help if you communicate the serialcode. Use
the UP and DOWN buttons to move between the parameters of the
program. And use the ENTER and EXIT buttons to change the parameter
value. After changing the parameter value with the UP and DOWN
buttons, record by pressing the ENTER button. Or you can press cancel
to return to the old setting.
01 Ocak 2017
www.hedefsan.net 6
EXIT MENU
Exit menu Press EXIT button to exit the menu. By pressing ENTER when you see
(ENTER) “EXIT MENU” you can exit the menu screen.
LANGUAGE SETTING
LIFT TYPE
01: Lift type
Asansörünüzün tahrik tipini bu parametre ile ayarlayabilirsiniz.
Double speed
Continous gear (with asynchronous machine) and gearless (with
Roped VVVF
synchronous machine)
Hydraulic Choose this setting for hydraulic elevators.
COMMAND TYPE
02: Command Type
Set your elevator command type here.
Simple Command
The cabin and floor buttons are connected parallely. No other except
Simple Command
the one registration is kept in memory.
The cabin and floor buttons are connected parallely. Registrations are
Mixed Collective
kept in memory.
The cabin and floor buttons are connected seperately. Cabin
Down Collective registrations are collected from both sides. Floor calls are collected
when when cabin moves in downward direction.
Cabin registrations and the up and down buttons at the floors are
Full Collective (both ways) connected seperately. Cabin registrations and floor calls are collected
in appropriate manner of movement direction.
If the number of stops in a duplex elevator is more then 9 stops, this
Duplex Special
setting is used for a full collective command.
01 Ocak 2017
www.hedefsan.net 7
NUMBER OF STOP
03: Number of Stops
Set the number of stops (maximum 16) here.
D:16
NUMBER OF BASEMENT
04: Number of basement
Set the number of basement here.
01
If the elevator is down collective, the floors that are under the basement that is set, it will be up
collective.
Note: Used in command types except for down collective.
DOOR TYPE
05: Door Type
Set the open‐close signal type for automatic doors here.
Swing Door
Swing Door Only for elevators that have no automatic door.
Aut. Unlimited Only used for elevators with automatic unlimited cabin doors.
Aut. limited Only used for elevators with automatic limited cabin doors.
Full Aut. Unlimited Only used for elevators with full automatic unlimited cabin doors.
Full Aut. limited Only used for elevators with full automatic limited cabin doors.
According to the EN 81‐1/2 standarts in states of emergency stop, revision and take back automatic
doors must remain stationary.
01 Ocak 2017
www.hedefsan.net 8
BUSY TIME
06: : Busy Time
Set the cabin light delay here.
006 Seconds
5 ‐ 20 Seconds Set the cabin light delay time between the minimum and maximum.
According to the EN 81‐1/2 standards it is not allowed to bypass the cabin light delay.
On elevators with simple cımmand (non‐collective) this parameter must be equal to the ‘’WAIT
AT STOP’’ time. And the busy time must be at least 2 seconds.
LOCK WAITING TIME
07: Lock waiting Set the maximum time to wait for the door lock signal (140) after
008 Seconds getting the door closed signal.
8 ‐ 30 Seconds Set the lock waiting time between the minimum and maximum.
WAITING AT STOP TIME
08: Waiting Time at Floor Set the waiting time before going to other registrations while
008 Seconds collecting.
3 ‐ 15 Seconds Set the waiting time at floor between the minimum and maximum.
According to the EN81‐1 and EN 81‐2 standards, elevators( menuel doors) when the car reached
to the stop, it has to wait 2 seconds before moving again.
On elevators with simple command (non‐collective) this parameter must me equal to the “CABIN
LIGHT” time and must be at least 2 seconds.
01 Ocak 2017
www.hedefsan.net 9
HIGH SPEED TIME
Set the maximum time of cruising between 2 stops. If this time should
09: : High speed time
be exceeded, the system automatically stops the movement of the
015 Seconds cabin and blocks it.
5 ‐ 120 Seconds Set the fast cruising time between the minimum and maximum.
According to the EN81‐1 / 2 standards motor operation time work must not exceed the smaller
of the following;
45 seconds
Longest cruising distance +10 seconds
If longest cruising distance is less than 10 seconds, the timeout should be at least 20 seconds
LOW SPEED TIME
Set the maximum time of slow cruising from the moment it meets the
10: Low speed time
stopper of the target floor. If this time should be exceeded, the
015 Seconds system automatically stops the movement of the cabin and blocks it.
5 ‐ 60 Seconds Set the slow cruising time between the minimum and maximum.
MAX. DOOR STILL OPEN ERROR TIME
If after the time set in this parameter the door is not closed yet the
11: Max. Door time
control panel will go out of service. It is possible to choose to bypass this
015 Seconds function.
Set the time for passing the door still open error between the minimum
15 ‐ 250 Seconds
and maximum.
GO TO PARK TIME
12: Go to park time
Set the waiting time before going to park stop.
015 Seconds
0 ‐ 250 Seconds Set the waiting time between the minimum and maximum.
01 Ocak 2017
www.hedefsan.net 10
PARK STOP
13: Park stop Set the park stop here. When elevator pauses its operation,it goes to
05 this floor and waits with open doors.
FIRE STOP
Set here the fire stop. When Fire input (at SIDE) is active the elevator
14: Fire Stop goes to the defined floor directly and waits with its doors open.
01 Elevator will return to normal operation mode when fire signal is
over.
This is the minimum and maximum time that is waited before going to
0 ‐ 250 Seconds
park stop.
Cancel Fire stop is not defined in the system.
1 – 16 Fire stop is defined in the system.
ARROW FLASH
15: Arrow flash
Set here the flashing direction arrow while the elevator is in motion.
Active
ACTIVE Direction arrow flashes in direction of movement.
CANCEL Direction arrow light up constantly in direction of movement.
CHANGE PASSWORD
16: Change password Set or change the password code here.
1_0_0_0_0 If the display looks like this, the password is activated.
CANCEL PASSWORD
01 Ocak 2017
www.hedefsan.net 11
17: Cancel password Cancel the password code here.
0_0_0_0_0 If the display looks like this, the password is canceled.
MAINTENANCE DONE
18: Maintenance done Reset here the maintenance period.
Maintenance done ! You can reset your maintenance time by pressing the enter key.
MAINTENANCE TIME
For every day the card operates the value of this parameter drops by
one. For example, if it is set for 45 days, this parameter will show a
19: Maintenance time value of 15 when 30 days have passed. After 45 days the value will be
0.
45 ‐ 250 days Set the maintenance time between the minimum and maximum.
ERROR LIST
Here you can view the last 20 errors with their stop names, starting
20: Error list
with the last error. When reaching the first error, an option to delete
817 Doesn’t come the errors pops up. You can delete all errors by pressing ENTER.
01 Ocak 2017
www.hedefsan.net 12
DIGITAL SETTING
21: Digital setting
When the floor number is blinking, set the floor number with the UP‐
DOWN buttons till you come to the floor number you want to change.
16
Press the ENTER button and next you will see the digits blinking. Set
the value you like. When finished exit with the exit button. Or if you
want to set another stop/floor, press the enter button, when floor
number is blinking, repeat the steps.
Indicator type Outputs that can be selected
‐4, ‐3, ‐2, ‐1, 0, 1, 2, 3, 4, 5, 6, 7, 8, 9, 10 ,11, 12, 13, 14, 15, 16
7 Segment indicator
A, B, C, D, E, F, H, J, L, N, O, P
SPECIAL DOOR SETTING
Set the floor at which you want to open the automatic A and B doors.
22: Special door setting When floor number is blinking, change the floor number with the UP‐
DOOR:01 A‐B DOWN buttons till you come to the floor number you want to change.
Press the ENTER button and next you will see the door setting
blinking. Determine the door setting again by using the UP‐DOWN
A‐B
buttons.
RESCUER
With stepless gear (asynchronous machine) and gearless
23: Rescuer (synchronous machine) hydraulic elevators the rescue‐type is
determined here.
DUPLEX SETTING
24: Duplex setting Set here the group ID of the control panel during the group operation.
A panel Group IDs A, B, C, D, E, or F can be used. The identity of each lift must
be different. Priority when in the same distance is given to the
elevator with the lowest group identity.
A‐B‐C‐D‐E‐F
01 Ocak 2017
www.hedefsan.net 13
CALL TRANSFER
If the elevator operates in group and external calls are connected to a
25: Call transfer
single panel, this paremeter should be ACTIVE, in other cases it
Active should be cancelled.
PHASE PROTECTION
26: Phase production
Set the phase sequence or deactivate the phase here.
Phase sequenced
Out of Order Deactivate phase
Phase unsequenced Activates phase without sequence
Phase sequenced Activates phase sequenced
PTC
27: Ptc
Choose the PTC motor thermistor input setting.
Active
ACTIVE Activates it.
CANCEL Deactivates it.
CABIN SERIAL CARD
28: Cabin Serial Card Activate this parameter when the serial communication card is
Active connected.
When this parameter is cancelled the serial communication continues but only the floor inputs and
other inputs will be canceled.
AUTOMATIC DOOR OPEN TIME
29: Automatic door open
time Set the time from opening till closing of the automatic door.
15 Seconds
01 Ocak 2017
www.hedefsan.net 14
05 – 20 Seconds Set the door open‐close time between the minimum and maximum.
SINGLE DOOR FULL AUTOMATIC
30: Single door full On elevators with swing doors, set this parameter when there’s only
automatic one full automatic door.
RP DELAY
It could be demanded with roped VVVF systems to delay the fall of
31: RP Delay the main contactor. In such cases, the RP delay of the relay output is
02600 set by this parameter. With hydraulic elevators it is used as motor
delay.
00000 – 25000 Miliseconds Set the contactor delay time between the minimum and maximum..
REVISION MOVEMENT TYPE
32: Revision movement
type Set the movement type of the up and down limit switches in revision.
Until Limit switch
When limit switches are enabled the elevator will stop before reaching
Until Limit switch
its floor.
Until Floor Even when limit switches are enabled the elevator will go to its floor.
Until Stop This parameter uses only for test.
EARLY DOOR OPENER
Activate here the early door opener function. (for roped VVVF and
33: Early door opener hydraulic elevators)
Active It is not possible to execute a levelling from inside cabin before
activating this parameter.
01 Ocak 2017
www.hedefsan.net 15
ACTIVE Early door opener activated.
CANCEL Early door opener canceled.
For the early door opener, the movement of the cabin while the door is open is resticted to the
door opening area and restricted to a speed of 0,15 m/s. This is permitted under the control of
the door bridging circuit on the HD BE.
STAR TRIANGLE
Set the waiting time after finishing the star connection of the motor
34 Star triangle
when rising and before continuing to the triangle connection in a
01000 hydraulic system.
Set the passing time to the triangle connection between the minimum
00000 – 25000 Miliseconds
and maximum.
MOTOR VALVE TIME
35: Motor valve time
The delay of the valves while rising in a hydraulic system is set here.
00100
00000 – 25000 Miliseconds Set the valve delay time between the minimum and maximum.
OPEN DOOR LEVELING
Activate here the open door releveling.
36: Door open leveling (For roped VVVF and hydraulic elevators)
Active It is not possible to execute a levelling from inside cabin before
activating this parameter.
ACTIVE Releveling is activated.
CANCEL Releveling is canceled.
01 Ocak 2017
www.hedefsan.net 16
BUTTOM STOP
This parameter is used only in group operation. If there’s a difference
37: Bottom stop in stops of the elevators, then this parameter is used to set the
2 bottom floor stop of the elevator that is different. For this setting,
the number of stops of the elevators in group operation must be the
same in the menu. For example, in a duplex system with 10 stops,
when elevator A doesn’t service the bottom floor and only elevator B
does: Both elevators must be set to 10 stops and the bottom floor
stop of elevator A must be set up as 2.
EARLY DOOR OPENER WAY
For the start of the early opening of the automatic door, set here the
38: : Early door opener way number of milimeters before reaching the floor.
080
Only applicable when early door opener is activated.
Set the early door opener distance between the minimum and
040 – 150 Milimeter
maximum.
TARGET FLOOR DISPLAY FLASH
39: Target floor display When this parameter is activated, the floor display flashes the
flash number of the target floor at each stop while moving down or up the
Active shaft.
ACTIVE Target floor display flash is activated.
CANCEL Target floor display flash is canceled.
DISPLAY OUTPUT
40: Display output Set the display output of the HD One X S controller card and HD Seri
7 segment output card.
7 Segment output Normal output.
Gray code output Gray code output.
01 Ocak 2017
www.hedefsan.net 17
Binary code output Binary code output.
MAX. CALL REGISTRATION
41: Max. Car Call Registration Set the maximum amount of calls that can be registrated from within
cabin. When this number is reached it stops registrating any calls
08 from within cabine.
01 ‐ 16 Set the number of stops between the minimum and maximum.
SAFETY DELAY
42: Safety delay Here set up the time to delay the movement of the elevator after the
0120 safety circuits 130 and 140 signals.
0000 – 1000 Milisecond Set the safety delay time between the minimum and maximum.
CAR MAX.SPEED
43:Car max.speed Selecting car max.nominal speed in this parameter
100 For example:For 1 m/sd 100.
COUNTER TYPE
44: Counter type
Set here your selection of the elevator floor sensor.
Encoder type
ML1 & ML2 ML1‐ML2 counter suitable for A3 standards (for Hydraulic)
Encoder counter It is uses shaft learning and suitable for A3.
Encoder 141 & 142 It is uses shaft learning and leveling from 141,142
01 Ocak 2017
www.hedefsan.net 18
GO AFTER JF
45:Go after JF
This parametere uses for finding floor level at 141,142 leveling
0100
If the car level up or down then you can set leveling as incerase or
000 – 200 Milisecond
lower the value.
PHOTOCELL WAITING TIME
46: Photocell waiting time Set the time of waiting for the photocell signal to close the door after
003 seconds the opening of the automatic door.
01 – 05 seconds Set the photocell waiting time between the minimum and maximum.
47 RESERVED
47 RESERVED 47 RESERVED
47 RESERVED 47 RESERVED
47 RESERVED 47 RESERVED
ENCODER DIVIDER
48: Encoder divider Enter here the result of the calculation according the elevator speed,
026 the number of encoder pulse and engine speed.
Scan the QR code
To calculate the Encoder Divider Rate Hedefsan has developed to open the app.
an app available on Google Play Store.
Without the app you can calculate the encoder divider rate by applying this formula:
Calculation: Motor speed X Encoder pulse number / 60 / Elevator speed = Enter result in the 48th parameter.
Example: 1500 X 1024 / 60 / 1000 =26
01 Ocak 2017
www.hedefsan.net 19
AUTOMATIC DOOR AT PARK
49: Aut.Door.At.Park Set the open or closed position of the automatic door when waiting
Wait closed at park.
Waiting Open Car waiting open door at park stop.
Waiting Close Car waiting close door at park stop.
POSITION RESET
Even when there’s a power blackout the controller card will
50: Position reset remember its last position. But in some special cases when the power
Cancel returns, a position reset may be wanted. In that case the elevator will
go until it reaches the 817 limit switch of the bottom floor. When it
reaches the bottom floor, the floor counter will reset. For example:
with systems that have battery charged rescuers, this parameter can
be activated to reset the position.
ACTIVE Position reset is activated.
CANCEL Position reset is canceled.
REGULATOR MONITORING / BRAKE MONITORING
51:Regulator & Brake
Monitoring
Cancel Regulator and Brake monitoring can be active in this parameter.
REGULATOR MONITORING Regulator monitoring is active.
BRAKE MONITORING Brake monitoring is active.
CANCEL Regulator and Brake monitoring is cancel.
FLOOR LANDING CORRECTION
01 Ocak 2017
www.hedefsan.net 20
If the elevator counter type is encoder, then the floor landing
52: Floor landing correction
correction is set here. The setting is done with – mm if the elevator is
[16] = 000 too high and with + mm if it is too low.
FLOOR ASCENT CORRECTION
If the elevator counter type is encoder, then the floor ascent
53:Floor ascent correction
correction is set here. The setting is done with – mm if the elevator is
[16] = 000 too high and with + mm if it is too low.
SHORT FLOOR WAY
54: Short floor way Adjust here the slowing down distance when elevator moves one
140 cm. floor distance.( This parameter uses at Encoder counter systems.)
100 – 180 cm Minimum ve Maksimum deceleration distance.
LONG FLOOR WAY
Adjust here the slowing down distance when elevator moves more
55:: Long floor way
then a floor distance.( This parameter uses at Encoder counter
140 cm. systems .)
100 – 180 cm Minimum ve Maksimum deceleration distance.
GONG SOUND
56: Gong sound FIRST SETUP
It activates or cancels the gong sound in serial communication.
Cancel
57: FIRST SETUP
This parameter uses for shaft learning. After shaft learning take it cancel
Cancel
01 Ocak 2017
www.hedefsan.net 21
LCD CONTRAST
58:LCD contrast
Adjust here the LCD contrast.
035
UCM TEST
59:UCM Test You can make ucm tes in this parameter.
INTERVAL SPEED
60: Interval speed Set here the interval speed.
KAK – SAK TIME
61:Kak – Sak time KL FROM BOARD
You can adjust passing rescuer mode time in this parameter..
007 Second
62:KL from board With this parameter, if the cabin lamp is set as active or canceled from the
Cancel control card, the KL relay is defined as the out relay at floor .
DELETE AUTOMATIC RECORDING
63:Delete automatic With this parameter, incorrectly given calls from the cabinet button can
INPUT ASSIGNMENT
record be deleted by holding down the button. In addition, in‐cab records
Cancel
64:Input assignment automatically delete all in‐cab records when there are 2 stops in or out
With this parameter, different features can be defined for assignable
PI4‐PI5 inputs on the mainboard
KRC, SGH, RFI, K20, DTS, 817, 818, ML1, ML2, 141, 142, 500, 501, DEP,
PI4 YNG can defined.
01 Ocak 2017
www.hedefsan.net 22
KRC, SGH, RFI, K20, DTS, 817, 818, ML1, ML2, 141, 142, 500, 501, DEP,
PI5 YNG can defined .
FACTORY SETTINGS
64: Factory settings Here you can cancel your settings and return to factory settings.
ERROR LIST
01 Stop Interrupted 120 circuit cuts in motion.
02 Plug Interrupted 130 or 135 circuit cut in motion
03 Lock Interrupted 136 or 140 circuit cut in motion
04 KRC Error Motor contactor must be adherent situation.
05 PTC Error Motor temperature is above the required value.
06 Power Off Check the main power.
07 High Speed Long The elevator did not reach to stop at high speed.
08 Low Speed Long The elevator did not reach to stop at low speed.
09 Lock Nor Realised Check door locks.
10 Plug Not Realised Check door plug contacts.
11 There is not Ksr Check the position of the 817 and 818.
12 R‐Phase Error Check R Phase.
13 S‐ Phase Error Check S Phase.
14 T‐ Phase Error Check T Phase.
15 None Phases Check all phases.
16 Low Voltage Check 24VDC feed input.
17 None Enc. Pals Check motor or regulator encoder.
18 Leveling Long Check leveling speed.
19 None Lower Limit Check 817 position.
20 None Upper Limit Check 818 position.
21 Lock Shor Circuit Check door lock. Seperate short circuit in the shor circuit situation.
22 Reg.C.Released Check regulator coil.
23 Phase.C. Error Check phase collocation.
Communication Check S1A‐S1B communication cable.
24
Error
25 Inverter Error Check SHG position. ”on the VVVF elevator ”
01 Ocak 2017
www.hedefsan.net 23
26 H. Unit Error Check SHG position. ”on the Hydraulic elevator ”
PERMANENT ERRORS
01 M. Brake Error Check motor brake.
Involuntary The elevator moved uncontrollably.
02
Movement
03 ML Short Circuit Check ML1 and ML2 distance position.
Reverse Direction Check the movement direction of the elevator.
04
Movement
Regulator Coil Check the elevator regulator coil.
05
Error
To erase the above permanent errors, it will be sufficient to hold down the "ÇIKIŞ" button on the
motherboard until the errors on the LCD screen are erased.
01 Ocak 2017