ARB OHL Catalogue
ARB OHL Catalogue
ARB OHL Catalogue
AND CONDUCTORS
CATALOGUE 2013
Electrical Wholesalers
Electrical Wholesalers
ARB Electrical Wholesalers (“ARB Electrical Wholesalers”), founded ARB Electrical Wholesalers offers a wide range of locally
in 1980 by Chairman, Alan Ronald Burke, operating from a shipping manufactured and imported products to over 6,000 customers
container in Richards Bay with a bakkie and one employee, is throughout Southern and sub-Saharan Africa servicing six strategic
Southern Africa’s fastest growing black-empowered electrical business sectors:
wholesaler, playing a pivotal role in providing the essential products
required for the electrification of large scale industrial, residential • Large and heavy industry
and parastatal projects. • Government and parastatals
• Construction industry
Anchored by a 26,000 square metre head office in Durban, and • Electrical contractors including those working on
with a branch network built over the past 32 years, ARB Electrical governments overhead electrification
Wholesalers has a presence in all major business centres and programme and independents
all nine provinces in South Africa. ARB Electrical Wholesalers is • Mining industry
very proud to have recently announced the acquisition of 100% • Domestic market
of Industrial Cable Suppliers (Pty) Limited (“ICS”) and 100% of
Elektro Vroomen (Pty) Ltd (“Elektro Vroomen”), following these ARB Electrical Wholesalers is a Level 4 contributor in terms of the
acquisitions, ARB Electrical Wholesalers has 19 branches. ARB’s DTI’s BBEEE scorecard and, together with ICS and Elektro Vroomen,
supply capabilities extend beyond the borders of South Africa. has a staff complement of approximately 600 employees, including
Having supplied distributors, major projects, mines and power 50 sales executives.
utilities throughout Africa over the last 15 years ARB has developed
the capabilities to service customers throughout Africa with all A strong work ethic, solid teamwork and service excellence are
of their electrical material requirements sourced from local and all entrenched in ARB’s culture ensuring it has the necessary
international factories. experience and expertise to service its customers in all the areas
in which it operates.
2
LONG ROD INSULATORS
OHE-1015 OHE-1016 OHL-1006 OHL-1007 OHL-10110 OHL-101100 OHE-1019 OHE-1020 OHL-10165 OHL-1016
CODE
OHL-10061 OHL-101101
NOMINAL VOLTAGE 11kV 11kV 22kV 22kV 33kV 33kV 33kV 66kV 66kV 132kV
CANTILEVER STRENGTH (UTS) 70kN 70kN 70kN 70kN 70kN 70kN 120kN 70kN 120kN 120kN
APPLICATION COASTAL COASTAL COASTAL INLAND INLAND COASTAL COASTAL COASTAL COASTAL COASTAL
TYPE DISTRIBUTION DISTRIBUTION DISTRIBUTION DISTRIBUTION DISTRIBUTION DISTRIBUTION DISTRIBUTION DISTRIBUTION TRANSMISSION TRANSMISSION
MINIMUM REQUIRED CREEPAGE DISTANCE 430mm 430mm 744mm 480mm 720mm 1116mm 1015mm 2200mm 2232mm 4495mm
Electrical Wholesalers
CLEVIS / TONGUE
BALL / SOCKET
EYE / EYE
GUY STRAIN
PORCELAIN
STAY INSULATORS
CODE OHL-1012 OHL-1013 OHL-10145
OHL-1012S OHL-1013S
NOMINAL VOLTAGE 22kV 22kV MV
CANTILEVER STRENGTH 110kN 45kN 97kN
LENGTH/HEIGHT 136mm 95mm 700mm
WIDTH 85mm 75mm
DRY WITHSTAND VOLTAGE 35kV 30kV 60kV
WET WITHSTAND VOLTAGE 30kV 20kV 60kV
FIBRE GLASS ROD +
MATERIAL PORCELAIN PORCELAIN
EYE/EYE END FITTINGS
DDT-DWGN 3144 3144
SAP NUMBER 0167312 0189400
PIN INSULATORS
CODE OHL-1011 OHE-10191
NOMINAL VOLTAGE 11kV 15kV
CANTILEVER STRENGTH 10kN 10kN
MATERIAL CYCLOALIPHATIC PORCELAIN
COLOUR LIGHT BROWN BROWN
DRY FLASHOVER 89kV 85kV
WET FLASHOVER 82kV 40kV
DRY WITHSTAND 76kV 82kV
WET WITHSTAND 70kV 38kV
MINIMUM REQUIRED CREEPAGE DISTANCE 320mm 305mm
INSERT / SPINDLE M20 x 180 x 80 SHANK LEAD HEAD
INSERT DIAMETER 20mm 20mm
ACCESSORIES: SPINDLES
CODE OHM-1045 OHEM-1020
SIZE M20 X 180mm M20 X 100mm
TYPE SPECIAL COLLAR LEAD HEAD
APPLICATION CYCLO PIN PORCELAIN PIN
LENGTH ABOVE COLLAR 80mm 30mm
LENGTH BELOW COLLAR 180mm 100mm
INSERT DIAMETER 20mm 20mm
THREAD LENGTH 180mm 100mm
ASSEMBLY 1 X RFW 20 1 X SW 20
1 X CW 20 1 X NUT 20
2 X NUT 20
*RFW = ROUND FLAT WASHER
*SW = SPRING WASHER
*CW = CURVED WASHER
DISC INSULATORS
CODE OHE-10190
NOMINAL VOLTAGE 11kV
CANTILEVER STRENGTH 70kN
MINIMUM REQUIRED CREEPAGE DISTANCE 280mm
LIGHTING IMPULSE WITHSTAND 130kV
RATED 50HZ WET WITHSTAND 50kV
END FITTINGS BALL/SOCKET
MATERIAL PORCELAIN
COLOUR BROWN
*ALSO AVAILABLE IN GLASS
*VARIOUS END FITTING OPTIONS AVAILABLE
MV SURGE ARRESTERS
CODE OHL-1114 OHL-1113 OHL-1112 OHL-11110 OHL-111101 OHL-1110 OHL-1111
APPLICATION DISTRIBUTION - COASTAL SPEC STATION CLASS - COASTAL SPEC
SWER GAPLESS
TYPE NEUTRAL GAPLESS GAPLESS METAL OXIDE GAPLESS METAL OXIDE
METAL OXIDE
RATED VOLTAGE 6kV 11kV 22kV 33kV 33kV 11kV 22kV
MAXIMUM
19.5kV 40kV 80kV 120kV 100kV 45 85
RESIDUAL VOLTAGE
MCOV 5kV 10kV 19.2kV 29kV 24kV 12kV 24kV
DISCHARGE
10kA 10kA 10kA 10kA 10kA 10kA 10kA
CURRENT
CLASS 1 1 1 1 1 2 2
POLYMER/ POLYMER/
MATERIAL POLYMER POLYMER POLYMER POLYMER POLYMER
PORCELAIN PORCELAIN
CONDUCTIVE MOUNT-
ING BRACKET, INSU- DISCONNECTING DEVICE, FLEXIBLE EARTH LEAD, INSULATED
SUPPLIED WITH LATED COPPER TAILS MOUNTING BKT, M12 X 50MM MOUNTING BOLT, NUT, SERATED
16MM2 x 250MM WASHER & 3 FLAT WASHERS
LONG
DDT-DWGN 3088 3100 3100 3100 3100 6215 6216
SAP NUMBER 0165094 0182607 0182608 0182610
0182609 0004627 0004626
APPLY ON
TO SEPERATE IV AND EFFECTIVELY
LV OR MV AND LV EARTHED 33kV APPLY ON 11kV AND 22kV NON-EFFECTIVELY
APPLY ON NON-EFFECTIVELY EARTHED 11kV, 22kV
USAGE EARTHS ON OPEN AND 19kV EARTHED SYSTEMS IN CORROSIVE
& 33kV SYSTEMS IN CORROSIVE ENVIRONMENTS
BUSHING SWER SYSTEMS ENVIRONMENTS
TRANSFORMERS IN CORROSIVE
ENVIRONMENTS
LV FUSES
OHL-1147
SWITCH DISCONNECTOR CODE OHL-1149 OHL-1150
OHL-1148
TYPE SWITCH DISCONNECTOR VERTICAL FUSE HOLDER
RATED AMPERAGE 160A 400A 400A
APPLICATION POLE POLE BUSBAR
RATED VOLTAGE 1000V 1000V 440V
DIN TYPE FUSES NH00 NH02 NH02
VERTICAL FUSE HOLDER FULLY SHROUDED LIVE
PARTS TO PREVENT
ACCIDENTAL CONTACT
ON FUSES AND CABLE
CONNECTION.
FLAP THAT ACCOMMODATE DIN TYPE FUSES
CONSIST OF BOLTED CABLE
ONE INCOMING AND TWO OUTGOING TERMINALS
CONNECTION.
GANG OPERATED LOAD
BREAK.
INTEGRATED OPERATING
HANDLE.
FOX - HARE
CONDUCTOR SUITABLE
CONDUCTOR/ 35-70MM ALUMINIUM FOR INCOMING SUITABLE FOR MOUNTING
CABLE/BUSBAR CONDUCTOR SUITABLE TERMINAL ONTO BUSBAR WITH
RANGE FOR ALL TERMINALS 70-185MM COPPER 185MM BUSBAR SPACING
CABLE SUITABLE FOR
OUTGOING TERMINALS
PHASE
1,2,3 2,3 3
CONFIGURATION
SUPPLIED WITH 1 X M8 BOLTS 2 X M8 BOLTS
DDT-DWGN 3182 3182 3409
SAP NUMBER 0165096 0186422 0180230
*SWITCH DISCONNECTOR: OPTIONAL EXTRA - NEON LIGHT TO INDICATE WHEN FUSE HAS BLOWN
*LV FUSES: LINK STICK OPERATED
LV ABC CLAMPS
CODE OHL-1098 OHL-1103 OHL-1100 OHL-11031
TYPE STRAIN STRAIN SUSPENSION SUSPENSION
ABC CONDUCTOR TYPE INSUL NEUTRAL BARE NEUTRAL INSUL NEUTRAL BARE NEUTRAL
ABC NEUTRAL SIZE 54.6MM2 35.0-50.0MM2 54.6MM2 35.0-50.0MM2
BODY COLOUR BLACK BLUE BLACK BLUE
MINIMUM FAILING LOAD 14kN 13kN 8kN 8kN
UV STABLE YES YES YES YES
DDT-DWGN 3060 3060 3061 3061
SAP NO 0168557 0168575 0168556 0168578 SUSPENSION
SUSPENSION
STRAIN
LV ABC S-HOOK
CODE OHL-1104
APPLICATION SUSPENSION LINK LV ABC PHASE SEPERATORS
MATERIAL HDG STEEL CODE OHL-1105
OVERALL LENGTH 72MM APPLICATION SEPERATION OF ABC PHASES
DIA 8MM COLOUR BLUE or ORANGE
RELEASE FORCE 8kN
16
LV INSULATING PIERCING CONNECTORS (I.P.C)
OHL-1106
CODE OHL-11075 OHL-1106 OHL-1108 OHL-11081 OHL-11082 OHL-11083
OHL-1170S
2 2 2 2 2
MAIN CONDUCTOR SIZE 35-95MM BARE 25-70MM BARE 35-95MM INSULATED 25-95MM INSULATED 25-95MM INSULATED 16-95MM INSULATED 25-95MM2 INSULATED
TAP CONDUCTOR SIZE 6-25MM2 INSULATED 25-70MM2 INSULATED 6-25MM2 INSULATED 25-95MM2 INSULATED 25-95MM2 INSULATED 15-10MM2 INSULATED 2.5-35MM2 INSULATED
COLOUR CODE BLUE CREAM BLACK BLACK BLACK BLACK BLACK
Electrical Wholesalers
© ARB Holdings (Pty) Ltd
POLE TOP BOXES & ACCESSORIES
1 - 2 WAY 2 - 4 WAY 5 - 8 WAY
DISTRIBUTION BOXES
CODE OHL-1135 OHL-1136 OHL-1137
TYPE 1-2WAY 2-4WAY 5-8WAY
HOW MANY CUSTOMERS 2 x 20A 4 x 20A 8 x 20A
COMPRESSION GLANDS 2 4 8
16MM² UV STABLE PVC INSULATED CU LEADS 2 2 3
LENGTH OF LEADS 1.5M 1.5M 1.5M
MINATURE CIRCUIT BREAKERS 1 x 50A 1 x 50A 2 x 50A
EXTERNAL TOGGLE FOR LINK STICK 1 1 NO
DIN RAIL MOUNTING FOR ADDITIONAL MCD YES NO NO
30MM² INSIDE DIA RESET LOOP YES YES YES
13MM DIA STREET LIGHT ENTRY HOLE NO 1 NO
NEUTRAL BAR 1 x 3 WAY 1 x 6 WAY 1 x 10 WAY
LIVE BAR 1 x 6 WAY 2 x 6 WAY
PROVISION FOR 2 STAINLESS STEEL STRAPS
MOUNTING 2 X COACH SCREWS M6 X 40MM
12MM WIDE X 0.75MM THICK
DDT-DWGN 3055 3055 3055
SAP NUMBER 0168788 0168574 0168710
SPLITTER BOX
CODE OHL-1132
TYPE 3WAY
HOW MANY CUSTOMERS 3
COMPRESSION GLANDS NO 4 3
KNOCK OUT 1
NEUTRAL BAR 1 x 4 WAY
LIVE BAR 1 x 4 WAY
PROVISION FOR 2 STAINLESS
MOUNTING STEEL STRAPS 12MM WIDE X
0.75MM THICK
DDT-DWGN 3188
SAP NUMBER 0168770
FOR FOR
METERS METERS
MCB
DIN RAIL
NEUTRAL NEUTRAL
BUSBAR BUSBAR
4 WAY 8 WAY
READYBOARDS : STANDARD
OHL-11382
CODE OHL-11384
OHL-11385
TYPE BULKHEAD NO BULKHEAD
MINIATURE CIRCUIT BREAKERS 20X20A 2X20A
SOCKET OUTLETS 3X15A 3X15A
EARTH LEAKAGE 1X63A 1X63A
APPROX HEIGHT 270MM 270MM
APPROX WIDTH 255MM 255MM
APPROX DEPTH 70MM 70MM
METERING
CODE OHL-1234
OHL-1235
OHL-1236
TYPE PREPAYMENT
SINGLE PHASE 2 WIRE ECU YES
CURRENT LIMIT 20A
LCD DISPLAY YES
1 2 3
BUILT-IN EARTH LEAKAGE AND
4 5 6 YES
5 OVER CURRENT PROTECTION
7 8 9
2 POLE CIRCUIT BREAKER WITH
20A
1 2 3
7
5
8
6
9
* #
OVERLOAD
* #
KEYPAD OPERATED YES
KEYPAD STS COMPLIANT YES
MOV SURGE ARRESTER FITTED YES
MATERIAL OF HOUSING PLASTIC
260MM HIGH X
APPROX DIMENSIONS 145MM WIDE X
100MM DEEP
COLOUR OF HOUSING CREAM
INCLUDING WALL BASE YES
TAMPER RESISTANT YES
DDT-DWGN 3145
SAP NO 0171706
METER KIOSKS
CODE OHL-1240 OHL-1242
RATING 25kVA 150kVA
MOUNTING POLE POLE/GROUND
POWER USER SMALL(SPU) LARGE(LPU)
FITTED WITH 1 X 3PH 100A KWH METER 1 X 300A MOULDED CASE
1 X 40A 3PH CURVE 1 CIRCUIT CIRCUIT BREAKER
BREAKER EXTENDED BUSBARS
CALLIBRATION CERTIFICATE CTS(CURRENT
TRANSFORMERS) 300-5A
MCBS(MINIATURE CIRCUIT
BREAKERS)
TEST BLOCKS
230V SURGE ARRESTERS
WIRING AND
DDT-1002 DDT-1000
TERMINALS
MATERIAL 3CR12 POWDER COATED 3CR12 POWDER COATED
DDT-DWGN 3236
SAP NO 0168867 0168622
MV H-CRIMP CONNECTORS
CODE OHL-11281
MAIN CONDUCTOR DIA RANGE 4.11 - 8.43MM
TAP CONDUCTOR DIA RANGE 4.11 - 8.43MM
MATERIAL ALUM
STRANDED ALUM CONDUCTOR RANGE 25 - 50MM2 FRONT VIEW
STANDED OR SOLID CU RANGE 16MM2
TOOL BURNDY Y35
SWEMEL C12
BRICK 12TON
ALCON 12A
DIE SET “O” 125U-0
DDT-DWNG 3019
SAP NO 0168675 FRONT VIEW
(CRIMPED)
COPPER LUGS
OHL-1121
CODE
LUG-1057
SIZE 16MM2
FIXING HOLE SIZE 12MM
HOLE SIZE DIA 12.5MM
MATERIAL TINNED COPPER
OVERALL WIDTH 18.0MM
DDT-DWGN 3102
SAP NO 024515
*ALSO AVAILABLE IN SIZES RANGING FROM 2.5MM2 TO 630MM2 WITH VARIOUS
HOLE SIZES
COPPER FERRULES
OHL-1121
CODE
LUG-1163
SIZE 70MM2
MATERIAL TINNED COPPER
OUTSIDE DIA 15.0MM
INSIDE DIA 11.7MM
OVERALL WIDTH 34.4MM
DDT-DWGN 8020
SAP NO 0180208
*ALSO AVAILABLE IN SIZES RANGING FROM
2.5MM2 TO 630MM2
1, 2 or 3 per phase
1 for neutral
CROSBY CLAMPS
CODE OHL-1305 OHL-1306 OHL-1310 OHL-1311
USED WITH WIRE
8MM 8MM 12MM 12MM
ROPE DIA
MATERIAL HDG MCI HDG DFS HDG MCI HDG DFS
TYPE Light Duty Heavy Duty Light Duty Heavy Duty
SINGLE SINGLE SINGLE SINGLE
TYPE
SADDLE SADDLE SADDLE SADDLE
DDT-DWNG 7032
SAP NO 0400083
MCI = Malleable Cast Iron
DFS = Dropped Forged Steel
CLIMBING SHOES
CODE OHA-1310
SAFETY WORKING LOAD (SWL) 150KG
RIVETED LEATHER STRAPS YES
FOOT REST YES
SICKLE PAINTED WITH ZINC RICH PRIMER YES
TYPE/CLASSIFICATION LIGHT DUTY
WEIGHT (PAIR) 7.35KG
*ALSO AVAILABLE IN HEAVY DUTY
*STRAPS CAN BE SUPPLIED SEPERATELY
FIBREGLASS LADDERS
CODE OHA-1315 OHA-1320 OHA-1325 OHA-1330 OHA-1335
MATERIAL FIBREGLASS FIBREGLASS FIBREGLASS FIBREGLASS FIBREGLASS
CLOSED HEIGHT 3.6M 4.2M 4.8M 5.4M 6.0M
EXTENDED HEIGHT 7.2M 8.4M 9.6M 10.8M 12M
WORKING HEIGHT 6.6M 7.5M 8.7M 9.6M 10.1M
SAFETY WORKING LOAD (SWL) 136KG 136KG 136KG 136KG 136KG
POLE RUNS AND SPIKED FEET YES YES YES YES YES
RESCUE KITS
CODE OHA-1635 OHA-1640
PERSONAL PROTECTIVE EQUIP-
APPLICATION MENT AGAINST FALLS FROM
HEIGHT EQUIPMENT
COMPRISES OF: YES YES
*ROPE SYSTEM 13MM DIA MADE FROM POLY-AMIDE MATERIAL 1x20M 1x30M
*DOUBLE/TRIPLE ACTION KARABINER WITH CAPTIVE EYE 1x25KN 1x25KN
*DOUBLE BREAK DECENDING DEVICE WITH A SAFE WORK LOAD 1x150KG SWL 1x150KG SWL
*WEBBING CUTTER 1 1
*DOUBLE/TRIPLE ACTION KARABINERS (ALUMINIUM/STAINLESS STEEL) 1x25KN 1x25KN
*HOLD ALL PROTECTOR BAG 1 1
*ATTACHMENT STRAP 1x1.5M 1x1.5M
DDT-DWGN 12704 12704
SAP NO 0249906 0249907
PICK HEADS
CODE OHA-1915
MATERIAL CAST STEEL
SIZE 600MM
PURPOSE DIGGING
USE WITH PICK SHAFT
PICK HANDLES
CODE OHA-1920 OHA-1925
MATERIAL WOOD PLASTIC
OVERALL LENGTH ± 900MM ± 900MM
USE WITH PICK HEAD PICK HEAD
DIGBARS/GWALA’S
CODE OHA-1905
MATERIAL FORGED STEEL
OVERALL LENGTH 1800MM
OVERALL DIA 32MM
ROAD STAMPERS
CODE OHA-1910
MATERIAL FORGED STEEL
OVERALL LENGTH 1160MM
HEAD SQUARE
GLOVES
CODE OHA-1605
MATERIAL PIG SKIN
PURPOSE PROTECTION
VARIOUS TYPES AVAILABLE YES
*HIGH VOLTAGE GLOVES ALSO AVAILABLE 1KV - 11KV
RATCHET PODGERS
CODE OHA-1525 OHA-1530 OHA-1530
SIZE 10 X 13MM 24 X 30MM 17 X 19MM
DROP FORGED STEEL YES YES YES
RATCHET MECHANISM WITH REVERSE ACTION YES YES YES
DOUBLE ENDED SOCKET IN 2 SIZES YES YES YES
TAPERED END FOR HOLE ALLIGNMENT YES YES YES
USAGE TIGHTENING OF NUTS AND BOLTS ON
STRUCTURES
BARRIER TYPE
CODE TAP-1047
COLOUR RED/WHITE
WIDTH 75MM
LENGTH 500M
DDT-DWNG 3217
SAP NO 0175862
*BARRIER NETTING ALSO AVAILABLE ON REQUEST
DANGER
DANGER
GEVAAR
GEVAAR
WIDTH 450MM
INGOZI
INGOZI
ORANGE BACKGROUND
COLOUR
BLACK WRITING
SUPPLIED IN ROLL SIZE 300M
ESKOM KABELS ESKOM KABELS ABOVE BURIED
FOR USE
LV AND MV CABLE
DDT-DWGN 8013
SAP NO 0171426
LINK STICKS
CODE OHA-1600
TYPE HEAVY DUTY TELESCOPIC HOT STICK
MATERIAL EPOXY RESIN REINFORCED FIBREGLASS
SIZE 30FT (9.708M)
HOW MANY SECTIONS 7
WITH OPERATING HEAD YES
COLOURING BRIGHT GREEN TIP WITH ORANGE SECTIONS
TEST CERTIFICATE EXTRA OPTIONAL
BAG EXTRA OPTIONAL
CLOTH EXTRA OPTIONAL
DDT-DWNG 12600
SAP NO 0212805
0212806
VOLTAGE DETECTOR
CODE OHA-1015 OHA-1020
SYSTEM VOLTAGE 11-33KV 6.6-132KV
TYPE CONTACT TYPE
APPLICATION DEAD TESTING OF VOLTAGE FOR OVERHEAD LINES
LINK STICK MOUNTABLE YES YES
BRIDGING PROTECTION YES YES
SPARK PROTECTION YES YES
GREEN = ARMED YES YES
RED = VOLTAGE DETECTED YES YES
CARRY BAG YES YES
DDT-DWNG 12500
SAP NO 0212340
DYNOMOMETER
CODE OHA-1000
USAGE ACCURATE MEAS OF
FORCES
FULL SCALE/CAPACITY 1000KG
OPERATES THROUGH PULL ROD
YES
MOVEMENT
SUPPLIED WITH BUILT - IN
YES
PRECISION POTENTIOMETER
PRESSURE TIGHT AND PRESSURE
YES
TESTED
WORKING TEMPERATURE MAX + 60 ° C
TARED TO APPROX. 10% OF FULL
YES
SCALE
SUPPLIED CALLIBRATED YES
ACCESSORIES CARRY CASE
PATHFINDERS
CODE OHA-1005 OHA-1010
TYPE MK8 MK10-GSM
SUITABLE VOLTAGE APPLICATION 11-33KV 11-33KV
USAGE OVERHEAD LINE FAULT PASSAGE INDICATOR
PORTABLE YES YES
GSM MODEM NO YES
TO ALLOW FAULT
GSM MODEM PURPOSE ALARM TO BE SENT
USING SMS TEXT MSG
INTEGRAL AND FACTORY
YES YES
CHANGEABLE LITHIUM BATTERY
BATTERY LIFE UP TO 10 YEARS UP TO 10 YEARS
RESPOND TO PHASE/PHASE AND
YES YES
PHASE/ EARTH FAULTS
INDENTIFIES PERMANENT,
TRANSIENT AND INTERMITTENT YES YES
FAULTS
WEATHER PROOFED AND SEALED YES YES
CABLE GRIPS
CODE OHA-1515 OHA-1520
TYPE ALUMINIUM UNIVERSAL
TONNAGE 2TON 2TON
ROPE SIZE DIA 4 - 22MM 4 - 22MM
JAWS BOTH SMOOTH ONE SMOOTH
ONE SERRATED
GALVINISED STEEL GUY GRIPS FOR GALVANISED STEEL STRAND (STAY WIRE)
OHW-1330 OHW-1350
CODE OHW-1333 OHW-1335 OHW-1340 OHW-1345 OHW-1355 OHW-1360 OHW-1365
OHW-1332 OHW-1352
DOUBLE DOUBLE
TYPE
WRAP WRAP
MATERIAL GALV STEEL GALV STEEL GALV STEEL GALV STEEL GALV STEEL GALV STEEL GALV STEEL GALV STEEL GALV STEEL
SUITABLE STAYWIRE 3/3.35MM 3/4.00MM 3/3.35MM 7/3.35MM 5/4.00MM 7/4.00MM 7/4.00MM 19/2.65MM 19.3.35MM
STAYWIRE STRENGTH 1100MPA 1100MPA 1100MPA 1100MPA 1100MPA 1100MPA 1100MPA 1100MPA 1100MPA
STAYWIRE DIA 7.2MM 8.76MM 7.21MM 10.05MM 10.97MM 12.19MM 12.19MM 13.21MM
COLOUR CODE BLACK RED BLACK BLUE BROWN GREEN GREEN ORANGE
ULTIMATE TENSILE
29KN 96.8KN
STRENGTH
SUITABLE POLE TOP DIA 200MM 250MM
APPROX LENGTH 600MM 790MM 860MM 890MM 960MM 1500MM 1300MM
DDT-DWNG 3069 7047 3069 7047
SAP NO 0168541 0185947 0402509 0212783
ALUMINIUM ARMOR - GRIPS SUSPENSION UNIT, WITH INTEGRAL RODS, FOR ALUMINIUM BASED CONDUCTORS
CODE OHW - 1480 OHW-1490
TYPE AGS + RODS AGS ONLY
CONDUCTOR RANGE PINE - MINK WOLF
CONDUCTOR DIA 10.83 - 10.98MM 18.13MM
COLOUR CODE RED WHITE
ROD LENGTH 1040MM 1395MM (IF COMPLETE SET)
ROD DIA 4.06MM 5.18MM (IF COMPLETE SET)
RODS PER SET 8 12 (IF COMPLETE SET)
DDT-DWNG 7033 7033 (IF COMPLETE SET)
SAP NO 0168965 0402019 (IF COMPLETE SET)
BASE PLATES
MATERIAL STEEL
CODE SIZE SHAPE SUITABLE STAY ROD SLOT/HOLE DDT-DWGN SAP NUMBER
GRADE
OHM-1170
300x300x6MM M12 NON-ADJUSTABLE 55X14MM SLOT 0163417
OHM-1170S
OCTAGONAL 300W
OHM-1180 3172
340x375x6MM 0163419
OHM-1180S
OHM-1168 350x6MM ROUND M20 NON-ADJUSTABLE 70X22MM SLOT 0243420
OHM-1190 380x380x6MM
OHM-1197 600x600x6MM 300W 3172 0163420
OHM-1192 380x380x6MM M16 ADJUSTABLE 18MM2 HOLE
OHM-1182 375x375x6MM
SQUARE
OHM-1195 M20 ADJUSTABLE 22MM2 HOLE
450x450x6MM 300W
OHEM-1075
OHM-1181 375x375x6MM
M24 ADJUSTABLE 27MM2 HOLE
OHM-1196 450x450x6MM 300W
ROCK ANCHOR
CODE OHM-1100
MATERIAL GRADE S355JR/350WA
STRENGTH 96KN
ASSEMBLY CONSISTS OF STAY ROD, ROCK ANCHOR AND WEDGE
STAYROD SPEC 20MM DIA X 770MM LONG ROD
1 X 42MM DIA AND 25MM DIA EYE
ROCK ANCHOR SPEC 32MM DIA X 910MM LONG ROD
10MM RING WRAPPED ROUND AND
WELDED ONE SIDE
1 X 75MM SAW CUT OTHER SIDE
WEDGE SPEC 50MM LONG X 12MM HIGH X 25MM WIDE
WITH A 3MM HOLE
DDT-DWNG 3054
SAP NO 0163401
EYE BOLTS
OHM-1300
CODE OHM-1304
OHM-1300S
SIZE (DIA X LENGTH) M20 X 250MM M20 X 350MM
THREAD LENGTH 240MM
EYE INSIDE DIA 19MM
SUPPLIED WITH 2 X CW
3 X R FW
2 X NUTS
MATERIAL GRADE STEEL 070M20
GALVANISING HOT DIPPED
MINIMUM FAILING LOAD 70KN
DDT-DWNG 3005
SAP NO 0163768
EYE NUTS
OHM-1280 OHM-1290
CODE
OHM-1280S OHM-1290S
SIZE (SUITABLE BOLT DIA) M16 M20
MATERIAL GRADE STEEL BS 970 070M20
GALVANISING HOT DIPPED
MINIMUM FAILING LOAD 40KN 70KN
DDT-DWNG 3004
SAP NO 0163908 0163909
*EYE NUT THREADS TO BE OILED WITH TAPPING OIL TO PREVENT
CORROSION
BONDING CLIP
OHM-1201
CODE
OHM-1200S
SIZE 50MM LONG
40MM WIDE
2MM THICK
INSIDE LOOP DIA 7MM
HOLE DIA 22MM
MATERIAL GRADE STEEL MILD STEEL
GALVANISING HOT DIPPED
MINIMUM FAILING LOAD 40KN
DDT-DWNG 3033
SAP NO 0164312
COACH SCREWS
OHM-1840
CODE OHM-1841 OHM-1845 OHM-1846
OHM-1840S
SIZE (DIA X LENGTH M12 X 75MM M8 X 40MM M10 X 60MM M6 X 75MM
MATERIAL GRADE STEEL SAE1008
GALVANISING HOT DIPPED ELECTRO
DDT-DWNG 3090
SAP NO 0163803
SET SCREWS
CODE OHM-1890 OHM-1895 OHM-1900 OHM-1910 OHM-1930
SIZE (DIA X LENGTH) M12 X 40MM M12 X 65MM M16 X 40MM M16 X 65MM M20 X 65MM
GALVANISING HOT DIPPED ELECTRO
SUPPLIED WITH 1 R FW 1 X SW 1 X NUT
MATERIAL GRADE STEEL 4.8
DDT-DWNG 3082
SAP NO 0163642 0163641 0404337 0163638 0163639
*R FW - ROUND FLAT WASHER
*SW - SPRING WASHER
CLOUT NAILS
CODE OHM-1164 OHM-1164S
SIZE (DIA X LENGTH) M2.8 X 40MM
GALVANISING ELECTRO HOT DIPPED
DDT-DWNG 3169
SAP NO 0163941
STAPLES/U-NAILS
CODE OHM-1460 OHM-1460S
SIZE (DIA X LENGTH) M4 X 40MM
GALVANISING ELECTRO HOT DIPPED
INSIDE SHOULDER SPREAD 8MM
SAFETY WORKING GAUGE 8SWG
DDT-DWNG 3129
SAP NO 0163938
SPRING WASHERS
CODE OHM-1420
SIZE M20
MATERIAL GRADE SPRING STEEL
GALVANISING HOT DIPPED
OUTSIDE DIA 30.6MM
INSIDE DIA 20.2MM
DDT-DWNG 3014
SAP NO 0241918
*SPRING WASHERS ALSO AVAILABLE IN OTHER SIZES
CURVED WASHERS
CODE OHM-1430 OHM-1450 OHM-1452 OHM-1453
SIZE: LENGTH X WIDTH X 50 X 50 X 65 X 65 X 80 X 80 X 75 X 75 X 6 X M20
THICKNESS X HOLE DIA 5 X M22 6 X M22 6 X M20 CURVED CAST FLAT
MATERIAL GRADE MILD STEEL MCI/SG
GALVANISING HOT DIPPED
RADIUS 75MM
DDT-DWNG 3014
SAP NO 0163896
U-BOLTS
CODE OHM-2050 OHM-2052
SIZE (DIA X BOLT LENGTH) M20 X 350MM M16 X 102MM
THREAD LENGTH 180MM 50MM
INSIDE DISTANCE BETWEEN LEGS 280MM 73MM
GALVANISING HOT DIPPED
SUPPLIED WITH 4 X M20 R FW 6 X M16 R FW
4 X M20 CW
4 X M20 NUTS
DDT-DWNG 6098
SAP NO 0163763
CLEVIS BOLT/PIN
CODE OHM-2030
SIZE (DIA X OVERALL LENGTH) M16 X 55MM
TYPE PIN
MATERIAL GRADE MILD STEEL
HOLE DIA M6
D-SHACKLES
OHM-1322
CODE OHM-1310 OHM-1963
OHM-1322S
TYPE STRAIGHT TWISTED
MATERIAL DROP FORGED
GALVANISING HOT DIPPED
MINIMUM FAILING LOAD 210KN 70KN 120KN
NOMINAL COUPLING
80MM 70MM 72MM
LENGTH
SHACKLE OPENING 20MM 18MM 18MM
SHACKLE THICKNESS 16MM 13MM 13MM
1 X BOLT M20 X 90 1 X BOLT M20 X 90
1 X PIN M16 X 57
CLEVIS BOLT OR PIN 1 X S/ST HB SPLIT PIN 1 X S/ST HB SPLIT PIN
1 X S/ST HB SPLIT PIN
ASSEMBLY 1 X M20 R FW 1 X M16 R FW
1 X M16 R FW
1 X M20 NUT 1 X M16 NUT
DDT-DWNG 7018 3010 7019
SAP NO 0163403 0163400 0163408
*S/ST = STAINLESS STEEL
*RFW = ROUND FLAT WASHER
CLEVIS-BALLS
CODE OHM-1986 OHM-1985
TYPE V-BOLT Y-BOLT
MATERIAL DROP FORGED STEEL
GALVANISING HOT DIPPED
MINIMUM FAILING LOAD 120KN
NOMINAL COUPLING LENGTH 80MM 60MM
OVERALL LENGTH 103MM 95MM
CLEVIS OPENING 18MM 50MM
1 X BOLT M16 X 75
1 X BOLT M16 X 100
1 X S/ST HB SPLIT PIN
CLEVIS BOLT ASSEMBLY 1 X M16 R FW
1 X M16 R FW
1 X M16 NUT
1 X M16 NUT
DDT-DWNG 6059
SAP NO 0167508
*S/ST = STAINLESS STEEL
*RFW = ROUND FLAT WASHER
BALL-EYE OVAL
CODE OHM-1960
MATERIAL DROP FORGED STEEL
GALVANISING HOT DIPPED CHAIN LINK
MINIMUM FAILING BALL-HOOK CODE OHM-1962
120KN
LOAD CODE OHM-1961 DROP FORGED
NOMINAL COUPLING MATERIAL
100MM MATERIAL DROP FORGED STEEL STEEL
LENGTH
GALVANISING HOT DIPPED GALVANISING HOT DIPPED
EYE OPENING 22MM
MINIMUM FAILING MINIMUM FAILING
EYE LENGTH 48MM 70KN 120KN
LOAD LOAD
MATERIAL THICKNESS 13MM NOMINAL NOMINAL
95MM 48MM
DDT-DWNG 7008 COUPLING LENGTH COUPLING LENGTH
SAP NO 0010258 HOOK OPENING 21MM EYE OPENING 24MM
SOCKET-CLEVIS
CODE OHM-1980
MATERIAL DROP FORGED STEEL
GALVANISING HOT DIPPED
MINIMUM FAILING LOAD 120KN
NOMINAL COUPLING LENGTH 80MM
1 X LOCKING SPLIT PIN
1 X CLEVIS BOLT M16 X 75
SUPPLIED WITH
1 X M16 R FW
1 X M16 NUT
DDT-DWNG 7021
SAP NO 0010259
*RFW = ROUND FLAT WASHER
SOCKET-THIMBLE
CODE OHM-1990
MATERIAL MCI
GALVANISING HOT DIPPED
NOMINAL COUPLING LENGTH 110MM
SOCKET OPENING 19.2MM
TONGUE-EYE
CODE OHEM-1000
MATERIAL DROP FORGED STEEL
GALVANISING HOT DIPPED
MINIMUM FAILING LOAD 70KN
NOMINAL COUPLING LENGTH 102MM
MATERIAL DIA 16MM
SAG ADJUSTER
CODE OHM-1959
MATERIAL S355JR/350WA
GALVANISING HOT DIPPED
MINIMUM FAILING LOAD 120KN
PLATE THICKNESS 16MM
ALL HOLES DIA 18MM
CHAMFERED 1MM ALL AROUND
DDT-DWNG 7042
SAP NO 0175857
BARBED WIRE
CODE OHM-1305
CLASS A
TYPE 4 POINT
STRANDING DOUBLE
GALVANISING FULLY GALVANISED
ANTI-CLIMBING & BIL GAP DEVICE
ANTI-CLIMBING DEVICE
CODE OHM-2000
CONSISTS OF 3 X 500MM STEEL SECTIONS
12 X CLOUT NAILS 40MM
DDT-DWNG 3036
2 TANK
3 TANK
MOULDS
MOULD MOULD COND WELD WELD HANDLE SCRAPER
CODE
TYPE REF A/B MM2 METAL METAL + CLAMP
CAD-221025 TA TAC-Y1 25/25 32 32PLUSF20 L160 B136A
CAD-222459 TA TAC-Y3 50/50 90 90PLUSF20 L160 B136B
TA
CAD-221035 TA TAC-Y4 70/70 90 90PLUSF20 L160 B136B
CAD-222461 TA TAC-Y5 95/95 115 115PLUSF20 L160 B136B
CAD-222463 TA TAC-Y6 120/120 150 150PLUSF20 L160 B136B
CAD-221063 TA TAC-Y2-Y1 35/25 45 45PLUSF20 L160 B136A
CAD-221071 TA TAC-Y3-Y2 50/35 65 65PLUSF20 L160 B136A
CAD-221077 TA TAC-Y4-Y3 70/50 90 90PLUSF20 L160 B136B
CAD-221094 TA TAC-Y6-Y4 120/70 90 90PLUSF20 L160 B136B
XA
CAD-221135 XA XAC-Y1-Y1 25/25 45 45PLUSF20 L160 B136A
CAD-221138 XA XAC-Y2-Y2 35/35 65 65PLUSF20 L160 B136A
CAD-221142 XA XAC-Y3-Y3 50/50 90 90PLUSF20 L160 B136B
CAD-221153 XA XAC-Y5-Y5 95/95 150 150PLUSF20 L160 B136B
CAD-221159 XA XAC-Y6-Y6 120/120 200 200PLUSF20 L160 B136B
VE
VF
D
WEL R
CAD D SEALE 03
MOL P/N: T-4
EAR-1000 THREADED B
COPPER
EAR-1002 M16X1.2M THREADED A (SABS)
EAR-1003 UNTHREADED A (SABS) COPPER
EAR-10042 UNTHREADED
M16X1.8M A (SABS) COPPER
EAR-1005 THREADED
STRIKER CAP
CODE EAR-1013
MATERIAL BRASS
THREAD 16MM
OVERALL LENGTH 60MM
DIAMETER 25MM
AUTO RECLOSERS
CODE OHT-1200 OHT-1210
RATED APPLICATION 11/22KV 33KV
MAXIMUM CONTINUOUS CURRENT 400A
SHORT CIRCUIT BREAKING CAPACITY 8KA
MOUNTING POLE
SURGE ARRESTER MOUNTING BRACKETS
MICRO-PROCESSOR BASED CONTROLLER
SUPPLIED WITH
INTEGRATED REMOTE TERMINAL UNIT (IRTU)
CONTROL CABLE
DDT-DWGN 3180
SAP NO 0185155 0182799
16-1000KVA SPECIFICATION
KVA NO PRIMARY SECONDARY DDT- SAP
CODE MOUNTING APPLICATION
RATING PHASES VOLTAGE VOLTAGE DWGN NO
OHT-1000 COASTAL 0175077
11kV
OHT-1005 INLAND 0402804
OHT-1010 COASTAL 3021 0175078
16 1 22kV 240V SINGLE POLE
OHT-1015 INLAND 0402806
OHT-1138 19kV SWER INLAND 0170851
OHT-1061 33kV COASTAL
OHT-11271 COASTAL
11kV
OHT-11270 PLATFORM INLAND
630 3 415V
OHT-11273 MNT COASTAL
22kV
OHT-11272 INLAND
OHT-11275 COASTAL
11kV PLATFORM
OHT-11274 800 3 415V INLAND
MNT
OHT-11276 22KV INLAND
2 (DUAL) PHASE
PLATFORM MOUNT
73
* Drawings are not for manufacturing purposes
ALUMINIUM CONDUCTOR STEEL REINFORCED - ACSR (BRITISH STANDARD SIZES)
OVERALL COEF- INITIAL FINAL CUR-
EQUIVAL STRANDING DIAME- ULTIMATE DC RESIS- STANDARD
DIAM- ALUMINI- STEEL TOTAL FICIENT MODULUS MODULUS RENT
CODE NAME COPPER AND WIRE TER OVER MASS KG/KM TENSILE TANCE AT DRUM
ETER UM AREA AREA AREA OF LINEAR OF ELASTIC- OF ELAS- RAT-
AREA DIAMETER STEEL STRENGTH 20° LENGTH
(STD) EXPANSION ITY TICITY ING
MM2 MM MM MM MM2 MM2 MM2 ALUMNIUM STEEL TOTAL NEWTON /°C X 10-6 MPA MPA Ω/K A M
SQUIRREL 12,90 6/1/2,11 2,11 6,33 20,98 3,50 24,48 57,70 27,50 85,20 8020 19,331 54600 80400 13,677 130 3000
GOPHER 16,30 6/1/2,36 2,36 7,08 26,25 4,37 30,62 72,20 34,40 107 9610 19,31 52700 80400 10,933 150 3000
FOX 22,58 6/1/2,79 2,79 8,37 36,68 6,11 42,80 101 48,10 149 13100 19,31 50700 80400 0,7822 190 2500
FERRET 25,81 6/1/3,00 3,00 9,00 42,41 7,07 49,48 117 55,60 173 15200 19,31 50200 80400 0,6766 210 1500
RABBIT 32,26 6/1/3,35 3,35 10,05 52,88 8,81 61,70 145 69,40 214 18500 19,31 49500 80400 0,5426 240 1500
MINK 38,71 6/1/3,66 3,66 10,98 63.13 10,52 73,65 174 82,80 257 21900 19,31 49100 80400 0,4546 260 1500
HARE 64,52 6/1/4,72 4,72 14,16 104,98 17,50 122,48 289 138 427 36000 19,31 48500 80400 0,2733 360 1500
6/4,72 +
DOG 64,52 4,71 14,15 104,98 13,55 118,53 289 100 389 34700 19,92 48800 76400 0,2733 360 2000
7/1,57
TIGER 80,65 30/7/2,36 4,72 16,52 131,23 30,62 161,85 364 242 606 58700 18,43 56900 83400 0,2202 420 2000
WOLF 96,77 30/7/2,59 7,77 18,13 158,06 36,88 194,94 438 292 730 69200 18,43 55700 83400 0,1828 470 2000
LYNX 112,90 30/7/2,79 8,37 19,53 183,41 42,80 226,20 508 330 846 79300 18,43 54900 83400 0,1576 520 2000
PANTHER 129,00 30/7/3,00 9,00 21,00 212,06 49,48 261,54 588 391 970 90800 18,43 54300 83400 0,1363 560 2000
Electrical Wholesalers
LION 145,20 30/7/3,18 9,54 22,26 238,27 55,60 293,86 660 440 1100 101000 18,43 53900 83400 0,1213 610 2000
BEAR 161,30 30/7/3,35 10,05 23,45 264,42 61,70 326,12 733 488 1220 112000 18,43 53600 83400 0,1093 650 2000
ZEBRA 258,10 54/7/3,18 9,54 28,62 428,88 55,60 484,48 1190 440 1630 133000 19,91 47,300 73200 0,0674 860 1500
48/4,27 +
BERSFORD 430,70 9,96 35,58 687,36 60,60 747,96 1906 480 2386 177650 20,68 43200 68800 0,0420 1132 2000
7/3,32
ALUMINIUM CONDUCTOR STEEL REINFORCED - ACSR CANADIAN STANDARD SIZES)
COEF- FINAL
EQUIVAL STRANDING DIAMETER OVERALL ULTIMATE INITIAL DC RESIS- CUR- STANDARD
ALUMINI- STEEL TOTAL FICIENT MODULUS
CODE NAME COPPER AND WIRE OVER DIAMETER MASS KG/KM TENSILE MODULUS OF TANCE AT RENT DRUM
UM AREA AREA AREA OF LINEAR OF ELASTIC-
AREA DIAMETER STEEL (STD) STRENGTH ELASTICITY 20° RATING LENGTH
EXPANSION ITY
KINGBIRD 197,04 18/1/4,78 4,78 23,90 323,01 17,95 340,96 896 142 1038 71320 21,69 40400 66200 0,0891 710 2000
45/3,38 +
TERN 253,00 6,75 27,00 403,77 27,83 431,60 1120 220 1340 98700 21,12 42900 66600 0,0718 830 1500
7/2,25
45/2,70 +
RAIL 304,00 7,41 29,59 483,84 33,54 517,39 1340 265 1610 117000 21,11 42400 66700 0.060 920 2000
7/2,47
INTERNATIONAL SIZES
CONDUCTOR
CORE RATED
ACCC® CONDUCTOR DIAMETER CORE DIAMETER WEIGHT RATED AC AMPACITY
STRENGTH
STRENGTH
INTERNATIONAL
kcmil mm2 in mm in mm lb/kft kg/km kips kN kips kN 90 ºC 180 ºC
SIZE
HELSINKI 297 150,6 0,616 15,65 0,235 5,97 317 471 13,6 60,4 15,5 68,9 473 765
COPENHAGEN 434 219,9 0,720 18,29 0,235 5,97 444 661 13,6 60,4 16,4 72,8 597 971
REYKJAVIK 440 223,1 0,741 18,82 0,280 7,11 466 694 19,3 85,7 22,1 98,3 605 986
MONTE CARLO 451 228,5 0,818 20,78 0,415 10,54 537 799 42,3 188,3 45,2 201,2 628 1,027
ULS MONTE
451 228,5 0,819 20,79 0,415 10,54 537 799 50,7 225,6 53,6 238,6 628 1,027
CARLO
GLASGOW 467 236,7 0,769 19,53 0,305 7,75 492 732 22,9 101,7 25,9 115,0 629 1,027
CASABLANCA 540 273,6 0,807 20,50 0,280 7,11 561 834 19,3 85,7 22,7 101,1 685 1,120
OSLO 619 313,8 0,882 22,40 0,345 8,76 659 981 29,3 130,2 33,2 147,8 752 1,234
LISBON 623 315,5 0,858 21,79 0,280 7,11 637 948 19,3 85,7 23,3 103,5 748 1,227
AMSTERDAM 725 367,4 0,927 23,55 0,305 7,75 740 1101 22,9 101,7 27,5 122,4 824 1,355
ULS 25MM 753 381,8 0,984 25,00 0,415 10,54 817 1216 50,7 225,6 55,6 247,2 855 1,406
BRUSSELS 832 421,4 0,990 25,15 0,320 8,13 850 1265 25,2 112,0 30,5 135,7 896 1,479
ULS LEIPZIG 802 406,4 0,990 25,15 0,415 10,54 842 1253 41,3 183,5 46,6 207,3 879 1,448
STOCKHOLM 2L 914 463,3 1,039 26,39 0,345 8,76 937 1395 29,3 130,2 53,1 156,2 952 1,576
STOCKHOLM 3L 895 453,7 1,039 26,39 0,345 8,76 913 1368 29,3 130,2 35,0 155,7 943 1,560
WARSAW 1002 507,5 1,091 27,71 0,345 8,76 1021 1520 29,3 130,2 35,7 158,7 1,008 1,673
DUBLIN 1035 524,5 1,108 28,14 0,375 9,53 1064 1583 34,6 153,8 41,2 183,3 1,030 1,711
HAMBURG 1078 546,4 1,127 28,63 0,345 8,76 1093 1627 29,3 130,2 36,2 160,9 1,045 1,752
KOLKATA 1073 543,5 1,127 28,63 0,375 9,53 1104 1643 34,6 153,8 41,4 184,0 1,051 1,748
ULS MAHAKAM 1075 544,9 1,142 29,01 0,415 10,54 1127 1677 50,7 225,6 49,2 218,9 10,56 1,752
MILAN 1120 567,7 1,146 29,11 0,345 8,76 1133 1686 29,3 130,2 36,4 162,1 1,079 1,797
ROME 1169 592,5 1,177 29,90 0,375 9,53 1192 1774 34,6 153,8 42,1 187,1 1,109 1,850
VIENNA 1242 629,2 1,198 30,43 0,345 8,76 1245 1853 29,3 130,2 37,2 165,5 1,149 1,918
BUDAPEST 1319 668,3 1,240 31,50 0,375 9,53 1333 1984 34,6 153,8 43,0 191,4 1,193 1,996
PRAGUE 1363 690,7 1,251 31,78 0,345 8,76 1364 2031 29,3 130,2 38,0 169,0 1,213 2,032
ULS PRAGUE 1363 690,7 1,251 31,78 0,345 8,76 1364 2031 53,0 155,9 43,8 194,8 1,213 2,032
MUMBAI 1353 685,4 1,251 31,78 0,375 9,53 1367 2035 34,6 153,8 43,2 192,0 1,209 2,125
MUNICH 1447 733,1 1,293 32,84 0,375 9,53 1458 2170 34,6 153,8 43,8 195,0 1,259 2,113
LONDON 1498 759,0 1,315 33,40 0,385 9,78 1511 2248 36,4 162,1 46,8 402,8 1,288 2,164
PARIS 1606 813,7 1,345 34,16 0,345 8,76 1590 2366 29,3 130,2 39,6 175,9 1,338 2,254
BORDEAUX 1738 880,8 1,408 35,76 0,415 10,54 1859 2766 52,3 188,3 53,5 237,9 1,409 2,381
ANTWERP 1865 944,8 1,451 36,86 0,385 9,78 1855 2760 36,4 162,1 48,4 215,2 1,466 2,483
ULS ANTWERP 1865 944,8 1,451 36,86 0,385 9,78 1855 2760 43,7 194,2 55,6 247,3 1,466 2,483
BERLIN (MADRID
1986 1006,5 1,504 38,20 0,415 10,54 1982 2949 42,3 188,3 55,1 245,0 1,527 2,594
ICE)
MADRID 1999 1013,0 1,504 38,20 0,385 9,78 1981 2948 36,4 162,1 49,2 219,1 1,530 2,602
ATHENS 2782 1409,6 1,762 44,75 0,415 10,54 2732 4066 42,3 188,3 60,2 267,6 1,845 3,189
ELECTRICAL PROPERTIES
SELF SUPPORTING SYSTEM SUPPORTING CORE SYSTEM
CURRENT SHORT CIR- CONDUCTOR CONDCUTOR
CABLE SIZE RATING CUIT RATING RESISTANCE RESISTANCE INDUCTION IMPENDANCE INDUCTION IMPENDANCE
SUPPORTING
(NOTE 1) (NOTE 2) @ 20°C (AC) @ 80°C REACTANCE (Z) @ 50HZ REACTANCE (Z) @ 50HZ
CORE SIZE
@ 50HZ @ 80°C @ 50HZ @ 80°C
MM2 A KA Ω/KM Ω/KM Ω/KM Ω/KM MM2 Ω/KM Ω/KM
25 105 2,3 1,200 1,490 0,096 1,493 54,6 0,101 1,493
53 144 3,2 0,868 1,078 0,096 1,082 54,6 0,097 1,082
50 183 4,6 0,641 0,796 0,090 0,801 54,6 0,089 0,801
70 228 6,4 0,443 0,550 0,089 0,557 54,6 0,086 0,657
95 277 8,5 0,320 0,397 0,086 0,406 54,6 0,081 0,405
120 322 11,0 0,253 0,314 0,084 0,325 70 0,079 0,324
150 350 13,8 0,206 0,256 0,082 0,269 95 0,079 0,268
Notes:
1. Continuous current ratings are given for ambient temperature of 35 ºC and maximum conductor temperature of 80 ºC. For other ambient temperatures
use adjoining rating factors.
2. Short circuit ratings of 1 second duration, for a final conductor temperature of Temp ºC 20 30 35 40 45
130 ºC. Factor 1.11 1.05 1.00 0.94 0.88
MECHANICAL PROPERTIES
CABLE SELF SUPPORTING SYSTEM SUPPORTING CORE SYSTEM
CONDUCTOR DIAMETER CORE DIAMETER
SIZE APPROX APPROX MAXIMUM SUPPORT- APPROX APPROX MAXIMUM
PHASE ASSEMBLY ASSEMBLY DESIGN ING CORE ASSEMBLY ASSEMBLY DESIGN
MIN MAX MIN MAX
CORES DIAMETER MASS LOAD SIZE DIAMETER MASS LOAD
MM2 MM MM MM MM MM KG/KM KN MM MM KG/KM KN
25 5,6 6,5 8,4 9,6 25 400 5 54,6 26 507 6
35 6,6 7,5 9,8 11,1 27 540 7 54,6 28 612 6
50 7,7 8,6 10,9 12,3 29 697 9 54,6 32 730 6
70 9,3 10,2 12,9 14,3 33 982 14 54,6 34 944 6
95 11,0 12,0 14,6 18,2 37 1302 19 54,6 38 1183 6
120 12,5 13,5 16,1 17,5 41 1470 24 70,0 40 1600 8
150 13,9 15,0 17,5 19,2 45 2011 30 95,0 44 1870 13
ABOVE PLUS 25MM2 AUXILIARY CORE
25 25 505 32 612
35 32 645 34 717
50 34 802 36 835
70 N/A N/A N/A N/A 38 1087 N/A N/A 38 1049 N/A
95 42 1407 42 1288
120 44 1575 50 1705
150 48 2116 56 1975
CABLE DESCRIPTION
CABLE SIZE (MM ) 2
4 10
PHASE CONDUCTOR RESISTANCE (OHM/KM) DC @ 20°C 4,80 1,90
PHASE CORE IMPEDANCE (Z) (OHM/KM) 5,88 2,34
CURRENT RATING (A)* 30 50
SYMMETRICAL SHORT CIRCUIT RATING FOR 1s IN KA 0,572 1,431
*NOTE: IN AIR WITH 30°C AMBIENT WITH MAXIMUM CONDUCTOR TEMPERATURE 90 °C
MECHANICAL PROPERTIES
CABLE SIZE (MM2) 4 10
PHASE CONDUCTORE (NO X OD) (MM) 7 X 0,92 7 X 1,45
NOMINAL INSULATION THICKNESS (MM) 1,0 1,0
EARTH SIZE (MM2) 4 10
EARTH CONDUCTOR (NO X OD) (MM) 8 X 0,85 18 X 0,85
NORMAL SHEATH THICKNESS (MM) 1,4 1,4
APPROXIMATE CABLE OD (MM) 9,0 11,0
APPROXIMATE CABLE MASS (KG/KM) 121 249
INSTALLATION DATA
BASED ON
SPAN (M) 10 20 30 40 50
UTS* MWT**
SAG*(MM) 4MM2 40 165 370 650 1020 1480 370
SAG*(MM) 10MM2 35 140 310 650 870 3600 900
NOTE:
*ASSUMING WORST CONDITIONS IE TEMEPRATURE -5,5°C WITH SIMULTANEOUS WIND SPEED OF 31M/S AND MEASURED AT MIDSPAN
*UTS = MINIMUM ULTIMATE TENSILE STRENGTH. SAFETY FACTOR OF 2.5
**MWT = MINIMUM WORKING TENSION
AIRDAC: SNE
CABLE DESCRIPTION
CABLE SIZE (MM ) 2
10 16
PHASE CONDUCTOR RESISTANCE (OHM/KM) DC @ 20°C 1,90 1,20
EARTH SIZE (MM2) 7,5 10
NEUTRAL SIZE (MM2) 10 16
PHASE CORE IMPEDANCE (Z) IOHM/KM) 2,34 1,47
CURRENT RATING *(A) 50 70
PILOT CORES (NO X OD) SOLID (MM) 2 X 1,13 2 X 1,13
*NOTE: IN AIR, WITH 30°C AMBIENT WITH MAXIMUM CONDUCTOR TEMEPRATURE 90°C
MECHANICAL PROPERTIES
CABLE SIZE (MM ) 2
10 16
PHASE CONDUCTOR (NO X OD) (MM) 7 X 1,35 7 X 1,35
NORMAL INSULATION THICKNESS (MM) 1,0 1,0
NEUTRAL CONDUCTOR (NO X OD) (MM) 7 X 1,33 7 X 1,76
EARTH CONDUCTOR (NO X OD) (MM) 3 X 1,78 3 X 2,20
NOMINAL SHEATH THICKNESS (MM) 1,6 1,6
APPROXIMATE CABLE OD (MM) 12,8 14,5
APPROXIMATE CABLE MASS (KG/KM) 320 485
INSTALLATION DATA
SPAN (M) 10 20
SAG*(MM) 10 MM2 45 180
SAG*(MM) 16 MM2 40 170
NOTE:
*ASSUMING WORST CONDITIONS IE -5,5°C WITH SIMULTANEOUS WIND SPEED OF 31 M/S AND MEASURED AT MIDSPAN
*UTS = MINIMUM ULTIMATE TENSILE STRENGTH
**MWT = MINIMUM WORKING TENSION
GLOSSARY
Amperage: the amp is a measure of
A
electric current.
Direct current: electrical current that
AAC All aluminium conductor. D.C.
normally flows in one direction only.
AAAC All aluminium alloy conductor.
ABC Aerial bundle conductor.
Alternating current: electric current The amount of electricity being used
which reverses direction repeatedly Demand at any given moment by a single
A.C.
due to a change in Voltage which customer, or a group of customers.
occurs at the same frequency.
Aliminium conductor steel re-
ACSR
inforced. Power lines that carry electricity
Basic unit of measurement for
Ampere Distribution through towns and neighbourhoods
electric current.
Line/Grid to homes and businesses. Can run
A cable provided with a wrapping of overhead or underground.
Armoured metal, usually steel wires or tapes,
Cable primarily for the purpose of mechani-
cal protection. A form of energy produced by the
Electricity
Basic insulation level - the measure movement of electrons.
of the insulation capability of a piece
BIL of electrical equipment; the equip- Electric Flow of electric charges (electrons)
ment’s ability to withstand very high Current measured in Amperes.
Voltage surges.
Bare A conductor not covered with insulat- ECU Energy Control Unit: i.e. a meter.
Conductor ing material.
An electrical conducting path formed
by the permanent joining of metallic Safety devices which protect
Bonding parts. Intended to assure electrical electrical appliances by preventing
continuity and the capability to safely too much electric current flowing
conduct any likely current. through them. The fuse is a thin wire
Fuse
inside a protective case. If too much
Strong lightweight material devel-
Composite/ electric current flows through the
oped in the laboratory with fibers
Silicone/ wire, it melts and stops the current
of more than one kind and bonded
Polymer flowing.
together chemically.
Current Transformers: Used for
measurement of electric currents.
When current in a circuit is too high, A device that converts mechani-
CT
a CT produces a reduced current cal power from an engine, water
accurately proportional to the current wheel, windmill, or other source,
in the circuit. Generator
into electrical power. Generator has
A stranded conductor with or without internal parts that spin as they make
insulation and other coverings, or a electricity.
Cable
combination of conductors insulated
from one another.
High Voltage Line: Electricity being
A device located in a substation that
transmitted from generating power
supports Voltage within a local area.
stations/plants to electrical substa-
Often added to transmission and dis- HV
Capacitor tions located near demand centres.
tribution systems to keep the Voltage
Also refer Transmission Line/
acceptably high as electric demand
Network.
grows over time.
Switch that turns utility equipment on Hz Hertz: Unit of frequency.
Circuit
or off. May be operated manually or A material (such as glass or porce-
Breaker
automatically. lain) that does not easily allow heat,
High-band width cable consisting of Insulator
electricity, light or sound to pass
two concentric cylindrical conductors through it.
Coaxial Cable with a common axis that is used for
high-speed data communication and kA kilo-Ampere = 1000 Amperes
video signals.
A material that conducts heat, kN kilo-Newton = 1000 Newtons
electricity, light or sound with little kV kilo-Volt = 1000 Volts
resistance because it’s usually a me-
tallic substance. Best conductor at kilovolt-Ampere = 1000 Volt
kVA
Conductor normal temperature ranges is silver. Amperes
Most common is copper. Conductor kW kilowatt = 1000 Watts
must have enough capacity to carry
the highest demand that it will ex- Kilowatt-hour: one kilowatt of elec-
perience, or it could overheat and fail. kWh
tricity produced or used in one hour
Provides electrical connection/
Connector disconnection. Join two or more con-
ductors together in one assembly. Low Voltage Line - electricity is
Cu Copper. transmitted from distribution substa-
LV
tions to properties and other places
The shortest path between two con- of consumption in low-voltage lines.
ductive parts, or between a conduc-
Creepage
tive part and the bounding surface of
Distance
the equipment, measured along the Eskom - Large Power User: Voltage
LPU
surface of the insulation. level 11kV or 22kV.