Stopping Procedure: MLN Block 405 Algeria Operator Training

This document provides instructions for normal and emergency stopping procedures for a CX501KB series gas turbine generator. The normal stopping procedure involves ramping the generator down to 100kW over 15 minutes of cooldown at idle speed. The emergency stop procedure opens the breaker and stops fuel and ventilation immediately, while an emergency trip also closes fuel valves and vents the enclosure.

Uploaded by

GUESSOUMA
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
82 views10 pages

Stopping Procedure: MLN Block 405 Algeria Operator Training

This document provides instructions for normal and emergency stopping procedures for a CX501KB series gas turbine generator. The normal stopping procedure involves ramping the generator down to 100kW over 15 minutes of cooldown at idle speed. The emergency stop procedure opens the breaker and stops fuel and ventilation immediately, while an emergency trip also closes fuel valves and vents the enclosure.

Uploaded by

GUESSOUMA
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

CX501KB Series

TRAINING GAS TURBINES

STOPPING PROCEDURE

MLN BLOCK 405 ALGERIA


OPERATOR TRAINING

CX501KB Series
TRAINING GAS TURBINES

KB7 STOPPING SEQUENCE

ENCLOSURE VENTILATION FAN VENT FAN


CONTINUES
FOR 30
FUEL GAS OPEN MINUTES

B.O.V. CLOSED R.P.M.


ON LINE
16,000
GOVERNING COOLDOWN 14,000
12200 RPM
14571 RPM 15 minutes at
LOAD BOVs OPEN
0kW 12,000
RAMP
100Kw per 10,000
second to
100kW 5 MINUTE CYCLE 8,000
"POST PURGE"
2200 RPM 6,000
OIL COOLER FAN STOPS
4,000
2,000
0
BoVs close
PRESS BREAKER Fuel Block
STOP OPEN Priming oil pump and
ValvesClosed Starter motor on

Time

STOP SECTION 8 PAGE 1-2


CX501KB Series
TRAINING GAS TURBINES

NORMAL STOP: Press the stop pushbutton, a confimation


window will appear...accept and the generator will start to
shutdown

CX501KB Series
TRAINING GAS TURBINES

The control system automatically ramps the generator down to


100kW...

POWER
kW
7

0
TIME

STOP SECTION 8 PAGE 3-4


CX501KB Series
TRAINING GAS TURBINES

The breaker is opened...

CX501KB Series
TRAINING GAS TURBINES

The turbine enters its cooldown period of 15 minutes at idle


(no load, minimum fuel)...

900.899.898.897.896
895.894.893.892.891...

STOP SECTION 8 PAGE 5-6


CX501KB Series
TRAINING GAS TURBINES

The gas or liquid fuel block valves are closed and the vent
valves are opened...

CX501KB Series
TRAINING GAS TURBINES

As the turbine drops below 12,000RPM ...Compressor blow off


valves open...

STOP SECTION 8 PAGE 7-8


CX501KB Series
TRAINING GAS TURBINES

As the turbine drops below ignition speed 2,200RPM ...Oil


Cooler Fan off...

CX501KB Series
TRAINING GAS TURBINES

The priming oil pump is started, the hydraulic start system


engaged and the compressor blow off valves closed and the
engine is cranked for a 5 minute cooldown purge to further
reduce engine oil temperature

GEARBOX

STOP SECTION 8 PAGE 9-10


CX501KB Series
TRAINING GAS TURBINES

The turbine coasts down to a standstill...

CX501KB Series
TRAINING GAS TURBINES

The enclosure vent fans continue to circulate cooling air


through the enclosure for a further 30 minutes.

STOP SECTION 8 PAGE 11-12


CX501KB Series
TRAINING GAS TURBINES

EMERGENCY STOP - Press the Emergency Stop Pushbutton


(panel or on the enclosure)...

READY TO START

EMERGENCY
STOP

CX501KB Series
TRAINING GAS TURBINES

The breaker opens immediately...

STOP SECTION 8 PAGE 13-14


CX501KB Series
TRAINING GAS TURBINES

The gas block valves shut and vent valves open...

To vent

CX501KB Series
TRAINING GAS TURBINES

All electric motors and fans are stopped...

VENT

OIL COOLER

STOP SECTION 8 PAGE 15-16


CX501KB Series
TRAINING GAS TURBINES

The turbine coasts down to a standstill


(approx 3 minutes).

CX501KB Series
TRAINING GAS TURBINES

Emergency Stop

The emergency stop pushbutton should ONLY be


used in an emergency, as the turbine misses its cool
down period which will eventually shorten turbine life.
A restart is inhibitted until the keyswitch has been
releases and reset on the HMI monitor.

STOP SECTION 8 PAGE 17-18


CX501KB Series
TRAINING GAS TURBINES

TURBINE TRIP - Shutdown

Any turbine trip will result in the breaker opening


immediately; the fuel block valves closing and vent
valves opening.
The ventilation fan will continue to run for 30 minutes
unless an Emergency Stop pushbutton has been
operated or a Fire Shutdown has occured (ie the
ventilation damper has closed)

STOP SECTION 8 PAGE 19-20