BFA2008 e
BFA2008 e
Design Manual
Barrier Free Access
2008
(2021 Edition)
Page
PREFACE i
Chapter 1 FOREWORD 1
Division 3 CARPARKS 18
Division 5 RAMPS 28
Division 8 HANDRAILS 42
Division 10 DOORS 56
Division 13 SIGNS 80
** The numbering system in Chapters 3 and 4 corresponds as far as practicable to the Third
Schedule of Building (Planning) Regulations.
CONTENTS
Page
Division 15 PUBLIC INFORMATION OR SERVICE COUNTERS 93
Division 16 ILLUMINATION 97
APPENDICES
LIST OF FIGURES
Page
Figure 1A - Wheelchair Space in an Auditorium 11
Figure 1B - Example of Wheelchair Spaces in a Lecture Hall 13
Figure 2 - Typical Guest Room Layout 17
Figure 3 - Dimension and Identification of Car Parking Space for Persons 19
with a Disability
Figure 4 - Side by Side Parking Spaces for Persons with a Disability 20
LIST OF FIGURES
Page
Figure 25A - Elevation of Power-operated Sliding Door 70
(View from Outside of Accessible Toilet)
Figure 25B - Elevation of Power-operated Sliding Door 70
(View from Inside of Accessible Toilet)
Figure 25C - Plan of Power-operated Swing Door 71
(Control Button(s) on Separate Walls)
Figure 25D - Plan of Power-operated Swing Door 71
(Control Button(s) on Same Wall)
Figure 26 - Flap-type Diaper Changing Station 72
Figure 26A - Indicating Tiles/Blocks for Urinal Used by Persons with 74
Ambulant Disabilities
Figure 26B - Details of Indicating Tiles/Blocks 74
Figure 27 - Examples of Bathroom and Shower Compartment 79
Figure 28 - Proportional Layout for International Symbol of Accessibility 80
Figure 29 - Directional Signs 81
Figure 30 - Proportional Layout for International Symbol of Access for 82
Hearing Loss
Figure 31 - Specifications of Braille Cells and Tactile Signs 83
Figure 32 - Braille and Tactile Fire Exit Map 84
Figure 32A - Example of Braille and Tactile Plan of Toilet and Changing 85
Room
Figure 33 - Tactile Guide Path to Lift Zone 87
Figure 34 - Tactile Guide Path to Information/Service Counter 88
Figure 35 - Tactile Guide Path to Tactile/Braille Directory Map/Floor Plan 88
Figure 36 - Tactile Warning Strip to Escalator or Passenger Conveyor 89
Figure 37 - Examples of Public Information Symbols 91
Figure 38 - Front View of Information/Service Counter for Wheelchair 94
Users
Figure 39 - Key Heights of Counters and Reception Desks 95
Figure 40 - Accessible Lift 104
Figure 41 - Tactile Graphic for Lift Control Buttons 106
Figure 42 - Proposed Standardised Position of Buttons for Keypad 109
Control Device
Figure 43 - Heights of Switches and Controls 118
Figure 44 - Digit 5 Indicator 122
Figure 45 - (repealed) -
Figure 46 - Built-in Drinking Fountain 131
Figure 47 - Examples of Door Handles and Faucets 138
PREFACE
1. This Design Manual is an updated version of the “Design Manual : Barrier Free
Access 1997”.
2. The Design Manual : Barrier Free Access 1997 sets out the design requirements
of providing proper access to and appropriate facilities in a building for persons
with a disability and other sectors of the population including the elderly, who at
times require the same provisions as persons with a disability. Following a review
of the 1997 Design Manual together with the legislation, legal framework and
administration, it has been identified that while Hong Kong’s existing principal and
subsidiary legislation caters for some of the needs of persons with a disability, it
does not adequately address the specific needs of the elderly in terms of spatial
requirements and facilities.
5. Since its first publication in 2008, the Design Manual 2008 (2021 Edition)
incorporates various amendments made in November 2012, September 2015,
April 2017, June 2019, October 2020 and December 2021 as summarised below:
i
1
Amendment by PNAP APP-41 Reference
https://www.bd.gov.hk/doc/en/resources/
November 2012
codes-and-references/code-and-design
-manuals/OldVersions/DM_BFA_ov.zip
September 2015
April 2017
June 2019
October 2020
December 2021
6. This Design Manual is available for viewing in the Buildings Department website
www.bd.gov.hk under the “Codes, design manuals and guidelines” page of the
“Resources” section. It may be downloaded subject to the terms and conditions
stipulated in the website.
1ii
CHAPTER 1
FOREWORD
1.1 The Disability Discrimination Ordinance was enacted in August 1995. It prohibits,
among other things, discrimination against persons with a disability by failing to provide
means of access to any premises that the public or a section of the public is entitled or
allowed to enter or use, or by refusing to provide appropriate facilities. However, there
is no discrimination in relation to the provision of access to premises if the premises are
so designed or constructed as to be inaccessible to persons with a disability and any
alteration to the premises to provide such access would impose unjustifiable hardship
on the persons who would have to provide it. A person who believes he or she has
been discriminated against in relation to access to premises or the provision of facilities
may lodge a complaint with the Equal Opportunities Commission or may institute legal
proceedings in the court. Reference may be made to this Manual as one sees fit in
considering whether it is reasonable to require the provision of such access or facilities.
1.2 For a new building or for the alterations or additions to an existing building, section 84 of
the Disability Discrimination Ordinance stipulates that:
(a) whether it is practicable to provide such access within the curtilage of the
building, bearing in mind the physical location and immediate environs of
the building; and
(b) whether providing such access would impose unjustifiable hardship on
the person seeking approval or on any other person.
(a) buildings of 13 m or less in height above ground level which are used, or
intended to be used, for occupation by a single family; or
(b) temporary buildings or contractor’s sheds referred to in Part VII of the
Building (Planning) Regulations (Cap. 123 sub. leg.).
1
1.2 (Cont’d)
1.3 This Manual applies to the design and construction of new buildings or alterations and
additions to existing buildings. Relevant Government authorities and departments will
also refer to it in the design and construction of their buildings.
1.4 To ensure effective enforcement, the following obligatory design requirements of this
Manual are put into the following legislation:
For those obligatory design requirements which are not put into the above legislation, it is
intended to incorporate them into the following codes of practice:
2
CHAPTER 2
EXTENT OF APPLICATION
2.1.1 The requirements set out in this Manual are classified into:
(a) the means of access and facilities stipulated in the Mandatory Section
shall be provided to the categories of buildings specified in the left column
of Table 1 and to the extent specified in the right column thereof; and
3
2.1 EXTENT OF APPLICATION (Cont’d)
TABLE 1
Domestic - All common areas of buildings of more than four (4) storeys.
buildings
- Main entrance and common area of the ground floor and means
of access to buildings which do not exceed four (4) storeys.
- Main entrance and common area of the ground floor and means
of access thereto, if the domestic parts do not exceed four (4)
storeys.
4
2.1 EXTENT OF APPLICATION (Cont’d)
TABLE 2
“Y” denotes “Applicable”
“-“ denotes “Not Applicable”
Braille & Tactile guide Visual Display Accessible Visual Fire Assistive Listening
tactile floor path Board Public Alarm System System
plan [para. 13 in [para. 69(4) in Information / [para. 5.2 in [para. 77 in
[para. 69(2) in Division 4 and Division 14] Service Chapter 5] Division 18]
Division 14] para. 69(3) in Counter
Division 14] [para. 70 in
Division 15]
1. Domestic use - - - - - -
2. Common areas - - - - Y -
of Office
3. Department Y Y - Y Y -
store and shopping
complex
4. Hotel, Y - - Y Y -
guesthouse, hostel
and bank
6. Cinema, theatre, Y Y Y Y Y Y
concert hall,
stadium, museum,
theme park and
purpose-built family
amusement centre
7. School, college, Y Y - Y Y -
university and
public library
8. Factory, - - - - Y -
workshop and place
for industrial use
9. Sports complex Y Y - Y Y -
and public
swimming pool
complex
5
2.1 EXTENT OF APPLICATION (Cont’d)
TABLE 2 (Cont’d)
Braille & Tactile guide Visual Display Accessible Visual Fire Assistive Listening
tactile floor path Board Public Alarm System System
plan [para. 13 in [para. 69(4) in Information / [para. 5.2 in [para. 77 in
[para. 69(2) in Division 4 and Division 14] Service Chapter 5] Division 18]
Division 14] para. 69(3) in Counter
Division 14] [para. 70 in
Division 15]
12. Hospital, Y Y Y Y Y Y
purpose-built clinic
13. Residential Y Y - Y Y -
home for the elderly
and welfare centre
16. Carpark Y - - - Y -
6
2.2 EXEMPTIONS
2.2.1 The Obligatory Design Requirements shall not apply to the following buildings:
(a) Buildings of 13 m or less in height above ground level which are used, or
intended to be used, for occupation by a single family; or
2.2.2 The Obligatory Design Requirements shall not apply to the following areas or
parts of a building as there is a relatively high risk to persons with a disability in
these areas/parts:
(b) Area only used for building services and maintenance (testing, inspection,
verification, repair and overhaul) including:
(i) plant, cooling tower and power plant;
(ii) equipment and lift motor room, and electrical transformer room and
switch room, battery room, machinery room, plant room and pump
room;
(iii) boiler room;
(iv) non-tenantable spaces accessed only by ladder, catwalk or crawl
space;
(v) access route for maintenance, pit, lift shaft and ventilation shaft; and
(vi) sub-station, telecommunication equipment room, metering area, or
the like.
(c) Area used for storage of raw material or produce or for bulk storage where:
(i) the stored material is hazardous; or
(ii) the public is not permitted to enter, such as waste containment area,
chemical store, or the like.
(d) Mezzanine floor used only for storage, plant and equipment installation or
the like.
7
CHAPTER 3
PRELIMINARY
1. INTERPRETATION
For the purpose of this Manual, the following terms are defined as:
“Access” is means to enable persons with a disability to approach, enter and leave
the building and to use the facilities therein without assistance or undue difficulties.
“Accessible lift” means a lift fully complied with the obligatory design requirements in
Division 19.
“Assistive listening system” means a system which enables sound signs that are
amplified in both volume and signal to be transmitted to persons with hearing
impairment without interference from background noise or excessive reverberation.
“Common areas” are those areas open to and available for the common use and
enjoyment of all occupiers of the building.
“Persons with ambulant disabilities” are persons with ambulant impairment who may
require the aid of devices such as prostheses, orthoses, sticks or crutches for walking.
“Tactile guide path” means a standardized pattern applied to or built onto walking
surfaces through the combined use of tactile directional tiles/blocks, positional
tiles/blocks and tactile hazard warning tiles/blocks for way finding and orientation for
persons with visual impairment.
8
1. INTERPRETATION (Cont’d)
“Tactile warning strip” means a standardized pattern applied to or built onto walking
surfaces through the use of tactile hazard warning tiles/blocks to warn persons with
visual impairment of certain construction features.
“Wheelchair users” are those persons who depend on wheelchairs for mobility.
“Luminous contrast” means the amount of light reflected from the surface of the
object compared to the amount of light reflected from the surface of its surrounding
background. Such contrast expressed in percent can be determined by:
[(B1-B2) / B1] x 100
Where
B1 = light reflectance value (LRV) of the lighter area and
B2 = light reflectance value (LRV) of the darker area.
[Sources from AMERICANS WITH DISABILITIES ACT ACCESSIBILITY
GUIDELINES (ADAAG)]
9
CHAPTER 4
DESIGN REQUIREMENTS
3. In this Division, “relevant activity” means the activity for the purpose of which
the audience in the premises attend the premises.
MANDATORY SECTION
Performance Objectives
The seating areas of an auditorium, the stage and backstage facilities, shall be
provided with safe and convenient access for all people including persons with
a disability.
4. Wheelchair Spaces
10
TOP VIEW
SIDE
SIDEVIEW
VIEW
*ALL DIMENSIONS ARE IN mm
11
Obligatory Design Requirements (Cont’d)
6. Braille and Tactile Fire Exit Maps and Tactile Warning Strips
(1) Braille and tactile fire exit maps as shown in Figure 32 shall be provided at
all entrances to the auditorium.
A. Design Considerations
(b) The wheelchair spaces should be so located that the wheelchair user
may have the choice of sitting with another wheelchair user or
conventionally seated companion.
12
Figure 1B – Example of Wheelchair Spaces in a Lecture Hall
(c) Access should be provided to the low and high levels of the auditorium.
13
Recommended Design Requirements (Cont’d)
(e) Where conventional seat numbers are provided, Braille and tactile seat
number should be provided at the top of each seat rest. The specification
of Braille cells is provided in Figure 31.
(f) Sound enhancement system may be provided at the designated areas for
persons with hearing impairment.
(i) A room with a view of the performance for “audio description” should be
provided for the visually impaired persons.
14
Division 2 --- HOTELS, HOSTELS AND GUESTHOUSES
This Division is applicable to guest rooms designated for the use of persons
with a disability in hotels, hostels and guesthouses.
MANDATORY SECTION
Performance Objectives
7. Guest Rooms
Minimum Provision
(2) A minimum of two accessible guest rooms with full facilities for persons
with a disability shall be provided in a hotel, hostel and guesthouse.
Two such accessible rooms shall be provided for every 100 guest rooms
and any part thereof. (For example, a total of four such accessible
rooms shall be provided if there are 150 guest rooms.)
The bathroom and shower facilities serving an accessible guest room shall
comply with Division 12.
A. Design Considerations
(a) A typical guest room layout is shown in Figure 2 and typical bathroom
and shower compartment are shown in Figure 27.
15
Recommended Design Requirements (Cont’d)
(b) For every 100 guest rooms and any part thereof, in addition to accessible
guest rooms, the following types of guest rooms should be provided:
(i) A minimum of two guest rooms with visual door bells installed at a
prominent location and the function can be switched on or off
conveniently by the guest; and
(ii) A minimum of two guest rooms located near lift lobby with Braille
and tactile fire exit maps at the back of guest room doors, and
Braille and tactile information for main lamp switch controls.
(c) Where planning allows, the accessible guest rooms required under
paragraph 7(2) of Division 2 should be provided with the facilities in
paragraph (b)(i) and (ii) above in full or in combination.
(d) Where planning allows, the guest rooms in paragraph (b)(i) above should
be provided with the facilities for accessible guest rooms in paragraph
7(2) of Division 2 and facilities in paragraph (b)(ii) above in full or in
combination.
(e) Where planning allows, the guest rooms in paragraph (b)(ii) above
should be provided with the facilities for accessible guest rooms in
paragraph 7(2) of Division 2 and facilities in paragraph (b)(i) above in full
or in combination.
(f) For floors with guest rooms provided under paragraph (b)(ii) above,
Braille sign should be installed on the wall adjacent to the open side of
each door leading to an exit staircase to indicate such information. The
sign should be placed at 900 mm to 1500 mm above the finished floor
level.
(g) A sign with guest room number in raised Arabic numerals/characters and
Braille should be installed on the wall adjacent to the door lock of all
guest rooms. The sign should be placed at 900 mm to 1500 mm above
the finished floor level.
16
SLIDING DOOR
Clear Opening
*ALL DIMENSIONS ARE IN mm 850 (MIN.)
17
Division 3 --- CARPARKS
This Division aims to provide standards for accessible car parking spaces
designated for the use of persons with a disability.
MANDATORY SECTION
Performance Objectives
(1) The parking spaces reserved for persons with a disability shall be
located in proximity and with an accessible route to the lobby with an
accessible lift or entrance.
(2) The minimum width for a parking space for persons with a disability shall
be 3500 mm.
The parking space shall be clearly marked with the international symbol of
accessibility and the parking space number on the floor as shown in Figure 3.
18
1500
1500
3500 (MIN.) 2500
19
1500
1500
2500 1200 (MIN.) 2500
20
BEST PRACTICE SECTION
A. Design Considerations
(b) The parking bay surface should allow the safe transfer of a passenger or
driver to a wheelchair and transfer from the parking bay to the access route
to the building without undue effort, barriers to wheelchairs or hazards
from tripping.
21
Figure 5 – Parking Space Indication Signage
22
Division 4 --- ACCESS ROUTE
This Division aims to ensure proper access for all people, with or without
disabilities to approach, enter or leave a building independently to reach and use
its facilities, such as foyers, lifts, toilets, shops, restaurants, cinemas, etc. without
undue difficulty.
MANDATORY SECTION
Performance Objectives
An easily identifiable continuous and relatively level path free from obstruction or
any kind of hazards shall be provided for persons with a disability to enter, move
within and leave a building to reach the accessible facilities.
Access shall be provided from a prominent point or points on the lot boundary,
which is accessible to a public street or pedestrian way, directly to at least one
entrance which is commonly used by the public or to a point directly adjacent to
one entrance which is commonly used by the public and to an accessible lift,
unless it is impractical to do so because of difficult terrain or unusual
characteristics of the site.
Width
(1) The clear width of an access route shall be not less than 1050 mm.
Surface
(3) The surface of an access route shall be firm.
23
*ALL DIMENSIONS ARE IN mm
24
600
POSITIONAL TILES/
BLOCKS
DIRECTIONAL TILES/
BLOCKS
25
Three kinds of tactile tiles/blocks as shown in Figure 6C are commonly used in constructing a tactile guide path:
i) Directional Tile/Block
This has parallel raised bars for guiding the users along an intended safe path.
ii) Hazard Warning Tile/Block
This has raised big dots (35 mm in diameter) arranged in square grid parallel to the sides of the slab for
indication of potential hazards ahead. This type of tile/block could be used alone to form tactile warning strips
at the top and bottom ends of staircase or ramps, and at dropped kerb.
iii) Positional Tile/Block
This has raised small dots (23 mm in diameter) placed in staggered positions for indication of possible
change in walking directions.
26
BEST PRACTICE SECTION
A. Design Considerations
(b) Access routes from the lot boundary to the entrance of a building should be
wide enough to allow wheelchair users and other users to pass
simultaneously.
(c) Easily identifiable access route e.g. tactile guide path for persons with visual
impairment should be provided from the lot boundary to the entrance of a
building.
(d) Indication signage for accessible entrances should be provided where more
than one entrance exist in a complex building.
Width
(a) The clear width of the access route should not be less than 1500 mm.
Floor Space
(b) In large floor space of more than 200 m2 where the cues of physical edges
such as walls and handrails are not present, tactile guide paths should be
used to facilitate orientation of persons with visual impairment.
Surface
(c) The surface of the access should be firm and slip-resistant with a “static
coefficient of friction” of “Good” grading (see Appendix C).
Directional Tiles/Blocks
27
Division 5 --- RAMPS
MANDATORY SECTION
Performance Objectives
14. Ramps of an appropriate design shall be provided at all changes in level
other than those served by an accessible lift or accessible lifting
mechanism accommodating the specific requirements of persons with a
disability.
15. Width
A ramp shall not be less than 1050 mm in width.
16. Landing
A clear space of not less than 1500 mm x 1500 mm shall be provided at
the head and foot of every ramp, i.e. door swing and alike shall not be
allowed to swing onto the landing.
(1) Any ramp with a rise greater than 200 mm, leading down towards
an area where there may be vehicular traffic, shall have a railing
or barrier across the full width of its lower end, and be not less
than 1500 mm from the foot of the ramp.
28
Obligatory Design Requirements (Cont’d)
(3) A kerb of at least 100 mm high, or a rail 200 mm above ramp level
shall be provided on both sides to prevent wheelchair from
slipping over the edge.
(6) The floor and wall along ramps shall be in contrasting colours.
LANDING TO BE PROVIDED
FOR EACH OF 10m LENGTH OF
HORIZONTAL RUN OR PART THEREOF
29
BEST PRACTICE SECTION
A. Design Considerations
(b) The more gradual the slope of the ramp (i.e. the less steep it is) the
more easily persons can use it without assistance. Therefore,
slope with the ratio of 1:20 (5%) to 1:15 (6.7%) is preferred. It can
take much energy to get up ramp with steep gradient, which also
makes speed control difficult when going down. Steep inclines can
put a wheelchair in danger of tipping backwards or forwards as
many users cannot lean or adjust their balance to accommodate
gradient (see Figure 8).
(c) A level resting space outside the swing of any door at the top of a
ramp should be provided to avoid the possibility of ‘roll-back’ for
wheelchair user when trying to open the door.
(d) A ramp should have handrails on both sides so that it can be used
in both directions by people with a mobility problem on one side
such as may be the case for stroke sufferers.
(e) A ramp that surmounts a major change in level has to be very long,
and requires multiple ramp and landing combinations. In such
circumstances, other design solutions should be considered.
30
B. Recommended Design Requirements
(a) A ramp should have a running slope 1:12 (8.33%) to 1:20 (5%).
(d) Tactile warning strips at the head, foot and landing should have a
minimum luminous contrast of 70% with the adjoining surfaces.
(e) The floor and wall along a ramp should have a minimum
luminous contrast of 30%.
31
Division 6 --- DROPPED KERBS
MANDATORY SECTION
Performance Objectives
21. Requirements
32
Obligatory Design Requirements (Cont’d)
1200 (MIN.)
*ALL
*ALLDIMENSIONS
DIMENSIONSARE
AREININmm
mm
22. Location
23. Surface
33
BEST PRACTICE SECTION
A. Design Considerations
(b) The tactile warning strip should be provided in order to notify the
presence of traffic.
(c) The tactile warning strip should have luminous contrast for the elderly
and persons with visual impairment.
(d) Dropped kerb should have slip-resistant surface. Raised traction strips
should be avoided in order to reduce the hazard to everyone.
(e) Examples of dropped kerb are shown in Figures 10, 11 and 12.
Slip Resistance
(a) Dropped kerb should have slip-resistant surface with a minimum “static
coefficient of friction” of “Very Good” grading (see Appendix C).
Luminous Contrast
(b) Tactile warning strip should have a minimum luminous contrast of 70%
with the adjoining surfaces.
34
15mm
15
35
*ALL DIMENSIONS ARE IN mm
36
Division 7 --- STEPS AND STAIRCASES
24. This Division applies only to the required staircase and the main circulation
staircase in the common areas of a building, and sets out requirements to
help people including persons with ambulant disabilities and persons with
visual impairment to negotiate steps and staircases.
MANDATORY SECTION
Performance Objectives
The required staircases and the main circulation staircase in common areas
of a building shall:
(a) be constructed with treads not less than 225 mm in width (measured at
the centre of the flight) from the face of one riser to the face of the next
riser and with risers not more than 175 mm in height;
(b) have risers built with vertical or receding face not more than 15 mm from
the vertical, without a projecting nosing;
(c) have not more than 16 steps in any flight without the introduction of a
landing;
(d) be provided on both sides with properly fitted handrails (see paragraph
28(2));
(e) be provided with non-slip nosing in contrasting colour; and
(f) have risers reduced to not more than 160 mm high and treads increased
to not less than 280 mm wide for greater ease of use for external steps
and stairs.
Colour Contrast
37
Obligatory Design Requirements (Cont’d)
Tactile warning strips shall be provided at landings and at both the bottom
and top ends of a staircase, regardless of the number of steps it comprises.
For landings leading to a floor or those enclosed by wall, railing or balustrade,
tactile warning strips of 300 mm in width shall be provided; for those leading
to an open space or the entrance/exit of a building, the tactile warning strips
shall be 600 mm in width (see Figure 13). In this case, Braille and tactile
information signs shall be provided on the adjacent wall to indicate the
presence of an opening. For a staircase with intermediate steps between
two flights, the provision of tactile warning strips shall follow the arrangement
in Figure 13.
38
EXIT
岀口
39
BEST PRACTICE SECTION
A. Design Considerations
(e) When ascending a stair, people who wear calipers or who have stiffness
in hip or knee joints are particularly at risk of trapping the toes of their
shoes beneath projecting nosings.
(f) Stair should be designed with more generous dimensions, e.g. wider
tread, and shorter travel distance is recommended. No open risers
should be installed.
(i) Despite the design requirements of tactile guide paths and tactile
warning strips would help orientation for persons with visual impairment,
they sometimes impose hazards to people with limited mobility, children
and the elderly.
40
B. Recommended Design Requirements
(a) For any internal stair with heavy circulation, riser should be reduced to
150 mm high and tread be increased to 300 mm wide for greater ease of
use.
(b) Individual flight should not exceed 1800 mm in height nor a total of 12
risers.
(c) The top nosing of any flight should be built not less than 300 mm from
the point at which the adjoining wall returns (see Figure 14).
Luminous Contrast
(e) Non-slip nosing should have a minimum luminous contrast of 30% with
the adjoining surfaces.
41
Division 8 --- HANDRAILS
Handrails provide support for everyone and are especially helpful for persons
with a disability and the elderly to use staircases, to pull themselves up inclines,
check themselves on declines and to assist them in moving within the building.
MANDATORY SECTION
Performance Objectives
(1) Handrail to ramp and step shall be fixed not less than 30 mm and not
more than 50 mm clear of wall and with a clear height of 70 mm from
the top of the bracket to the top of the handrail.
(2) The top of handrail shall be at a height of not less than 850 mm and
not more than 950 mm above any nosing, floor or landing.
(5)&(6) Handrail shall extend horizontally not less than 300 mm beyond the
first and last nosing of every flight of steps or beyond the ends of a
ramp and terminate into a closed end which shall turn down or return
fully to end post or wall face and which shall not project into a route of
travel. Where a door opening is in place, a shortened extension of
not less than 100 mm shall be permitted.
29. Loading
(1) Handrail shall be installed to resist a load of not less than 1.3 kN applied
vertically or horizontally.
42
*ALL DIMENSIONS ARE IN mm
Figure 15 - Handrails
43
Obligatory Design Requirements (Cont’d)
Braille and tactile information on directional arrow and floor number shall be
provided on handrail on every floor at a designated location as illustrated in
Figures 16A to facilitate persons with visual impairment. Where a directional
sign exists on handrails, Braille and tactile information shall also be provided
as illustrated in Figure 13.
44
*ALL DIMENSIONS ARE IN mm
45
BEST PRACTICE SECTION
A. Design Considerations
(a) Handrail should be designed to provide easy, firm and comfortable grip
to all users and should have no obstruction when people slide their
hands along the handrail.
(b) The installation level of the handrail and clearance dimensions should
facilitate a safer grip and prevent hand injuries especially for the elderly
and persons with visual impairment.
(c) Handrail finished in more noticeable colours with Braille and tactile
information should facilitate self-help circulation of persons with visual
impairment.
(e) Handrail should be set at a height that is convenient for all users of the
building and should extend safely beyond the top and bottom of a flight
of steps, or a ramp, to give both stability and warning of the presence of
a change in level.
Clear Space
(a) Where the wall has a rough surface, the clear space should be not less
than 45 mm between the handrail and the wall.
(b) A recess containing a handrail should extend not less than 450 mm
above the top of the handrail as illustrated in Figure 16B.
46
*ALL DIMENSIONS ARE IN mm
Double Handrail
(c) One more handrail should be provided at a height of not less than 700
mm and not more than 800 mm above any nosing, floor or landing for
schools and places of public entertainment.
Luminous Contrast
(d) Handrail should have a minimum luminous contrast of 30% with the
surrounding wall surfaces.
Slip-resistant
47
Division 9 --- CORRIDORS, LOBBIES AND PATHS
MANDATORY SECTION
Performance Objectives
(a) area shall have a clear width of not less than 1050 mm;
(b) a space not less than 1500 mm x 1500 mm shall be provided within 3500
mm of every dead end;
(c) any lobby in a corridor shall have a length of not less than 1200 mm,
excluding space for door swings;
(d) a level area, extending not less than 1200 mm beyond the swings of the
doors and not less than 1500 mm in width shall be provided on both sides
of every entrance of a building; and
(e) this paragraph shall not apply to lobby which lead to staircase only.
For the purpose of this paragraph, “dead end” is a corridor, lobby or path where
the means of exit for persons with a disability is in one direction only.
On footpath, cover to a channel shall be flush with the surface of the footpath.
Any hole in such cover or between such covers shall have a dimension of not
more than 20 mm.
33. Gratings
Slot of gratings shall have a width of not more than 13 mm and shall not be
parallel with pedestrian travel path (see Figure 17).
48
SLOTS OF GRATING SHALL
NOT BE PARALLEL WITH
PEDESTRIAN TRAVEL PATH
34. Protrusion
No appliances, fixtures and fittings shall project beyond 90 mm from the surface
of any wall in corridors, paths and lobbies below a level of 2000 mm above the
finished floor level unless they are unavoidable, in which case they shall also be
extended downwards to the finished floor level or guided by tactile flooring
materials.
49
*ALL DIMENSIONS ARE IN mm
50
Obligatory Design Requirements (Cont’d)
36. Headroom
Where the headroom is 2000 mm or less from the finished floor level, a warning
guardrail or other barrier shall be provided for detection, having its leading edge
at or below 680 mm above the finished floor level (see Figure 19).
51
BEST PRACTICE SECTION
A. Design Considerations
(b) To facilitate the way finding for persons with visual impairment, surfaces
and finishes with luminous contrast between the wall and the ceiling, and
between the wall and the floor should be adopted. Appropriate lighting
design with adequate illumination should also be considered.
(d) Protruding object can be extremely hazardous to the persons with visual
impairment as well as the general public. Examples of protruding
obstruction are sign, drinking fountain, fire extinguisher, telephone
enclosure, and underside of stairway or escalator, etc. Protruding object
should be recessed into the wall as far as possible.
(e) Long corridors and passageways are difficult for persons with locomotion
impairment to negotiate. Therefore, adequate resting places with resting
facilities should be provided therein. Such resting facilities should not
reduce the statutory requirements on the clear width of access and
manoeuvring space and should not cause obstruction to access,
circulation and exit routes.
Width
(a) Path width should be more than 1200 mm to enable a wheelchair user to
pass anyone who is on the same path or preferably at least 1500 mm to
allow two wheelchairs to pass. At right angle turns, inside corner should
be splayed or rounded to at least 300 mm radius (see Figure 20).
52
D
A. A CLEAR WIDTH OF 1500 mm WILL ALLOW TWO WHEELCHAIR USERS TO PASS EACH OTHER.
B. DEPTH OF RECESS SHOULD NOT BE LESS THAN THE WIDTH OF THE DOOR LEAF.
53
B. Recommended Design Requirements (Cont’d)
Surface
(b) All corridors should have slip-resistant surfaces with a “static coefficient of
friction” of “Good” grading (see Appendix C).
(c) Surface paved with loose gravel or stone is hazardous and should be
avoided.
Luminous Contrast
(e) A minimum luminous contrast of 30% should clearly define between wall,
floor and door surfaces
Protruding Objects
(f) The protruding object should not reduce the statutory required clear width
and height of access and manoeuvering space (see Figure 21).
(g) Protruding object should include but not limited to sign, telephone
enclosure, drinking fountain, fire extinguisher, underside of stairway or
escalator.
Round Edges
(i) The counters or devices installed at controlled passages and the warning
guard rails provided for low headroom should be designed with round
edges.
Resting Places
54
*ALL DIMENSIONS ARE IN mm
55
Division 10 --- DOORS
MANDATORY SECTION
Performance Objectives
Door, including one leaf of a pair of double doors, shall have a clear width of
not less than 800 mm between the open door and opposite jamb or the other
leaf (see Figure 22).
(1) The unobstructed area adjacent to the door handle on the leading face of
a single door shall not be less than 330 mm in width (see Figure 22).
(2) Door, if less than 330 mm from the corner of a room, shall swing from the
side nearer to that corner.
56
*ALL DIMENSIONS ARE IN mm
41. Handles
Door handle shall not be less than 950 mm and not more than 1050 mm above
the finished floor level, measured from the top surface of the grip.
57
Obligatory Design Requirements (Cont’d)
Door closing devices shall be designed to allow exterior and interior doors to be
opened with horizontal force of not more than 30 N and 22 N respectively. Door
required to have fire resistance period installed along accessible routes shall be
opened with horizontal force of not more than 30 N. Closer for interior door
shall have a closing period of at least 3 seconds measured from an open
position of 70° to a point 75 mm from the closed position measured from the
leading edge of the door. Door closing devices include door closer, spring
hinge and floor hinge.
A. Design Considerations
(b) A door fitted with a self-closing device to stand against wind force is
difficult to be openable by many people, particularly those who are
wheelchair users or who have limited strength. Where closing devices are
needed for fire control, the use of electrically powered hold open devices
or swing-free closing devices is appropriate.
(c) All doors should be wide enough to allow unrestricted passage for different
users, including wheelchair users, people carrying luggage and parents
with baby carriages and small children.
58
A. Design Considerations (Cont’d)
(d) Sufficient space alongside the leading edge of a door should be provided
to enable a wheelchair user to reach and grip the door handle, then open
the door without releasing hold on the handle and without the wheelchair
footrest colliding with the return wall.
External Doors
(a) External door should be single-action and open outwards to obviate high
tension in spring closers in sustaining wind pressure.
Latched Doors
Kick-plates
(c) All doors which allow the passage of wheelchairs should have kick-plates
of not less than 200 mm high fitted on the face which swings away.
59
*ALL DIMENSIONS ARE IN mm
Vision Panels
Glass Doors
(f) The leading edge of glass door should be marked to indicate glass.
60
Recommended Design Requirements (Cont’d)
(fa) The marking provided at a frameless glass door should consist of at least
a horizontal band with a minimum height of 100 mm and contrasting
colours with the background to assist visibility. The marking including
those in broken or solid lines, patterns or company logos, etc., should
cover at least 10% of the glazing area within the zone between 900 mm
and 1500 mm above the internal finished floor. If the horizontal band
design is not adopted, other types of marking should still be designed
horizontally across the glass door. Such kind of marking should cover at
least 30% of the glazing area within the zone between 900 mm and 1500
mm above the internal finished floor.
Luminous Contrast
(g) Door handle of manually operated doors and control switch or button of
door with powered open devices should have a minimum luminous
contrast of 30% with the background finishes.
(h) Fire rated doors leading to areas with accessible facilities should be
provided with hold-open device except for doors to a required staircase
forming part of a protected exit and its protected lobby. Doors not for fire
safety purposes leading to areas with accessible facilities should be
automatic.
Width of Doors
(i) Door, including one leaf of a double-leaf door, should have a clear width of
not less than 850 mm between the open door and opposite jamb or the
other leaf.
Unobstructed Area
(j) An unobstructed area adjacent to the door handle on the leading face of a
single door should not be less than 600 mm in width.
Door Thresholds
(k) Door threshold (see Figure 23A) should have a bevelled and round edge
on each side at a gradient not steeper than 1:2.
61
Division 11 --- TOILETS AND W.C. CUBICLES
MANDATORY SECTION
Performance Objectives
Sufficient, properly designed and located toilet and W.C. cubicles shall be
available for use by everybody including people of either sex, people with
babies and small children, persons with a disability, wheelchair users and the
elderly and elderly with frailty, etc. with or without any assistance from others.
Space requirements are set to enable a wheelchair user to manoeuvre into
position for frontal, side or diagonal transfer to and from the W.C. seat.
There shall be at least one accessible W.C. cubicle on a floor, or in that part of a
floor designed for access by the persons with a disability where the total
number of W.C. cubicles provided on that floor or in that part of a floor is 20 or
less, or 2 where the total number exceeds 20. This paragraph shall not apply to
domestic buildings and the domestic parts of composite buildings or where
there is no toilet provided on the particular floor.
Where the accessible W.C. cubicles are within a toilet with multiple cubicles, the
minimum number of such accessible W.C. cubicles to be provided for each sex
shall be based on the total number of W.C. cubicles for each sex on that floor or
in that part of a floor designed for access by persons with a disability.
62
Obligatory Design Requirements (Cont’d)
The accessible W.C. cubicle shall not be less than 1500 mm x 1750 mm in area
and the clear manoeuvring space within the cubicle shall not be less than 1500
mm x 1500 mm measured at 350 mm above finished floor level and the cubicle
shall have in it a watercloset at a height not less than 380 mm and not more
than 450 mm, measured to the top of the toilet seat. Waterclosets shall be
equipped with a back support such as a seat lid and seats shall not be
spring-actuated.
Flushing control shall be mounted on the wide side of the cubicle at a height
between 600 mm and 1050 mm above the finished floor level and shall be
hand-operated or automatic. Hand-operated controls shall be capable of being
operated with one hand and shall not require tight grasping, pinching or twisting
of the wrist. The force required shall not be greater than 22 N.
The toilet shall be provided with a wash basin mounted with the rim not higher
than 750 mm above the finished floor level. A clearance of 550 mm shall be
maintained from the finished floor level to the bottom of the apron.
Tap for wash basin shall be automatic or of lever control type without spring
loading, subject to the approval of the Water Supplies Department. Tap shall
not require tight grasping, pinching or twisting of the wrist. The operating force
required shall not be greater than 22 N.
63
Obligatory Design Requirements (Cont’d)
There shall be at least two grab rails which shall not be less than 32 mm and not
more than 40 mm in external diameter and shall be fixed on the wall leaving a
grip space of not less than 30 mm clear of the mounting wall. The two grab rails
constructed in one continuous piece is acceptable. The length of grab rail shall
not be less than 600 mm.
There shall be one grab rail fixed on each of both the inner and outer surfaces of
the cubicle door; which shall not be less than 32 mm and not more than 40 mm
in external diameter. The grab rail shall have a grip space of not less than 30
mm clear of each door surface.
There shall be one folding grab rail on the wide side of the cubicle adjacent to
the watercloset at a height between 725 mm and 750 mm above the finished
floor level when lowered from the wall. Simple instructions in English, Chinese
and Braille on how to unfold the rail should be affixed to the wall. The grab rail,
folding grab rail and wash basin shall be capable of carrying a static load of 150
kg.
The grab rail shall not rotate within its fixing fittings.
64
Obligatory Design Requirements (Cont’d)
55. Urinals
(a) have a clear levelled space of not less than 800 mm wide x 1500 mm
deep in front; and
(b) be wall hung urinal with a front rim not higher than 400 mm, and have
vertical grab rails of not less than 32 mm and not more than 40 mm in
external diameter and of 600 mm length on both sides at a height of 1200
mm above the finished floor level for use by persons with ambulant
disabilities (see Figure 25).
65
MIRROR FOR
WHEELCHAIR USER
600
1800 (MIN.)
900 - 1050
950 - 1050
750 - 820
725 - 750
725 - 750
600 - 650
380 - 450
600
1500 ( MIN. )
600
1950 (MIN.)
800 (MIN.)
600
66
*ALL DIMENSIONS ARE IN mm
A. Design Considerations
67
Design Considerations (Cont’d)
(d) If there is adequate space inside the toilet or cubicle units, double
swing door open both inwards and outwards or sliding door may be
provided to enable assistance during emergency situations.
(e) Urinals should be accessible and can be easily found by persons with
visual impairment. The grab rails for aiding the elderly and tactile
surface materials for aiding persons with visual impairment should be
provided.
(f) Accessible unisex toilet facilities can serve both sexes, those with or
without assistance, and accommodate a greater number of users. It is
more easily identified than a facility in a separate-sex toilet and more
likely to be available when required, particularly as the elderly and
some persons with a disability need to use toilets more frequently than
others. In addition, a unisex facility enables assistants of either sex to
assist the user.
(g) There is a tendency for the specification of sanitary fittings and fixtures
to be in white colour to make cleanliness easily observable. Often the
fittings are set against light or white coloured tiling which makes clear
identification difficult for the persons with visual impairment. Sanitary
fittings should have luminous contrast or colour contrast against the
background finishes.
Unisex Facilities
(a) W.C. cubicles should, where possible, be unisex and accessible from a
corridor so that they can be used by either sex with assistance from
members of the opposite sex, if necessary.
(b) If two or more accessible unisex facilities are provided, at least one
should be of opposite handed layout to the other(s).
W.C. Cubicles
(c) The clear distance between the watercloset and the wash basin should
not be more than 600 mm for the users’ convenience after toileting. The
clear manoeuvring space within the cubicle shall not be less than 1500
mm x 1950 mm.
(d) The angle between the two grab rails should be within the range of 80
to 90.
68
Recommended Design Requirements (Cont’d)
Toilet/Compartment Doors
(e) Double swing doors which open both inwards and outwards may be
provided in any toilets or cubicles. Sliding door fixed with vertical grab
rails on both sides of the door in accordance with paragraph (ea) (viii)
below is equally acceptable provided that it is not heavy or awkward to
use. The requirements of door handle and horizontal grab rail will not
be applicable to sliding doors.
(xiii) separate door open and lock buttons should be provided inside
the toilet and placed together;
(xiv) Braille and tactile marking should be provided to the control
buttons in compliance with the requirements stipulated in
paragraphs 80(5) and 80(6) in Division 19 and Figures 25A and
25B; and
(xv) user instructions in Chinese, English and Braille on how to open
and lock the door should be provided adjacent to the control
buttons inside the toilet.
71
Recommended Design Requirements (Cont’d)
Diaper-changing Facilities
(fa) The room should be provided with a clear manoeuvring space not less
than 1500 mm x 1500 mm measured at 350 mm above finished floor
level.
72
Recommended Design Requirements (Cont’d)
Bathroom/Shower Compartment
(g) The floor of the bathroom and the shower compartment should be
slip-resistant with a minimum “static coefficient of friction” of “Good”
grading (see Appendix C) and self-draining.
Luminous Contrast
(h) Wall tiling should have a minimum luminous contrast of 30% with
sanitary appliances and fittings, grab rails and toilet roll holders, etc.
(ha) Toilet door and compartment door should have a minimum luminous
contrast of 30% with its frame and adjacent wall.
Avoidance of Obstruction
(i) Waste pipe, disposal bins and other fittings within the toilet should be
located to avoid any obstruction or creating a tripping hazard including
those under the wash basin.
(j) Toilets and W.C. cubicles for use by persons with a disability should be
located to avoid proximity to or obstruction by exit doors to the staircase.
(k) An additional emergency call bell near the toilet seat should be provided,
if practicable.
(l) Large size symbols with luminous contrast for male and female toilets
should be used.
Grab Rails
(m) The surface of the grab rails should be slip-resistant, e.g. stainless steel
with hair-line finish.
Indicating Tiles/Blocks
(n) Two indicating tiles/blocks on the floor to facilitate the use by persons
with visual impairment (see Figures 26A and 26B) should be provided in
front of the urinal for use by persons with ambulant disabilities.
73
URINAL
VERTICAL VERTICAL
GRAB RAIL GRAB RAIL
INDICATING
150 150
TILES/BLOCKS
Washroom Accessories
74
Division 12 --- BATHROOMS AND SHOWER COMPARTMENTS
MANDATORY SECTION
Performance Objectives
56. Bathtubs
(1) There shall be a clear floor space of not less than 1500 mm x 800
mm in front of the bathtub (see Figure 27);
(2) The bathtub shall be provided with a seat of not less than 250 mm
in width (see Figure 27); and
(3) The bathtub shall have a maximum height of 380 mm.
(a) have lever type handles at least 75 mm long from the centre of
rotation to the handle tip;
(b) be installed at the plug end of the bathtub; and
(c) be not more than 450 mm above the rim of the bathtub.
75
Obligatory Design Requirements (Cont’d)
(2) Where shower heads are mounted on a vertical bar, the bar shall:
(a) have a minimum length of 500 mm with the lower end not less
than 450 mm above the finished floor level;
(b) be installed so as not to obstruct the use of grab rails referred
to in paragraph 57; and
(c) be so mounted to be able to carry a static load of 150kg in
case they are mistakenly used as a grab rail.
62. Thresholds
76
Obligatory Design Requirements (Cont’d)
A. Design Considerations
(a) Taps and other controls should be installed between the centre
line and the outer edge of the bathtub.
Grab Rails
(b) The surface of the grab rails should be slip-resistant, e.g. stainless
steel with hair-line finish.
(c) Two additional vertical grab rails should be installed for shower
compartments and they should:
(i) have a minimum length of 750 mm;
(ii) be installed at a height between 700 mm and 800 mm
measured from the bottom of the bars to the finished floor
level; and
(iii) be provided adjacent to the shower seat such that one is
mounted beside the shower seat and another one is
mounted not more than 450 mm from the edge of the
shower seat (see Figure 27).
Shower Seats
77
Recommended Design Requirements (Cont’d)
78
VERTICAL GRAB
RAIL
100mm (MAX.) (a) BATHROOM
FROM BATHTUB
RIM
150-300 600 (MIN.)
150-300
ADJUSTABLE
SHOWER HEAD
450mm (MIN.)
AND
850mm (MAX.)
ABOVE FLOOR
LEVEL 380(MAX.)
(b) SHOWER
COMPARTMENT
750 (MIN.) #
750 (MIN.) #
ADJUSTABLE
SHOWER
700 – 800 #
700 – 800
430 – 480
HEAD
700 – 800 #
750-1300mm
ABOVE FLOOR
LEVEL
79
Division 13 --- SIGNS
MANDATORY SECTION
Performance Objectives
Signs shall give clear directions, information and instructions for the users of the
building.
GRIDLINES
Gridlines areARE SHOWN TO DEFINE
THE PROPORTION
provided to how ONLY
th ti l
80
Obligatory Design Requirements (Cont’d)
戲 院
Theatre
DIRECTION IDENTIFICATION INFORMATION
66. Size
81
Obligatory Design Requirements (Cont’d)
82
Obligatory Design Requirements (Cont’d)
(1)&(2) Braille and tactile signs shall be installed on adjacent wall or door of
public toilet to indicate whether the toilet is for male, female or unisex.
The signs shall be placed at 900 mm to 1500 mm above the finished
floor level. Specifications of Braille cells and tactile signs are shown in
Figure 31.
(3) If there is no door, the sign shall be provided on the wall in front of the
toilets.
(4)&(5) A Braille and tactile fire exit map as shown in Figure 32 shall be
provided directly above the call button of the accessible lift in the lobby
of the accessible lift in a building if a fire exit map for the use of the
public is provided. The map shall be placed at 800 mm to 1200 mm
above the finished floor level.
83
(+0 mm) Base Plate
(+4 mm)
(+4 mm)
A. Design Considerations
Persons with visual impairment may have difficulty in identifying their locker for
public use, and sanitary fitments in a public toilet or changing room.
(a) Each locker door in a sports complex, public swimming pool complex or
public area should be provided with the locker number in Braille and
raised Arabic numerals/characters*.
(b) A Braille and tactile plan (see Figure 32A) should be provided for the
toilets with five or more waterclosets (urinal in a public male toilet and
changing room is regarded as a watercloset for this purpose) in a public
toilet/changing room. The plan should be installed on the wall adjacent to
the door of the public toilet/changing room, or their entrance if entrance
door is not provided. The plan should be placed at 900 mm to 1500 mm
above the finished floor level.
84
Watercloset
Figure 32A – Example of Braille and Tactile Plan of Toilet and Changing Room
85
Division 14 -- Special Obligatory Design Requirements to Assist Persons with
Visual/Hearing Impairment to Various Uses of Buildings in Table 2
(1) This paragraph applies to any part of a building used for the purposes as
specified in Table 2 in Chapter 2.
(2) If a floor plan for the use of the public is provided, Braille and tactile floor
plan showing the main entrance, public toilet and major common facilities
shall be provided in a place in that building which is conspicuous to
persons with visual impairment.
(3) Tactile guide path shall be installed from a point of access at the lot
boundary to the main entrance of the building and from the main entrance
to lift zone, the nearest accessible toilet, public information/service counter,
Braille and tactile floor plan and staircase as illustrated in Figures 33, 34
and 35 respectively.
(4) If visual display board (such as LED) is provided, it shall be able to display
the essence of the information broadcasted by the public address system
in the building. Examples include display boards to inform travellers of the
arrival and destination of the MTR trains.
86
TACTILE
POSITIONAL
TILE/BLOCK WITH
RAISED DOTS OF
NOMINAL 23mm
DIAMETER AT BASE
87
TACTILE POSITIONAL
TILE/BLOCK WITH RAISED
DOTS OF NOMINAL 23mm
DIAMETER AT BASE
TACTILEPOSITIONAL
TILE/BLOCKWITHRAISED
DOTSOFNOMINAL 23mm
DIAMETER AT BASE
88
TACTILE WARNING
(PASSENGER CONVEYOR) TILE/BLOCK WITH
RAISED DOTS OF
NOMINAL 35mm
DIAMETER AT BASE
(PASSENGER CONVEYOR)
89
BEST PRACTICE SECTION
A. Design Considerations
(a) Signs should be clear and easy to read and understand in order to assist
persons with intellectual, cognitive and sensory disabilities.
(c) Prominent signs with high color and luminous contrasts as well as special
shapes are recommended to be used for the elderly.
(e) To account for persons with visual impairment, larger fonts, more
prominent and well-defined shapes of signs are recommended.
(fa) For any part of a building used for the purposes as office, hotel,
guesthouse, hostel or bank, a tactile guide path should be installed from
the main entrance of the building to lift zone, the nearest accessible toilet,
public information/service counter, Braille and tactile floor plan, and
staircase.
90
Figure 37 — Examples of Public Information Symbols
Location
Luminous Contrast
(b) Luminous contrast of not less than 70% should be provided to differentiate
the international symbol of accessibility from the background, either
light-on-dark or dark-on-light. The commonly employed colours are white
for the wheelchair figure and blue for the background.
91
Recommended Design Requirements (Cont’d)
(c) Lettering should be plain and legible, e.g. Helvetica (medium) using lower
case letters except for initial capitals.
(h) Braille and tactile building name and address (i.e., street name with
number) or a device which when activated will provide the same
information in audible form should be provided on both sides of the
building entrance at a height of between 900 mm and 1500 mm above the
finished floor level.
(j) If a floor plan for the use of the public is provided, Braille and tactile floor
plan with audible device indicating the main entrance, public toilet and
major common facilities should be provided in a place in that building
which is conspicuous to persons with visual impairment.
(ja) The Braille and tactile sign for public toilet required under paragraph 68(1)
and (2) in Division 13 should be installed on the wall adjacent to the open
side of the toilet door or toilet entrance if toilet door is not provided.
Visual Sign
(k) Visual display board (such as LED) should be provided in public waiting
areas other than those required in Table 2 in Chapter 2 and where there is
an announcer installed to regularly convey information to the people
inside. The visual display board should be able to display the essence of
the information so announced.
92
Division 15 --- PUBLIC INFORMATION OR SERVICE COUNTERS
MANDATORY SECTION
(2)(a) There shall be at least one public information/service counter built with
a portion not higher than 750 mm above the finished floor level and not
less than 750 mm wide to assist wheelchair users (see Figures 38 and
39).
(2) Leg space of a depth between 400 mm and 600 mm and a height of not
less than 680 mm above finished floor level shall be provided.
93
400-600
680 (MIN.)
*ALL DIMENSIONS ARE IN mm
94
*ALL DIMENSIONS ARE IN mm
A. Design Considerations
(a) The approach to the counter should be direct, clear and unobstructed.
(e) For the convenience of the people using sticks, a recess should be
provided to the information/service counter for them to place the
assistive tools.
95
B. Recommended Design Requirements
Leg space of a depth between 480 mm and 600 mm should be provided for
public information or service counters.
96
Division 16 --- ILLUMINATION
MANDATORY SECTION
Performance Objectives
Signs provided under Division 13 shall have illumination level on the sign
surface of not less than 120 lux.
A. Design Considerations
(a) Artificial lighting should be designed to give uniform illumination and good
colour rendering of all surfaces, without creating glare, or pools of bright
light and strong shadows.
(b) Where appropriate, lighting should be so designed to illuminate the face of
a person speaking in order to make communication easier.
97
A. Design Considerations (Cont’d)
(c) To enhance the illumination level of the lift lobby of upper floors, corridors,
accessible paths and staircases, additional lighting to be provided may be
activated by sensors. The following factors should be considered in
setting the duration of such sensors:
Common Areas
(aa) Lift lobby of upper floors, corridors, accessible paths and staircases should
have an illumination level of not less than 120 lux measured at the finished
floor level. Such enhanced illumination may be provided by additional
lighting activated by sensors.
(b) Lighting with lower illumination level should be provided at the entrances
and exits to provide a contrast between the treads and the risers.
Illumination Level
(d) Higher illumination level at the entrance doors to flats and the exit doors
should be provided.
98
Division 17 --- EMERGENCY CALL BELLS IN ACCESSIBLE TOILETS
This Division sets out the requirements for provision of emergency call bell in
accessible toilets.
MANDATORY SECTION
Performance Objectives
The push button of the emergency call bell shall be appropriately located and
conveniently accessible to all users. The emergency call bell when activated
shall emit audible or visible alarm signal which shall be readily noticeable for
summoning assistance for the person in the accessible toilet. The alarm shall
be installed outside the toilet or a buzzer shall be fitted in the caretaker’s office
(see Figure 24).
An emergency call bell shall be equipped with a weatherproof push button for
activating the alarm. The push button shall be installed below the vertical grab
rail inside the W.C. cubicle adjacent to the water closet at a height between 600
mm and 650 mm above the finished floor level. A notice “Emergency Call” in
both English, Chinese and Braille shall be fitted next to the emergency push
button.
A. Design Considerations
(a) A push button should be easily operated and be provided in any individual
accessible toilet compartment or a water closet cubicle designed for the
persons with a disability to summon assistance at seated position or on the
floor when the person has fallen accidentally. The call button, sometimes
equipped with a pull cord of a length between 700 mm and 750 mm should
be suitably positioned and reachable not more than 300 mm from floor
level.
(c) Emergency call bells should be equipped with a back-up power supply.
99
B. Recommended Design Requirements
(a) The emergency call bell when activated should emit audible and visible
alarm signal which should be readily noticeable for summoning assistance.
(b) Visible and audible signal should be emitted inside the accessible toilet
when the emergency call bell is activated.
100
Division 18 --- ASSISTIVE LISTENING SYSTEM
MANDATORY SECTION
Performance Objectives
A. Design Considerations
101
B. Recommended Design Requirements
Coverage
The assistive listening system must be available to cover not less than
70% of the floor area of the room or space served by the system. If a
system requiring the use of receivers or the like is adopted, a minimum
of 2 receivers should be provided. The number of receivers provided
must be not less than 1 for every 50 persons (or part thereof).
102
Division 19 --- LIFTS
MANDATORY SECTION
Performance Objectives
(2) Where there are more than three lifts in a building, access shall
be provided to every floor by at least one lift having minimum
internal car dimensions of 1500 mm x 1400 mm (either wide or
deep) with a minimum clear entrance width of 850 mm.
103
NOTE: WHERE THE NUMBER OF LIFTS IN A BUILDING EXCEEDS 3, AT LEAST 1 LIFT
SHALL HAVE MINIMUM INTERNAL CAR DIMENSIONS OF 1500mm X 1400mm
104
Obligatory Design Requirements (Cont’d)
(1) Lift car doors and landing doors shall be of the horizontally
sliding type, power-operated and automatically controlled.
(2) Lift call buttons at the lift halls shall not be less than 900 mm
and not more than 1200 mm above the floor of the finished
floor level of the lift hall.
(7) The tactile marking of the push buttons for the main entrance
floor shall be identified with a symbol in a star shape (see
Figure 41).
105
Figure 41 – Tactile Graphic for Lift Control Buttons
106
Obligatory Design Requirements (Cont’d)
A. Design Considerations
(a) Lifts can help to provide access to storeys above or below the
main entrance level. If designed appropriately, lifts are the
most convenient form of vertical access for persons with a
disability. However, given the space constraints in some
buildings, it may not always be possible to install the type and
size of passenger lift that would be suitable for use by all, and
other options may need to be considered to provide for users
with ambulant impairments.
(c) A wheelchair user needs sufficient space and time to enter and
leave a passenger lift, particularly when sharing it with other
people. Lift sizes should therefore be chosen to suit the
anticipated frequency of use of the building and the needs of
persons with a disability.
107
Design Considerations (Cont’d)
(e) The use of visually and acoustically reflective wall surfaces can
cause discomfort for persons with visual and hearing
impairment.
(f) For lifts of the size that does not allow a wheelchair user to turn
around within the lift car, mirror should be installed with the
bottom edge to be set at 900 mm above the floor level in the lift
car to facilitate a wheelchair user in reversing and to see which
level the lift has reached.
(g) Where planning allows, lift cars may be provided with opposing
doors to allow a wheelchair user to leave without having to
reverse.
(a) The graphics for tactile markings for open-door and close-door
push buttons, emergency alarm button, and main entrance
level are shown in Figure 41 for reference.
(bb) Lift control buttons in lift cars should have a minimum luminous
contrasts of 50% with the background surfaces.
Keypad design
108
Recommended Design Requirements (Cont’d)
109
Recommended Design Requirements (Cont’d)
Illumination Level
Lift Doors
(f) The minimum time for lift doors to remain fully open at a
landing should be 3 seconds.
(h) The clear depth of an accessible lift car should be not less
than 1500 mm.
110
INDICATION AND NOTIFICATION FOR LIFTS COMPLYING WITH DIVISION 19
MANDATORY SECTION
Performance Objectives
111
Obligatory Design Requirements (Cont’d)
A. Design Considerations
(b) The audio indication of the stopping floor should be clear and
without background noise.
Tactile Warning
(a) Tactile warning tiles should be placed in front of the lift door of
the accessible lift complying with Division 19 at each landing
for ease of identification by persons with visual impairment.
Control
(b) A separate call button for the accessible lift complying with
Division 19 should be installed on each floor to ensure that the
accessible lift will stop at the called floor. Priority of attendance
to call for the accessible lift should be given to this button.
112
Recommended Design Requirements (Cont’d)
113
Recommended Design Requirements (Cont’d)
114
Division 20 --- ESCALATORS AND PASSENGER CONVEYORS
MANDATORY SECTION
Performance Objectives
(1) Tactile warning strips shall be provided at both bottom and top
ends of an escalator. The provision of tactile warning strips is
illustrated in Figure 36.
A. Design Considerations
115
Design Considerations (Cont’d)
Audio Indicator
Alternative Access
116
CHAPTER 5
Switches, socket outlets and controls for lighting and other equipment shall be
located so that they are easily reachable for all users.
A. Design Considerations
(a) Ease of operation, visibility, reachable height and free from obstruction are
key factors that affect the use of building services by persons with a
disability.
(b) All outlets, switches and controls should be positioned consistently in
relation to doorways and corners within a building and in a logical
sequence of passage through the building.
(c) Switches close to the floor or skirting are difficult to reach and dangerous
because the users have to stoop or kneel to operate them. The higher the
socket outlet, the easier it is to push in or pull out the plug. However, there
may be exceptions to height requirements for some socket outlets, e.g.
those set into the raised flooring in open plan offices.
(d) Operation of controls intended to be used by persons with a disability
should not require the use of both hands simultaneously.
(e) To cater for persons with visual impairment, controls should be in colour
and luminous contrast with the background, and with embossed
information on them for tactile reading.
Positioning
(a) Except as otherwise provided in Division 19 for lifts, the controls for the
operation of building services or safety devices including electrical
switches, light switches, thermostats, intercom switches and card reading
machines which are intended to be accessible to wheelchair users should
be located between 450 mm and 1200 mm above the finished floor level
(see Figure 43).
117
Recommended Design Requirements (Cont’d)
Positioning (Cont’d)
(b) Electric sockets should be located not lower than 450 mm above the
finished floor level.
Luminous Contrast
(c) Light switches and socket outlets should have a minimum luminous
contrast of 30% with their background to indicate their locations.
Controls
450
118
5.2 FIRE ALARM SYSTEMS
5.2.1 Persons with hearing impairment depend on visual cues to alert them of
emergencies. Persons with hearing impairment may need a visible as well as
audible alarm which is only sufficient to deliver warning to a normal person.
MANDATORY SECTION
Visual Alarm
(a) Subject to paragraph (b), visual alarm signal shall be provided to form part
of the fire alarm system in the form of a flashing red light, labelled “Fire
Alarm 火警” in both English and Chinese. It shall be indicated on separate
plate affixed nearby or engraved on the light cover. The alarm shall be
installed at a prominent location which shall be readily noticeable when
activated in the categories of buildings as specified in Table 2 in Chapter
2.
(b) The provision of visual alarm shall not apply to all exit staircases as
required under the Code of Practice for Fire Safety in Buildings including
the smoke lobbies adjoining the exit staircase, and the following areas:
119
Obligatory Design Requirements (Cont’d)
120
Obligatory Design Requirements (Cont’d)
(c) The manual fire alarm call points or activation controls, e.g. breakglass
units, in places which are intended to be accessible to wheelchair users,
shall be positioned at prominent and accessible locations and installed in
accordance with the Code of Practice for Minimum Fire Service
Installations and Equipment and the Code of Practice for Inspection,
Testing and Maintenance of Installations and Equipment or Fire Services
Department Circular Letter.
Audible Alarm
(d) Audible alarm shall comply with the requirements of the Code of Practice
for Minimum Fire Service Installations and Equipment and the Code of
Practice for Inspection, Testing and Maintenance of Installations and
Equipment published by the Director of Fire Services.
A. Design Considerations
Audible and visual alarm may not be appropriate for use in hospitals and some
specialized medical facilities, such as operating rooms, where it is not intended
to alert or alarm patients who are incapable of independent evacuation. The
sudden strobe flash might disrupt a surgical operation in progress which could
be catastrophic. For such facilities, the requirements for visual and audible
alarm may be modified to suit the norm of industry-accepted practices.
Except for areas designed for domestic use, areas listed in paragraph 5.2.3(b)
should also be provided with visual alarm in situations where person with
hearing impairment has to work alone.
121
5.3 PUBLIC TELEPHONES
A. Design Considerations
(b) Other helpful features which should be provided include support rails;
adequate lighting; seats; big buttons; lamp signaling; amplifying
handset; inductive coupler; speakerphone; and digit 5 indicator.
Keypad
122
Recommended Design Requirements (Cont’d)
123
Recommended Design Requirements (Cont’d)
(f) Phone cards for payphones should bear a “notch” on the left bottom
to aid orientation for persons with visual impairment.
124
5.4 REMOTE SIGNAGE SYSTEMS
A. Design Considerations
(b) With the hand-held receiver, persons with visual impairment can
scan the environment and locate his relative position. It can work
effectively in both interior and exterior applications for landmark
identification and way-finding.
125
5.5 VERTICAL LIFTING PLATFORMS
A vertical lifting platform is a mechanical lift with a platform and walls which
provides vertical circulation between two levels.
A. Design Considerations
(d) Clear instructions for use and emergency alarm should be provided
inside the lifting platform.
Automatic Door
Platform size
126
Recommended Design Requirements (Cont’d)
Safety Barrier
Control
(vi) lifting platform buttons and emergency call button should comply
with paragraphs 80(1) to 80(8) and 80(i) and 80(ii) in Division 19.
For automatic swing doors, the control buttons at the landing side
should meet the requirements in paragraph (ea)(xi) in Section B of
Division 11. The hold-to-run button should be of a minimum
dimension of 50 mm;
(viA) the vertical lifting platform should be self-operable by users
holding a common key;
(viB) call button and CCTV should be provided at every landing to a
vertical lifting platform. The call button should activate an intercom
and video contact with a caretaker’s office or public
information/service counter provided under paragraph 70 in
Division 15 for assistance;
(vii) automatic homing device should be installed so that in the event of
a power failure, the platform lift will descend to the entrance level;
Grab Bars
(viii) grab bars complying with paragraphs 28(3) and (4) in Division 8
should be placed at a height of 900mm from the finished floor level
and be fixed on both sides and at the rear of the platform (door(s)
excepted). The vertical distance between the grab bar and the
control buttons should not be less than 100 mm;
Sign
127
Recommended Design Requirements (Cont’d)
Landing (repealed)
(xii) (repealed)
Figure 45 – (repealed)
128
5.6 DRINKING FOUNTAINS
This paragraph sets out the requirements for provision of drinking fountains.
A drinking fountain is a primary means for providing the public with sanitary
water.
A. Design Considerations
(a) The design and provision of drinking fountains should take into account
the envisaged use of persons with a disability.
(b) The operable controls and direction of water flow should be designed and
installed in a manner to facilitate the use by persons with a disability.
(c) Facilities for wheelchair users call for extra consideration in relation to
access and manoeuvering space.
Provision
(a) Where drinking fountains are provided, at least one of the drinking
fountains on a given floor should have a design complying with this
section.
Spout
(c) Automatic controls or controls with handles of the lever type operable with
a closed fist should be provided.
129
Recommended Design Requirements (Cont’d)
Control
Spatial Arrangement
(e) The spatial arrangement should allow for the provision of:
(i) a clear floor space of at least 750 mm x 1200 mm;
(ii) a clear knee space of at least 750 mm wide, 200 mm deep and
680 mm high between the bottom of the apron and the floor or
ground; and
(iii) a toe space not less than 750 mm wide, 230 mm deep and 230 mm
high.
(g) A wall guard should be installed to protect a drinking fountain that extends
into a corridor and has an open space underneath.
Dimensions relating to the design of drinking fountains are shown in Figure 46.
130
230
(MIN.)
230 (MIN.)
230
(MIN.)
131
CHAPTER 6
6.1 GENERAL
Many aspects of design for persons with a disability are already covered in the
Mandatory Sections of this Design Manual and can be usefully applied to the
design of both interiors and exteriors of all structures and buildings to make them
more friendly to the elderly. The guidelines set out in this Chapter aim to provide
additional design recommendations for building a more comfortable, healthy and
safe built-environment for older persons.
132
6.2 DESIGN CONSIDERATIONS (Cont’d)
133
6.2 DESIGN CONSIDERATIONS (Cont’d)
6.2.3 The elderly would have Resting places with resting facilities,
decreased stamina. such as seats (including fold-down
seats) or lean-on railings, should be:
134
6.2 DESIGN CONSIDERATIONS (Cont’d)
6.2.4 The elderly may have Different colours should be used for
difficulties in way finding. different floor levels, zonings or areas of
different functional purposes.
6.2.5 The elderly may fall due to Switches and controls should be
bending, stooping and installed at reachable heights preferably
stretching. at the same level as door handles.
135
6.2 DESIGN CONSIDERATIONS (Cont’d)
6.2.7 The elderly may have Sliding door is a good choice. Should
difficulties in pushing open door closing devices be used, they
heavy doors. should be designed to allow external
and internal doors to be opened with
horizontal forces of not more than 28N
and 18N respectively.
6.2.8 The elderly require safety Doors of bathrooms and toilets should
design provisions for open outward or both ways. Locks and
bathrooms and toilets. latches should be of larger sizes and be
able to open from outside with a coin.
136
6.2 DESIGN CONSIDERATIONS (Cont’d)
137
Figure 47 – Examples of Door Handles and Faucets
138
Appendix A
Anthropometrics
APPENDIX A
ANTHROPOMETRICS
(All dimensions are in mm)
A.1 Objective:
This Appendix contains dimensional data which can be used for guidance when
designing facilities and equipment for use by persons with a disability.
A.2 Considerations:
The dimensions of the individual human being vary with time and from one person to
another. In addition, the average dimensions vary from one country to another.
When carrying out detailed design, consideration should be given to size variation
between males and females as well as between different ages.
A/1
Figure A3 - Dimensional Data of a Wheelchair User
A/2
A.3 Forward reach of a wheelchair user
The maximum forward reach, without obstruction, is 1200 mm from the floor and the
minimum forward reach is 400 mm from the floor as shown in Figures A5 and A7.
The maximum forward reach over an obstruction 500 mm deep is 1100 mm from the
floor as shown in Figure A6.
The maximum side reach over an obstruction 860 mm high by 500 mm deep is 1200
mm from the floor as shown in Figure A10.
A/4
Persons with visual impairment using a long white cane Persons using crutches
Path width for a person together with Path width for two wheelchair users
a wheelchair user
A/5
Appendix B
Guidelines for
Wheelchair Transfer and
Movement
APPENDIX B
800 MIN
10-27 kg
36-100 kg
B/1
Figure B2 – Manoeuvring Spaces for Doorway
B/2
1/4 Turn 1/2 Turn
Complete Turn
WASTE
1000 MAX
1200 MAX
B/3
Figure B5 – Diagonal Approach for Transferring from a wheelchair
to a W.C. (Diagonal Approach)
B/4
Figure B6 – Side Approach for Transferring from a
Wheelchair to a W.C.
B/5
Appendix C
Slip Resistance of
Flooring Materials
APPENDIX C
This appendix aims to provide design references of slip resistance for flooring
materials and floor finishes.
Materials and finishes are graded under dry and wet conditions. The gradings given
herein are for reference only, actual value of “static coefficient of friction” shall be
subject to the manufacturer’s recommended characteristics.
Excessive slip resistance can also be hazardous since it may create unexpected grip
on the surface.
“Very Good” - Material surface suitable for use in areas where special design care
is required, with an approximate “static coefficient of friction” value
of 0.8 or above.
“Poor” - Unsafe material surface with high potential for slip, with an
approximate “static coefficient of friction” value below 0.2.
Commentary
“Slip resistance” is based on the frictional force required to keep a shoe heel or crutch
tip from slipping on a walking surface. While the “dynamic coefficient of friction” during
walking varies in a complex and non-uniform way, the “static coefficient of friction”,
which can be measured in several ways, provides a close approximation of the slip
resistance of a surface. However, it is generally recognized that the “static coefficient
of friction” varies considerably due to the presence of contaminants, water, floor
finishes, and other factors not under the control of the designer or builder and not
subject to design and construction guidelines and that compliance of which would be
difficult to measure on the building site. For details of method of measuring “slip
resistance”, readers are suggested to make reference to some available overseas
standards such as AS/NZS 4586-2004, AS/NZS 4663-2004, ASTM 1679, ASTM 1677,
BS 7976-2, BS 8204 etc.
C/1
Appendix D
Luminous Contrast
APPENDIX D
LUMINOUS CONTRAST
Types of contrast
Colour contrast
Colour contrast is the difference between colours positioned on a colour wheel. For
example violet is the contrast to yellow, red is contrasted to green. Colours can
contrast on the basis of their lightness, saturation or hue.
(a) lightness measures the relative amount of light reflected from a colour;
(b) saturation relates to its intensity; and
(c) hue refers to elementary colour names, that is red, green, blue etc.
The perception of colour, however, can change with the type of light. Some people
with visual impairment are unable to see colours as ageing and sight loss diminish
their sensitivity of colour perception. Therefore colour contrast on its own may not
be sufficient to provide a visual contrast.
D/1
Luminous contrast
Luminous contrast is the amount of light reflected from one surface or component,
compared to the amount of light reflected from the background or base surfaces.
Luminous contrast is preferred to colour contrast because it offers light/dark
differences that can be picked up more easily by people with visual impairment.
Two quite differently coloured surfaces may have a similar luminous. For example,
cherry red on black has a high colour contrast but low luminous contrast and is not as
visible as pale pink or yellow on black to people with visual impairment.
D/2
Measurement of Luminous Contrast
“Luminous contrast” means the amount of light reflected from the surface of the
object compared to the amount of light reflected from the surface of its surrounding
background. Such contrast expressed in percent can be determined by:
[(B1-B2) / B1] x 100
Where
B1 = light reflectance value (LRV) of the lighter area and
B2 = light reflectance value (LRV) of the darker area.
Lighting
D/3