Ansi C57.92 Trafo
Ansi C57.92 Trafo
Ansi C57.92 Trafo
AND TECHNIQUES
Volume 1-5
PERMISSIBLE LOADING OF
OIL-IMMERSED TRANSFORMERS
AND REGULATORS
Paragraph Page
1 Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
3 Overload Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
5 Aging of Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
6 Hottest-Spot Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
B. Supplemental Cooling
15 Supplemental Cooling for Existing Transformers . . . . . . . . . . . . . . . . . . . . . . . 4
17 Water Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
19 Transformer Operation With Part or All of the Cooling Out of Service ..... 4
Bibliographic References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Figure Page
14 Loss of life versus temperature for different time periods (55 OC rise) . . . . . . . . . . 20
15 Loss of life versus temperature for different time periods (65 OC rise) . . . . . . . . 21
the load factor, and the altitude above sea level temperatures below 95° and 110 °C respectively.
if air is used as the cooling medium. This is due to the fact that aging is a cumulative
Transformers are designed on the basis of 55° or process. The limitations are given in figures 8
65°C rise above the ambient temperature as through 13.
determined by average winding resistance and
are so rated on the nameplate, However, In The maximum temperatures permissible for
actual operation, the hottest-spot temperature transformer operation under the above
should be used as the limitation rather than the conditions are the following ANSI (American
average winding temperature rise. Transformers Standards Institute) values:
may be operated continuously at hottest-spot
temperatures up to 95°C for 55°C rated
transformers; 110°C for 65°C rated transformers. Maximum temperature,°C
Where no hottest-spot temperature indicator is
available, or when it is desired to determine in Type of Insulation temperature
advance approximately what the load limit will be temperature rise design, °C
under special conditions, the data in figures 1
though 13 can be used. Indicator 55 65
14. OVERLOADS DURING SYSTEM may have the output increased in many cases
EMERGENCIES.- Certain transformers critical to 25 to 33 percent by the addition of forced-air
system operation may, at some time, have to be cooling by means of fans. Similarly, the
overloading during power system emergencies, in addition of external forced-oil cooling to oil-
order to preserve system stability. As a guide, an insulated self-cooled or water-cooled
overload resulting in a loss of insulation life of 5 transformers may increase the output in many
percent in any one emergency is considered cases 25 to 50 percent.
reasonable. Such critical transformers should be
so designated on switching diagrams and the 17. WATER COOLING.- Do not spray water
thermal relay wired through the high temperature on transformers or radiators except in dire
contact to provide a second alarm, rather than emergency. As water evaporates, minerals
trip. The magnitude and duration of the overload from the water will adhere to cooling surfaces,
should be carefully estimated (using maximum the minerals are almost impossible to remove.
reading on the transformer thermometer and This will further reduce cooling and transformer
system load charts) and records maintained to life.
ensure that transformer life is not being sacrificed
needlessly. However, when system conditions C. STEP-VOLTAGE AND INDUCTION-
require that transformers be routinely overloaded VOLTAGE REGULATORS
have been extracted from ANSI Appendix: inoperative, the following operating conditions
C57.92- 1962, and NEMA Publication No. TR are as to occur infrequently and without undue
98 - 1964. Older transformers purchased injury to the transformer:*
under earlier standards may require more
conservative operating practices with all or a. Rated load may be maintained for
part of the cooling out of service. If any doubt approximately 1 hour following normal
exists about permissible loading under these operation at nameplate rating at 30 °C
conditions, the problem should be referred to ambient.
the Facilities Engineering Branch, Code D
5210, Denver Office, for recommendations b. Rated load may be carried for
and instructions. approximately 2 hours if started with the
windings and oil at 30 °C ambient.
Where auxiliary equipment, such as pumps or
fans or both, is used to increase the coding c. Rated voltage may be maintained for
efficiency, the transformer may be required to 6 hours at no load, following continuous
operate for some time without this equipment operation at nameplate rating at 30 °C
functioning. The permissible loading under the ambient with cooling equipment in
conditions as specified is given in the following operation.
paragraphs.
For forced-oil-cooled transformer (FOA or
For forced-air-cooled (OA/FA or OA/FA/FA) FOW) ratings with part of the coolers in
transformers with fans inoperative, use the operation, use the following:
self-cooled rating and apply loads on the same
basis as if the transformer were self-cooled. Percent of total Permissible load in
For forced-air, forced-oil-cooled transformers coolers in operation percent of
triple rated (OA/FA/FOA or OA/FOA/FOA) with nameplate rating
all or part of the forced cooling inoperative,
use the nameplate rating based on the cooling 100 100
in operation and load on this basis. 80 90
60 78
For forced-oil-coded (FOA or FOW) 50 70
transformers with all pumps or fans or both 40 60
33 50
• The oil temperature for large units may exceed 100 °C for 55 °C rise transformers; 110 °C for 65 °C
rise transformers. Check with the manufacturer for limitations.
Calculating Transformer Rise for Various Guide for Loading Oil-Immersed Step-Voltage
Loads, Allis-Chalmers Electrical Review, First and Induction-Voltage Regulators, American
Quarter 1948 National Standard Appendix: C57.95-1955
General Requirements for Distribution. Power, It's Simple to Overload Transformers Safely-If
and Regulating Transformers, American Na- You Know How, AIIis-Chalmers Electrical Re
Standard C57.12.00-1973 view, March 1944
Guide for Loading Oil-Immersed Distribution Quick Determination of Safe Transformer Over
and Power Transformers, American National loads, Westinghouse Engineer, February 1943
Standard Appendix: C57.92-1962
Transformer Ratings Based on Life Expec
Guide for Loading Oil-Immersed Power Trans tancy, Electric Light and Power, October 1945
formers with 65 °C Average Winding Rise,
NEMA Publication No. TR 98-1964