HF-REGULATOR Electronic Regulating Ballasts For PL-T and PL-C Lamps
HF-REGULATOR Electronic Regulating Ballasts For PL-T and PL-C Lamps
HF-REGULATOR Electronic Regulating Ballasts For PL-T and PL-C Lamps
79
Applications
Typical areas of application
123 include:
• Installations with daylight-linked
1-lamps and remote control systems
• Installations with emergency
146 back-up, according to VDE 0108
• Installations with infrared
4.5
remote control systems
• Conference rooms
• Cinemas
• Department stores, shops,
supermarkets
• Office buildings: insurance
companies, banks, government
102
90
ministries
• Hospitals
• Hotels.
38
158
2-lamps
1
HF-REGULATOR electronic regulating ballasts
for PL-T and PL-C lamps
Technical data in relation to energy saving
Lamp Qty. of Ballast System Lamp
lamps power* Power* Efficacy* Lumen*
W W lm/W lm
PL-T 18W 1 HF-R 118 PL-T/C 21 16.5 73 1200
PL-C 18W 1 HF-R 118 PL-T/C 21 16.5 73 1200
PL-T 18W 2 HF-R 218 PL-T/C 38 16.5 73 1200
PL-C 18W 2 HF-R 218 PL-T/C 38 16.5 73 1200
PL-T 26W 1 HF-R 126 PL-T/C 29 24 75 1800
PL-C 26W 1 HF-R 126 PL-T/C 29 24 75 1800
PL-T 26W 2 HF-R 226 PL-T/C 54 24 75 1800
PL-C 26W 2 HF-R 226 PL-T/C 54 24 75 1800
PL-T 32W 1 HF-R 132 PL-T 38 32 75 2400
PL-T 32W 2 HF-R 232 PL-T 72 32 75 2400
PL-T 42W 1 HF-R 142 PL-T 50 43 74 3200
PL-T 42W 2 HF-R 242 PL-T 96 43 74 3200
* At 100%.
Technical data for installation Automatic restart after lamp
replacement or voltage dip yes
Mains operation
Rated mains voltage 220 - 240 V Insulation resistance test 500 V DC from Line/Neutral to Earth
with tolerances for safety: +/- 10% 198 - 264 V (not between Line and Neutral)
tolerances for performance: +6% -8% 202 - 254 V Note: Ensure that the Neutral is
Mains frequency 50/60 Hz reconnected again after above-
Operating frequency > 42 kHz mentioned test is carried out and
Power factor 0.95 at 100% before the installation is put into
power operation.
Smart power: with AC mains voltage fluctuations, 202 - 254 V
luminous flux varies by ± 2% max. Mains current at 230 V
Ballast Input current
DC voltage operation (during emergency back-up) A
Required battery voltage for guaranteed ignition 198 - 254 V DC HF-R 118 PL-T/C 0.09
Required battery voltage for burning lamps 176 - 254 V DC HF-R 218 PL-T/C 0.17
HF-R 126 PL-T/C 0.13
Control input HF-R 226 PL-T/C 0.24
Control voltage 1 - 10 V DC HF-R 132 PL-T 0.17
Protected against accidental mains HF-R 232 PL-T 0.31
voltage connection yes HF-R 142 PL-T 0.22
HF-R 242 PL-T 0.42
Regulating level (lamp power) 3 to 100%
The control input complies with IEC 929,
Amendment 1, Annex E and is compatible
with Philips lighting control equipment.
Inrush current
Ignition time <2s Ballast Max. quantity of Inrush current
Earth leakage current < 0.5 mA per ballasts per 1/2 value time
ballast Miniature Circuit at typical
Breaker mains impedance
Maximum number of ballasts 30 type B 16 A type C 16 A
which can be connected to one HF-R 118 PL-T/C 28 48 40A/110µs
Residual Current Detector of 30 mA HF-R 218 PL-T/C 28 48 35A/120µs
HF-R 126 PL-T/C 28 48 40A/110µs
Overvoltage protection 48 hr at 320 V AC HF-R 226 PL-T/C 28 48 35A/120µs
2 hr at 350 V AC HF-R 132 PL-T 28 48 40A/110µs
HF-R 232 PL-T 12 20 45A/170µs
Dual fixture; master slave operation not advisable HF-R 142 PL-T 28 48 40A/110µs
HF-R 242 PL-T 12 20 45A/170µs
Advised maximum cable capacity for
optimum performance and
EMI suppression max. 30 pF between lamp wires; Conversion table for max. quantities of ballasts on other types of
max. 75 pF between lamp wires and Miniature Circuit Breaker
earth; care has to be taken for
MCB type Relative quantity of
symmetrical wiring ballasts
Lamp wiring The use of 500 V rated components is B 16 A 100% (see table above)
B 10 A 63%
advised for PL-T 32 W and 42 W types
C 16 A 170%
Note: Keep lamp wiring as short as C 10 A 104%
possible; do not bunch wires from L, I 16 A 108%
terminals 1 & 2 with those from L, I 10 A 65%
terminals 3 & 4 (1-lamp ballasts), or G, U, II 16 A 212%
wires from terminals 3, 4, 5 & 6 with G, U, II 10 A 127%
K, III 16 A 254%
those from terminals 1, 2, 7 & 8 K, III 10 A 154%
(2-lamp ballasts)
2
HF-REGULATOR electronic regulating ballasts
for PL-T and PL-C lamps
N
L
N
L –
+
–
+
1
2
3
4
1-lamp 2-lamps
Wiring diagrams
100 Notes:
Lamp power (W %)