Calculation: Pt. Abb Sakti Industri

1) The document provides calculations for sizing current transformers (CTs) for a 150kV transformer bay project for PT. Star Ajibarang Purwokerto. 2) It calculates parameters such as primary current, secondary current, rated burden, lead resistance, and knee point voltage requirement for three CT cores serving transformer differential protection, overcurrent/earth fault protection, and metering purposes. 3) The calculations determine that the selected CTs meet the knee point voltage requirements for accurate protection and metering.

Uploaded by

Anto Damanik
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
358 views13 pages

Calculation: Pt. Abb Sakti Industri

1) The document provides calculations for sizing current transformers (CTs) for a 150kV transformer bay project for PT. Star Ajibarang Purwokerto. 2) It calculates parameters such as primary current, secondary current, rated burden, lead resistance, and knee point voltage requirement for three CT cores serving transformer differential protection, overcurrent/earth fault protection, and metering purposes. 3) The calculations determine that the selected CTs meet the knee point voltage requirements for accurate protection and metering.

Uploaded by

Anto Damanik
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 13

PT.

ABB SAKTI INDUSTRI

CALCULATION

Project :

GI 150kV PELANGGAN
PT. STAR AJIBARANG PURWOKERTO

Title :

CT SIZING CALCULATION

Reference Drawing :

SLD START-EM-PRJ-001

Rev No Date Remarks Prepare Check Approve


GI 150kV PELANGGAN
PT. ABB SAKTI INDUSTRI BAY TRANSFORMER
PT. STAR AJIBARANG PURWOKERTO

CT SIZING CALCULATION
SELECTION OF PARAMETER OF CURRENT TRANSFORMER FOR BAY TRANSFORMER

Maxsimum cable route length CT to relay panel located in switcyard control building 75 meters

Core 1
Purpose Transformer Differential Protection
Rasio 250/1 A
Primary Current Ipn 250 A
Secodary Current Isn 1 A
Rated Current of the protection IED Ir 1 A
Accuracy Class X
Burrden 30 VA
MVA Rated of the Transformer P 50 MVA
impedance of the transformer Z 12 %
Rated Primary Current of the transformer Int 192.45 A
Rated primary Voltage of the transformer Vnt 150 kV
Maximum primary fundamental frequency
1.604
that passed thru main CT and the power Trafo
Itf 1.604 kA
Conductor cross-section 6 mm²
Conductor material Copper
Number of runs per phase 1
Conductor unit resistance 3.08 Ω/km
lead Resistance at 20⁰C CF+CT Rc 3.75 Ω
Rc = xR
lead Resistance at 70⁰C CF+WT
Two way lead loop resistance RL 1.73 Ω

Relay Burden for RET650 (ABB make) Pb 0.25 VA


Rb Pb/(Isn)²=Ω 0.25 Ω
Total connected burden = Lead Burden + Instrumen Burden 1.98 VA

Current Transformer knee point voltage requirment


Equation 1 Vk 30 x Int x Isn/Ipn x (Rct+RL+Rb/Ir²) 91.93 V
Rct is current transformer secondary winding resistance at 75⁰C at selected ratio 2 Ω
Current transformer knee point voltage requirment Vk 91.93 V
Knee point volatge of CT
Vk = ALF x Is (VA/(Is²)+ (Is x Rct)) V
Vk 640 V
Required knee point voltage is less than selected,Hence CT selected is adequate.
where

RC is the corrected resistance


RM is the measured resistance
CF is the correction factor for copper (234.5) or aluminum (225) windings
CT is the corrected temperature (75°C or 85°C)
WT is the winding temperature (°C) at time of test

Page : 3 of 13
GI 150kV PELANGGAN
PT. ABB SAKTI INDUSTRI BAY TRANSFORMER
PT. STAR AJIBARANG PURWOKERTO

Core 2
Purpose O/C & E/F Prot
Rasio 250/1 A
Primary Current Ipn 250 A
Secodary Current Isn 1 A
Rated Current of the protection IED Ir 1 A
Accuracy Class X
Burrden 30 VA
MVA Rated of the Transformer P 50 MVA
impedance of the transformer Z 12 %
Rated Primary Current of the transformer Int 192.45 A
Rated primary Voltage of the transformer Vnt 150 kV
Maximum primary fundamental frequency P
1.604
that passed thru main CT and the power Trafo V3xZxVnt
Itf 1.604 kA
Conductor cross-section 6 mm²
Conductor material Copper
Number of runs per phase 1
Conductor unit resistance 3.08 Ω/km
lead Resistance at 20⁰C CF+CT Rc 3.75 Ω
Rc = xR
lead Resistance at 70⁰C CF+WT
lead loop resistance RL 1.73 Ω
Lead Burden 1.73 VA
Relay Burden for REF615 (ABB make) Pb 0.05 VA
Rb Pb/(Isn)²=Ω 0.05 Ω
Total connected burden = Lead Burden + Instrumen Burden 1.78 VA

Current Transformer knee point voltage requirment


Equation 1 Vk 30 x Int x Isn/Ipn x (Rct+RL+Rb/Ir²) 87.31 V
Rct is current transformer secondary winding resistance at 75⁰C at selected ratio 2 Ω
Current transformer knee point voltage requirment Vk 87.31 V
Knee point volatge of CT
Vk = ALF x Is (VA/(Is²)+ (Is x Rct)) V
Vk 640 V

Page : 4 of 13
GI 150kV PELANGGAN
PT. ABB SAKTI INDUSTRI BAY TRANSFORMER
PT. STAR AJIBARANG PURWOKERTO

Core 3
Purpose Metering
Rasio 250/1 A
Primary Current Ipn 250 A
Secodary Current Isn 1 A
Rated Current of the protection IED Ir 1 A
Accuracy Class 0.5
Burrden 30 VA
MVA Rated of the Transformer P 50 MVA
impedance of the transformer Z 12 %
Rated Primary Current of the transformer Int 192.45 A
Rated primary Voltage of the transformer Vnt 150 kV
Maximum primary fundamental frequency P
1.604
that passed thru main CT and the power Trafo V3xZxV
Itf 1.604 kA
Conductor cross-section 6 mm²
Conductor material Copper
Number of runs per phase 1
Conductor unit resistance 3.08 Ω/km
lead Resistance at 20⁰C CF+CT Rc 3.75 Ω
Rc = xR
lead Resistance at 70⁰C CF+WT
lead loop resistance RL 1.73 Ω
Lead Burden 1.73 VA
Metering Relay Burden Pb 0.3 VA
Rb Pb/(Isn)²=Ω 0.3 Ω
Total connected burden = Lead Burden + Instrumen Burden 2.03 VA

Required Burden is less than selected,Hence CT selected is adequate.

Page : 5 of 13
GI 150kV PELANGGAN
PT. ABB SAKTI INDUSTRI BAY TRANSFORMER
PT. STAR AJIBARANG PURWOKERTO

Page : 6 of 13
GI 150kV PELANGGAN
PT. ABB SAKTI INDUSTRI BAY OVER HEAD LINE
PT. STAR AJIBARANG PURWOKERTO

CT SIZING CALCULATION
SELECTION OF PARAMETER OF CURRENT TRANSFORMER FOR BAY OVER HEAD LINE

Maxsimum cable route length CT to relay panel located in switcyard control building 150 meters

Core 1
Purpose Line Differential
Rasio 600/1 A
Primary Current Ipn 600 A
Secodary Current Isn 1 A
Rated Current of the protection IED Ir 1 A
Accuracy Class X
Burrden 30 VA
MVA Rated of the Transformer P 100 MVA
impedance of the transformer Z 12 %
Rated Primary Current of the transformer Int 384.90 A
Rated primary Voltage of the transformer Vnt 150 kV
Maximum primary fundamental frequency
3.208
that passed thru main CT and the power Trafo
Imax 3.208 kA
Conductor cross-section 6 mm²
Conductor material Copper
Number of runs per phase 1
Conductor unit resistance 3.08 Ω/km
lead Resistance at 20⁰C CF+CT Rc 3.75 Ω
Rc = xR
lead Resistance at 70⁰C CF+WT
Two way lead loop resistance RL 3.46 Ω

Relay Burden for RED650 (ABB make) Pb 0.15 VA


Rb Pb/(Isn)²=Ω 0.15 Ω
Total connected burden = Lead Burden + Instrumen Burden 3.61 VA

Current Transformer knee point voltage requirment


Equation 1 Vk 30 x Int x Isn/Ipn x (Rct+RL+Rb/Ir²) 107.98 V
Rct is current transformer secondary winding resistance at 75⁰C at selected ratio 2 Ω
Current transformer knee point voltage requirment Vk 107.98 V
Knee point volatge of CT
Vk = ALF x Is (VA/(Is²)+ (Is x Rct)) V
Vk 640 V
Required knee point voltage is less than selected,Hence CT selected is adequate.
where

RC is the corrected resistance


RM is the measured resistance
CF is the correction factor for copper (234.5) or aluminum (225) windings
CT is the corrected temperature (75°C or 85°C)
WT is the winding temperature (°C) at time of test

Page : 7 of 13
GI 150kV PELANGGAN
PT. ABB SAKTI INDUSTRI BAY OVER HEAD LINE
PT. STAR AJIBARANG PURWOKERTO

Core 2
Purpose O/C & E/F Prot
Rasio 600/1 A
Primary Current Ipn 600 A
Secodary Current Isn 1 A
Rated Current of the protection IED Ir 1 A
Accuracy Class 5P20
Burrden 30 VA
MVA Rated of the Transformer P 100 MVA
impedance of the transformer Z 12 %
Rated Primary Current of the transformer Int 384.90 A
Rated primary Voltage of the transformer Vnt 150 kV
Maximum primary fundamental frequency
3.208
that passed thru main CT and the power Trafo
Imax 3.208 kA
Conductor cross-section 6 mm²
Conductor material Copper
Number of runs per phase 1
Conductor unit resistance 3.08 Ω/km
lead Resistance at 20⁰C CF+CT Rc 3.75 Ω
Rc = xR
lead Resistance at 70⁰C CF+WT
Two way lead loop resistance RL 3.46 Ω

Relay Burden for REF615 (ABB make) Pb 0.05 VA


Rb Pb/(Isn)²=Ω 0.05 Ω
Total connected burden = Lead Burden + Instrumen Burden 3.51 VA

Current Transformer knee point voltage requirment


Equation 1 Vk 30 x Int x Isn/Ipn x (Rct+RL+Rb/Ir²) 106.06 V
Rct is current transformer secondary winding resistance at 75⁰C at selected ratio 2 Ω
Current transformer knee point voltage requirment Vk 106.06 V
Knee point volatge of CT
Vk = ALF x Is (VA/(Is²)+ (Is x Rct)) V
Vk 640 V

Page : 8 of 13
GI 150kV PELANGGAN
PT. ABB SAKTI INDUSTRI BAY OVER HEAD LINE
PT. STAR AJIBARANG PURWOKERTO

Core 3
Purpose Metering
Rasio 600/1 A
Primary Current Ipn 600 A
Secodary Current Isn 1 A
Rated Current of the protection IED Ir 1 A
Accuracy Class 0.2
Burrden 30 VA
MVA Rated of the Transformer P 100 MVA
impedance of the transformer Z 12 %
Rated Primary Current of the transformer Int 384.90 A
Rated primary Voltage of the transformer Vnt 150 kV
Maximum primary fundamental frequency
3.208
that passed thru main CT and the power Trafo
Itf 3.208 kA
Conductor cross-section 6 mm²
Conductor material Copper
Number of runs per phase 1
Conductor unit resistance 3.08 Ω/km
lead Resistance at 20⁰C CF+CT Rc 3.75 Ω
Rc = xR
lead Resistance at 70⁰C CF+WT
Two way lead loop resistance RL 3.46 Ω

Metering Relay Burden Pb 0.3 VA


Rb Pb/(Isn)²=Ω 0.3 Ω
Total connected burden = Lead Burden + Instrumen Burden 3.76 VA

Required Burden is less than selected,Hence CT selected is adequate.

Page : 9 of 13
GI 150kV PELANGGAN
PT. ABB SAKTI INDUSTRI BAY OVER HEAD LINE
PT. STAR AJIBARANG PURWOKERTO

Core 4
Purpose SPARE
Rasio 600/1 A
Primary Current Ipn 600 A
Secodary Current Isn 1 A
Rated Current of the protection IED Ir 1 A
Accuracy Class X
Burrden 30 VA
MVA Rated of the Transformer P 100 MVA
impedance of the transformer Z 12 %
Rated Primary Current of the transformer Int 384.90 A
Rated primary Voltage of the transformer Vnt 150 kV
Maximum primary fundamental frequency
3.208
that passed thru main CT and the power Trafo
Imax 3.208 kA
Conductor cross-section 6 mm²
Conductor material Copper
Number of runs per phase 1
Conductor unit resistance 3.08 Ω/km
lead Resistance at 20⁰C CF+CT Rc 3.75 Ω
Rc = xR
lead Resistance at 70⁰C CF+WT
Two way lead loop resistance RL 3.46 Ω

Relay Burden for Spare Pb 0.25 VA


Rb Pb/(Isn)²=Ω 0.25 Ω
Total connected burden = Lead Burden + Instrumen Burden 3.71 VA

Current Transformer knee point voltage requirment


Equation 1 Vk 30 x Int x Isn/Ipn x (Rct+RL+Rb/Ir²) 109.91 V
Rct is current transformer secondary winding resistance at 75⁰C at selected ratio 2 Ω
Current transformer knee point voltage requirment Vk 109.91 V
Knee point volatge of CT
Vk = ALF x Is (VA/(Is²)+ (Is x Rct)) V
Vk 640 V

Page : 10 of 13
GI 150kV PELANGGAN
PT. ABB SAKTI INDUSTRI BAY OVER HEAD LINE
PT. STAR AJIBARANG PURWOKERTO

Page : 11 of 13
GI 150kV PELANGGAN
PT. ABB SAKTI INDUSTRI PT. STAR AJIBARANG PURWOKERTO

PARAMETERS OF CURRENT TRANSFORMERS


SELECTION OF PARAMETER OF CURRENT TRANSFORMER FOR ALL BAY

Bay Transformer

Selected Calculated Required Proposed


Ratio CT Rct
Core Class Burden Burden Vk Equiv. Vk Device
[A] [Ω] [VA] [VA] [V] [V]
1 250-500/1 X ≤2 30 1.98 91.93 640.00 RET650
2 250-500/1 X ≤2 30 1.78 87.31 640.00 REF615
3 250-500/1 5P20+0,5 - 30 2.03 - - Metering

Bay Line

Selected Calculated Required Proposed


Ratio CT Rct
Core Class Burden Burden Vk Equiv. Vk Device
[A] [Ω] [VA] [VA] [V] [V]
1 300-600/1 X ≤2 30 3.61 107.98 640.00 RED670
2 300-600/1 X ≤2 30 3.51 106.06 640.00 REF615
3 300-600/1 0.2 - 30 3.76 - - Metering
4 300-600/1 X - 30 3.71 109.91 640.00 N/A

Page : 12 of 13
GI 150kV PELANGGAN
PT. ABB SAKTI INDUSTRI PT. STAR AJIBARANG PURWOKERTO

Page : 13 of 13