ABB Motor Protection and Control REM615 Products
ABB Motor Protection and Control REM615 Products
Contents
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB Oy. ABB Oy assumes
no responsibility for any errors that may appear in this document.
Trademarks
ABB and Relion are registered trademarks of ABB Group. All other brand or product names mentioned in this document may be trademarks or
registered trademarks of their respective holders.
2 ABB
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
Revision: B
Description Std.conf.
Motor protection with current and voltage based protection and
C
measurements functions
ABB 3
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
Functionality C
Protection 1)
4 ABB
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
ABB 5
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
GUID-12D3399C-F58F-441D-A795-A71F71910B19 V1 EN
6 ABB
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
ABB 7
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
GUID-52860380-D410-4969-A44E-7C7311221D0F V1 EN
Figure 2. Motor protection and control of contactor and circuit-breaker controlled motors
using REM615 with the standard configuration C. To prevent possible power system
instability due to busbar voltage collapse, the simultaneous starting of several motors
is inhibited. The motor start-up signal from each REM615 is connected to the “Restart-
inhibit” inputs of the other REM615s. Hence while one motor is starting-up, the
starting of the other motors is inhibited. The same motor start-up signal is also used
to dynamically increase the setting level of the lowest O/C protection stage of the
REF615 on the incoming feeder
8 ABB
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
Product Version
Station Automation COM600 3.3 or later
MicroSCADA Pro 9.2 SP1 or later
ABB 9
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
ABB
System 800xA
OPC
COM600 COM600
Web HMI Web HMI
COM600 COM600
Binary signal
transfer
Fibre optic LD
REF615 RET615 REM615 RED615 communication RED615 REM615 RET615 REF615
GUID-6984D893-45D5-427A-BABF-F1E1015C18E2 V1 EN
Figure 3. Industrial power system example using 615 series IEDs, Station Automation COM600
and System 800xA
8. Disturbance recorder
7. Measurement The IED is provided with a disturbance
recorder featuring up to 12 analog and 64
The IED continuously measures the phase binary signal channels. The analog channels
currents and the neutral current. Further, the can be set to record either the waveform or
IED measures the phase voltages and the the trend of the currents and voltage
residual voltage. In addition, the IED measured.
calculates the symmetrical components of the The analog channels can be set to trigger the
currents and voltages, maximum current recording function when the measured value
demand value over a user-selectable pre-set falls below or exceeds the set values. The
time frame, the active and reactive power, the binary signal channels can be set to start a
power factor, and the active and reactive recording on the rising or the falling edge of
energy values. Calculated values are also the binary signal or both.
obtained from the protection and condition
monitoring functions of the IED.
10 ABB
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
ABB 11
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
12 ABB
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
Modbus implementation supports RTU, ASCII In addition, the IED supports time
and TCP modes. Besides standard Modbus synchronization via the following serial
functionality, the IED supports retrieval of communication protocols:
time-stamped events, changing the active
ABB 13
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
14 ABB
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
Description Value
Width frame 179.8 mm
case 164 mm
Height frame 177 mm (4U)
case 160 mm
Depth 194 mm (153 + 41 mm)
Weight IED 3.5 kg
spare unit 1.8 kg
80...120% of Un (38.4...300 V
DC)
Start-up threshold 19.2 V DC (24 V DC * 80%)
Burden of auxiliary 250 V DC ~ 9.0 W (nominal)/~ 60 V DC ~ 8.5 W (nominal)/~
voltage supply under 13.7 W (max) 13.4 W (max)
quiescent (Pq)/operating 240 V AC ~ 10.6 W (nominal)/
condition ~ 15.5 W (max)
Ripple in the DC auxiliary Max 12% of the DC value (at frequency of 100 Hz)
voltage
Maximum interruption • 110 V DC: 86 ms 48 V DC: 64 ms
time in the auxiliary DC • 110 V AC: 118 ms
voltage without resetting
the IED
Fuse type T4A/250 V
ABB 15
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
Description Value
Rated frequency 50/60 Hz ± 5 Hz
Current inputs Rated current, In 0.2/1 A1) 1/5 A2)
Thermal withstand
capability:
• Continuously 4A 20 A
Dynamic current
withstand:
• Half-wave value 250 A 1250 A
Description Value
Operating range ±20% of the rated voltage
Rated voltage 24...250 V DC
Current drain 1.6...1.9 mA
Power consumption 31.0...570.0 mW
Threshold voltage 18...176 V DC
Reaction time 3 ms
16 ABB
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
Description Value
Rated voltage 250 V AC/DC
Continuous contact carry 5A
Make and carry for 3.0 s 10 A
Make and carry 0.5 s 15 A
Breaking capacity when the control-circuit 1 A/0.25 A/0.15 A
time constant L/R<40 ms, at 48/110/220 V DC
Minimum contact load 100 mA at 24 V AC/DC
Description Value
Rated voltage 250 V AC/DC
Continuous contact carry 8A
Make and carry for 3.0 s 15 A
Make and carry for 0.5 s 30 A
Breaking capacity when the control-circuit 5 A/3 A/1 A
time constant L/R<40 ms, at 48/110/220 V
DC (two contacts connected in series)
Minimum contact load 100 mA at 24 V AC/DC
Trip-circuit supervision (TCS):
• Control voltage range 20...250 V AC/DC
ABB 17
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
Description Value
Rated voltage 250 V AC/DC
Continuous contact carry 8A
Make and carry for 3.0 s 15 A
Make and carry for 0.5 s 30 A
Breaking capacity when the control-circuit 5 A/3 A/1 A
time constant L/R<40 ms, at 48/110/220 V
DC, at 48/110/220 V DC
Minimum contact load 100 mA at 24 V AC/DC
Table 13. Lens sensor and optical fibre for arc protection
Description Value
Fibre-optic cable including lens 1.5 m, 3.0 m or 5.0 m
Normal service temperature range of the lens -40...+100 °C
Maximum service temperature range of the +140°C
lens, max 1 h
Minimum permissible bending radius of the 100 mm
connection fibre
Description Value
Front side IP 54
Rear side, connection terminals IP 20
Description Value
Operating temperature range -25...+55ºC (continuous)
Short-time service temperature range -40...+85ºC (<16h)1)2)
Relative humidity <93%, non-condensing
Atmospheric pressure 86...106 kPa
Altitude Up to 2000 m
Transport and storage temperature range -40...+85ºC
1) Degradation in MTBF and HMI performance outside the temperature range of -25...+55 ºC
2) For IEDs with an LC communication interface the maximum operating temperature is +70 ºC
18 ABB
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
1) For IEDs with an LC communication interface the maximum operating temperature is +70oC
ABB 19
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
• Air discharge 15 kV
• Radiated, amplitude- 10 V/m (rms), f=80...2700 MHz IEC 61000-4-3 and IEC
modulated 60255-22-3, level 3
20 ABB
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
ABB 21
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
Description Reference
EMC directive 2004/108/EC
Standard EN 50263 (2000)
EN 60255-26 (2007)
22 ABB
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
Description Reference
LV directive 2006/95/EC
Standard EN 60255-27 (2005)
EN 60255-6 (1994)
Description
Complies with RoHS directive 2002/95/EC
ABB 23
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
Protection functions
Table 24. Three-phase non-directional overcurrent protection (PHxPTOC)
Characteristic Value
Operation accuracy Depending on the frequency of the current
measured: fn ±2Hz
PHHPTOC1) and
PHLPTOC:
IFault = 2 x set Start 22 ms 24 ms 25 ms
value
Reset time < 40 ms
Reset ratio Typical 0.96
Retardation time < 30 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 4)
24 ABB
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
PHHPTOC1) 40...200000 ms 10
PHIPTOC 20...200000 ms 10
Operating curve PHLPTOC Definite or inverse time
type2) Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12,
13, 14, 15, 17, 18, 19
ABB 25
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
Characteristic Value
Operation accuracy Depending on the frequency of the current
measured: fn ±2Hz
DEFLPDEF Current:
±1.5% of the set value or ±0.002 x In
Voltage
±1.5% of the set value or ±0.002 x Un
Phase angle:
±2°
DEFHPDEF1) Current:
±1.5% of the set value or ±0.002 x In
(at currents in the range of 0.1…10 x In)
±5.0% of the set value
(at currents in the range of 10…40 x In)
Voltage:
±1.5% of the set value or ±0.002 x Un
Phase angle:
±2°
DEFHPDEF1) and
DEFLPTDEF:
IFault = 2 x set Start 61 ms 64 ms 66 ms
value
Reset time < 40 ms
Reset ratio Typical 0.96
Retardation time < 30 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 4)
26 ABB
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
DEFHPDEF1) 60...200000 ms 10
ABB 27
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
Characteristic Value
Operation accuracy Depending on the frequency of the current
measured: fn ±2Hz
EFIPTOC1):
IFault = 2 x set Start 16 ms 19 ms 23 ms
value 11 ms 12 ms 14 ms
IFault = 10 x set Start
value
EFHPTOC1) and
EFLPTOC: 22 ms 24 ms 25 ms
IFault = 2 x set Start
value
Reset time < 40 ms
Reset ratio Typical 0.96
Retardation time < 30 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 4)
28 ABB
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
EFHPTOC 1) 40...200000 ms 10
EFIPTOC1) 20...200000 ms 10
ABB 29
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
Characteristic Value
Operation accuracy Depending on the frequency of the voltage
measured: fn ±2Hz
±1.5% of the set value or ±0.002 x Un
1) For further reference please refer to the Operating characteristics table at the end of the Technical data chapter
30 ABB
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
Characteristic Value
Operation accuracy Depending on the frequency of the voltage
measured: fn ±2Hz
ABB 31
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
Characteristic Value
Operation accuracy Depending on the frequency of the voltage
measured: fn ±2Hz
±1.5% of the set value or ±0.002 x Un
32 ABB
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
Characteristic Value
Operation accuracy Depending on the frequency of the current
measured: fn ±2Hz
±1.5% of the set value or ±0.002 x In
Table 37. Negative phase-sequence overcurrent protection for motors (MNSPTOC) main
settings
ABB 33
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
Characteristic Value
Operation accuracy Depending on the frequency of the current
measured: fn ±2Hz
Characteristic Value
Operation accuracy Depending on the frequency of the current
measured: fn ±2Hz
±1.5% of the set value or ±0.002 x In
34 ABB
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
Characteristic Value
Operation accuracy Depending on the frequency of the current
measured: fn ±2Hz
ABB 35
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
Characteristic Value
Operation accuracy Depending on the frequency of the current
measured: fn ±2Hz
±1.5% of the set value or ±0.002 x In
Characteristic Value
Operation accuracy Depending on the frequency of the current
measured: fn ±2Hz
36 ABB
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
Table 47. Thermal overload protection for motors (MPTTR) main settings
Characteristic Value
Operation accuracy Depending on the frequency of the current
measured: fn ±2Hz
ABB 37
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
Characteristic Value
Operation accuracy ±3% of the set value or ±0.01 x In
38 ABB
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
Control functions
Table 52. Emergency startup (ESMGAPC) main settings
Measurement functions
Table 53. Three-phase current measurement (CMMXU)
Characteristic Value
Operation accuracy Depending on the frequency of the current
measured: fn ±2Hz
±0.5% or ±0.002 x In
(at currents in the range of 0.01...4.00 x In)
ABB 39
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
Characteristic Value
Operation accuracy Depending on the frequency of the current
measured: f/fn = ±2Hz
±0.5% or ±0.002 x In
at currents in the range of 0.01...4.00 x In
Characteristic Value
Operation accuracy Depending on the frequency of the voltage
measured: fn ±2Hz
At voltages in range 0.01…1.15 x Un
±0.5% or ±0.002 x Un
Characteristic Value
Operation accuracy Depending on the frequency of the current
measured: f/fn = ±2Hz
±0.5% or ±0.002 x Un
Characteristic Value
Operation accuracy Depending on the frequency of the voltage
measured: fn ±2Hz
At voltages in range 0.01…1.15 x Un
±1.0% or ±0.002 x Un
40 ABB
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
Characteristic Value
Operation accuracy At all three currents in range 0.10…1.20 x In
At all three voltages in range 0.50…1.15 x Un
At the frequency fn ±1Hz
Active power and energy in range |PF| > 0.71
Reactive power and energy in range |PF| <
0.71
±1.5% for power (S, P and Q)
±0.015 for power factor
±1.5% for energy
Suppression of harmonics DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,
…
Supervision functions
Table 59. Current circuit supervision (CCRDIF)
Characteristic Value
ABB 41
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
Characteristic Value
Operate time1)
• NPS function UFault = 1.1 x set Neg < 33 ms
Seq voltage Lev
UFault = 5.0 x set Neg < 18 ms
Seq voltage Lev
• Delta function ΔU = 1.1 x set < 30 ms
Voltage change rate
ΔU = 2.0 x set < 24 ms
Voltage change rate
1) Includes the delay of the signal output contact, fn = 50 Hz, fault voltage with nominal frequency injected from
random phase angle, results based on statistical distribution of 1000 measurements
Description Value
42 ABB
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
IECA070901 V2 EN
IECA070904 V2 EN
ABB 43
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
25°
160
91 10 7
12 9
103
41
15 3
IECA070903 V2 EN IECA070902 V2 EN
IECA070900 V2 EN
Figure 7. Semi-flush Figure 8. Semi-flush with a
Figure 6. Flush mounting mounting 25º tilt
44 ABB
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
The IED type and serial number label Use the ordering key information to generate
identifies the protection IED. The label is the order number when ordering complete
placed above the HMI on the upper part of IEDs.
the plug-in-unit. An order number label is
H B M CAEAG N B B 1AB N 1 X C
# DESCRIPTION
1 IED
615 series IED (including case) H
615 series IED (including case) with test switch, wired
K
and installed in a 19” equipment panel
615 series IED (including case) with test switch, wired
and installed in a mounting bracket for CombiFlex rack L
mounting (RGHT 19” 4U variant C)
2 Standard
IEC B
3 Main application
Motor protection and control M
GUID-9FB976AB-D4D5-41C4-AF30-245FD5154CFF V1 EN
The standard configuration determines the I/O hardware and available options. Choose the digits
from one of the blue standard configuration rows below to define the corect digits for # 4-8. The
example below shows standard configuration “C” with chosen options.
H B M CAEAG N B B 1AB N 1 X C
# DESCRIPTION
4-8 Standard configuration description in short:
C = Motor protection with current and voltage based protection
and measurement functions
Std. Available analog Available binary in-
conf. inputs options puts/output options
#4 # 5-6 # 7-8
AE = 4 I (I0 1/5 A) + 5 U
C or AG = 16 BI + 10 BO
AF = 4 I (I0 0.2/1 A) + 5 U
GUID-3ECCF522-316F-4426-A6B2-311154457904 V1 EN
ABB 45
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
The communication module harware determines the available communication protocols. Choose
the digits from one of the blue communication rows below to define the corect digits for digits 9-11.
Note that the communication options are not dependant on the chosen standard configuration.
H B M CAEAG N B B 1AB N 1 X C
# DESCRIPTION
9 Communication descriptions in short:
- Serial communication options digit #9
11 Ethernet communication options digit #10
Communication protocol options #11
Serial Ethernet Protocol
options options options
#9 # 10 # 11
A= A = Ethernet B = Modbus
RS-485 100BaseFX (LC) or
(incl. or C = IEC 61850
IRIG-B) B = Ethernet and Modbus
100BaseTX (RJ-45) or
D = IEC 60870-5-103
or
E = DNP3
A= N = None B = Modbus
RS-485 or
(incl. D = IEC 60870-5-103
IRIG-B) or
E = DNP3
B= B = Ethernet B = Modbus
Glass 100BaseTX (RJ-45) or
fibre C = IEC 61850
(ST) 1) 2) and Modbus
or
D = IEC 60870-5-103
or
E = DNP3
B= N = None B = Modbus
Glass or
fibre D = IEC 60870-5-103
(ST) 1) 2) or
E = DNP3
N= A = Ethernet A = IEC 61850
None 100BaseFX (LC) or
or B = Modbus
B = Ethernet or
100BaseTX (RJ-45) C = IEC 61850
and Modbus
or
E = DNP3
N= N = None A = IEC 61850
None
1)
Serial communication using glass fibre (ST) cannot be
combined with arc protection.
2)
The communication card includes an RS-485 connector and
an input for IRIG-B.
46 ABB
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
GUID-E4E2B657-C4F8-41A2-805F-B8607AFE160D V1 EN
H B M CAEAG N B B 1AB N 1 X C
# DESCRIPTION
12 Language
English 1
English and German 3
English and Spanish 5
English and Russian 6
English and Portugese (Brasilian) 8
13 Front panel
Small LCD A
Large LCD B
14 Option 1
Arc protection 1) B
None N
15 Option 2
None N
16 Power supply
48...250 V DC, 100...240 V AC 1
24...60 V DC 2
17 Vacant digit
Vacant X
18 Version
Version 2.0 C
1)
The arc protection hardware is located on the
communication module (digit 9-10). Thus a communication
module is always required to enable arc protection. Note
that arc protection cannot be combined with serial communication
using glass fibre (ST).
GUID-B88570A0-FD0E-4788-B06D-6E9EBEF844B9 V1 EN
Example code: H B M C A E A G N B B 1 A B N 1 X C
Digit (#) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Code
GUID-3E7299ED-8963-4619-BDAC-0D2F15ED4B75 V1 EN
ABB 47
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
48 ABB
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
connect and interact with the IED. The errors in system integration, minimizing
connectivity packages reduce the risk of device configuration and set-up times.
ABB 49
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
GUID-1589F909-AB4D-44A7-9445-057B7385AFD7 V1 EN
50 ABB
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
You will find the latest relevant information The Features and Application tabs contain
on the REM615 protection IED on the product related information in a compact
product page. format.
ABB 51
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
52 ABB
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
ABB 53
Motor Protection and Control 1MRS756890 B
REM615
Product version: 2.0 Issued: 01.10.2009
54 ABB
55
Contact us
www.abb.com/substationautomation