Turret Weighting Calibration Procedure
Turret Weighting Calibration Procedure
Turret Weighting Calibration Procedure
Note: If two DISOBOX PLUS scales are disturbed and DISOMAT Tersus controller showing M7501-N
(either 1 or 2) DISOBOX ERROR message. So follow below calibration procedure
Pre-conditions:
1. First ensure RS-485 connections tightness and correct connections as per diagram at DISOBOX
PLUS 1&2 and DISOMAT Tersus
2. All connections are ok , so follow below procedure
3. Information: 1. Master acts as a DISOMAT Tersus controller
2. Slave-1 acts as a DISOBOX PLUS -1 (arm-1)
3. Slave-2 acts as a DISOBOX PLUS -2 (arm-2)
4. In both DISOBOX PLUS boxes we need to put SCALE-1 only in all channel of
loadcell for both slave-1 and slave-2 and configure with different names like
DISOBOX PLUS -1 set as a SLAVE-1 and DISOBOX PLUS -2 set as a SLAVE-2.
5. When both DISOBOX PLUS boxes RS-485 communication established to
DISOMAT Tersus controller, then only the M7501-N(either 1 or 2) DISOBOX
ERROR message will disappear and SCALE-1&2 option appear in “57:SCALE”
parameter.
6. Passwords: parameter setting: 393852
Configuration : 618349
Calibration :505442
Service parameter(5) : 235711
4. Calibration procedure:
Step-1: Switch off the total power supply of DISOMAT Tersus controller and DISOBOXes.
Step-2: At first only turn power on to the DISOBOX PLUS -2 designated as SLAVE-2 and DISOMAT
Tersus controller.
Step-3: DISOMAT boots up, the event message” power fail” will be displayed in the topmost row
Step-6: Go into parameter 448: Meas input configuration Set Measurement input 1 to “off”
Step-9: Go into parameter 4471: Configuration Set count of DISOBOX PLUSES TO “2”.
Step-11: Go into parameter 4474: Address setup Serial no ……….. (Not required)
Note: now the slave-2 agained to DISOBOX PLUS-2 and the M7501-2 DISOBOX ERROR message will
disappear and the M7501-1 DISOBOX ERROR message will appear
Step-15: Go into parameter 446: SELECT SCALE Select “scale-1” and press “enter” button.
Note: So now we entered into SLAVE-1 (arm-1) and Go into parameter 441: calibration parameters
Unit: “t”
Maxi value: 70.000t
digit: 0.500 like that….
Step-15A: Go into parameter 4472: CHANNEL Select “Channel-1” and press “enter” button.
Enter scale option: “scale-1” and similarly channel-2, 3&4 also enter “scale-1” in scale option
Step-16: Go into parameter 446: SELECT SCALE Select “scale-2” and press “enter” button.
Note: So now we entered into SLAVE-2 (arm-2) and Go into parameter 441: calibration parameters
Unit: “t”
Maxi value: 70.000t
digit: 0.500 like that….
Step-16A: Go into parameter 4472: CHANNEL Select “Channel-1” and press “enter” button.
Enter scale option: “scale-1” and similarly channel-2, 3&4 also enter “scale-1” in scale option
iv) Press batten to perform quick tare. This will zero the bin weight values, if bin
weight is 2% lesser than its capacity.
i) Follow above point no – “a to f”. Now display will show you [441.CALIBRATION
PARAMETERS].Then
iii) Press batten, Display will show you [4451. DEAD WEIGHT], Then
iv) Press battens, Display will show you [DEAD WEIGHT ACTIVE] & [DEAD WEIGHT
COMPLETED] messages.
viii) Finally enter “field actual weight of the ladle” the above “EX” place and press
“enter” button.
ix) After the entered value display on controller main page display.