How A 4-20 Ma Transmitter Works
How A 4-20 Ma Transmitter Works
A sensor is an input device that provides a usable output in response to the input measurand. A
sensor is also commonly called a sensing element, primary sensor, or primary detector. The
measurand is the physical parameter to be measured. An input transducer produces an electrical
output that is representative of the input measurand. Its output is conditioned and ready for use by
the receiving electronics like PLC or DCS. The receiving electronics can be an indicator, controller,
computer, PLC, DCS etc. The term “transmitter,” as commonly used with industrial process control
instrumentation, has a more narrow definition than those of a sensor or transducer:
4-20 mA Transmitter
This is generally the basic configuration for industrial process control systems when digital
communication is not required. As shown in Below Figure, only two wires are used to accommodate
both power to the transmitter and output signal from the transmitter.
To facilitate a closed-loop control system, information from the process must be obtained before a
controller can determine what action may be required by a control element. Some popular names
for the sensing devices that provide the information are sensors, transducers, and/or transmitters.
The standard loop current is usually 4 to 20 mA. Important calibration parameters with a current loop
are Zero, full scale, and span. With the 4- to 20mA range, the loop current is normally 4 mA when
the measurand or Process Variable is at zero, and 20 mA when the measurand or Process Variable
is at full scale.
The difference between Zero and full scale, 16 mA, is called the span. Thus, the span corresponds
to the indicated range of the measurand or Process Variable. When considering a flow transmitter,
for example, the range of the measurand or Process Variable is 0.0 to 100.0 m3/hr, corresponding
to a 4- to 20-mA loop current (output span is then 16 mA); the output scaling factor is 0.16
mA/(m3/hr) (which is 100 m3/hr 16 mA).
In General PLC / DCS Analog Input card channel supplies more than 20mA current to power the
loop.
The PLC / DCS Analog Input card transmits a standard +24 V DC, 20 mA signal to Power the
Transmitter. A one pair cable is used to power the transmitter and the same cable is used to receive
the data in the 4-20mA current range.
Transmitter receives +24V DC, more than 20mA signal in the loop. A minimum +5V DC, 20mA signal
is required to proper functioning of transmitter. In Practical there will be a voltage drop in the loop.
Transmitter have an inbuilt voltage regulator function which is used to regulate the loop current. The
Transmitter will be configured with LRV, URV and other details of Process variable. The loop current
will be varied / changed by the transmitter as per the measured Process variable. The 4-20mA
current will be converted into standard 1 – 5 V DC using a precision 250 ohms resistor. The Analog
to Digital converter will be used to convert the voltage into digital signal which is used to indicate the
Process Variable value in the DCS / PLC HMI.
Example:
A Flow Transmitter with a range of 0 to 100 m3/hr. Transmitter indicates 0 m3/hr as there is no flow
in the line. DCS / PLC powers the transmitter with +24V DC, 20mA. As Process Variable is 0 m3/hr,
the transmitter regulates the loop current to 4mA and its equivalent voltage is 1 V DC which is
measured by A/D Converter which indicates 0% of Process Variable.
Note: The loop current will be same either at starting or end or any point in the loop. For easy
understanding only, both 20mA & 4 mA signals are shown in the animation.
In Practical, When we measure the current at any point in the loop, the transmitter output current
will be found i.e. 4mA as per above figure, so just assume DCS/PLC system powers the loop with
+24V DC, 20mA (generally systems supplies more than 20mA) while transmitter regulates the loop
current within 4mA to 20mA as per its configuration & real time process variable value.
If you want to measure the PLC/DCS loop power i.e. 20mA (as per above figure) signal then
disconnect the transmitter from the loop & Connect the multimeter in series with DCS/PLC to
measure the loop current. And the one pair cable is a twisted pair cable.
Same Principle applies. The Transmitter adjust the loop current as per the Process Variable. The
only difference is the transmitter sensing element changes its output as process variable varied from
0% to 50%. The transmitter regulates the loop current as per the sensing element.
Example:
Process variable indicates 50 m3/hr. Transmitter regulates output to 12mA in the loop as per the
configured range and measured process variable and its equivalent voltage is 3 V DC which is
measured by A/D Converter which indicates 50% of Process Variable.
Same Principle applies. The Transmitter adjust the loop current as per the Process Variable. The
only difference is the transmitter sensing element changes its output as process variable varied from
50% to 100%. The transmitter regulates the loop current as per the sensing element.
Example:
Process variable indicates 100 m3/hr. Transmitter regulates outputs to 20mA in the loop as per the
configured range and measured process variable and its equivalent voltage is 5 V DC which is
measured by A/D Converter which indicates 100% of Process Variable.
Process Variable
Although almost any type of transducer can be configured as a transmitter, the most common types
for industrial process control comprise measurands or Process Variables like temperature, pressure,
flow, level etc. Transmitters for measuring other parameters will have the same possibilities for
connection and communication methods, with the main differences being in the sensing element
design of transmitter and electronic equipment will be same with slightly software modification.
Since the receiving electronics connected to the transmitter is designed to ignore common-mode
signals, the resulting common-mode electrical noise is ignored. The sensitivity to loading effects is
reduced because the current in the twisted pair is not affected by the added resistance of long cable
runs. A long cable or other series resistance will cause a greater voltage drop but does not affect
the current level as long as enough voltage compliance is available in the circuit to supply the signal
current.
The circuit compliance to handle a given voltage drop from additional loop devices depends on the
transmitter output circuit and on the power supply voltage. The typical power supply for industrial
transmitters is +24 VDC. If 6 volts, for example, are needed to power the transmitter and its output
circuit, then 18 volts of compliance remain to allow for wire resistance, load resistance, voltage drops
across intrinsic safety (IS) barriers and remote displays, etc.
Where the current loop signal is connected to the main receiving equipment (PLC/DCS) or data
acquisition system, a precision load resistor of 250 ohms is normally connected. This converts the
4 to 20 mA current signal into a 1 to 5 volt signal, since it is standard practice to configure the analog-
to-digital converter of the receiving equipment (PLC/DCS) as a voltage-sensing input.
In contrast to the two-wire current-loop configuration, some current-loop devices require a three or
four wire connections. These are not loop powered and therefore have a separate means for
providing power by adding one or two more wires.
In a four-wire configuration, the current-loop wires can be a twisted pair, and the power supply wires
a separate twisted pair. This preserves the ability to reject electrical and magnetic common-mode
interference. This is not so effective in a three-wire configuration due to the common connection for
the return current path. Typically, though, when an instrumentation engineer specifies a current-loop
transmitter for industrial process control, it is assumed that a two-wire, loop-powered 4 to 20 mA
device is intended. Other data signals may also be impressed upon the same wire pair, or
alternatively, various digital communication techniques can be used instead of a current loop, if
required.