Short Current Calculation For Derba Substation
Short Current Calculation For Derba Substation
CONTRACT: CD-1
SUBMISSION OF
CALCULATION NOTE
- SHORT CIRCUIT CURRENT
2 Standards.....................................................................................................................................................3
5.2.2 Short circuit current of k2 and k3 position fault under two-parallel and one-seperate
operation..........................................................................................................................................................5
5.2.3 Short circuit current of k2, k3 and k4 position fault under three-seperate operation...... 6
1 Substation’s profile
Debra Substation mainly has three(3) voltage levels: 132kV, 33kV and 6.6kV. It contains two(2) incoming lines from
Geferssa line and Chancho line, which will be established in this project. And the maximum three-phase short current of
132kV busbar got from both Chancho and Deaba-TP is 4485.2A supplied by letter of Ref No.TSDD/1016/2021.
2 Standards
In order to determine short circuit current of 6.6kV side of our workscope, calculation procedure can be identified using
SB 100
UB.132 132kV ; IB.132 103 437.40A ;
3 UB.132 3 132
UB.132 132 10 3
Z B.132 174.24 Ω
3 IB.132 3 437.40
SB 100
U B.15 = 6.6kV ; I B.6.6 = = ×103 = 8747.73A ;
3 × U B.6.6 3 × 6.6
EMPLOYER DERBA MIDROC CEMENT & Derba - Chancho 132kV Power Expansion Project
CONTRACTOR SINOHYDRO CORPORATION LTD.
PROJECT NO. CD-1 DOCUMENT NO. DEBA--DD-EL-CC-3144 PAGE < 4 / 9> REV. 0
U B .6.6 6.6 × 10 3
Z B .6.6 = = = 0.4356 Ω
3 × IB .6.6 3 × 8747.73
For132//333/6.6kV transformer,
Impedance voltage for nominal tap position between 132 and 6.6 kV windings: U k = 12.16%
There is no enough information about the 6.6kV system, so assumption: the 6.6kV system and feeders are distribution
system, and there is no short circuit current supplied from 6.6kV system when short circuit fault occurs.
Short circuit current of existing 132KV busbar in the substation is IK .132.BUSBAR = 4485.2 A .
UB.132 132
Equivalent impedance of 132kV system in the substation Z132 = = = 16.99 Ω
3 × IK .132 3 × 4.4852
Z132 16.99
and per unit value is Z132 = = = 0.0975177 .
Z B.132 174.24
TR3
EMPLOYER DERBA MIDROC CEMENT & Derba - Chancho 132kV Power Expansion Project
CONTRACTOR SINOHYDRO CORPORATION LTD.
PROJECT NO. CD-1 DOCUMENT NO. DEBA--DD-EL-CC-3144 PAGE < 5 / 9> REV. 0
4.2 The state of two-parallel and one-seperate operation, the positive sequence figure of Debra substation is as follow:
1 3 2 kV B U S 0 .2 7 6 .6 kV B U S k3
0 .0 9 7 5 1 7 7
1 3 2 K V IN C O M IN G L IN E TR1
(E q u iva le n t S Y S T E M )
0 .2 7 k2
k1
TR2
0 .2 7
TR3
4.3 The most save state of three-seperate operation, the positive sequence figure of Debra substation is as follow:
1 3 2 kV B U S 0 .2 7 6 .6 kV B U S k3
0 .0 9 7 5 1 7 7
1 3 2 K V IN C O M IN G L IN E TR1
(E q u iva le n t S Y S T E M )
0 .2 7 k2
k1
TR2
0 .2 7 k4
TR3
When TR1,TR2 and TR3 are paralleling operation. The value of short circuit current at point k2 will be maximum, which
0.27
Z k1/k 2 = ZT.132/6.6 /3 = = 0.09 , and the per unit value of voltage is U Uc1 1.0 .
3
The three-phase short circuit current is IK 2 = I* × IB .6.6 = 5.33 × 8747.73 = 46650.15 A = 46.65 kA
5.2.2 Short circuit current of k2 and k3 position fault under two-parallel and one-seperate operation
When TR2 and TR3 are paralleling and TR1 is seperately operating. The value of short circuit current at point k2 will be
0.27
Z k1/k 2 = ZT.132/6.6 /2 = = 0.135 , and the per unit value of voltage is U Uc1 1.0 .
2
The three-phase short circuit current is IK 2 = I* × IB .6.6 = 4.3 × 8747.73 = 37621.78 A = 37.62 kA
5.2.3 Short circuit current of k2, k3 and k4 position fault under three-seperate operation
When TR1, TR2 and TR3 are seperately operating. The value of short circuit current will be same at k2, k3 and k4,
which is:
The three-phase short circuit current is IK 2 = IK 3 = IK 4 = I* × IB .6.6 = 2.72 × 8747.73 = 23793 .82 A = 23.8 kA
Three phase ground capacitance are regarded as capacitive symmetrical load when the system operate normally.
In such good condition, the neutral point electric potential is earthing potential, so EO 0 . At the same time phase
voltage is UR ER , US ES , UT E T , correspondingly ICO.R , ICO.S , ICO.T are capacitance current to the ground which
ER UR
R UR
ES US
O S I CO.S
ET UT I CO.R
T
I CO.T I CO.S I CO.R UT I CO.T US
is earthed and equal to zero. Non-fault phase R and S voltage to the ground were raised to line -to -line voltage,
EMPLOYER DERBA MIDROC CEMENT & Derba - Chancho 132kV Power Expansion Project
CONTRACTOR SINOHYDRO CORPORATION LTD.
PROJECT NO. CD-1 DOCUMENT NO. DEBA--DD-EL-CC-3144 PAGE < 7 / 9> REV. 0
So :
UR 3ER , US 3ES , UT 0
According to Kirchhoff’s Current Law, the currents of single phase ground capacitance is:
ICO.R ICO.S IC 0
UR 3ER
ICO.R ICO.S
XC XC
Then:
3ER E
IC 3ICO.R 3 3 R 3ICO
XC XC
Thus it can be seen that short circuit current to the ground is 3 times capacitance current under normal
UR
ER UR
R
IC
ES US I CO.S
O S
I CO.R
ET UT =0 US
T
I CO.S I CO.R UT
IC
I CO.R + I CO.S = - I C
earth
For DERBA Substation, earthing transformer should withstand capacitive currents of 1 outgoing line, one capacitor
bank line and one transformer cable incoming line under bus bar “C”. So:
cable length of capacitor bank is about 40m, we also take 0.1km for calculation, 6.6kV outgoing line cable is 3km
assumed and 6.6kV overhead transmission line is about 100km assumed, So:
In this project, the size of cable we selected is YJV-6/10-4x630 per phase for transformer incoming cable and for
the 6.6kV outgoing line cables and YJV-6/10-2x240 per phase for capacitor bank. According to the parameter provided
by cable manufacturer, the capacitance of YJV-6/10-1x240 is 0.429uF/km and YJV-6/10-1x630 is 0.6481uF/km. So:
C240=0.429uF/km , C630=0.6481uF/km.
6.6.2 Calculation
The short circuit current of fault point is from three capacitance current sources which are 1 outgoing line cable, 1
capacitor bank and 1 transformer incoming cable. Each capacitance current is as followed:
ER 6.6
IC.L.1 = nl × L l1 × 3 × 2 × π × f × C 630 × × 10 3 = 1× 3 × 3 × 2 × 3.14 × 50 × 4 × 0.6481× × 10 3 = 27.92 A
3 3
ER 6.6
IC.T. = nT × L T × 3 × 2πf × C 630 × × 10 3 = 1× 0.1× 3 × 2 × 3.14 × 50 × 4 × 0.6481× × 10 3 = 0.930A
3 3
ER 6.6
IC.C. = nC × L C × 3 × 2πf × C 240 × × 10 3 = 1× 0.1× 3 × 2 × 3.14 × 50 × 2 × 0.429 × × 10 3 = 0.308A
3 3
IC. = K × (IC.L.1 + IC.T. + IC.L.2 + IC.C ) = 1.3 × (27.92 + 0.930 + 0.308 + 16) = 58.71A
EMPLOYER DERBA MIDROC CEMENT & Derba - Chancho 132kV Power Expansion Project
CONTRACTOR SINOHYDRO CORPORATION LTD.
PROJECT NO. CD-1 DOCUMENT NO. DEBA--DD-EL-CC-3144 PAGE < 9 / 9> REV. 0
7 Recommendation
Compare the three-phase short circuit current of the above operation condition:
Obviously, the short cicuit current are very high above 40kA when transformer are operating in parallel, meanwhile the
rated current of 6.6kV switchgear is only 4000A, which can’t withstand 8000A under parallel operation. And based on
substation operation experience from other substation, the low voltage side of transformers are usually separately
operated.
So, we recommend that transformer to be supplied in this project is designed and followed by the existing transformer,
and the transformers are operating seperately and interlocked by the control of 6.6kV bus couplar.
At the same time, we propose that the thermal stability current of 6.6kV equipment remain 40kA/3s.