Recloser-Fuse Coordination of Radial Distribution Systems in Presence of DG: Analysis, Simulation Studies, & An Adaptive Relaying Scheme
Recloser-Fuse Coordination of Radial Distribution Systems in Presence of DG: Analysis, Simulation Studies, & An Adaptive Relaying Scheme
4.1 INTRODUCTION
Figure 4.1 shows an example of a typical radial distribution feeder with protective
devices. Their conventional protection coordination is shown in Figure 4.2.
Substation Circuit
Breaker Recloser
To main feeder
Fuse Fuse
F1
Load 1 Load 2
Figure 4.1 A typical radial distribution section with recloser and fuse
88
4.2 CURRENT STATE OF THE ART
89
Many adaptive protection schemes have been proposed to solve coordination problems
of distribution networks including DG, which can respond to changes in the network
conditions [78], [2], [95], [112]. Javadian et al. [112] proposed a scheme which divides the
distribution network into various zones with a reasonable balance of load and DG in each
zone. The scheme aims at maintaining protection coordination, while keeping most of the DG
online during a fault by allowing islanded operation of DG. However, due to the location of
DG units with respect to the loads, the fluctuating nature of power from these DG units and
uncertainty of utility loads, it might not be possible to establish zones that fulfil the required
criteria. Moreover, islanded operation of DG may not be desirable. According to the current
utility practice, islanding is not allowed.
However, none of these schemes has completely solved the problem of
miscoordination between recloser and fuse in radial distribution system containing DG.
Therefore, to achieve proper coordination between recloser and fuse in the presence of DG in
radial distribution system, a new adaptive relaying scheme has been presented.
THE PRESENCE OF DG
Figure 4.3 shows single line diagram of a portion of power distribution network of
Madhya Gujarat Urja Vikas Nigam Limited (MGVCL), Gujarat, India. Two 66 kV sub-
transmission lines (emanated from 220 kV Karamsad substation) are connected between bus
B1 and bus B2. Two power transformers (TR-1 and TR-2) are used to step-down the voltage
at 11 kV. Thirteen different distribution feeders are emanated from bus B3 for further
distribution of power. Here, the proposed scheme has been implemented on Feeder-1. Two
DGs (each of 1 MVA rating) are connected to 11 kV systems through step of transformers
(TR-3 and TR-4). The parameters of Feeder-1, synchronous generators and exciter are given
in Appendix-E. Test data for verifying the proposed adaptive schemes have been generated by
modeling the complete system of Figure 4.1 using the PSACD/EMTDC software package
[106]. The test data include different types of fault, such as L-L-L-G, L-L-L, L-L-G, L-L and
L-G. The transmission and distribution lines are represented using the Bergeron line model.
90
The other components of the power system such as synchronous generator, transformers,
loads etc. are designed according to the collected data and specifications. Some of the
components such as fuse model and recloser model are developed using PSCAD/EMTDC
software package. A sampling frequency of 4 kHz (80 samples/cycle) for a system operating
at a frequency of 50 Hz is used in this study.
Utility
220kV/66kV
B1 66kV Bus
66kV Line
B2 66kV Bus
66kV/11kV
TR-1 10MVA TR-2
11kV
B3 Bus
circuit
Feeder-1 breaker Distribution
Line
TR-3
P1+jQ 1 ……………………
Fuse 1
DG-2 …..…
Load Load
Fault 2
Recloser 0.415kV/11kV
1 MVA
P2+jQ 2
Fuse 2
DG-1
Fault 1
TR-4
Function
Input RMS Gain Block Output
91
A control circuit has been designed to represent the operation of a fuse so that it can
open and isolate the fault according to its time current characteristics. Figure 4.4 shows block
diagram of fuse control circuit.
(i) Input: The sinusoidal block is the representation of Alternating Current (AC) source
that is considered as sinusoidal supply source. For fuse AC (11 kV) source can be considered
as supply source.
(ii) RMS (Root Mean Square): The RMS block is used to measure the root mean square
value of the instantaneous current passing through the recloser.
(iii) Gain: The gain block is used to obtain peak value of the instantaneous current passing
through the recloser.
(iv) Function Block: The peak value will pass to the function block parameter which
contains the Time-Current Characteristics (TCC) of the fuse. The equation for TCC is given in
equation (4.3), the output of this block is a time corresponding to the passing current.
(v) Output: The next block is a output block, which contains relay that allows its output to
switch between two specified values (0, 1). If the current is less than a specific value (fuse
setting) the relay output will stay at zero value. On the other hand for the current value greater
than that specific value, the output of the relay will be stick with 1.
4.3.3 Recloser Model
For a reclosing device, the control circuit sends the closing signal to the switch when
the reclosing time is reached. A control circuit has been designed to represent the operation of
a recloser that automatically trips and recloses a preset number of times to clear temporary
faults and separate permanent faults. Figure 4.5 shows block diagram of recloser control
circuit.
Relay
Function
Block
92
The first three blocks and the output block work in a similar were as they work in fuse model.
The peak value will pass to two blocks; the first is a function block parameter which contains
the fast characteristic of the recloser (TCC). This fast curve is based upon the IEEE standard
inverse time characteristic equations. The equation for TCC is given in equation (4.1), the
output of this block is a time corresponding to the passing current.
These two models can entirely simulate the operation of both fuse and recloser in
simulink environment and can be used for any other system.
The circuit breaker and recloser are normally equipped with inverse-time overcurrent
trip devices. The general characteristics of such devices can be described by the following
equation (4.1).
(4.1)
Where,
t is the operating time of device, TDS is the time dial setting, MP is the multiple of pick-up
current and given by equation (4.2) and A, B, p are constants for particular characteristic.
(4.2)
Where,
If is the fault current seen by the device (on secondary side of CT), Ipickup is the recloser
current set point. Similarly, fuse also has an inverse-time overcurrent characteristic. The
general equation describing the fuse characteristic curve can be expressed as shown by
equation (4.3).
(4.3)
Where, t and I are the associated time and current, and the coefficients a & b can be obtained
from the curve fitting technique [117].
93
respectively [53]. The value of TDS is set to be 1.0 for the slow-mode recloser, while 0.5 is
considered for the fast-mode recloser. The protection settings are done when there is no DG
installation as the initial or existing condition. With regard to the CBs and reclosers, they are
assumed to be equipped with the extremely inverse characteristic of overcurrent relays. The
pickup current Ipickup for CBs and reclosers can be computed by the nominal current Inom as
shown by equation 4.4 [61].
(4.4)
Where, OLF is the overload factor that depends on the equipment being protected.
For the protection settings, this scheme uses the mathematical equations for
overcurrent relays and the straight line I2t log–log curve. This is shown in section 4.4.
With regard to the fuse, the constant ‘a’ represents the slope of the straight line on I2t
log-log graph. It is fixed at a specified value for all fuses in the system. This condition is
practically acceptable because all fuses in the system should be of the same type. The value of
constant ‘a’ is selected as ‘-1.8’. The constant b is calculated from three phase fault current on
load feeder. With a calculated fault current, fuses are set to operate slower than fast-mode of
recloser and faster than slow-mode of recloser. These two lag times are set to be of the same
value. The operating time of fuse is obtained by dividing the time range of recloser as shown
in equation (4.5) (i.e. the difference between the operating times of the slow and fast operating
modes).
(4.5)
94
Table 4.1 Different cases considered for recloser-fuse miscoordination
Case DG Source Fault location Current seen by protective device
1 DG-1 Fault 1 IR =IS & IF =IS + IDG
2 DG-1 Fault 2 IR = IDG & IF = IS + IDG
3 DG-2 Fault 1 IR = I F = IDG + IS
4 DG-2 Fault 2 IR = 0 & IF = IS + IDG
For Case-1, the fault current seen by the fuse is vector summation of fault currents
flowing from the substation and the DG. In this situation, it may possible that miscoordination
between recloser and fuse may occur. Hence, miscoordination will occur whenever DG source
and fault location are located behind the recloser [119]. To obtain the proper sequential
coordination, the fault current must comply with the minimum and maximum current as
shown in Figure 4.2. This is expected in normal circumstances, where there is no DG installed
and all protective devices see the same fault current. However, in this case, the fault current
flowing through the recloser is different than the fault current flowing through the fuse. It is
obvious that the fault current seen by the fuse is higher than the fault current seen by the
recloser. Initially in this explanation, the fault currents from loads are neglected. The fault
current seen by the recloser is only a portion from the substation, whereas the fault current
seen by the fuse is the portions from the substation and the DG. With different fault currents
seen by the two devices, the sequence of protection operation may be lost, and fuse blowing
may occur meaninglessly. This causes temporary faults to become permanent. Since the
occurrence rate of temporary faults is very high in distribution system, recloser–fuse
miscoordination is considered to be critical for the system reliability and must be taken into
account when the worth of DG is evaluated.
In Case-2, DG is located after the recloser and the fault location is before it. In this
situation, reverse current flows through the recloser. The magnitude of fault current, flows
from DG through the recloser, is normally much lower than the fault current flows from the
substation through the fuse. Therefore, the fuse would blow much faster than the recloser and
coordination is maintained.
For Case-3, the magnitude of fault current flows through the recloser and the fuse is
same. This will lead to increase in margin and hence, the coordination may lose.
95
In Case-4, DG and fault location both are in the rear of recloser and the fault current
from the substation and DG will flow only through the fuse. Therefore, coordination between
recloser and fuse remains unaffected.
First, the fault current from the substation can be predetermined and it will be the fault
current seen by recloser. Then, the time at which recloser F and fuse MM operate
simultaneously can be known. Since the current seen by fuse is the summation of the fault
currents flowing from substation and DG, the maximum fault current from DG must be lower
than the margin. From Figure 4.2, the relation of the fault current from utility substation and
the maximum or margin fault current from DG can be written as follows.
(4.6)
(4.7)
Where, IDG is the fault current from DG.
DG
Figure 4.6 shows the recloser and fuse coordinated graph regarding the implemented
feeder (Figure 4.1) for all fault currents within Ifmin (minimum short circuit in F) and Ifmax
(maximum short circuit in F1). This is called the coordination range (Margin-I) and
simulation results are shown in Table 4.2. Therefore, as long as the fault current values for
faults on lateral feeder are within coordination range, the recloser and fuse coordination is
accepted. In Figure 4.6, we see that the fast characteristic of the recloser lies below the MM
characteristics of fuse between Ifmin and Ifmax. Therefore, within coordination range the
recloser operates in less time than the time sufficient to damage the fuse.
96
Figure 4.6 Operating curves of recloser and fuse for Case-1 and Case-3
97
The three phase fault current used to set up the coordination is 1637 A ( Refer Table
4.2 ), that causes the recloser operating time of 0.2505 s and 0.1066 s for slow and fast curves,
respectively. By using equation (4.5), the operating time of fuse is 0.1785 s.
Using equation (4.3), the value of constant ‘b’ is calculated as ‘5.1429’ for Fuse 2.
Similarly the value of constant ‘b’ is chosen as ‘5.39’ for Fuse 1.
tR tF
A B C A B C A B C A B C
99
Table 4.4 Results from the conventional scheme for different type of faults with 3.5 and 5 MVA DG
L-G 2335 228 57 336 282 114 290 257 66 2603 72 78 NO 0.0145
L-L 2905 2719 210 500 658 205 449 621 196 3328 3313 65 NO 0.01125
3.5 L-L-G 3067 2747 203 514 650 239 465 608 213 3510 3319 84 NO 0.0115
L-L-L 3230 2981 2641 626 657 549 576 607 502 3777 3564 3122 NO 0.01175
L-L-L-G 3221 2979 2635 624 655 547 573 605 500 3766 3442 3113 NO 0.01174
L-G 2297 260 49 386 321 125 339 293 75 2613 72 78 NO 0.0145
L-L 2875 2652 220 580 756 222 529 717 211 3348 3332 65 NO 0.0112
5 L-L-G 3011 2677 212 596 746 261 547 702 231 3525 3343 85 NO 0.01149
L-L-L 3160 2907 2576 727 751 632 676 701 584 3802 3587 3147 NO 0.01175
L-L-L-G 3150 2899 2570 725 749 630 673 698 582 3790 3576 3138 NO 0.01175
NO: no operation of recloser
100
Table 4.5 Results from the conventional scheme for different type of faults with 1 and 2 MVA DG
tR tF
A B C A B C A B C A B C
101
Table 4.6 Results from the conventional scheme for different type of faults with 4 and 6 MVA DG
L-G 1052 414 192 702 462 301 1564 77 83 1564 77 83 0.1277 0.287
L-L 1454 1198 341 1539 1690 347 2574 2558 38 2574 2558 68 0.0966 0.1875
4 L-L-G 1427 1335 413 1572 1683 463 2688 2523 93 2688 2523 93 0.0962 0.1846
L-L-L 1552 1427 1323 1903 1838 1641 2931 2815 2479 2931 2815 2479 0.0932 0.1816
L-L-L-G 1550 1425 1322 1897 1834 1637 2924 2808 2473 2924 2803 2473 0.0932 0.1812
L-G 975 487 226 830 543 343 1620 78 83 1620 78 83 0.1252 0.2744
L-L 1331 1044 376 1944 2134 386 2838 2822 68 2838 2822 68 0.0937 0.17726
6 L-L-G 1273 1219 467 1980 2125 525 2948 2785 94 2975 2785 94 0.0929 0.17225
L-L-L 1410 1288 1228 2379 2336 2062 3231 3117 2732 3231 3117 2732 0.0879 0.17225
L-L-L-G 1408 1286 1228 2371 2330 2056 3223 3109 2725 3222 3109 2725 0.0881 0.1726
102
Table 4.7 Results from the conventional scheme for different type of faults with 0.5 and 1 MVA DG
tF tR
A B C A B C A B C A B C
103
Table 4.8 Results from the conventional scheme for different type of faults with 3 MVA DG
tF tR
A B C A B C A B C A B C
104
4.9.4 Case-1
Table 4.9 to Table 4.11 show simulation results obtained from the conventional
scheme in terms of fault currents and Time of Operation (Top) of recloser and fuse for L-G, L-
L-G, L-L, L-L-L-G and L-L-L faults with zero fault resistance. It has been observed from
Table 4.9 to Table 4.11 that the fault current seen by the fuse is vector sumn of fault currents
flow from the substation and the DG.
It is clear From Figure 4.6, I fuse margin = 3100 A.
It has been observed from Table 4.2 that the fault current from the utility substation
without DG = 1637 A.
Using equation (4.6), Imargin= 3100-1637= 1463 A.
To ensure that the recloser will operate faster than fuse MM characteristic, the fault
current from DG must be lower than Imargin.
It is clear from Figure 4.6 that the Margin-I (1171 A in Table 4.10) is sufficient for DG
having 2 MVA capacity. There is no miscoordination between recloser and fuse. This is clear
from Figure 4.7, in which recloser operates before fuse. However, the coordination between
recloser and fuse is lost if the capacity of DG exceeds 3.0 MVA (Margin–II in Figure 4.6). In
this situation, the fuse can operate prior to the intended operation time of the recloser. Thus it
can result in no actual operation of the recloser, as we can see in Fig.4.8. It is to be noted that
in Fig. 4.7 and Fig. 4.8, the fault is applied at 3.0 sec prior to the operation of recloser and
fuse.
Figure 4.7 Operating time of recloser and fuse for L-L-L fault on Feeder-1 with DG capacity
2.0 MVA
105
Figure 4.8 Operating time of recloser and fuse for L-L-L fault on Feeder-1 with DG capacity
3.0 MVA
From the above discussion, it is clear that the problem of miscoordination is highly
pronounced only during Case-1. For rest of the cases as mentioned in Table 4.1, the problem
of miscoordination is not very severe. Therefore, in order to overcome most of the drawbacks
of the conventional based scheme, a new adaptive digital relaying scheme has been developed
and discussed in the next section.
106
Table 4.9 Results from the conventional scheme for different type of faults with 0.5 and 1 MVA DG
107
Table 4.10 Results from the conventional scheme for different type of faults with 2 and 2.5 MVA DG
L-G 1165 294 142 501 325 233 1117 288 168 1482 75 83 0.236 0.3252
L-L 1598 1418 260 1011 1093 260 1555 1358 250 2239 2223 67 0.1727 0.2127
2 L-L-G 1616 1499 302 1038 1088 340 1570 1451 305 2357 2188 90 0.1642 0.2063
L-L-L 1730 1615 1449 1262 1171 1056 1681 1564 1401 2550 2428 2154 0.1445 0.2022
L-L-L-G 1728 1613 1448 1258 1169 1054 1679 1562 1400 2545 2423 2150 0.1444 0.2028
L-G 1131 335 162 572 372 260 1083 332 192 1511 75 83 0.2787 0.3264
L-L 1561 1355 289 1192 1291 294 1519 1312 282 2351 2335 67 0.1921 0.2092
2.5 L-L-G 1566 1451 343 1223 1285 386 160 1403 349 2472 2295 91 0.1855 0.202
L-L-L 1679 1560 1408 1484 1392 1253 1630 1510 1361 2680 2556 2262 0.1577 0.2007
L-L-L-G 1676 1558 1407 1480 1389 1250 1628 1508 1360 2674 2551 2258 0.1577 0.1982
108
Table 4.11 Results from the conventional scheme for different type of faults with 3 and 4 MVA DG
tR tF
A B C A B C A B C A B C
L-G 1100 371 179 632 412 282 1053 370 212 153 76 83 0.307 0.3272
L-L 1525 1298 314 1355 1468 320 1085 1254 308 2455 2438 67 NO 0.2025
3 L-L-G 1518 1407 377 1389 1461 424 1472 1359 384 2578 2395 92 NO 0.1937
L-L-L 1631 1510 1373 1682 1591 1429 1583 1460 1325 2799 2675 2362 NO 0.1977
L-L-L-G 1629 1508 1371 1677 1587 1426 1581 1458 1324 2792 2669 2357 NO 0.1977
L-G 1049 427 205 728 475 316 1001 429 242 1579 77 83 0.368 0.3277
L-L 1458 1199 349 1636 1775 359 1419 1153 344 2639 2622 68 NO 0.144
4 L-L-G 1429 1332 427 1673 1767 480 1384 1283 437 2763 2574 93 0.266 0.135
L-L-L 1545 1422 1311 2019 1937 1730 1497 1372 1265 3009 2886 2538 NO 0.188
L-L-L-G 1543 1420 1310 2013 1932 1726 1495 1370 1264 3002 2879 2533 NO 0.1884
NO: no operation of recloser
109
4.10 A NEW ADAPTIVE DIGITAL RELAYING SCHEME
IR/IF
<1.0
No
Yes
TDS=TDS × (IR/IF)
Calculate recloser time using equation (1)
110
4.10.2 Selection of IF/IR Ratio
In order to select the ratio of IR/IF as the index, we have carried out various simulations
on the sample system, as shown in Figure 4.3, with and without DG. Table 4.12 shows the
simulation results for two types of faults (L-L-L and L-G) having two different locations
(fault at fuse end and far end). It is to be noted from Table 4.12 that the ratio of IR/IF remains
constant for a given type of fault irrespective of the location of fault on the feeder [115].
Table 4.12 Simulation results obtained for different types of fault in different locations with
and without DG
The above fact is well understood from Figure 4.10, which shows the distribution of
fault current in the presence of DG. By neglecting the load current with respect to the fault
current, the current through the fuse (IF) depends on the impedance of the DG (ZDG) and
impedance towards the source (Zs). Since, for a given location of DG, these impedances are
fixed, the IR/IF ratio would obviously be constant. However, this value would be different of
course for a three-phase fault and a phase to ground fault. This property was exploited to
coordinate a fuse and a recloser in a distribution system with significant penetration of DG.
Hence, we have selected IR/IF ratio in the proposed schemes [115].
ZS Zsection
Utility IR
ZDG
IDG
IF
DG Load
111
4.11 SIMULATION RESULTS
The section 4.11.1 to section 4.11.5 describes the simulation results using the proposed
adaptive relaying scheme for protection of radial distribution systems in the presence of DG.
4.11.1 Comparison between the Proposed Scheme and the Conventional Scheme for
Different Types of Fault
Table 4.13 and Table 4.14 show the simulation results in terms of recloser/fuse
current ratio and their time of operation for different types of fault using the conventional
scheme and the proposed scheme, respectively. It has been observed from Table 4.13 that the
coordination between recloser and fuse is lost. This is true for all types of fault except single
line to ground fault (shown bold-italic in Table 4.13). In contrast, the coordination between
recloser and fuse is maintained for all types of fault (Table 4.14). It is clear from Table 4.14
that as the ratio of recloser current to fuse current decreases, the TDS of recloser fast
characteristic also decreases (which remains constant in the conventional scheme as observed
from Table 4.13). Therefore, the margin between recloser and fuse increases as the recloser
fast characteristic (with lower value of TDS) is shifted down with reference to previous
recloser fast characteristic.
Table 4.13 Results of the conventional scheme for different types of fault with 3.0 MVA DG
112
Table 4.14 Results of the proposed scheme for different types of fault with 3.0 MVA DG
Fault Ratio Time Dial Setting Time of
Type IR/IF (TDS) Operation (s)
tR tF
A B C A B C
L-G 0.67 5 2.36 0.3397 0.5 0.5 0.206 0.32725
L-L 0.6 0.5 3.36 0.3021 0.2556 0.5 0.1147 0.2025
L-L-G 0.57 0.57 3.5 0.2859 0.2859 0.5 0.1135 0.1937
L-L-L 0.56 0.55 0.59 0.2841 0.2788 0.2992 0.0945 0.19774
L-L-L-G 0.56 0.55 0.59 0.2842 0.2791 0.2994 0.0945 0.19775
tR and tF is the time of operation of recloser and fuse, respectively.
Similarly, Table 4.15 and Table 4.16 shows the simulation results obtained from the
conventional scheme and the proposed scheme, respectively, for 5 MVA DG capacity. It is
impossible to obtain coordination between recloser and fuse using the conventional scheme
as the recloser is not in a position to operate for all types of fault. This is clear by observing
NO (no operation of recloser) from Table 4.15. Hence, the prime objective of fuse saving is
violated, particularly, for temporary faults in the distribution system. On the other hand,
proper coordination between recloser and fuse is achieved by the proposed scheme for all
types of fault (Table 4.16) as the recloser (in fast mode) always operates prior to the fuse.
Table 4.15 Results from the conventional scheme for different type of faults with 5 MVA DG
Fault Ratio Time Dial Setting Time of Operation (s)
Type IR/IF (TDS)
tR tF
A B C A B C
L-G 0.58 6.5 3.19 NO 0.322
113
Table 4.16 Results from the proposed scheme for different type of faults with 5 MVA DG
Fault Ratio Time Dial Setting Time of
Type IR/IF (TDS) Operation (s)
tR tF
A B C A B C
L-G 0.58 6.5 3.19 0.293 0.5 0.5 0.2155 0.322
L-L 0.44 0.45 4.3 0.2213 0.2258 0.5 0.094 0.1592
L-L-G 0.48 0.377 4.15 0.2408 0.1888 0.5 0.093 0.163
L-L-L 0.43 0.43 0.47 0.2193 0.2198 0.2392 0.0755 0.1747
L-L-L-G 0.43 0.44 0.47 0.2195 0.2201 0.2394 0.0757 0.1752
tR and tF is the time of operation of recloser and fuse, respectively.
It is to be noted from Table 4.17 that, the TDS of recloser fast characteristic decreases
as the capacity of DG increases. Therefore, the margin between recloser and fuse increases
as the recloser fast characteristic (with lower value of TDS) is shifted down with reference to
114
previous recloser fast characteristic. Hence, the coordination between recloser and fuse is
maintained for all types of fault even with enhancement in DG capacities. The proposed
adaptive scheme is capable to maintain proper coordination between recloser and fuse for
very high capacity of DG (8 MVA) during which conventional scheme fails.
In order to validate the performance of the proposed scheme during various scenarios
of the distribution system with low capacities of DG, we have carried out various simulations.
The simulations results are shown in Table 4.18. It has been observed from Table 4.18 that
the proper coordination is maintained between fuse and recloser even though the fault current
through DG is much smaller than utility. Therefore, even though the fault current provided by
DG (IDG) is much smaller than provided by the system (the situation of a strong system), the
index IR/IF changes significantly. This effectively shifts down the curve which in turn
enhances coordination margin between fuse and recloser.
Table 4.18 Simulation results given by the proposed scheme during low capacities of DG
DG Fault IR IDG Ratio Time Dial Setting Time of
Capacity Type (A) (A) IR/IF (TDS) Operation (s)
(MVA) A B C tR tF
0.15 L-G 1316 59 0.9748 0.4874 0.5 0.5 0.1270 0.4317
L-L-L 1959 124 0.9678 0.4839 0.4816 0.484 0.084 0.2104
L-G 1304 95 0.9588 0.4793 0.5 0.5 0.1274 0.424
0.25
L-L-L 1945 203 0.9473 0.4736 0.47 0.4738 0.0842 0.2102
L-G 1274 176 0.92 0.46 0.5 0.5 0.1267 0.4215
0.5
L-L-L 1908 389 0.89 0.4488 0.4429 0.45 0.0847 0.2022
L-G 1220 309 0.85 0.4268 0.5 0.5 0.1277 0.3337
1.0
L-L-L 1838 722 0.8 0.4045 0.3963 0.4086 0.08525 0.2012
tR and tF is the time of operation of recloser and fuse, respectively.
115
Table 4.19 shows the simulation results obtained from the proposed scheme for line to
ground (L-G) faults having two different DG capacitates (2.5 and 5 MVA) with varying fault
resistances. Though the time of operation of recloser as well as fuse increases as the value of
fault resistance increases, the proposed scheme is capable to maintain proper coordination
between recloser and fuse
Table 4.19 Simulation results of the proposed scheme for high resistance single line to
ground (L-G) fault at different DG capacitates
DG Fault Ratio Time Dial Setting Time of
Capacity Resistance IR/IF (TDS) Operation (s)
(MVA) RF (ohm)
tR tF
A B C A B C
5.0 0.755 3.15 1.16 0.377 0.5 0.5 0.539 0.938
10 0.788 2.11 1.141 0.394 0.5 0.5 1.092 1.947
2.5 20 0.842 2.18 1.278 0.421 0.5 0.5 2.931 4.690
30 0.89 2.0 1.36 0.444 0.5 0.5 5.601 7.964
40 0.932 1.90 1.409 0.466 0.5 0.5 10.42 11.45
5.0 0.653 4.31 1.539 0.326 0.5 0.5 0.648 0.887
5.0 10 0.708 3.54 1.396 0.354 0.5 0.5 1.431 1.876
20 0.802 2.94 1.6 0.401 0.5 0.5 4.455 4.632
t R and tF is the time of operation of recloser and fuse, respectively
116
Figure 4.11 Coordination time interval for close-in L-L-L fault at different lengths of the
feeder
4.14 CONCLUSION
This chapter deals with the study of miscoordination between fuse and recloser during
DG interconnections.
In order to overcome the drawbacks of the conventional schemes, a new adaptive
relaying scheme for proper coordination between recloser and fuse has been presented. The
proposed scheme is based on derivation of the ratio of recloser current (IR) and fuse current
(IF). By using this ratio and without changing fuse characteristic, the recloser fast
characteristic is shifted down from its original characteristic which in turn enhances
coordination margin between recloser and fuse. This is achieved by modifying the time dial
setting of the recloser fast characteristic. The proposed scheme has been tested extensively by
simulating various types of faults on distribution system in the presence of DG. Fault data are
generated using PSCAD/EMTDC software package by modeling an existing 11 kV Indian
power distribution network. The proposed scheme is capable to maintain proper coordination
between recloser and fuse irrespective of types of fault. Moreover, it enhances margin
between recloser and fuse during higher capacity of DG (3.0 MVA to 8 MVA) by shifting
down recloser fast characteristic with reference to previous recloser fast characteristic.
Furthermore, the proposed scheme also preserves correct coordination between recloser and
fuse during high resistance single line to ground faults.
117