IMPORTANT DEFINITIONS
• A WARNING indicates a potentially hazardous situation which, if not avoided, could result in
death or serious injury.
• A CAUTION indicates a potentially hazardous situation which, if not avoided, could result in
damage to equipment or property.
• A NOTE provides other helpful information that does not fall under the warning or caution
categories.
Woodward Governor Company reserves the right to update any portion of this publication at any time.
Information provided by Woodward Governor Company is believed to be correct and reliable. However, no
responsibility is assumed by Woodward Governor Company unless otherwise expressly undertaken.
© Woodward 2003
All Rights Reserved
Manual 26237 L-Series Position Controller
Contents
REGULATORY COMPLIANCE ........................................................................III
ELECTROSTATIC DISCHARGE AWARENESS ................................................. IV
CHAPTER 1. GENERAL INFORMATION ........................................................... 1
Purpose and Scope ................................................................................................1
How to Use This Manual ........................................................................................1
Intended Applications .............................................................................................1
Introduction .............................................................................................................1
Programmable Features .........................................................................................2
Service Tool Software ............................................................................................3
CHAPTER 2. SYSTEM DESCRIPTION/APPLICATION OVERVIEW ....................... 4
System Operation ...................................................................................................4
Communications .....................................................................................................8
Temperature Sensing .............................................................................................9
Current Limiting based on Temperature.................................................................9
Faults ......................................................................................................................9
CHAPTER 3. INSTALLATION........................................................................ 13
Introduction ...........................................................................................................13
General Installation, Operation Notes and Requirements....................................13
Unpacking .............................................................................................................14
Mechanical Installation .........................................................................................14
Electrical Installation .............................................................................................19
Description of Electrical I/O ..................................................................................21
CHAPTER 4. SERVICE TOOL....................................................................... 27
Introduction ...........................................................................................................27
Description ............................................................................................................27
Getting Started .....................................................................................................29
L-Series Configuration ..........................................................................................30
Configuration Parameters.....................................................................................31
Position Calibration and Verification.....................................................................42
Calibration Sequence Overview ...........................................................................43
Position Verification ..............................................................................................43
CHAPTER 5. TROUBLESHOOTING ............................................................... 47
Introduction ...........................................................................................................47
General System Troubleshooting Guide ..............................................................47
Engine/Generator Troubleshooting ......................................................................48
Electrical Troubleshooting Guide .........................................................................50
CHAPTER 6. SERVICE OPTIONS ................................................................. 51
Product Service Options .......................................................................................51
Returning Equipment for Repair ...........................................................................52
Replacement Parts ...............................................................................................53
How to Contact Woodward ...................................................................................53
Engineering Services............................................................................................54
Technical Assistance ............................................................................................55
APPENDIX A. ACRONYMS/ABBREVIATIONS ................................................ 56
APPENDIX B. L-SERIES CONFIGURATION SUMMARY ................................... 57
APPENDIX C. L-SERIES CONTROL SPECIFICATIONS ................................... 58
DECLARATIONS ......................................................................................... 62
Woodward i
L-Series Position Controller Manual 26237
ii Woodward
Manual 26237 L-Series Position Controller
Regulatory Compliance
The L-Series is suitable for use in Class I, Division 2, Groups A, B, C, D per CSA
for Canada and U.S. or non-hazardous locations only.
These listings are limited only to those units bearing the CSA agency
identification.
WARNING—EXPLOSION HAZARD
Do not connect or disconnect while circuit is live unless area is known to be
non-hazardous.
AVERTISSEMENT—RISQUE D’EXPLOSION
Ne pas raccorder ni débrancher tant que l’installation est sous tension, sauf
en cas l’ambiance est décidément non dangereuse.
Woodward iii
L-Series Position Controller Manual 26237
2. Avoid the build-up of static electricity on your body by not wearing clothing
made of synthetic materials. Wear cotton or cotton-blend materials as much
as possible because these do not store static electric charges as much as
synthetics.
4. Do not remove the printed circuit board (PCB) from the control cabinet
unless absolutely necessary. If you must remove the PCB from the control
cabinet, follow these precautions:
• When replacing a PCB, keep the new PCB in the plastic antistatic
protective bag it comes in until you are ready to install it. Immediately
after removing the old PCB from the control cabinet, place it in the
antistatic protective bag.
CAUTION—ELECTROSTATIC DISCHARGE
To prevent damage to electronic components caused by improper handling,
read and observe the precautions in Woodward manual 82715, Guide for
Handling and Protection of Electronic Controls, Printed Circuit Boards, and
Modules.
iv Woodward
Manual 26237 L-Series Position Controller
Chapter 1.
General Information
Intended Applications
The L-Series control is designed for various industrial applications, including but
not limited to generator sets, welders, portable refrigeration units, irrigation
pumps, chipper shredders, and mobile industrial gas or gasoline reciprocating
engines. Key environmental characteristics of these applications include
extended industrial operating temperatures (–40 to +105 °C/–40 to +221 °F),
Industrial EMC Requirements, electrical transients, and lower operating voltages
(12/24 V).
Introduction
The L-Series provides a building block approach to total engine management.
The modular bi-directional actuator design easily attaches to fuel pumps, mixers,
or throttle bodies. For information on Woodward throttle body applications, refer
to manual 26249 (ITB and LC-50).
Woodward also offers L-Series actuator versions for Speed Control and Process
Control, like Air/Fuel Ratio control, applications. Refer to manuals 26250 (Speed
Control) and 26251 (Process Control).
The L-Series position control accepts a position command and drives the 0–60
degree output shaft to the commanded position based on an internal shaft
position sensor. The high-efficiency torque motor delivers 0.34 Nxm (0.25 lb-ft)
nominally over 60° travel range to operate fuel or air control devices. See the
specifications (Appendix C) for more details.
Woodward 1
L-Series Position Controller Manual 26237
The L-Series position control accepts either a PWM command or a 0–5 V
command for output positioning. The command signals are issued by the
appropriate supervisory engine management system, and the L-Series must be
set up properly in software to expect the correct signal for the application.
For status purposes, a relay driver output is available on the L-Series control
which changes state whenever a fault or error condition is experienced by the
L-Series controller.
If the system so requires, the L-Series provides a direct position output signal in
the form of a dc voltage. The throttle position (TPS) output represents full
counterclockwise (ccw) to clockwise (cw) rotation of the actuator shaft, and thus
gives the operator an external position indication after installation and while the
unit is operating.
More detail on the features of the L-Series can be found later in this manual.
WARNING—EMERGENCY STOP
When included with an ITB, the actuator depends solely on the return spring
inside the throttle body assembly to drive toward minimum fuel when not
powered, therefore other positive shutdown devices like fuel shut-off
solenoids are recommended to ensure shutdown upon loss of signal to the
control system. Also, separate overspeed trip devices are always
mandatory.
Programmable Features
Control setup and tuning is accomplished through the use of a PC (personal
computer), Woodward Service Tool software, and a programming harness. The
features identified below are described in Chapters 2 and 4. Briefly, the
programmable features include:
• 4 General Setup Parameters
o Position Demand Select (PWM or Analog)
o Fail Direction (ccw or cw)
o Min Position Direction (ccw or cw)
o Actuator Curve Selection (Linear or Non-linear)
• PWM Setup Parameters
o PWM Drive Select (Push-Pull, High-Side Drive or Low-Side Drive)
o PWM Offset
• 4 Valve Position Control Parameters
o Proportional Gain
o Integral Gain
o Derivative Gain
o Friction/Dither Setting
• 10 Non-Linear Actuator Settings
o Position Request (5 curve input points)
o Actuator Position (5 curve output points)
• 12 Discrete Output Settings
o Output’s Non-Fault Condition (ON or OFF)
o 11 Selections as Discrete Output Indications
• 10 Fault Settings
o Latching or Non-Latching Fault Indications
o Position Error Magnitude
o Position Error Delay
o 7 Fault Selections as Alarms or Shutdowns
2 Woodward
Manual 26237 L-Series Position Controller
Woodward 3
L-Series Position Controller Manual 26237
Chapter 2.
System Description/Application Overview
System Operation
The L-Series actuator is ready for operation immediately (within 0.25 second)
when the power supply is connected. Power may be connected to the control at
the same time the engine starter motor is engaged. Upon power-up, the actuator
will immediately go to the commanded position. The actuator will then drive to
maintain the position commanded by the supervisory control.
Position Demand
(Analog/PWM)
Power Input
(10-32Vdc)
RS-232
Service Tool
The supply voltage failure levels are below 6.25 V and above 33 V. The unit can
be configured to either alarm or shutdown upon detection of a supply voltage
fault.
4 Woodward
Manual 26237 L-Series Position Controller
+V
Discrete
Status F (any fault)
Out Logic
(discrete output driver)
24Vdc = ON (status ok)
Relay Discrete
Out
Run Enable
(optional)
The PWM will function with various types of input sources, including high-side,
low-side open collector, and push-pull—depending on the configuration. It will
handle a PWM frequency range from 300 to 1500 Hz at amplitudes ranging from
5 V up to battery voltage. Normal operating range is from 10% to 90% duty cycle,
representing the hard stops in the actuator (Figure 2-1). The input can be
optionally set to a non-linear mode which provides a 5-point curve relationship
between position signal and desired position (Figure 2-2).
The input failure levels are below 3% and above 97% duty cycle. The unit can be
configured to either alarm or shut down on detection of a position command
failure. The shutdown failsafe direction is also user configurable as either
clockwise or counterclockwise.
Woodward 5
L-Series Position Controller Manual 26237
90 failsafe direction
80
70
60
50
40
30
20 user-defined points
10
0
0 10 20 30 40 50 60 70 80 90 100
PWM Position Signal Duty Cycle, %
The 0–5 V input uses a different pin in the connector, and it has a usable range
of 0.5 to 4.5 V to command the throttle from minimum to maximum position
(Figure 2-3). The input can be optionally set to a non-linear mode which provides
a 5-point curve relationship between position signal and desired position (Figure
2-4).
The input failure levels are below 0.2 and above 4.8 V. The unit can be
configured to either alarm or shut down on detection of a position command
failure. The shutdown failsafe direction is also user-configurable as either
clockwise or counterclockwise direction.
6 Woodward
Manual 26237 L-Series Position Controller
90 failsafe direction
80
70
60
50
40
30
20 user-defined points
10
0
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5
Position Signal Voltage
Discrete Output
A discrete output is provided to serve as a status indicator. This switchable
discrete output is a closure to ground capable of sinking 250 mA with an output
voltage rise of less than 1.5 V, and it is available to power external relays for
devices such as alarms or fuel shutoff solenoids. The circuit is protected
internally against overcurrent and inductive spikes, so external clamping is not
necessary.
Woodward 7
L-Series Position Controller Manual 26237
There are two conditions that will prevent the discrete output from operating
correctly. The first is if battery positive is accidentally connected to it, and the
second is if it is shorted to ground. The circuit will protect itself in the event of a
mis-wire, but it will hold the output open(floating) until the fault is removed.
Additional Inputs/Outputs
Auxiliary Inputs—There are four auxiliary inputs on the L-Series controller, all of
which are capable of both analog and discrete functions. They can all be
functionally defined for purpose in the software application. Although they are
very flexible, two of them are shared with the serial communications, so will be
unavailable if the L-Series is connected to the Service Tool. More detail
concerning the auxiliary inputs is provided in Chapter 3 (Installation).
5V Output—A 5 Vdc output has been provided on the L-Series actuator to power
external sensors, if necessary. The 5 V output is limited to 10 mA, but this is
sufficient for most light-duty ratiometric sensors.
Communications
RS-232 communications are available on the L-Series when used with an
external transceiver connected to pins 4 and 6. Serial communications allow for
the use of a service and configuration tool with the L-Series actuator. The
simplest way to establish this interface is to use Woodward kit # 8923-1061.
Functions available through this port include tuning, monitoring, and configuration
of the position controller. Detailed driver status information is also available.
Any RS-232 wiring must meet the requirements in the EIA RS-232 Standard
document. The RS-232 standard states that the length of the RS-232 cable
between the driver and the PC must be less than 50 ft (15 m) with a total
capacitance less than 2500 pF. The RS-232 data rate is fixed at 19.2 kbps. The
communication port is non-isolated and susceptible to both EMI noise and
ground loops related to PC connections and typical industrial environments.
8 Woodward
Manual 26237 L-Series Position Controller
NOTE
The service port is not isolated and is not intended to function while the
prime mover is in normal operation. The service port is provided for
configuration and setup only.
Temperature Sensing
The L-Series has an on-board temperature sensor to monitor board temperatures
and protect the unit from overtemperature. This temperature is monitored and a
fault is annunciated if the set point is exceeded.
Current limiting based on temperature begins when the combined current and
temperature environment causes board temperatures greater than 117 °C. The
limit curve is a linear derate from full current at 117 °C down to zero current at
125 °C. At 125 °C, an OverTemp fault is annunciated. Depending on the current
(actuator torque) and ambient operating temperatures, the unit may never reach
a reduced level.
Faults
Faults are separated into two categories: Logged Faults and Current Faults. The
Current Faults are volatile and reset every time power is applied. The Current
Faults annunciates faults that are presently active/detected; they may latch or not
latch depending on the fault. All latching Current Faults are reset by a power
cycle or Service Tool reset. All logged faults are latched and written to the
EEPROM. They must be cleared through the Service Tool.
A fault can have three effects on the control: change the discrete output state
(Alarm), Shutdown–drive to fail direction and change the discrete output state
(Alarm), or Shutdown–go limp and change the discrete output state (Alarm). A
parameter is available to configure the fault to either an alarm or a shutdown.
The shutdown action performed (go limp or drive to fail direction) is fault-
dependent. Some faults are dedicated shutdowns and cannot be configured—
they are identified as such below. A "go limp" command overrides a "drive to fail
position" if more than one fault is set.
Watchdog Reset
Watchdog Reset is true if a watchdog timer timeout occurred which resulted in a
reset of the microprocessor. This is a hard-coded alarm. If detected, the control
will attempt to continue normal operation.
Woodward 9
L-Series Position Controller Manual 26237
Brownout Reset
Brownout Reset is true if CPU Voltage drops below 4.2 V but not below 1 V. The
brownout detect circuit will reset the CPU. This is a hard-coded alarm. If
detected, the control will attempt to continue normal operation.
EEPROM Fail
EEPROM Fail indicates failure or corruption of the internal non-volatile memory.
If the CRC is not correct for the EEPROM data, this fault will be set true. This is a
hard-coded internal shutdown. If detected, the control output will go limp. A
power cycle is required to clear this fault.
OverTemp
If the on-board temperature sensor reads above 125 °C, this error will be set.
Above 125 °C, the processor can fail in an unpredictable manner, so this fault is
recommended as a shutdown. The Current Limiting based on temperature will
effectively make the output "limp" by reducing the drive current to zero.
10 Woodward
Manual 26237 L-Series Position Controller
Can be configured as an alarm or shutdown. If configured as a shutdown, the
control will go limp if this fault is detected. If configured as an alarm, the control
will attempt to continue normal operation if this fault is detected.
Position Error
Position Error detection logic will indicate a difference between commanded
position and actual position exceeded for longer than the set delay. The error
magnitude and duration are customer-configurable parameters.
Woodward 11
L-Series Position Controller Manual 26237
12 Woodward
Manual 26237 L-Series Position Controller
Chapter 3.
Installation
Introduction
This chapter provides instructions on how to mount and connect the L-Series
controller into a system. Hardware dimensions are provided for mounting the
device to a specific application.
WARNING—NOISE
Due to typical noise levels in turbine or engine environments, hearing
protection should be worn when working on or around the L-Series.
WARNING—BURN HAZARD
The surface of this product can become hot enough or cold enough to be a
hazard. Use protective gear for product handling in these circumstances.
Temperature ratings are included in the specification section of this manual.
WARNING—EXPLOSION HAZARD
Do not connect or disconnect while circuit is live unless area is known to be
non-hazardous.
CAUTION—FIRE PROTECTION
Explosion Hazard—External fire protection is not provided in the scope of
this product. It is the responsibility of the user to satisfy any applicable
requirements for their system.
CAUTION—WIRING
Due to the hazardous location listings associated with this product, proper
wire type and wiring practices are critical to operation.
Woodward 13
L-Series Position Controller Manual 26237
Unpacking
Be careful when unpacking the actuator. Check the unit for signs of damage,
such as bent or dented panels, scratches, and loose or broken parts. Notify the
shipper and Woodward if damage is found.
Mechanical Installation
Mounting Location
Locate the L-Series control a distance from sources of extreme radiant heat,
such as exhaust manifolds or turbochargers. The operating temperature range of
the control is –40 to +105 °C (–40 to +221 °F). In spark-ignited applications,
make sure the L-Series is located away from the ignition coil, and that harness
wires are not routed next to the spark plug wires.
Mounting Orientation
While it is not a requirement, it is good practice to orient the connector feature on
the control in a horizontal or downward orientation to minimize fluid accumulation
between the enclosure and the mating connector’s gasket.
Actuator Configuration
The L-Series actuator utilizes a 2” (51 mm) square mounting bolt pattern and is
intended to fit within an envelope of 2.618 x 2.618 x 2.540 (66.50 x 66.50 x 64.52
mm) with the short dimension along the shaft axis. Two shaft seal configurations
are available, an internal lip seal and an external lip seal with spring backup
(Figure 3-2). In addition, six independent output shaft configurations are available
(Figure 3-3). Consult Woodward Applications Engineering for the application
appropriate seal and shaft configuration.
Mounting Hardware
Use #10 or M5 fasteners to attach the L-Series control to the mounting bracket.
The bracket and attaching hardware must be designed to hold the weight and to
withstand the vibration associated with prime mover mounting. Use the
appropriate fasteners for securing the mounting bracket to the engine.
14 Woodward
Manual 26237 L-Series Position Controller
Woodward 15
L-Series Position Controller Manual 26237
16 Woodward
Manual 26237 L-Series Position Controller
Woodward 17
L-Series Position Controller Manual 26237
18 Woodward
Manual 26237 L-Series Position Controller
Electrical Installation
A wiring pinout of the L-Series control, as viewed by looking into the control’s
connector feature, is shown in Figure 3-4. Typical connections to external
devices are also shown.
Woodward 19
L-Series Position Controller Manual 26237
The L-Series has an operating voltage range of 8 to 32 Vdc with nominal
voltages of 12 or 24 Vdc. The power supply is reverse polarity protected, and
consumes 32 W maximum power at a peak current of 1 A (32 V) assuming 4 Ω
stator resistance at 25 °C. These assumptions are based on the fact that the
software limits the power to the rotary actuator to 25 W at any given time and
input voltage (in the valid range). The control system should be protected with a
6 A slow-blow fuse in the voltage supply lines. Typical max average current is 2.1
A, or max 25 W at 12 V. The application should be configured to turn on power to
the actuator when the engine is first cranked.
Electrical Connections
WARNING—EXPLOSION HAZARD
Do not connect or disconnect while circuit is live unless area is known to be
non-hazardous.
Prior to installation, refer to the wiring diagrams and the representative I/O
interfaces schematic in this chapter. Also, review the hardware I/O specifications
in Appendix C.
WARNING—INGRESS PROTECTION
The control will only meet ingress protection specifications while the
Deutsch connector is installed in the unit. As such, the unit should not be
exposed to operating environments unless the mating connector is installed.
In addition, if a wire is not used for each of the 12 pins on the control, a
Deutsch 114017 plug must be used in place of each missing wire. Failure to
adhere to these guidelines may result in product failure or decreased life.
Use 16 to 18 AWG (1 to 1.5 mm²) stranded copper wire with insulation that
meets temperature requirements in the harness design. A wiring harness stress
relief within 16” (406 mm) of the control’s connector is recommended. Limit all I/O
and signal lines to less than 30 m (98 ft). Also limit input power (B+/B–)
connections to an earth grounded battery or conditioned power interface to less
than 10 m (33 ft) from the L-Series product.
NOTE
A conditioned power interface is an interface which offers equivalent
common mode and differential mode conditioning of that of a grounded 24 V
lead acid battery.
Dress the harness with wire loom to contain it in a single bundle. Use grommets
when passing the harness through metal panels.
Connector
The following Deutsch connector components are recommended for harness
designs:
Recommended Optional
Mating Connector DT06-12SA-P012 DT06-12SA
Secondary Lock W12S-P012 N/A
Sockets 0462-201-16141 0462-201-16141
20 Woodward
Manual 26237 L-Series Position Controller
Woodward part number 8928-396 is a kit that provides all the necessary Deutsch
components.
Connector
Pin # Description Comment
1 +12V/24 Vdc Input Power Supply power
2 TPS Signal Output Direct position feedback output indication
3 PWM – / AUX – Ground for the PWM or AUX command signal common
4 RS-232 transmit For use with the service tool
5 Input Power Ground Ground for the 12 V/24 V input power
6 RS-232 receive For use with the service tool
7 5 V Out Power for external sensors (10 mA max)
8 Aux Input 1 Optional Run Enable discrete input
9 Relay Driver Output Status signal and fault detection output
10 Aux Input 2 0–5 V command signal input
11 PWM + PWM command signal input
12 Ignition Input Not used—Leave open
Power Supply Input (+12 Vdc/24 Vdc at pin 1, ground at pin 5)—The L-Series is
configured for 12 or 24 V nominal operation, although it will handle 8–32 V. The
power supply terminals are reverse polarity protected, and in the case that a
reverse polarity condition exists, the L-Series actuator will not power-up and will
remain at the minimum stop if attached to a throttle body with an internal return
spring.
Woodward 21
L-Series Position Controller Manual 26237
Woodward recommends using a 6 A slow-blow fuse on the power supply line
feeding pin 1 of the L-Series actuator.
PWM Command Input (+PWM at pin 11, PWM ground at pin 3)—This actuator
can be configured to handle a PWM signal from a high-side or low-side open-
collector or open-drain source, as well as from a push-pull (customer pull-up)
source. The necessary pull-up and pull-down voltages to accommodate the
open-collector sources are handled within the L-Series actuator. Nominally, the
frequency of PWM is 1 kHz, but it will handle the full range of 300 to 1500 Hz.
See Figure 3-5 below, which describes the possible input types and
configurations for the PWM input.
NOTE
This actuator can also be commanded using an analog signal of 0–5 V. See
the description below for the auxiliary input pins. AUX2 is used as the
analog command input. The PWM and AUX2 input pins should not be tied
together.
RS-232 Connections (pin 4 and pin 6)—These pins are for serial communication
with the L-Series actuator. An external RS-232 transceiver is necessary to make
communications possible with the Woodward L-Series Service Tool. A
connectivity kit can be purchased from Woodward to accomplish this. Further
instructions for using this connectivity kit are provided in Chapter 4. See also the
description below on Auxiliary Inputs.
TPS Output (pin 2, referenced to either pin 3 or pin 5)—This pin feeds the output
of the Hall effect position sensor to the terminal wiring. The output range of this
pin should be approximately 0.75 Vdc when the actuator is full counterclockwise
(when viewed at the end of the shaft), and approximately 4.25 Vdc when the
actuator is at full clockwise. This gives the end user an indication of throttle
position.
NOTE
This output is meant for an approximate indication of shaft position only.
The unconditioned output accuracy must be considered when using this
signal externally. Refer to the specification for TPS accuracy.
WARNING—TPS OUTPUT/OVERSPEED
It is recommended that the TPS output be used to externally verify that the
position command and subsequent actual position matches the command
signal sent. In addition to a positioning error validation, the TPS signal
should be monitored to detect out-of-range errors on the TPS output. Failure
to comply with this recommendation can result in undetected system faults,
and in extreme cases, can cause personal injury and/or property damage.
22 Woodward
Manual 26237 L-Series Position Controller
For this type of PWM Source... ...the L-Series PWM Input looks like...
5 - 32 VDC
L-Series
Pin 11
To
PNP (or P-Channel FET) 4 kW 9.5 kW Processor
Internal Clamped to 5V, then
12 kW
Command compared with 2.5V reference.
L-Series 12 kW
NPN (or N-Channel FET) Pin 11
To
Internal 4 kW 9.5 kW Processor
Command
Compared with 2.5V
reference.
L-Series
Pin 11
To
Internal 5 - 32 VDC
Processor
Command OR 13.5 kW
Internal
Command
5 - 32 VDC
OR
Internal
Command
Woodward 23
L-Series Position Controller Manual 26237
Relay Driver Output (pin 9)—This pin provides the end user with a means for
detecting a fault or shutdown condition that is experienced by the L-Series
actuator. It is a low-side driver capable of sinking 250 mA (not to exceed 500 mA)
through an external load such as a lamp or relay. This circuit is internally
protected against over-current conditions and inductive flyback, such as from a
relay coil. By default, this circuit will be configured in a failsafe manner, meaning
it will be active (conducting) when no fault exists, but if power is lost or a fault is
detected by the L-Series actuator, the circuit will open. See Figure 3-6 below for
typical usage of this feature.
WARNING—OVERSPEED
It is recommended the Relay Output be configured for the failsafe ‘Normally
On’ mode, to ensure maximum fault protection and annunciation. Failure to
follow these guidelines could, under exceptional circumstances, lead to
personal injury and/or property damage.
5-32 VDC,
500mA maximum
Lamp Relay
Indicator Coil
OR Relay Driver
Status back
L-Series
to Processor
Pin 9
Self-Protecting From
.01mF FET Processor
Auxiliary Inputs (pins 4, 6, 8, and 10)—The L-Series has three dedicated digital
inputs (AUX2, AUX3, and AUX4) used to activate various features of the control.
Shorting an auxiliary input pin to battery voltage activates it. Removing battery
voltage from an input pin or shorting the pin to ground deactivates the input. If it
is decided not to use battery voltage with the auxiliary digital inputs, it is
recommended that at least 3 V be present on an input pin in order to change its
state from inactive to active. All discrete inputs will be the same voltage as the
system power supply and will be active only while the input is in a high state. For
AUX2, AUX3, and AUX4, greater than 2.5 Vdc is considered high, and less than
0.8 Vdc is considered low. For the AUX1 discrete input only, the input must
exceed 3 V to activate the discrete state. AUX3 and AUX4 are also used for
digital communications such as RS-232 (service tool) or CAN (If the CAN option
was purchased). RS-232 and CAN will NOT run simultaneously.
24 Woodward
Manual 26237 L-Series Position Controller
When used as a position control, AUX1 on the L-Series actuator can be
configured as a run enable discrete input. This configuration must be specified in
the configuration of the device using the Service Tool. If AUX1 is selected to
perform the run enable function, then 5 V (5–32 V) applied to pin 8 will allow the
control to run normally. When this input is opened, the actuator will be in stand-
by mode. When in stand-by, the actuator driver will be disabled, and the shaft will
be limp.
AUX2 can be used as a 0–5 V command signal for position control. The software
must recognize that the unit is expecting an analog command as opposed to a
PWM command. See Figure 3-7 below for typical usage of AUX1 and AUX2
when the L-Series is configured as a position control.
NOTE
This actuator can also be commanded using a PWM signal. See the
description above in the PWM Command Input section. The PWM and AUX2
input pins should not be tied together.
NOTE
All connector pins are short-circuit protected to ground and power except
pins 3 and 5, which are not protected against shorts to battery positive.
Installation of a fuse on the power ground wire to pin5 would provide
protection to these pins but does not mean one is not needed in the power
connection. Pin 1 (B+) still needs protection against a short to ground.
L-Series
Aux.2 Input
(Pin 10) Clamp to 5V Analog
Command
0.5V to 4.5VDC 10k Signal to
Command Signal Processor
1000pF 499k
** if optional external Run Enable is chosen during L-Series configuration, Aux. 1 can be used to enable or
disable the actuator output shaft torque.
Woodward 25
L-Series Position Controller Manual 26237
Ground Junction (see Figure 3-8)—This grounding junction is provided for
joining external ground wires. THERE IS NOT AN INTERNAL CONNECTION TO
CIRCUIT GROUND. Terminal pins 3 and 5 must be used for access to the circuit
ground. This junction point is completely electrically isolated from the L-Series
actuator’s electronics, and is solely for convenience during installation.
Ground
Junction
26 Woodward
Manual 26237 L-Series Position Controller
Chapter 4.
Service Tool
Introduction
This chapter covers the process of tuning, configuring, calibrating, and servicing
the control via the L-Series Service Tool. It is assumed that the control has
already been installed on the engine.
NOTE
Many applications are delivered pre-configured, calibrated, and tuned. These
units do not require the use of the Service Tool.
Description
The Service Tool software is used to configure, tune, and troubleshoot the
L-Series controller. This chapter describes installation and use of the Service
Tool. It identifies the parameters available that can be viewed. It also provides
detailed information on configuring and setting up the L-Series to the customer-
specific field application.
Woodward 27
L-Series Position Controller Manual 26237
The following hardware is required to work with the L-Series control:
• PC-compatible laptop or desktop computer* with at least one available serial
communications port, and Windows 95/98/00/NT/Me/XP as the operating
system.
• Programming/datalink harness as shown in Figure 4-2.
In addition to the hardware, the following are the distributions of tool software
needed to communicate with the control:
• Woodward part number 9927-1222, L-Series Service Tool
To PC
(loaded with
Service Tool)
232
9-Pin Straight-
To L-Series Thru Cable
Actuator
Engine
Control
Harness
28 Woodward
Manual 26237 L-Series Position Controller
Getting Started
Installation Procedure
The Service Tool software can be downloaded and installed from the Woodward
internet site (www.woodward.com).
What to do next
After the software is installed, connect a serial communications cable between
the RS-232 connections on the L-Series control and an unused serial port on
your computer. Run the Service Tool program and select the appropriate comm
port. Once connected to the control, the status bar will display ‘connected’ and
the Service Tool screen will populate with monitor parameters.
WARNING—TRAINED PERSONNEL
An unsafe condition could occur with improper use of these software tools.
Only trained personnel should have access to these tools.
Woodward 29
L-Series Position Controller Manual 26237
Configuration Password
If a password has been saved in the configuration file, the file cannot be opened
without first entering the password. Once a configuration with a password has
been loaded into the L-Series driver, the control configuration cannot be opened
without the password. All other service tool functions do not require a password
including: writing over a password protected file configuration, writing over a
password protected control configuration, using the Position Calibration Tool, and
using the Edit Position PID.
L-Series Configuration
The L-Series can be configured either on-line or off-line. On-line configuration
can only be performed when the Service Tool is connected to and
communicating with the L-Series control. Off-line configuration can be done at
any time, however, settings will not take effect until they are loaded into the
control.
NOTE
If using non-linear mode, control power must be cycled after loading a new
configuration.
The current L-Series control configuration settings can be viewed at any time
when connected to the control by opening the Configuration Editor (File/Open
Control Configuration). See Figure 4-3.
NOTE
As changes are made to Configuration parameters, they are not used by the
driver until a ‘load’ command is issued. Selecting the ‘Close Window’
box/button closes the Configuration Editor and does not make any changes
to the driver.
30 Woodward
Manual 26237 L-Series Position Controller
Configuration Parameters
There are three tab sheets that contain all the configuration settings: Overview,
Discrete Output, and Alarm/Shutdown.
Woodward 31
L-Series Position Controller Manual 26237
Proportional Gain
Sets the position controller PID’s proportional gain. Increased gain corresponds
to increased PID output (higher proportional = faster response). This setting can
also be dynamically adjusted using the PID Tuning screen. Allowed values: 0–
100%.
Integral Gain
Sets the position controller PID’s integral gain. Increased gain corresponds to
increased PID output (higher integral = faster response). This setting can also be
dynamically adjusted using the PID Tuning screen. Allowed values: 0–100%.
Derivative Gain
Sets the position controller PID’s derivative gain. Increased gain corresponds to
increased PID output (higher derivative = faster response). This setting can also
be dynamically adjusted using the PID Tuning screen. Allowed values: 0–100%.
Friction/Dither Setting
Sets the position controller’s friction and dither values. This parameter should be
set to zero (no effect) while tuning the PID and then increased for optimum
response. If unsure, a typical value would be 25. Allowed values: 0–100.
32 Woodward
Manual 26237 L-Series Position Controller
Non-linear Actuator
Selects either a Linear position command, when unchecked, or a Nonlinear
5-point curve command. Linear/Nonlinear refers to the relationship between the
position requested and the position commanded to the position PID. When this
box is checked, additional parameters appear to set up the 5-point demand curve
(Figure 4-4).
NOTE
If the non-linear curve is changed, control power must be cycled.
These values must maintain a monotonic increase in their values, in order from
lowest to highest. Also, after the configuration is loaded into the control, power
must be cycled on the control before the settings take effect.
PWM Settings
Two additional configuration parameters appear when the position demand is set
to PWM (see Figure 4-5).
PWM Offset
Sets the PWM Duty cycle offset. This setting is provided to compensate for duty
cycle variations in PWM input frequencies, voltages, and types. Allowed values:
–5.01 to +5.01%
Woodward 33
L-Series Position Controller Manual 26237
WARNING—OVERSPEED
It is recommended that the Relay Output be configured for the failsafe
‘Normally On’ mode, to ensure maximum fault protection and annunciation.
Failure to follow these guidelines could, under exceptional circumstances,
lead to personal injury and/or property damage.
WARNING—FAULT ANNUNCIATION
It is recommended that all faults be configured to activate the discrete
output, this ensures maximum fault annunciation.
34 Woodward
Manual 26237 L-Series Position Controller
WARNING—FAULT PROTECTION
It is recommended that all faults be configured as shutdowns, this ensures
maximum fault protection. Failure to follow these guidelines could, under
exceptional circumstances, lead to personal injury and/or property damage.
Woodward 35
L-Series Position Controller Manual 26237
Each screen displays the position setpoint and actual position values.
Position Setpoint
Displayed value of the position demand, in percent.
Actual Position
Displayed value of the actual position, in percent.
36 Woodward
Manual 26237 L-Series Position Controller
Communication Status
This section of the status bar shows the status of communication between the
service tool and the L-Series Driver. For more information, see Establishing
Communication.
• Connected—The Service Tool is connected to and communicating with the
driver.
• Not Connected—The Service Tool is not connected to the driver.
• Connecting—The Service Tool is attempting to connect to the driver. This
message is displayed when Connect is selected from the Communications
menu or when attempting to re-establish communication to the driver. If the
connection is lost it will continuously attempt to re-connect.
Alarm Status
One or more alarms on the Alarms screen is active.
Shutdown Status
One or more shutdowns on the Shutdowns or Internal Shutdowns screen is
active.
Woodward 37
L-Series Position Controller Manual 26237
Supply Voltage
Displayed value of the input power, in volts, as read by the processor.
Power Demand
Displayed value of the power demanded, in watts, as read by the processor. This
is an indication of the work output.
Electronics Temperature
Displayed value of the electronics temperature sensor, in degrees Celsius, as
read by the processor. The temperature sensor is physically located between the
electronics module and the LAT motor.
AUX2 Input
Displayed value of the analog 0–5 V input, in volts. This indication is displayed
only when the position demand is set to ‘0.5 V’.
Discrete Output
On/Off status of the discrete output command. The indicator is illuminated when
the channel is commanded to ON and grayed-out when the command signal is
OFF.
Run Enabled
Open (off) / Closed (on) indication of the Run Enable discrete input.
38 Woodward
Manual 26237 L-Series Position Controller
An active fault is one that is currently active or latched in the control. The
latching/non-latching faults configuration setting factors into this indication. If the
fault is latching, then an active fault could either be one that is still present or one
that occurred but has not been reset. Latched faults can be cleared by cycling
power on the L-Series control or by selecting the ‘Reset Alarms and Shutdowns’
button on any of the Alarm or Shutdown screens.
A logged fault is one that occurred but is no longer currently active or latched in
the control. Logged faults are permanently cleared by selecting the ‘Reset
Logged Alarms and Shutdowns’ button on any of the Alarm or Shutdown
screens.
Alarms Screen
To monitor the alarm conditions, go to the Alarms page on the main window. The
values displayed on this screen dynamically change with the fault configuration.
Refer to chapter 2 for a complete listing and details of all the faults.
Woodward 39
L-Series Position Controller Manual 26237
40 Woodward
Manual 26237 L-Series Position Controller
Identification Screen
To monitor the L-Series product identification, go to the Identification page on the
main window.
The L-Series controller can be put into a manual control mode from this screen
by selecting the “Enable Manual Position Tuning’ checkbox (Figure 4-13). Once
in manual mode, the position setpoint box is highlighted and the value displayed
is actively positioning the output. Use this command to create step changes for
the PID and monitor the response using the displayed trend.
Pressing the Properties button pops open the Properties Window (Figure 4-14).
From this window the user can adjust the trending window properties including
the update rate and display range.
Woodward 41
L-Series Position Controller Manual 26237
42 Woodward
Manual 26237 L-Series Position Controller
There are two methods available to perform a position calibration: Automatic or
Manual. If the application has hard stops that correspond to the actual min/max
travel, then either Auto or Manual methods can be used—although auto is easier.
If hard stops are not available, then the auto method will give invalid results and
the manual method must be followed.
The Service Tool can be used to calibrate the control to end user stops (physical
or soft) or to verify the position calibration. To get to the Position Calibration
screens select the desired function from Position Calibration under the Tools
menu selection.
NOTE
Position Calibration is only used when the full travel of the actuator is
constrained or limited such that 0 to 60 degrees of travel is not used.
Automatic Mode
1. Select Automatic Position Calibration Mode.
2. Select cw or ccw Direction.
3. L-Series automatically rotates in both cw and ccw directions until the stops
are detected. The values are then captured and stored.
4. When completed, cycle the power on the L-Series.
5. It is recommended that a Position Verification be performed to confirm the
calibration is correct. See Position Verification below.
Manual
1. Determine to rotational travel limits. This can be done by positioning the unit
to the minimum and maximum positions and recording the position settings.
2. Select Manual Position Calibration Mode.
3. Select Direction.
4. Enter the pre-determined rotational travel limits values.
5. When completed, cycle the power on the L-Series.
6. It is recommended that a Position Verification be performed to confirm the
calibration is correct. See Position Verification below.
Position Verification
When the Verify Position screen is entered, the control is put into position control
and the position is set to the position the control was at when the screen was
entered. The screen displays the “User” Requested Position, Actual Position,
Minimum Position, and Maximum Position (see figure 4-13). These User
Positions are calculated from the user-calibrated stops.
Woodward 43
L-Series Position Controller Manual 26237
The Full Travel Actual Position is the full stroke factory position without user
stops after software linearization. The Full Travel Sensor Position is the full
stroke factory position without user stops before software linearization. The Full
Travel Sensor Position will match the TPS Output Signal.
The Verify Position screen can be used to check the calibration or to get the
minimum and maximum position values for the manual calibration. If the Enable
Requested Position Tuning box is checked the valve can be positioned anywhere
from 0 to 100% of the user minimum and maximum stops by entering a value into
the Requested Position. If the Enable Requested Position Tuning box is
unchecked the valve will go limp and can be physical positioned by hand.
NOTE
If the full factory position calibration range is not being used (the Manual or
Automatic Calibration has been performed) and the minimum position
direction is changed, the calibration must be run again for the Verify
Position mode to work correctly.
Manual
The manual calibration mode is used to set the minimum position and fail
direction and to calibrate the valve to user soft stops (inside of any physical
stops). The first screen to appear when entering the manual mode is used to set
the minimum position and fail direction. This setting must be correct before
manually calibrating the valve.
44 Woodward
Manual 26237 L-Series Position Controller
The next screen is used to set the minimum and maximum positions for the user
soft stops. To find the minimum and maximum soft stops use the verify position
mode described above to position the valve and use the Full Travel Actual
Position reading for minimum and maximum position values.
NOTE
After leaving this mode, power must be cycled for the new settings to take
effect.
Woodward 45
L-Series Position Controller Manual 26237
Automatic
The automatic calibration mode is used to set the minimum position and fail
direction and to calibrate the valve to user physical stops (mechanical hard
stops). Like the manual mode, the first screen to appear is used to set the
minimum position and fail direction. This setting must be correct before automatic
calibration is performed.
After setting minimum position and fail direction the screen below will appear.
The control is now moving first to the ccw stop and then to the cw stop to get the
physical minimum and maximum positions.
NOTE
After leaving this mode, power must be cycled for the new settings to take
effect.
46 Woodward
Manual 26237 L-Series Position Controller
Chapter 5.
Troubleshooting
Introduction
This chapter presents several broad categories of application failures typically
experienced in the field, possible causes, and some tests used to verify the
causes. Because the exact failure experienced in the field is the product of the
mechanical/electrical failure combined with the configuration file resident in the
control, it is left as the OEM’s responsibility to create a more detailed
troubleshooting chart for the end user. Ideally, this end-user troubleshooting
chart will contain information about mechanical, electrical, engine, and load
failures in addition to the possible governor failures. For more detailed
information about governor system failure modes and effects, contact Woodward
for a copy of the system DFMEA.
The troubleshooting scenarios listed below assume that the end user has a
digital multimeter at his disposal for testing voltages and checking continuity, and
assume that the application has been engineered and tested thoroughly.
Woodward 47
L-Series Position Controller Manual 26237
Engine/Generator Troubleshooting
Problem Possible Cause Suggested Test/Correction
Engine does not Stuck throttle/frozen shaft Move throttle by hand. Assess
start smoothness, friction, and return
spring force.
Power not applied to control Disconnect starter motor solenoid.
Disconnect harness from governor.
Activate application. Test for +12/24
V between +12/24 V pin and ground
pin.
Run Enable not closed Verify status of input. Measure input.
Verify input and configuration using
Service Tool.
No configuration or Using Service Tool, read
incorrect configuration in configuration from controller and
controller. evaluate parameters for correction.
Fault detected in controller. Using Service Tool, read faults from
controller. Verify/correct any
shutdown conditions.
Engine unstable Improperly tuned dynamics. Using Service Tool, tune the position
dynamics.
Intermittent position Using Service Tool, verify fault
command input signal. indications.
Device sending position Measure input signal. Verify signal
command is sending using Service Tool.
oscillating signal.
Poor frequency Improperly tuned dynamics. Using Service Tool, tune the position
control dynamics.
Friction/dither improperly Using Service Tool, adjust the
set. Friction/Dither setting.
Unable to develop Non-indexed linkage Manually verify full travel of throttle
full power slipped on shaft. plate.
Fault detected in controller. Using Service Tool, view status of
fault codes. Take appropriate action
for active faults.
48 Woodward
Manual 26237 L-Series Position Controller
Problem Possible Cause Suggested Test/Correction
Not controlling at PWM input signal Measure input duty cycle and
desired position inaccuracy. convert to percentage. Verify
setpoint controller signal using Service Tool.
If different, adjust the PWM Offset
value in the Configuration Editor.
Wiring fault or ground loop. Check the wiring.
Service Tool not Old version of Service Tool Re-install Service Tool, get the latest
communicating– or file corruption or bad version from the Woodward web site
‘Error message install. (www.woodward.com)
displayed on PC
when trying to
connect
Service Tool will Cap Lock is on. Password is case sensitive, make
not except sure you enter the password
password correctly using upper and lower
case.
Woodward 49
L-Series Position Controller Manual 26237
PWM Input
If the PWM input is not functioning properly, verify the following:
• Measure the input voltage, frequency, and duty cycle.
• Check the values seen by the L-Series driver using the Service Tool and
verify that is matches the input signal.
• Check the wiring. Look for loose connections and disconnected /
misconnected cables/connections.
• Check the software configuration to ensure that the input is configured
properly as the demand source.
Discrete Output
If the discrete output is not functioning properly, verify the following:
• Measure the output voltage on the terminal block. It should be in the range
of 10–28 Vdc when the output is off/false. The voltage will be in this range
only if all shutdowns are false. This can be verified through the Service Tool.
• Check the wiring, looking for loose connections or disconnected /
misconnected cables.
• Verify the configuration of the output.
Service Tool
If the service tool is not functioning properly, review the installation information in
Chapter 4. Verify the following:
• Check the wiring, looking for loose connections or disconnected /
misconnected cables.
• Check that Service Tool is running. Verify the Port setting is correct.
• Follow on-screen error messages. Re-install software as needed. The latest
version of software is available for download from the Woodward web site
(www.woodward.com).
50 Woodward
Manual 26237 L-Series Position Controller
Chapter 6.
Service Options
Replacement/Exchange
Replacement/Exchange is a premium program designed for the user who is in
need of immediate service. It allows you to request and receive a like-new
replacement unit in minimum time (usually within 24 hours of the request),
providing a suitable unit is available at the time of the request, thereby minimizing
costly downtime. This is also a flat rate structured program and includes the full
standard Woodward product warranty (Woodward Product and Service Warranty
5-01-1205).
Charges for the Replacement/Exchange service are based on a flat rate plus
shipping expenses. You are invoiced the flat rate replacement/exchange charge
plus a core charge at the time the replacement unit is shipped. If the core (field
unit) is returned to Woodward within 60 days, Woodward will issue a credit for
the core charge. [The core charge is the average difference between the flat rate
replacement/exchange charge and the current list price of a new unit.]
Woodward 51
L-Series Position Controller Manual 26237
CAUTION—ELECTROSTATIC DISCHARGE
To prevent damage to electronic components caused by improper handling,
read and observe the precautions in Woodward manual 82715, Guide for
Handling and Protection of Electronic Controls, Printed Circuit Boards, and
Modules.
Packing a Control
Use the following materials when returning a complete control:
• protective caps on any connectors;
• antistatic protective bags on all electronic modules;
• packing materials that will not damage the surface of the unit;
• at least 100 mm (4 inches) of tightly packed, industry-approved packing
material;
• a packing carton with double walls;
• a strong tape around the outside of the carton for increased strength.
52 Woodward
Manual 26237 L-Series Position Controller
NOTE
We highly recommend that you make arrangement in advance for return
shipments. Contact a Woodward customer service representative at
1 (800) 523-2831 in North America or +1 (970) 482-5811 for instructions and
for a Return Authorization Number.
Replacement Parts
When ordering replacement parts for controls, include the following information:
• the part number(s) (XXXX-XXXX) that is on the enclosure nameplate;
• the unit serial number, which is also on the nameplate.
For assistance outside North America, call one of the following international
Woodward facilities to obtain the address and phone number of the facility
nearest your location where you will be able to get information and service.
You can also contact the Woodward Customer Service Department or consult
our worldwide directory on Woodward’s website (www.woodward.com) for the
name of your nearest Woodward distributor or service facility.
Woodward 53
L-Series Position Controller Manual 26237
Engineering Services
Woodward Industrial Controls Engineering Services offers the following after-
sales support for Woodward products. For these services, you can contact us by
telephone, by email, or through the Woodward website.
• Technical Support
• Product Training
• Field Service
Contact information:
Telephone—+1 (970) 482-5811
Toll-free Phone (in North America)—1 (800) 523-2831
Email—[email protected]
Website—www.woodward.com
54 Woodward
Manual 26237 L-Series Position Controller
Technical Assistance
If you need to telephone for technical assistance, you will need to provide the following information.
Please write it down here before phoning:
General
Your Name
Site Location
Phone Number
Fax Number
Control/Governor Information
Please list all Woodward governors, actuators, and electronic controls in your system:
Serial Number
Serial Number
Serial Number
If you have an electronic or programmable control, please have the adjustment setting positions or
the menu settings written down and with you at the time of the call.
Woodward 55
L-Series Position Controller Manual 26237
Appendix A.
Acronyms/Abbreviations
AUX auxiliary
EEPROM electrically-erasable programmable read-only memory
EMC electro-magnetic compatibility
GUI graphic user interface
I/O inputs/outputs
Isoch isochronous
ITB integrated throttle body
L-Series Woodward electronic engine governor that contains both a rotary
actuator and a controller circuit board
MPU magnetic pick up
OEM original equipment manufacturer
PWM pulse-width modulated
rpm revolutions per minute
RS-232 a communications standard
TPS throttle position sensor
56 Woodward
Manual 26237 L-Series Position Controller
Appendix B.
L-Series Configuration Summary
APPLICATION ________________________________________________
Woodward 57
L-Series Position Controller Manual 26237
Appendix C.
L-Series Control Specifications
Specifications
Power Supply 12/24 V systems (10–32 Vdc) reverse polarity
protection, 2.5 A max
Power Consumption 32 W maximum
Torque Nominal: 0.34 Nm (0.25 lb-ft)
Minimum Transient (up to 105 °C):
0.28 Nm (0.21 lb-ft)
Minimum Continuous (up to 105 °C):
0.20 Nm (0.15 lb-ft)
Mass/Weight 425 g (15 oz)
Power-Up to Operation Time <250 ms
Performance
Positioning Accuracy ±2% (analog or PWM command), ±1.0% (CAN)–at 25 °C
±4% (analog), ±3.6% (PWM), ±3% (CAN)–over
temperature range
Slew Time 10%–90% 33 ms
Overshoot 1%
Settling Time 10 ms
–6 db Roll-off at ±0.5% Input 32 Hz
–3 db Roll-off at ±2% Input 8 Hz
Environment
Ambient
Operating Temperature –40 to +105 °C (–40 to +221 °F)
Storage Temperature –40 to +125 °C (–40 to +257 °F)
EMC EN61000-6-2: Immunity for Industrial Environments
EN61000-6-4: Emissions for Industrial Environments
SAE J1113-21: Radiated Immunity (100 V/m)
SAE J1113-11: Conducted Transient Immunity –
Pulse 5b, Suppressed Load Dump (45 V)
Humidity US MIL-STD 810E, Method 507.3, Procedure III
Salt Spray US MIL-STD 810E, Method 509.3, Procedure I
Shock MS1-40G 11 ms sawtooth
Random Vibration Random: 0.3 G²/Hz, 10–2000 Hz (22.1 Grms) 3 h/axis
Sine: 5 G 2.5 mm peak-to-peak, 5–2000 Hz, 3 h/axis,
90 min dwells, 1 octave/min
Drop SAE J1211, Paragraph 4.8.3 (modified)
Thermal Shock SAE J1455, Paragraph 4.1.3.2
Ingress Protection IP56 per EN60529
Regulatory Compliance
European Compliance for CE Marking:
These listings are limited only to those units bearing the CE Marking.
58 Woodward
Manual 26237 L-Series Position Controller
North American Compliance:
These listings are limited only to those units bearing the CSA agency identification.
Woodward 59
L-Series Position Controller Manual 26237
Discrete Input
Parameter Value
Input Current 0.5 mA @ 5 Vdc
Input Type Ground referenced discrete input
Delay Time for Shutdown < 200 ms for system to recognize shutdown
Delay Time for Reset < 1 s for valves to move to minimum position
Detection
Max Voltage from + 32 V (power input voltage)
Connection
Isolation None, Intended for use with external relay or other dry
contact
Input Thresholds > 3.1 Vdc = “ON” < 0.8 Vdc = “OFF”
Input Current 0.5 mA @ 5 Vdc
Discrete Output
Parameter Value
Output Type Low-side output driver
Max Contact Voltage (Open) 32 V
Max Current 0.5 A
Max Contact Voltage at 0.5 1.5 V
A (Closed)
Max Delay Time for Opening 6.5 ms
Contact
Default at Power Up Configurable in software
Error Condition Configurable in software
OK Condition Configurable in software
Driving Inductive Loads Yes, internally protected low-side switch
Protection Utilizes circuitry that will open the contact when output
contacts are short-circuited. Self-resetting when fault is
removed
TPS Output
Parameter Value
Output Type 0–5 V, single-ended
Output Scaling 0.75 V = full ccw position and 4.25 V = full cw position
Isolation None
3 db Circuit Bandwidth 350 Hz
Transient Protection According to EMC norm
Output Impedance 2.8 kΩ (±1%)
Accuracy ±10% of full scale, @ 25 °C
Temperature Drift ±0.4% over the full temperature range
I/O Latency n/a–direct from position sensor
Calibration Method Sensor-in-place factory calibration. 2-point linear
Out of Range Signal < 0.25 V or > 4.75 V
Overvoltage Protection Output protected against 32 Vdc, steady-state; if >28 V is
applied to pin 2, a position-related error will be
annunciated
60 Woodward
Manual 26237 L-Series Position Controller
Electronics Temperature Sensor
Parameter Value
Accuracy ±2 °C at 25 °C ambient
±3 °C over full range (–40 to +125 °C)
I/O Latency 6.5ms
Woodward 61
We appreciate your comments about the content of our publications.
Send comments to: [email protected]
Please include the manual number from the front cover of this publication.
2008/3/Fort Collins