Cb2420A Battery Charger: Lead Acid: 2.4 Nicd:1.51 Li-Ion: 3.65

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Input: Single-phase 115  277 Vac

CB2420A Battery Charger Output: Battery charging 24 Vdc; 20 A


Suited for the following battery types: Open Lead
Acid, Sealed Lead Acid, lead Gel, Ni-Cd and Li-Ion
Automatic diagnostic of battery status. Charging
curve IUoU, constant voltage and current
Switching technology, output voltage 28.8 Vdc
Five charging levels: Recovery, Bulk, Absorption,
Boost, Float
Protected against short circuit, inverted polarity,
over Load.
Signal output (contact free) for fault battery state
ModBus (RTU) connection
Protection degree IP20 - DIN rail

Technical features External Fuse (recommended) 16 A (MCB curve B)


The CB series is a “Switching technology” and “Battery Care Battery Output (Battery Care)
philosophy”, since years parts of the core know-how at ADEL system, Boost-Fast charge Jumper Configuration Lead Acid: 2.4
led to the development of this advanced multi-stage battery charging 25°C (V/cell) NiCd:1.51
method, completely automatic and suited to meet the most advanced
requirements of battery manufacturers. The Battery Care concept is Li-ion: 3.65
base on algorithms that implement rapid and automatic charging, Max. time Boost Charge (tpy. At In) 15 h
battery charge optimization during time, flat batteries recovery and real Min. time Boost Charge (tpy. At In) 1 min.
time diagnostic during installation and operation. The Real Time Auto- Float Charge Jumper Configuration 25°C Lead Acid: 2.23;
diagnostic system, monitoring battery faults such as, elements in short (V/cell): 2.25;2.27;2.3
circuit, accidental reverse polarity connection, disconnection of the NiCd:1,4 Li-ion: 3.45
battery, they can easily be detected and removed by help of Blink Code Recovery Charge 2 – 16 Vdc
of Diagnosis Led; during the installation and after sell. Each device is Charging. Max Ibatt (In) 20 A  5%
suited for all battery types, by means of jumpers it is possible setting Efficiency (50% of In) 91%
predefined curves for Open Lead Acid, Sealed Lead Acid, Gel, Ni-Cd Charging current limiting Iadj 10 ÷ 100 % / In
and Li-Ion. They are programmed for two charging levels, boost and Quiescent Current  100 mA
float. A rugged casing with bracket for DIN rail mounting provides IP20 Charging Curve automatic: IUoU 5 stage
protection degree. Detection of element in short circuit Yes
Norms and Certifications Sulfated battery check Yes by Jumper
In Conformity to: EN60950 / UL60950-1 and CSA C22.2 No. Short-circuit protection) Yes
60950-1-07 (Information Technology Equipment) – Safety – Part1: Over Load protection Yes
General Requirement. Electrical safety; EN54-4 Fire Detection and fire Over Voltage Output protection Yes
alarm systems; 2014/30/UE (EMC Directive); 2014/35/UE (Low Power Supply Mode Yes
Voltage); Safety EN IEC 62368-1: 2014/AC:2015; DIN41773 (Charging
Remote Input Control (RTCONN cable) Boost / Float
cycle); Emission: IEC 61000-6-4; Immunity: IEC 61000-6-2. CE.
General Data Signal Output (free switch N°2 contact)
Insulation voltage (In /Out) 3000 Vac Dry Contact. Current can be switched (EN60947.4.1): Max: DC1: 30
Insulation voltage (In / PE) 1605 Vac Vdc 1 A; AC1: 60 Vac 1A (Resistive load ) Min: 1mA at 5 Vdc (Min
Insulation voltage (Out / PE) 500 Vac permissive load)
Protection Class (EN/IEC 60529) IP20 Fault System / Low Battery C NC NO
Protection class I, with PE connected Main or Back Up C NC NO
Reliability: MTBF IEC 61709 > 300.000 h
Pollution Degree Environment 2 Signal Input / Output (RJ45)
Connection Terminal Blocks screw Type 2.5mm(24–14AWG) Temp. Comp. Battery (with external probe) RJTemp(cable) Aux1
Signal: Remote monitoring data: RJ45: Aux 2
Connection Terminal Blocks screw Type 4 mm (30-10 AWG) Protocol: ModBusRTU (RS485)
Protection class (PE Connected) I, with PE
Dimensions (w-h-d) 150x115x135 mm
Charging
Automatic multi-stage charging and real time diagnostic allow fast
Weight 1.5 Kg approx
recharge and recovery of deep discharged batteries, adding value and
Climatic Data reliability to the system hosting. Type of charging it is Voltages and
Ambient temperature (operation) -25 ÷ +70°C current stabilized IUoU. The state of charging battery and Auto-
De Rating Ta > 50°C - 2.5%(In) / °C diagnosis of the systems are identified by a flashing code on a
Ambient temperature Storage -40 ÷ +85°C Diagnosis LED and Fault Battery LED:
Humidity at 25 °C no condensation 95% to 25°C State Diagnosis LED Battery Fault LED
Altitude: 0 to 2 000m - 0 to 6 560ft No restrictions Float 1 Blink/2 sec OFF
Altitude: 2 000 to 6 000m - 6 560 to 20 000ft De-rating Charging Absorption 1 Blink/sec
5°C/1000m Type Boost 2 Blink/sec OFF
Cooling Auto Convection Recovery 5 Blink/sec OFF
Input Data Reverse polarity 1Blink ON
Nominal Input Voltage (2 x Vac) 115 – 230 – 277 Auto Battery No connect 2Blink ON
Input Voltage range (Vac) 90 – 135 / 180 – 305 diagnosis Element in Short C. 3Blink ON
Inrush Current (Vn and In Load) I2t  35 A  5 msec. Replace Battery 5Blink ON
Frequency 47 – 63 Hz 6%
Input Current (115 – 230 Vac) 9 – 4.5 A
Internal Fuse 10 A

All specifications are subject to change without notice