0% found this document useful (0 votes)
76 views62 pages

Power System Protection Schemes by Mr1604577442

Uploaded by

AET Rawalpindi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
76 views62 pages

Power System Protection Schemes by Mr1604577442

Uploaded by

AET Rawalpindi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 62

1

Power System Protection Schemes

2 Fahim Dad
RE (Telecom), NTDC
Power Station Tarbela
Overview
Power Protection Need, Functions & Objectives
Equipment's to protect, and used
Types of Relays
Transmission Line Protection
Direct Transfer Trip Scheme
PUTT & POTT
Auto Recloser
Breaker Failure Protection
3
Cross Trip Schemes
Tele-Protection
Book Review
Power System Protection
detecting problems with the power system
components and isolating these problematic
component to ensure stability of system and
avoid blackout
4
Need for Protection
• Reliable service

• Continuous operation without breakdown

• Maximum return on large investment

5 • Protect equipment therefore is very essential


Functions of Protection
• To safeguard the entire system to maintain the
continuity of supply
• To detect the presence of fault
• To identify the faulty component
6
• To initiate trip command to the concerned
circuit breaker.
Functions of Protection
• To remove the defective component from the
system

• To minimize damage and repair costs

• To ensure safety of personnel


7
Objective of Protection
• Selectivity: maximum continuity of service
with minimum system disconnection.
• Stability: provide stability by isolating
unstable section from the system
• Speed: Detect and isolate the faulty section
8 from the power system as quickly as possible.
Minimizing the fault duration and consequent
equipment damage and system instability.
Objective of Protection
• Sensitivity: Protection equipment must be
sufficiently sensitive to detect even the small
abnormalities and must discriminate normal
from abnormal conditions.
• Simplicity: Minimum and simple protective
equipment and associated circuitry to achieve
9
the protection objectives
• Economics: should be economical
Objective of Protection
• Reliability:

Dependability: It must trip when called upon

Security: It must not trip when not supposed to

10
Problems in Power System
Problems in power system mainly includes:

• Short circuits

• Abnormal Conditions

11 • Equipment failures

• Operators/Human Error
Equipment: Do We Protect?
• Generators

• Transformers

• Reactors

12 • Transmission Lines

• Buses
Protection Block Diagram

13
Equipment: For Protection
• CTs

• PTs

• Circuit Breakers

14 • Relays

• Communication Channel
Current Transformer (CT)
• Transforms the current on the power system
from large primary values to safe secondary
values

• Secondary Value is acceptable to Relays,


15
Control Equipment and Meters
Potential Transformer (PT)
• Transforms the voltage on the power system
from large primary values to safe secondary
values

• Secondary Value is acceptable to Relays,


16
Control Equipment and Meters
Circuit Breakers
• From protection point of view CB receives trip
command initiated by Relay

• Used to make/break circuits carrying full load


and fault currents within few cycles
17
Protection Relays
• Monitors current and/or voltage of system

• Currents & voltages to relays are supplied via


CT’s & PT’s

• Detect/sense problems within system


18

• Sends command to Faulty Equipment Breaker


Relays: Types
• Electromagnetic Relays: These are based
on Electromagnetic Induction Principle,
Induction Coils are used for comparisons
• Static Relays: Contains Power Electronics
devices like transistors etc. for
calculations/comparisons
19
• Numerical Relays: these are based on
Microprocessors
Over Current & Earth Fault
Over-Current Protection:
• Relay picks up when the magnitude of current
exceeds the pick-up level
• The over current relays are connected to the
system by means of current transformer.
20 Earth Fault Protection
• When the fault current flows through earth
return path, the fault is called Earth Fault.
• Which do not involve earth are phase faults
Types of Over Current Relays
Based on the relay operating characteristics,
overcurrent relays can be classified into three
groups
• Definite Current or Instantaneous
• Definite Time
21 • Inverse Definite Minimum Time (IDMT)
Types of Over Current Relays
Definite-Current /Instantaneous Relays:
• These relays operates instantaneously when the
current reaches a predetermined value.
Definite Time Current Relays:
• These relays operates after a definite time when
current reaches a pre-determined value.
22 Inverse Definite Minimum Time Relays (IDMT):
• These relays operate in a time that is inversely
proportional to the fault current.
Types of Over Current Relays
Current Grading Scheme:
• Relies on difference in fault level at different
system locations.
• Choose current settings so that only the relay
nearest to fault operates
23
Types of Over Current Relays
Time Grading Scheme:
• Relay operating time is independent of current
magnitude
• Relay furthest away from source has shortest
operating time
24
Types of Over Current Relays
Time Grading Scheme:
• The main disadvantage of this method of grading
is that the longest fault clearance time occurs for
faults in the section closest to the power source,
where the fault level is highest.
25
Types of Over Current Relays
Current and Time Grading Scheme:
• Operating time depends on fault current level
• Can get faster clearance times than using
definite time delay relays

26
Differential Relays
• Operates according to the difference between
two parameter such as Current etc.

27
Differential Relays
• Low Accuracy due to Mismatch, this can be
amplified when fault current is high
• Difference in the C.T. characteristics due to ratio
error at high values of short circuit currents. This
causes an appreciable difference in the
28
secondary currents which can operate the relay.
• Matching CT are required
Generator Protection:

29
Generator Protection:
• Reverse Power
• Stator/Rotor Earth Fault Protection
• Differential Protection
• Over Voltage Protection
• Under Frequency Protection
30
Transformer Protection:

31
Transformer Protection:
• Main differential between HV & LV Bushing CT
• LV Connection between LV Bushing CT & LV
Breaker CT
• HV Connection between HV Bushing CT & HV
Breaker CT
32 • Rough Balance: LV Breaker CT and HV
Breaker CT
• REF: Restricted to Earth Fault
Transmission Line Protection

33
Transmission Protection:
For 500kV transmission line network, we have
following protections

• Main-I Distance Protection

• Main-II Distance Protection


34

• Backup Over Current & Earth Fault Protection


Transmission Protection:
• Reactor Protection

• Over Voltage Protection

High Set

35 Low Set

Inverse Type
Transmission Line Protection:
For 220kV transmission line network, we have
following protections

• Main-I Distance Protection

• Main-II Distance Protection


36

• Backup Over Current & Earth Fault Protection


Distance Protection Relays
• Bi-Quantity Relay
• Requires Voltage & Current Input from CT &
PT respectively
• Works on Impedance based principle i.e.
Z=V/I
37 • Fault Locator works on Reactance Based
Feature i.e. X is directly proportional to L
(Length)
Differential Protection Relays
• Current is measured by the Line Differential
Relays & transmits the measured values to
remote end
• Under Normal Conditions, the sum of Current
is Zero.
• When fault occurs, the sum of current is non-
38 zero, hence, fault is detected on the line.
• Both ends add their own measured current &
current of remote end.
Direct Transfer Trip Scheme
• Fault Detection at One End Send the Tripping
Signal to the remote end over the PLC /
OPGW Link
• On the receiving end, on receipt of Trip Signal
from remote end, tripping command is issued
to both controlling CBs of T/Line.
39
Direct Transfer Trip (DTT)
• In NTDC’s Network, DTT is send on operation
of:
• Over Voltage Protection
• Breaker Failure Stage-II of Line Controlling
CBs
40
Direct Transfer Trip (DTT)

41
Permissive Under Reach Transfer Trip (PUTT)

• Fault is detected in Zone-I (Under Reaching


Zone) of Distance Relay at One End of T/Line
& Transfer Trip Signal is sent to the remote
end
• On the receiving end, on receipt of Signal from
remote end, receive signal is ANDed with
42
Zone-2 Pickup.
Permissive Under Reach Transfer Trip (PUTT)

• If the above condition is satisfied, trip


command is issued to both line controlling
CBs instantaneously.
• Thus for all Faults any where on T/Lines, both
ends clears the faults instantaneously.
43
Permissive Under Reach Transfer Trip (PUTT)

44
Permissive Over Reach Transfer Trip (POTT)

• Fault is detected in Zone-II (Over Reaching


Zone) of Distance Relay at One End of T/Line
& Transfer Trip Signal is sent to the remote
end.
• On the receiving end, on receipt of Signal from
remote end, receive signal is ANDed with
45
Zone-II Pickup.
Permissive Over Reach Transfer Trip (POTT)

• Moreover, Zone-II Pickup also re-transmits the


trip signal to remote end. If the above
condition is satisfied, trip command is issued
to both line controlling CBs instantaneously.
• Thus for all Faults any where on T/Lines, both
ends clears the faults instantaneously.
46
Auto Recloser
• Auto Recloser Relays are used to give an
Automatic try to CB for closing following the
tripping.
• Auto Recloser can be Single Shot or Multi
Shot(2,3,…).
47 • On EHV T/Lines, Auto Recloser is normally
Single Shot.
Auto Recloser
• Both Single Phase & 3-Phase Reclosing can
be done. NTDC adopt 3-Phase Tripping &
Reclosing
• For Closing on Live Line & Live Bus
Conditions, Synchronism Check is required.
48 • Δf = 0.1 Hz ΔV = 10% Δθ= 25 –30
• Closing Command is sent after fulfilling above
criteria
• Auto Recloser are a way to enhance system
Breaker Failure Protection
• If the CB fails to open/lockout, on receipt of
Trip Command, this condition can lead to
dangerous condition for power system
equipment
• BF Protection is a 2 stage Protection
49 • BF Stage-I trips the failed CB. i e. Re-trip is
issued. Time Delay=150ms.
• BF Protection is initiated on issuance of trip
command from relay.
Breaker Failure Protection
• BF Stage-II issues the trip command to all
feeding CBs at local end & sends to DTT
command to remote end to trip the line
controlling CBs at other end. Thus trip all the
fault feeding sources. Trip Delay=250ms.
• NTDC implements Breaker Failure Protection
50
to cater for these conditions.
Breaker Failure Protection

51
Breaker Failure Protection

52
Breaker Failure Protection

53
Breaker Failure Protection

54
Cross Trip Schemes
• Cross Trip Schemes are used to protect the
NTDC’s EHV system from tripping on
Overload, Under Voltage, Under Frequency or
Over Frequency etc. condition.
• This ensures safe, stable & reliable operation
of EHV System.
55
Cross Trip Schemes
• Normally the below mentioned Cross Trip
Schemes have been implemented
• Overloading Detection by OC & EF Relays.
• Under Voltage Detection by Under Voltage
Relays.
56 • Under/Over Frequency is detected by
Under/Over Frequency Relays respectively.
Cross Trip Schemes
• Cross Trip Schemes ensures healthy
operation of EHV System by detecting the
Overload/Under Voltage etc. on EHV system &
tripping the 132kV T/Lines or Transformers.

57
Tele-Protection Scheme
Block Diagram

58
Book Review
Power System Protection and Switch Gear
Authors:
• Bhuvanesh A Oza
• Nirmal Kumar C Nair
• Rashesh P Mehta
59 • Vijhay H Makwana
Published by McGraw Hill Education
Available at TSG Library
Book Review

60
Book Review
• Introduction
• EM Relays
• Static Relays
• u- Processor based Digital Protection Relays
• Generator Protection
• Transformer Protection
• T/L Protection
• Bus zone Protection
61
• Testing, Commissioning & Maintenance of Relays
• Circuit Breakers
• Electrical Switchgear
• Lightening Over Voltage Protection
THANK YOU
62

You might also like