HYDRAULIC CONTROL SYSTEM INTERMEDIATE
The hydraulic power unit (HPU) is provided with a steel oil tank suitable for outdoor service able to collect the full
volume of oil present in the circuit. The tank is equipped with inspection door, breather with filter, 2 level switches,
1 temperature switch, 1 visual level indicator.
Two main motor-pump groups P1 and P2, each one fitted with an electric motor, are provided on the tank; the
fixed displacement pump is able to deliver the required flow rate at a pressure of 200 bar.
A filtering/conditioning group composed by fixed displacement pump P3, filter with clogging detector (DPS3) and
exchanger (R) with fan piloted by internal thermostat is provided on board.
Functions of the main pumps are :
n° 1 active pump, to maintain all control valves in closed/open position or under continuous control.
n° 1 stand-by pump to be activated on alarm signal from low pressure switch mounted on pump common
delivery manifold
The pump flow rate is enough to ensure the maximum stroke time required in control mode for each valve without
involving the accumulator intervention.
Four pressure switches are installed in the common delivery manifold of the motor-pump groups, as follows:
PS1 supplies the “low oil pressure signal"
PS2 supplies the “minimum oil pressure signal” (i.e. plant out of commission).
PS3 stops the active pump
PS4 starts the active pump
One accumulator A1, constantly inserted on the delivery manifold, is installed on the hydraulic power unit to grant
trouble-free change-over from a motor/pump group to the other one.
The overflow valve VS3 controls the oil pressure in the primary circuit.
Two sealed maximum pressure safety valves VS1 and VS2 are mounted on pump deliveries.
A double filter F provided with electric clogging detectors DPS1-DPS2 is installed at power unit outlet.
The hydraulic power unit is provided with two terminal boxes: the first one is intended for instrument cables, the
second one for the electric motor control cabinet (M.C.C.).
Options:
-2-
HYDRAULIC CONTROL SYSTEM INTERMEDIATE
HYDRAULIC DIAGRAM
-3-
HYDRAULIC CONTROL SYSTEM INTERMEDIATE
The HCP houses also analogue positioning cards (steam valves and desuperheating valves) for stroke control
in closed loop system.
The response time of ON-OFF valves may be separately adjusted by suitable throttling devices.
The hydraulic circuit should be provided with gate valves to allow maintenance actions.
Complete cycles are allowed, when pumps are still, within 15 minutes from pump stop, because of leakages.
Options:
Hand pump
ON-OFF valves for fast closing < 3 sec
HYDRAULIC DIAGRAM
-4-
HYDRAULIC CONTROL SYSTEM INTERMEDIATE
-5-
HYDRAULIC CONTROL SYSTEM INTERMEDIATE
The electric control cabinet is supplied with a redundant feeder/transformer for auxiliary circuits (240 Vac 24
Vdc), warning lights, lamps, contactors and any other necessary component to grant the efficiency of the whole
hydraulic equipment.
The cabinet, fitted with a fan (extractor) complete with replaceable cartridge, includes an auxiliary electrical
socket .
Manufactured according to the industrial standards, with minimum protection degree IP42, houses the control
system for emergency solenoid valves and 1 PLC to manage the Hydraulic Power Unit, the Control Panel and
the interchange signals with control room.
The cabinet houses also analogue positioning cards (steam valves and desuperheating valves) for stroke
control in closed loop system.
Auxiliary circuits are separately protected, even when redundant (pumps control, PLC power supply and
proportional valves).
Cable entry from bottom.
Max cable run from cabinet to control panel approx. 200 m.
Max resistance of proportional valves supply cable 2 W.
Approximate sizes 1200 x 2000 (+ 100) x 600 mm.
FUNCTION DESCRIPTION
1 - Operating mode selection - manual mode
- automatic mode
2 - Pump change over start/stop - temporary
- failure
- external commutation
3 - Main alarm control - oil pressure too low
( shutdown) - minimum oil level
- emergency shut-down
4 - Secondary alarm - clogged filter (3)
control (monitored) - low oil level
- low oil pressure
- high oil temperature
- aut/man selector
-6-
HYDRAULIC CONTROL SYSTEM INTERMEDIATE
The operating mode may be selected by a suitable selector located on control cabinet front.
Manual Mode
Necessary in order to allow the plant start-up. The PLC does not affect the pump selection, but allows to
select the pump to be started (by using the pump change-over push-buttons).
By this mode all monitoring functions towards warning lights and Control Room are implemented.
2 PUMPS CONTROL
Start-Stop
Timed change-over
Change-over due to failure
External commutation
Options:
-7-
HYDRAULIC CONTROL SYSTEM INTERMEDIATE
Double acting cylinders built in compliance with ISO 6020-2 and DIN 24554.
On board are installed the inductive limit switches (n° 1 open posit. + n° 1 close posit. – SPDT contacts) and
position transducer (4 ÷ 20 mA)
Double acting cylinders built in compliance with ISO 6020-2 and DIN 24554.
On board are installed the mechanical limit switches (n° 1 open posit. + n° 1 close posit. – SPDT contacts)
Options: