GSCC005 Rev3
GSCC005 Rev3
Countries I&N
Argentina C. Espinoza
Brazil R. Sales
Chile D. Sarkis
Colombia J. C. Gomez
Italy L. Giansante
Peru R. Sanchez
Romania V. Obrejan
Spain J. Gonzalez
This document is intellectual property of ENEL Group distribution companies; reproduction or distribution of its contents in any way or by
any means whatsoever is subject to the prior approval of the above mentioned companies which will safeguard their rights under the civil
and penal codes. This document is for Internal Use.
Contents
1 SCOPE ........................................................................................................................................................................................ 4
13 TESTS...................................................................................................................................................................................... 21
1 SCOPE
This Global Standard applies to 12/20(24) kV and 18/30(36) kV indoor and outdoor cold shrink terminations
for MV cables with extruded insulation, both full and reduced insulating thickness, with copper wires or
aluminum tape screen.
These Global Standard applies to the Distribution Companies of Enel Group listed below:
2 FIELD OF APPLICATION
These requirements apply to the underground and overhead distribution network with rated maximum voltage
of 24 kV and 36 kV. Other existing rated maximum voltage levels up to 24 kV are covered by the 12/20(24) kV
class, whereas those with rated maximum voltage up to 36 kV are covered by the 18/30(36) kV class.
Cenelec HD 629-1;
IEC 61238-1;
IEC 60587;
IEC 60695-11-10
IEC 60721-2-1
IEC 62217
ISO IEC 17067
1 The characteristics of the cables are included in the Enel Group Global Standard. Besides installation on new
cables, which comply to GSC001, the termination may be installed on the existing network, which is made of
cables compliant to older local standards. Nevertheless, this Global Standard also takes into account the main
characteristics of existing cables for each Country (rated voltage, section and min/max diameter over
insulation).
GLOBAL STANDARD Page 5 of 24
3.3.1 Italy
DJ4580
PVR 006
GUI 101
3.3.2 Brazil
NBR14643, Corrosão atmosférica – Classificação da corrosividade de atmosferas
Nr-10, Segurança em Instalações e Serviços em Eletricidade
3.3.3 Chile
NSEC 5
NCH 4/2003
3.3.4 Colombia
RETIE – Reglamento Técnico de Instalaciones Eléctricas
3.3.5 Iberia
R.D. 614/2001, de 8 de junio, sobre disposiciones mínimas para la protección de la salud y seguridad
de los trabajadores frente al riesgo eléctrico.
R.D. 337/2014, de 9 de mayo, por el que se aprueban el Reglamento sobre condiciones técnicas y
garantías de seguridad en instalaciones eléctricas de alta tensión y sus Instrucciones Técnicas
Complementarias ITC-RAT 01 a 23.
5 UNIT OF MEASURE
Number of pieces.
6 TYPES OF TERMINATIONS
Rated voltage
Installation
Type code U0/U (Um) (kV)
12/20(24) 18/30(36) Indoor Outdoor
GSCC005/1 X X
GSCC005/2 X X
GSCC005/3 X X
GSCC005/4 X X
Table 1 – Type codes
7 ELECTRICAL CHARACTERISTICS
8 OVERALL DIMENSIONS
With reference to Figure 1 and Figure 2, overall dimension of terminations are defined in Table 4:
L D
Support
(not included in the supply)
D
L
Support
(not included in the supply)
9 SERVICE CONDITIONS
10 CONTRUCTION CHARACTERISTICS
10.1.3 Heating
All the materials that make up the termination shall withstand the heating conditions expected during operation,
without having an adverse effect on their proper functioning of the termination or the cable.
10.2 TERMINATIONS
Terminations are composed by the following elements:
Items 2 (component to control the electric field) and 3 (main insulating housing) of the above list shall be
assembled on the same single body.
It may be designed in order to ensure the following functions (e.g. through embedded sealing compounds):
to seal the termination,
to protect the junction of the metallic screen.
The lugs shall have a lock to assure the correct positioning of the conductor, even for the smaller sections.
The internal and external surface of the lugs shall not have sharp edges, spikes or deformities.
Lugs must be designed and constructed so that, when properly installed, the electrical resistance of the
connection is not greater than the equivalent resistance of the reference conductor.
It is allowed to use greases to improve the electrical contact between the lug and the cable conductor and
avoid corrosion as well as a sealing compound to fill screw cavities of the lug. In any case, the design of screw
cavities protection shall be so that no material is dispersed inside the termination during the cold shrinking
operation and/or in the installation.
The lug shall be suitable for connecting the metallic screen sections reported in Table 7. It shall be compatible
with both aluminum tape and copper wire cable screens.
In the case of cables with aluminum tape screen, the connection with the screen of the cable shall be made
by means of :
a) plate of tin-plated hard copper with a tin coating having minimum thickness of 0,5 m. The plate shall
be as shown in Figure 6 and shall be bent on a cylinder of diameter 25 2 mm; the convex side of the
plate shall include 65 asperities, arranged as shown in the Figure 6. These asperities shall have a
particular shape (see example in Figure 6) in order to allow piercing the aluminum tape, to obtain a
satisfactory contact with the screen, and to partly penetrate the outer thermoplastic sheath of the cable,
to prevent movement or removal of the device. The edge and the internal side of the plate shall be
free of sharp or rough parts, in particular in the lower side in contact with the semiconductive layer of
the cable. The lower side going under the aluminum tape shall have no protruding edge (an example
is shown in Figure 6) but a small rounded edge lower than the asperities.
b) A tin coated copper braid with a minimum length of 0,6 m. One end of the braid shall be welded to the
rectangular plate described above at the position shown in Figure 6; the other end shall be connected
to the lug described in 10.2.4.1. The section of the tin copper braid shall be compatible with the
sections prescribed in Table 7.
GLOBAL STANDARD Page 15 of 24
If the distance is sufficient, connection to earth could be made directly connecting the copper wires of the
screen to earth with the earthing lug described in 10.2.4.1.
Greases and sealing compounds shall have no electrical functions for the assembling of the termination but
only provide mechanical and/or sealing features.
All the necessary elements and accessory to install the termination on-field shall be included, namely:
12 LIST OF COMPONENTS
The list of components included in this Global Standard is reported in the following tables for 12/20(24) kV and
18/30(36) kV rated voltages:
GLOBAL STANDARD Page 17 of 24
13 TESTS
13.1 GENERAL
Tests are classified into:
Type tests
Acceptance tests
They shall be carried out according to HD 629-1. Lugs shall be tested according to IEC 61238-1 class A.
For E-Distribuzione, E-Distributie Banat, E-Distributie Dobrogea and E-Distributie Muntenia, type tests shall be
carried out on both HPTE and XLPE insulated cables.
For Endesa Distribución code 200022 type tests shall be carried out using a 185 mm2 – 18/30(36) kV cable.
Type tests shall be carried out at the maximum rated voltage level prescribed for the termination (i.e. 12/20(24)
kV or 18/30(36) kV).
The lugs shall be tested both for their maximum and minimum section, according to IEC 61238-1, class A.
Insulating materials shall be tested for resistance to tracking and erosion according to IEC 60587, with 3.5 kV
test voltage.
The Supplier shall declare the resistance to fire of the main insulating housing according to IEC 60695-11-10
or another equivalent standard.
An expiration test shall be performed in order to verify the capability of the termination to maintain its properties
during its life according to the expiry date declared by the manufacturer.
The test shall be performed of a new termination and on a termination of the same lot aged 7 days at 65°C in
oven in expanded stage (to simulate 2 years of storage at 35°C of mean temperature).
After ageing, the new termination and the aged termination are put in expanded stage at +5°C during 24h. After
that cooling phase, the terminations are installed on the minimum cross-section cable of their reference range.
For E-Distribuzione, E-Distributie Banat, E-Distributie Dobrogea and E-Distributie Muntenia additional type
tests shall be carried out on both HPTE and XLPE insulated cables.
Acceptance tests shall be carried out at the maximum rated voltage level prescribed for the cable (see Table
3).
The samples for the acceptance tests shall be selected from among the entire batch that was prepared for
testing even if made up of different material codes.
3 Tests performed on a 12/20(24) kV are considered sufficient to demonstrate compliance also for the
installation on a 8.7/15(17.5) kV cable with normal thickness insulation.
GLOBAL STANDARD Page 23 of 24
Batch (units)
Acceptance test
≤ 50 units > 50 and ≤ 1200 > 1200
Visual inspection 2 samples for each 5 samples for each 10 samples for each
Accessory manufacturing material code material code material code
specifications check* prepared for testing prepared for testing. prepared for testing.
Accessory assembly check
Power frequency withstand 1 sample for each 2 samples for each 3 samples for each
test material code material code material code
Partial discharge test at prepared for testing. prepared for testing prepared for testing
ambient temperature
* the nominal tightening torque of shear bolts specified by the manufacturer shall be always verified.
Table 12 – Samples for acceptance tests
In all cases, the acceptance number will be 0 and the rejection number will be 1.
On the scheduled acceptance testing date the supplier shall prepare the cables, stripped as required by the
assembly instructions of terminations being tested. This will facilitate the assembly of the termination and
reduce the testing time, which benefits both parties.
14 SUPPLY REQUIREMENTS
14.1 LABELLING
The termination must bear the following information:
a) name of the manufacturer;
b) maximum voltage Um in kV
c) year and month of manufacture (e.g.: 15/2);
In particular, this information shall be placed on the external sheath of the terminations by means of indelible
and permanent screen printing or an equivalent method accepted by the Distribution Companies of Enel Group.
14.2 PACKAGING
Terminations shall be supplied in individual packages which shall bear the following information:
Material code assigned by the Distribution Companies of Enel Group;
name of the manufacturer;
type of termination (e.g. cold shrink outdoor termination);
type of cables for which the accessory is intended, section and conductive material allowed;
year and month of packaging;
progressive identification number assigned by the manufacturer (or serial number);
barcode (only for E-Distribuzione and Endesa Distribucion, see 14.2.1);
production batch number;
identification abbreviation;
maximum voltage Um in kV;
expiry date (year/month) of the materials.
GLOBAL STANDARD Page 24 of 24
Furthermore, the packages shall contain a self-adhesive label with the following information (only for E-
Distribuzione and Endesa Distribucion):
manufacturer identification code (CUI);
material code assigned by the Distribution Companies of Enel Group;
year and month of manufacture (e.g.: 15/2);
progressive identification number (assigned by the manufacturer);
barcode (only for E-Distribuzione and Endesa Distribucion, see 14.2.1)
For E-Distribuzione, shipping (of several individual packages) shall meet the requirements of the packaging in
compliance with GUI 101 specifications.
Name: ………………
Date: ………………
Company: ………………
Accessory assembly instructions shall be written on A4 paper, and the various stages of construction of the
termination shall be illustrated by photographs or diagrams in color.
• Extruded cables with aluminum tape screen (only for the Country listed in table Table 6)
• Extruded cables with copper wires screen
Furthermore, for processing steps that require the use of a special tool, the description of these operations
shall be accompanied by the Distribution Companies of Enel Group material code/type code4 for the tool and
a color photograph.
Additionally a QR code shall be included in the instructions to provide a web-link to demonstration videos and
tutorials on the related termination. They shall be in the local language of the Country of delivery.
Installing instruction and templates shall be in the local language of the Country of delivery and shall be
approved by Distribution Companies of Enel Group.
4 This information, if any, will be provided by Distribution Companies of Enel Group during the examination of
the installation instructions (before the certification process)