This document provides standards for 12/20(24) kV AND 18/30(36) kV COLD SHRINK TERMINATIONS FOR MV CABLES. It covers the scope, field of application, reference laws and standards, terms and definitions, unit of measure, types of terminations, electrical characteristics, overall dimensions, service conditions, and construction characteristics. The document was revised three times with the latest revision on 09/07/2018 updating material codes for Brazil and a note on Table 11. It aims to standardize cold shrink terminations for medium voltage cables globally and in various countries.

Uploaded by

Palade Cristi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
135 views24 pages

GSCC005 Rev3

This document provides standards for 12/20(24) kV AND 18/30(36) kV COLD SHRINK TERMINATIONS FOR MV CABLES. It covers the scope, field of application, reference laws and standards, terms and definitions, unit of measure, types of terminations, electrical characteristics, overall dimensions, service conditions, and construction characteristics. The document was revised three times with the latest revision on 09/07/2018 updating material codes for Brazil and a note on Table 11. It aims to standardize cold shrink terminations for medium voltage cables globally and in various countries.

Uploaded by

Palade Cristi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 24

GLOBAL STANDARD Page 1 of 24

12/20(24) kV AND 18/30(36) kV COLD SHRINK TERMINATIONS GSCC005


FOR MV CABLES Rev. 3
09/07/2018

12/20(24) kV AND 18/30(36) kV COLD SHRINK TERMINATIONS


FOR MV CABLES

Countries I&N

Argentina C. Espinoza

Brazil R. Sales

Chile D. Sarkis

Colombia J. C. Gomez

Italy L. Giansante

Peru R. Sanchez

Romania V. Obrejan

Spain J. Gonzalez

Elaborated by Verified by Approved by

Global I&N – O&M/NCS L. Foddai N. Cammalleri M. Mazzotti

This document is intellectual property of ENEL Group distribution companies; reproduction or distribution of its contents in any way or by
any means whatsoever is subject to the prior approval of the above mentioned companies which will safeguard their rights under the civil
and penal codes. This document is for Internal Use.

Revision Data List of modifications


00 25/11/2015 First emission.
Material codes updated. Chapter on barcode updated, Painted or coated semiconducting
layer not allowed; New tests: expiration test, UV test for outdoor accessories; Modification
of requirements for resistance to fire; pin lugs eliminated, Modification of requirements of
01 23/02/2018 screen connecting plate; modification of requirements of tracking and erosion test. Class
24 kV for Italy and Rumania. Rated short time withstand current in the screen; Increase of
the minimum section of the earthing lug for Italy, Rumania, Spain and Peru from 16 to 25
mm2.
Revised tables 4, 5, 6, 7, 8, 9, 10 and 11. Expiration tests description. Paragraph on
02 25/05/2018
robustness test eliminated.
03 09/07/2018 Note on table 11. Revised material codes for Brazil.
GLOBAL STANDARD Page 2 of 24

12/20(24) kV AND 18/30(36) kV COLD SHRINK TERMINATIONS GSCC005


FOR MV CABLES Rev. 3
09/07/2018

Contents

1 SCOPE ........................................................................................................................................................................................ 4

2 FIELD OF APPLICATION ...................................................................................................................................................... 4

3 REFERENCE LAWS AND STANDARDS ............................................................................................................................. 4

3.1 International standards ..................................................................................................................................... 4

3.2 Global Standards ............................................................................................................................................... 4

3.3 Local standards.................................................................................................................................................. 5


3.3.1 Italy .................................................................................................................................................................. 5
3.3.2 Brazil ................................................................................................................................................................ 5
3.3.3 Chile ................................................................................................................................................................. 5
3.3.4 Colombia .......................................................................................................................................................... 5
3.3.5 Iberia ................................................................................................................................................................ 5

4 TERMS AND DEFINITIONS ................................................................................................................................................. 5

5 UNIT OF MEASURE ................................................................................................................................................................ 5

6 TYPES OF TERMINATIONS ................................................................................................................................................. 5

7 ELECTRICAL CHARACTERISTICS ..................................................................................................................................... 6

8 OVERALL DIMENSIONS ....................................................................................................................................................... 7

9 SERVICE CONDITIONS ......................................................................................................................................................... 9

9.1 General service conditions ................................................................................................................................ 9

9.2 Specific service conditions ................................................................................................................................. 9

10 CONTRUCTION CHARACTERISTICS ................................................................................................................................ 9

10.1 GENERAL CHARACTERISTICS ......................................................................................................................... 9


10.1.1 Shrink technology ....................................................................................................................................... 9
10.1.2 Resistance to corrosion, infiltrations, moisture and dust ........................................................................... 9
10.1.3 Heating ........................................................................................................................................................ 9
10.1.4 Resistance to fire ........................................................................................................................................ 9
10.1.5 Resistance to surface currents .................................................................................................................... 9
GLOBAL STANDARD Page 3 of 24

12/20(24) kV AND 18/30(36) kV COLD SHRINK TERMINATIONS GSCC005


FOR MV CABLES Rev. 3
09/07/2018

10.1.6 Materials compatibility ............................................................................................................................... 9

10.2 TERMINATIONS ............................................................................................................................................10


10.2.1 Shear bolt lug ............................................................................................................................................ 10
10.2.2 Component to control the electric field ................................................................................................... 12
10.2.3 Main insulating housing ............................................................................................................................ 13
10.2.4 Metallic screen earthing connection ........................................................................................................ 13
10.2.5 Greases and sealing compounds............................................................................................................... 15

11 CONTENT OF THE KIT ...................................................................................................................................................... 16

12 LIST OF COMPONENTS ..................................................................................................................................................... 16

13 TESTS...................................................................................................................................................................................... 21

13.1 GENERAL ......................................................................................................................................................21

13.2 TYPE TESTS ...................................................................................................................................................21


13.2.1 EXPIRATION TEST ...................................................................................................................................... 21
13.2.2 UV RESISTANCE TEST FOR OUTDOOR TERMINATION ............................................................................... 22
13.2.3 ADDITIONAL TYPE TESTS ........................................................................................................................... 22

13.3 ACCEPTANCE TESTS ......................................................................................................................................22

13.4 RETIE Certification (only apply to Enel Distribución Colombia) ....................................................................23

14 SUPPLY REQUIREMENTS ................................................................................................................................................. 23

14.1 LABELLING ...................................................................................................................................................23

14.2 PACKAGING .................................................................................................................................................23


14.2.1 Barcode (only for E-Distribuzione and Endesa Distribucion) .................................................................... 24
14.2.2 Identification label .................................................................................................................................... 24

14.3 INSTALLATION INSTRUCTIONS AND TEMPLATES ..........................................................................................24


GLOBAL STANDARD Page 4 of 24

12/20(24) kV AND 18/30(36) kV COLD SHRINK TERMINATIONS GSCC005


FOR MV CABLES Rev. 3
09/07/2018

1 SCOPE

This Global Standard applies to 12/20(24) kV and 18/30(36) kV indoor and outdoor cold shrink terminations
for MV cables with extruded insulation, both full and reduced insulating thickness, with copper wires or
aluminum tape screen.

These Global Standard applies to the Distribution Companies of Enel Group listed below:

Enel Distribución Colombia Colombia


Enel Distribución Perú Perú
Edesur Argentina
e-distributie Banat Romania
e-distributie Dobrogea Romania
e-distributie Muntenia Romania
e-distribuzione Italy
Endesa Distribución Eléctrica Spain
Enel Distribución Chile Chile
Enel Distribuição Ceará Brazil
Enel Distribuição Rio Brazil
Enel Distribuição Goiás Brazil

2 FIELD OF APPLICATION

These requirements apply to the underground and overhead distribution network with rated maximum voltage
of 24 kV and 36 kV. Other existing rated maximum voltage levels up to 24 kV are covered by the 12/20(24) kV
class, whereas those with rated maximum voltage up to 36 kV are covered by the 18/30(36) kV class.

3 REFERENCE LAWS AND STANDARDS

3.1 International standards


Unless otherwise specified the following standards applies:

 Cenelec HD 629-1;
 IEC 61238-1;
 IEC 60587;
 IEC 60695-11-10
 IEC 60721-2-1
 IEC 62217
 ISO IEC 17067

3.2 Global Standards


 GSC0011
 GSCC015

1 The characteristics of the cables are included in the Enel Group Global Standard. Besides installation on new
cables, which comply to GSC001, the termination may be installed on the existing network, which is made of
cables compliant to older local standards. Nevertheless, this Global Standard also takes into account the main
characteristics of existing cables for each Country (rated voltage, section and min/max diameter over
insulation).
GLOBAL STANDARD Page 5 of 24

12/20(24) kV AND 18/30(36) kV COLD SHRINK TERMINATIONS GSCC005


FOR MV CABLES Rev. 3
09/07/2018

3.3 Local standards

3.3.1 Italy
 DJ4580
 PVR 006
 GUI 101

3.3.2 Brazil
 NBR14643, Corrosão atmosférica – Classificação da corrosividade de atmosferas
 Nr-10, Segurança em Instalações e Serviços em Eletricidade

3.3.3 Chile
 NSEC 5
 NCH 4/2003

3.3.4 Colombia
 RETIE – Reglamento Técnico de Instalaciones Eléctricas

3.3.5 Iberia
 R.D. 614/2001, de 8 de junio, sobre disposiciones mínimas para la protección de la salud y seguridad
de los trabajadores frente al riesgo eléctrico.

 R.D. 337/2014, de 9 de mayo, por el que se aprueban el Reglamento sobre condiciones técnicas y
garantías de seguridad en instalaciones eléctricas de alta tensión y sus Instrucciones Técnicas
Complementarias ITC-RAT 01 a 23.

 R. D, 223/2008de 15 de febrero, por el que aprueba el Reglamento sobre condiciones técnicas y


garantías de seguridad en líneas eléctricas de alta tensión y sus instrucciones técnicas
complementarias ITC-LAT 01 a 09 (R.L.A.T.).

4 TERMS AND DEFINITIONS

See Cenelec HD 629-1.

5 UNIT OF MEASURE

Number of pieces.

6 TYPES OF TERMINATIONS

The following types of terminations are defined:


GLOBAL STANDARD Page 6 of 24

12/20(24) kV AND 18/30(36) kV COLD SHRINK TERMINATIONS GSCC005


FOR MV CABLES Rev. 3
09/07/2018

Rated voltage
Installation
Type code U0/U (Um) (kV)
12/20(24) 18/30(36) Indoor Outdoor
GSCC005/1 X X
GSCC005/2 X X
GSCC005/3 X X
GSCC005/4 X X
Table 1 – Type codes

7 ELECTRICAL CHARACTERISTICS

The following requirements apply:

Rated voltage U0/U (Um) (kV) 12/20(24) 18/30(36)


Rated power frequency withstand voltage (kV) 50 70
Rated impulse withstand voltage (kV) 125 170
Rated short time withstand current in the conductor (kA) According to HD629-1 (EN 61442)
Rated short time (0,5 sa) withstand current in the screen (kA) 5b; 10c
NOTE (see Table 7):
a: for E-distribuzione, E-distributie, Endesa Distribución Eléctrica the rated short time is 1 s
b: for 16 mm2 and 25 mm2 screen (all Distribution Companies except Enel Distribución Colombia)
c: for 25 mm2 screen (only for Enel Distribución Colombia) and 50 mm2 screen (all Distribution Companies
to which applies)
Table 2 – Electrical characteristics
The rated voltage levels of the cables for which is foreseen the installation of the terminations is the following:

Rated voltage of the termination U0/U (Um) (kV) 12/20(24) 18/30(36)


Distribution Company (Country) Rated voltage of the cables U0/U (Um)
(kV)
Enel Distribuição Ceará (Brazil)
8.7/15(17.5) -
Enel Distribución Colombia (Colombia)
Enel Distribución Chile (Chile) 8.7/15(17.5) 15/25(31)
Enel Distribución Perú (Perù) 8.7/15(17.5);
-
12/20(24)
Edesur (Argentine)
Enel Distribuição Rio (Brazil) 8.7/15(17.5) 18/30(36)
Enel Distribuição Goiás (Brazil)
Endesa Distribución Eléctrica (Spain) 18/30(36)
12/20(24)
12/20(24)*
E-distributie Banat (Romania);
E-distributie Dobrogea (Romania);
12/20(24) -
E-distributie Muntenia (Romania);
E-Distribuzione (Italy)
* Only for 200022
Table 3 – Rated voltage of the cables
GLOBAL STANDARD Page 7 of 24

12/20(24) kV AND 18/30(36) kV COLD SHRINK TERMINATIONS GSCC005


FOR MV CABLES Rev. 3
09/07/2018

8 OVERALL DIMENSIONS

With reference to Figure 1 and Figure 2, overall dimension of terminations are defined in Table 4:

Type GSCC005/1 GSCC005/2 GSCC005/3 GSCC005/4


Minimum creepage distance (mm) 420 600a 580 900
840b
Maximum height L (from first hole center of the 350 450 450 750
lug to the support axis) (mm)
Maximum diameter of sheds D (mm) 130 - 130 -
a apply to Enel Distribución Colombia (Colombia), Endesa Distribución Eléctrica (Spain), E-Distributie
Banat (Romania), E-Distributie Dobrogea (Romania), E-Distributie Muntenia (Romania), E-Distribuzione
(Italy);
b apply to Enel Distribuição Rio (Brazil), Enel Distribución Chile (Chile), Enel Distribuição Ceará (Brazil),
Enel Distribución Perú (Perù), Edesur (Argentine);
Table 4 – Overall dimensions for indoor and outdoor installation
GLOBAL STANDARD Page 8 of 24

12/20(24) kV AND 18/30(36) kV COLD SHRINK TERMINATIONS GSCC005


FOR MV CABLES Rev. 3
09/07/2018

L D

Support
(not included in the supply)

Figure 1 – Indoor termination

D
L

Support
(not included in the supply)

Figure 2 – Outdoor termination


GLOBAL STANDARD Page 9 of 24

12/20(24) kV AND 18/30(36) kV COLD SHRINK TERMINATIONS GSCC005


FOR MV CABLES Rev. 3
09/07/2018

9 SERVICE CONDITIONS

9.1 General service conditions


IEC 60721-2-1.
Severe ambient conditions according to IEC 60587.

9.2 Specific service conditions


For Enel Distribución Colombia (Codensa): the reference altitude is 2.700 m.

10 CONTRUCTION CHARACTERISTICS

10.1 GENERAL CHARACTERISTICS

10.1.1 Shrink technology


The terminations shall be cold shrink type2.

10.1.2 Resistance to corrosion, infiltrations, moisture and dust


The external surfaces of terminations shall be resistant to atmospheric conditions that can occur during normal
operation (moisture, dust, UV rays, etc.). The insulating body shall ensure non-infiltration of moisture and dust
and there shall be no standing water at the seals under normal conditions of installation.
The supplier shall provide appropriate documentation of the material used, the characteristics of aging, the
details of construction and assembly demonstrating the reliability of seals; the use of paints, enamels or similar
materials is not be considered sufficient to ensure the level of protection required.
Furthermore, special precautions must be taken to avoid the risk of corrosion resulting from contact of different
metals. All parts of ferrous material in contact with the air, including hardware, must be made of austenitic
stainless steel.

10.1.3 Heating
All the materials that make up the termination shall withstand the heating conditions expected during operation,
without having an adverse effect on their proper functioning of the termination or the cable.

10.1.4 Resistance to fire


The insulating housing (see 10.2.3) shall be resistant to fire.

10.1.5 Resistance to surface currents


The insulating housing (see 10.2.3) shall be resistant to surface currents.

10.1.6 Materials compatibility


All the component parts of the termination shall be made out of materials that can be in contact with each other
and with the parts that make up the cable, without having an adverse effect on their proper functioning. Greases
and sealing compounds, if any, shall be absolutely neutral in relation to the materials with which they are in
contact and shall remain stable in contact with air.

2 Slip-on type may be accepted as well.


GLOBAL STANDARD Page 10 of 24

12/20(24) kV AND 18/30(36) kV COLD SHRINK TERMINATIONS GSCC005


FOR MV CABLES Rev. 3
09/07/2018

10.2 TERMINATIONS
Terminations are composed by the following elements:

1. Shear bolt lug


2. Component to control the electric field
3. Main insulating housing
4. Metallic screen earthing connection
5. Greases and sealing compounds

Items 2 (component to control the electric field) and 3 (main insulating housing) of the above list shall be
assembled on the same single body.

It may be designed in order to ensure the following functions (e.g. through embedded sealing compounds):
 to seal the termination,
 to protect the junction of the metallic screen.

10.2.1 Shear bolt lug


The shear bolt lug shall be made of tin plated aluminum alloy suitable for both aluminum and copper cables
and shall be compliant with IEC 61238-1, Class A.
No additional hole (e.g. for inspection) shall be made. The shear bolts shall be made to break inside their
holes, assuring that no spike of any projection of material remain on the lug surface.

The lugs shall have a lock to assure the correct positioning of the conductor, even for the smaller sections.

The internal and external surface of the lugs shall not have sharp edges, spikes or deformities.

Lugs must be designed and constructed so that, when properly installed, the electrical resistance of the
connection is not greater than the equivalent resistance of the reference conductor.

It is allowed to use greases to improve the electrical contact between the lug and the cable conductor and
avoid corrosion as well as a sealing compound to fill screw cavities of the lug. In any case, the design of screw
cavities protection shall be so that no material is dispersed inside the termination during the cold shrinking
operation and/or in the installation.

10.2.1.1 Lugs for indoor terminations

10.2.1.1.1 Palm lugs


With reference to Figure 3, Table 5 reports the main characteristics and dimensions of the palm lugs for indoor
installation:
GLOBAL STANDARD Page 11 of 24

12/20(24) kV AND 18/30(36) kV COLD SHRINK TERMINATIONS GSCC005


FOR MV CABLES Rev. 3
09/07/2018

Figure 3 – Indoor lug


nº of
Cable section A C ØD
Ø B min E max F min G min H screws
(mm2) max max ± 0,2
min
35  95 28 13 27 13 105 8,5 12,5 1
95  240
38 19,5 37 13 130 9 14,5 2
150  240 (*)
400 45 26 42 13 ; 17a 170 12 18,5 2; 3a
630 47 29,6 45 13 173 20 22 3
a. apply to Enel Distribuição Rio (Brazil), Enel Distribuição Ceará (Brazil), Enel Distribuição Goiás (Brazil),
Enel Distribución Perú (Peru);
(*) The palm and the barrel shall be on a different quote (to be verified by visual inspection).
Table 5 – Indoor lugs dimensions (mm)
GLOBAL STANDARD Page 12 of 24

12/20(24) kV AND 18/30(36) kV COLD SHRINK TERMINATIONS GSCC005


FOR MV CABLES Rev. 3
09/07/2018

10.2.1.2 Lugs for outdoor terminations

10.2.1.2.1 Palm lugs


With reference to Figure 4, Table 6 reports the main characteristics and dimensions of the palm lugs for outdoor
installation:

Figure 4 - Outdoor lug


nº of
Cable section A ØD E
Ø B min C min F min G min M -0,5/+0 N -0/+1 screws
(mm2) max ± 0,2 max
min
35  95 28 13 20 13 143 8,5 12,5 32 45 2
95  240
38 19,5 33 13 168 13 14,5 32 45 2
150  240
400 45 26 40 13; 17a 208 15 18,5 32 45 2; 3a
630 47 29,6 45 13 200 20 20 44 - 3
a. apply to to Enel Distribuição Rio (Brazil), Enel Distribuição Ceará (Brazil), Enel Distribuição Goiás (Brazil), Enel
Distribución Perú (Peru);

Table 6 - Outdoor palm lugs dimensions (mm)

10.2.2 Component to control the electric field


It shall be applied on the insulation of the cable and connected to the external cable semiconductor.
GLOBAL STANDARD Page 13 of 24

12/20(24) kV AND 18/30(36) kV COLD SHRINK TERMINATIONS GSCC005


FOR MV CABLES Rev. 3
09/07/2018

10.2.3 Main insulating housing


The main insulating housing ensure the prescribed creepage distance (see Table 2).
Only for GSC005/4, the main insulating housing may be made of 2 (two) parts.

10.2.4 Metallic screen earthing connection

10.2.4.1 Earthing lug


The metallic screens of the cables shall be connected to earth by means of a tin plated copper palm straight
lug with a M12 screw hole, to be applied by compression with the tools indicated in Figure 5 or equivalent.
GLOBAL STANDARD Page 14 of 24

12/20(24) kV AND 18/30(36) kV COLD SHRINK TERMINATIONS GSCC005


FOR MV CABLES Rev. 3
09/07/2018

Figure 5 – Tool for compressing the earthing lug

The lug shall be suitable for connecting the metallic screen sections reported in Table 7. It shall be compatible
with both aluminum tape and copper wire cable screens.

The lug shall be supplied un-mounted and compressed on field.

Distribution Company (Country) Cable section (mm2) Earthing lug section


(mm2)
Enel Distribuição Rio (Brazil) ≤ 240 25
Enel Distribuição Ceará (Brazil)
Enel Distribuição Goiás (Brazil)
Enel Distribución Chile (Chile) 400 and 630 50
Enel Distribución Colombia (Colombia)
Enel Distribución Perú (Perù)
Endesa Distribución Eléctrica (Spain)
E-distributie Banat (Romania)
all sectionsa 25
E-distributie Dobrogea (Romania)
E-distributie Muntenia (Romania)
E-Distribuzione (Italy)

NOTE: for Edesur (Argentina) no earthing lug is required.


a: in those companies, MV cables could have aluminum tape screen or copper wire screens.

Table 7 – Earthing lug section

10.2.4.2 Cables with aluminum tape screen

In the case of cables with aluminum tape screen, the connection with the screen of the cable shall be made
by means of :

a) plate of tin-plated hard copper with a tin coating having minimum thickness of 0,5 m. The plate shall
be as shown in Figure 6 and shall be bent on a cylinder of diameter 25  2 mm; the convex side of the
plate shall include 65 asperities, arranged as shown in the Figure 6. These asperities shall have a
particular shape (see example in Figure 6) in order to allow piercing the aluminum tape, to obtain a
satisfactory contact with the screen, and to partly penetrate the outer thermoplastic sheath of the cable,
to prevent movement or removal of the device. The edge and the internal side of the plate shall be
free of sharp or rough parts, in particular in the lower side in contact with the semiconductive layer of
the cable. The lower side going under the aluminum tape shall have no protruding edge (an example
is shown in Figure 6) but a small rounded edge lower than the asperities.

b) A tin coated copper braid with a minimum length of 0,6 m. One end of the braid shall be welded to the
rectangular plate described above at the position shown in Figure 6; the other end shall be connected
to the lug described in 10.2.4.1. The section of the tin copper braid shall be compatible with the
sections prescribed in Table 7.
GLOBAL STANDARD Page 15 of 24

12/20(24) kV AND 18/30(36) kV COLD SHRINK TERMINATIONS GSCC005


FOR MV CABLES Rev. 3
09/07/2018

Figure 6 – Detail of rectangular plate for aluminum tape screen connection

10.2.4.3 Cables with copper wire screen


For cables with copper wires metallic screen, the earthing connection shall be made by collecting the copper
wires of the metallic screen and connecting them to the tin coated copper braid described in 10.2.4.2 b). In
order to do so, the braid shall be cut at the point of welding to the rectangular plate. The connection of copper
wires and the tin coated copper braid shall be made by means of the connector described in par. 10.2.4.3.1.

If the distance is sufficient, connection to earth could be made directly connecting the copper wires of the
screen to earth with the earthing lug described in 10.2.4.1.

10.2.4.3.1 Connector for copper wire screen


The copper wires of the metallic screen of the cable shall be connected to the tin coated copper braid described
in 10.2.4.2 b), by means of a compression straight connector with the tools indicated in or equivalent. The
section of the connector shall be compatible with the screen sections prescribed in Table 7.
The connector shall be supplied un-mounted and compressed on field.

10.2.5 Greases and sealing compounds


GLOBAL STANDARD Page 16 of 24

12/20(24) kV AND 18/30(36) kV COLD SHRINK TERMINATIONS GSCC005


FOR MV CABLES Rev. 3
09/07/2018

Sealing compounds are not allowed, except those:


 to seal the whole termination,
 to protect the junction of the metallic screen
 inside the lug screws cavities

Greases are not allowed, except those:


 over the main insulation of the cable and over the lug

Greases and sealing compounds shall have no electrical functions for the assembling of the termination but
only provide mechanical and/or sealing features.

11 CONTENT OF THE KIT

All the necessary elements and accessory to install the termination on-field shall be included, namely:

 1 (one) shear bolt lug (see 10.2.1)


 1 (one) component to control the electric field (see 10.2.2)
 1 (one) main insulating housing (see 10.2.3)
 1 (one) earthing lug (see 10.2.4.1)
 1 (one) plate for aluminum tape screen cables (see 10.2.4.2) (only in the Countries which use them,
see Table 7);
 1 (one) connector for copper wire screen (see 10.2.4.3.1)
 Greases and sealing compounds (see 10.2.5)
 Accessories for cleaning;
 Plastic bag for collecting residual materials of installation;
 List of materials;
 Installing instructions and templates (see 14.3);
 Identification label (see 14.2.2);
 Other materials, tools and accessories (according to supplier’s design).

12 LIST OF COMPONENTS

The list of components included in this Global Standard is reported in the following tables for 12/20(24) kV and
18/30(36) kV rated voltages:
GLOBAL STANDARD Page 17 of 24

12/20(24) kV AND 18/30(36) kV COLD SHRINK TERMINATIONS GSCC005


FOR MV CABLES Rev. 3
09/07/2018

Distribution Company (Country) Type: GSCC005/1


Enel Distribuição Rio (Brazil)
Enel Distribuição Ceará (Brazil) 6772090 6811850 6811851 6811852
Enel Distribuição Goiás (Brazil)
Enel Distribución Chile (Chile) 6811573 6812045 6812046 -
Enel Distribución Colombia (Colombia) 6811863 6811864 - -
Enel Distribución Perú (Perù) 6812293 6811502 6811483 -
Edesur (Argentine) - - - -
Endesa Distribución Eléctrica (Spain) 200026 270098 270099 -
E-distributie Banat (Romania);
E-distributie Dobrogea (Romania);
273055 273041 - -
E-distributie Muntenia (Romania);
E-Distribuzione (Italy)
Characteristics of the cable
Cable section (mm 2) 35 ÷ 95 95 ÷ 240 400 630
Rated voltage U0/U (Um) (kV) See Table 3
Min/max diameter over insulation (mm) 14.9/ 25.0 20.6/32.2 31/37.5 37.9/43.5
Table 8 – Material codes for cold shrink 12/20(24) kV indoor termination
GLOBAL STANDARD Page 18 of 24

12/20(24) kV AND 18/30(36) kV COLD SHRINK TERMINATIONS GSCC005


FOR MV CABLES Rev. 3
09/07/2018

Distribution Company (Country) Type: GSCC005/2


Enel Distribuição Rio (Brazil)
Enel Distribuição Ceará (Brazil) 6772085 6776450 6789739 6792743
Enel Distribuição Goiás (Brazil)
Enel Distribución Chile (Chile) 6811552 6812041 6812043 -
Enel Distribución Colombia (Colombia) 6811865 6811868 - -
Enel Distribución Perú (Perù) 6812294 6811484 6811485 -
Edesur (Argentine) - - - -
Endesa Distribución Eléctrica (Spain) 200024 270094 270095 -
E-distributie Banat (Romania);
E-distributie Dobrogea (Romania);
273056 273069 - -
E-distributie Muntenia (Romania);
E-Distribuzione (Italy)
Characteristics of the cable
Cable section (mm 2) 35 ÷ 95 95 ÷ 240 400 630
Rated voltage U0/U (Um) (kV) See Table 3
Min/max diameter over insulation (mm) 14.9/ 25.0 20.6/32.2 31/37.5 37.9/43.5
Table 9 – Material codes for cold shrink 12/20(24) kV outdoor termination
GLOBAL STANDARD Page 19 of 24

12/20(24) kV AND 18/30(36) kV COLD SHRINK TERMINATIONS GSCC005


FOR MV CABLES Rev. 3
09/07/2018

Distribution Company (Country) Type: GSCC005/3


Enel Distribuição Rio (Brazil)
- - - - - -
Enel Distribuição Goiás (Brazil)
Enel Distribución Chile (Chile) 6811574 6811575 6811576 6811534
Enel Distribución Colombia (Colombia) - - - - - -
Enel Distribuição Ceará (Brazil) - - - - - -
Enel Distribución Perú (Perù) - - - - - -
Edesur (Argentine) - - - - - -
Endesa Distribución Eléctrica (Spain) 200027 - - 270110 270111 -
E-distributie Banat (Romania);
E-distributie Dobrogea (Romania);
- - - - - -
E-distributie Muntenia (Romania);
E-Distribuzione (Italy)
Characteristics of the cable
Cable section (mm 2) 35 ÷ 95 95 ÷ 240 70 ÷ 150 150 ÷ 240 400 630
Rated voltage U0/U (Um) (kV) See Table 3
Min/max diameter over insulation (mm) 20.4/30.0 24.8/37.2 19.0/32.2 27.3/37.2 34.9/42.5 41.3/46.7
Table 10 – Material codes for cold shrink 18/30(36) kV indoor termination
GLOBAL STANDARD Page 20 of 24

12/20(24) kV AND 18/30(36) kV COLD SHRINK TERMINATIONS GSCC005


FOR MV CABLES Rev. 3
09/07/2018

Distribution Company (Country) Type: GSCC005/4


Enel Distribuição Rio (Brazil)
- - - - - -
Enel Distribuição Goiás (Brazil)
Enel Distribución Chile (Chile) - - 6811554 6811557 6811558 6811571
Enel Distribución Colombia (Colombia) - - - - - -
Enel Distribuição Ceará (Brazil) - - - - - -
Enel Distribución Peru (Perù) - - - - - -
Edesur (Argentine) - - - - - -
Endesa Distribución Eléctrica (Spain) 200025 200022 270096 270097
E-distributie Banat (Romania);
E-distributie Dobrogea (Romania);
- - - - - -
E-distributie Muntenia (Romania);
E-Distribuzione (Italy)
Characteristics of the cable
Cable section (mm 2) 35 ÷ 95 95 ÷ 240 70 ÷ 150 150 ÷ 240 400 630
Rated voltage U0/U (Um) (kV) See Table 3
Min/max diameter over insulation (mm) 20.4/30.0 24.8/37.2 19.0/32.2 27.3/37.2 34.9/42.5 41.3/46.7
20.6/32.2*
*Only for 200022
Table 11 – Material codes for cold shrink 18/30(36) kV outdoor termination
GLOBAL STANDARD Page 21 of 24

12/20(24) kV AND 18/30(36) kV COLD SHRINK TERMINATIONS GSCC005


FOR MV CABLES Rev. 3
09/07/2018

13 TESTS

13.1 GENERAL
Tests are classified into:

 Type tests
 Acceptance tests

They shall be carried out according to HD 629-1. Lugs shall be tested according to IEC 61238-1 class A.

13.2 TYPE TESTS


For each material code, type tests shall be carried out on a sample installed on cables with the maximum
section indicated in Table 8, Table 9, Table 10 and Table 11, respectively for Uo/U (Um) 12/20(24) kV indoor
and outdoor and 18/30(36) kV indoor and outdoor (e.g. 270096 shall be tested on a 240 mm 2 – 18/30(36) kV
cable and 270094 on a 240 mm2 12/20(24) kV cable).

For E-Distribuzione, E-Distributie Banat, E-Distributie Dobrogea and E-Distributie Muntenia, type tests shall be
carried out on both HPTE and XLPE insulated cables.

For Endesa Distribución code 200022 type tests shall be carried out using a 185 mm2 – 18/30(36) kV cable.

Type tests shall be carried out at the maximum rated voltage level prescribed for the termination (i.e. 12/20(24)
kV or 18/30(36) kV).

The lugs shall be tested both for their maximum and minimum section, according to IEC 61238-1, class A.

Insulating materials shall be tested for resistance to tracking and erosion according to IEC 60587, with 3.5 kV
test voltage.

The Supplier shall declare the resistance to fire of the main insulating housing according to IEC 60695-11-10
or another equivalent standard.

13.2.1 EXPIRATION TEST

An expiration test shall be performed in order to verify the capability of the termination to maintain its properties
during its life according to the expiry date declared by the manufacturer.
The test shall be performed of a new termination and on a termination of the same lot aged 7 days at 65°C in
oven in expanded stage (to simulate 2 years of storage at 35°C of mean temperature).

After ageing, the new termination and the aged termination are put in expanded stage at +5°C during 24h. After
that cooling phase, the terminations are installed on the minimum cross-section cable of their reference range.

Then, the following test sequence is applied:


GLOBAL STANDARD Page 22 of 24

12/20(24) kV AND 18/30(36) kV COLD SHRINK TERMINATIONS GSCC005


FOR MV CABLES Rev. 3
09/07/2018

Test Indoor termination Outdoor termination


(table 3 of HD 629-1) (table 4 of HD 629-1)
Partial discharge at ambient X (test n°4)
temperature
X (test n°3)
Immersion - X (test n°7)
Lightning impulse voltage test at X (test n°12)
ambient temperature
X (test n°10)
Power-frequency voltage tests X (test n°2) X (test n°2)
Partial discharge at ambient X (test n°4)
temperature
X (test n°3)
Visual inspection of water penetration X
-

13.2.2 UV RESISTANCE TEST FOR OUTDOOR TERMINATION


Outdoor terminations shall be tested according to the IEC 62217 2012 par 9.3.2 (1000 h).

13.2.3 ADDITIONAL TYPE TESTS


For each material code, the extension of compliance from maximum section to minimum section in the
reference range shall be verified on a cable having the minimum diameter over insulation (or lower) specified
in Table 8, Table 9, Table 10 and Table 11, by carrying out all the additional tests prescribed by HD 629-1,
table 10, taking into account that test No. 5 must be performed, additionally to prescribed conditions, also by
subjecting the samples to 63 cycles in water (to be performed according to HD 629-1, table 5, test No. 7).
Additional type tests shall be carried out at the maximum rated voltage level prescribed for the termination (i.e.
12/20(24) kV or 18/30(36) kV).

For E-Distribuzione, E-Distributie Banat, E-Distributie Dobrogea and E-Distributie Muntenia additional type
tests shall be carried out on both HPTE and XLPE insulated cables.

13.3 ACCEPTANCE TESTS


For each material code, acceptance tests shall be carried out using the smallest cable section (see Table 8,
Table 9, Table 10 and Table 11 for reference) for each rated voltage of the cable according to Table 3 (e.g.
270098 shall be tested on a 95 mm2 - 12/20(24) kV cable).
For Enel Distribución Peru acceptance tests shall be carried out using the smallest cable section with 12/20(24)
kV rated voltage3 (e.g. 6811484 shall be tested on a 95 mm2 – 12/20(24) kV).

Acceptance tests shall be carried out at the maximum rated voltage level prescribed for the cable (see Table
3).

The samples for the acceptance tests shall be selected from among the entire batch that was prepared for
testing even if made up of different material codes.

3 Tests performed on a 12/20(24) kV are considered sufficient to demonstrate compliance also for the
installation on a 8.7/15(17.5) kV cable with normal thickness insulation.
GLOBAL STANDARD Page 23 of 24

12/20(24) kV AND 18/30(36) kV COLD SHRINK TERMINATIONS GSCC005


FOR MV CABLES Rev. 3
09/07/2018

Batch (units)
Acceptance test
≤ 50 units > 50 and ≤ 1200 > 1200
Visual inspection 2 samples for each 5 samples for each 10 samples for each
Accessory manufacturing material code material code material code
specifications check* prepared for testing prepared for testing. prepared for testing.
Accessory assembly check
Power frequency withstand 1 sample for each 2 samples for each 3 samples for each
test material code material code material code
Partial discharge test at prepared for testing. prepared for testing prepared for testing
ambient temperature
* the nominal tightening torque of shear bolts specified by the manufacturer shall be always verified.
Table 12 – Samples for acceptance tests
In all cases, the acceptance number will be 0 and the rejection number will be 1.

On the scheduled acceptance testing date the supplier shall prepare the cables, stripped as required by the
assembly instructions of terminations being tested. This will facilitate the assembly of the termination and
reduce the testing time, which benefits both parties.

13.4 RETIE Certification (only apply to Enel Distribución Colombia)


For Enel Distribución Colombia (Colombia), RETIE certification shall be also provided according to local
regulation (see 3.3.4). It is requested that this certification be made under the scheme 5 (ISO IEC 17067).

14 SUPPLY REQUIREMENTS

14.1 LABELLING
The termination must bear the following information:
a) name of the manufacturer;
b) maximum voltage Um in kV
c) year and month of manufacture (e.g.: 15/2);

In particular, this information shall be placed on the external sheath of the terminations by means of indelible
and permanent screen printing or an equivalent method accepted by the Distribution Companies of Enel Group.

14.2 PACKAGING
Terminations shall be supplied in individual packages which shall bear the following information:
 Material code assigned by the Distribution Companies of Enel Group;
 name of the manufacturer;
 type of termination (e.g. cold shrink outdoor termination);
 type of cables for which the accessory is intended, section and conductive material allowed;
 year and month of packaging;
 progressive identification number assigned by the manufacturer (or serial number);
 barcode (only for E-Distribuzione and Endesa Distribucion, see 14.2.1);
 production batch number;
 identification abbreviation;
 maximum voltage Um in kV;
 expiry date (year/month) of the materials.
GLOBAL STANDARD Page 24 of 24

12/20(24) kV AND 18/30(36) kV COLD SHRINK TERMINATIONS GSCC005


FOR MV CABLES Rev. 3
09/07/2018

Furthermore, the packages shall contain a self-adhesive label with the following information (only for E-
Distribuzione and Endesa Distribucion):
 manufacturer identification code (CUI);
 material code assigned by the Distribution Companies of Enel Group;
 year and month of manufacture (e.g.: 15/2);
 progressive identification number (assigned by the manufacturer);
 barcode (only for E-Distribuzione and Endesa Distribucion, see 14.2.1)

For E-Distribuzione, shipping (of several individual packages) shall meet the requirements of the packaging in
compliance with GUI 101 specifications.

14.2.1 Barcode (only for E-Distribuzione and Endesa Distribucion)


The characteristics of the barcode are listed in E-Distribuzione specification PVR 006.

14.2.2 Identification label


It shall include blank fields to be filled after installation:

Name: ………………
Date: ………………
Company: ………………

14.3 INSTALLATION INSTRUCTIONS AND TEMPLATES


The instruction for the preparation of the cable shall be written in compliance with Enel Global Standard
GSCC015. For E-distribuzione the technical specification DJ4580 also applies.

Accessory assembly instructions shall be written on A4 paper, and the various stages of construction of the
termination shall be illustrated by photographs or diagrams in color.

Templates shall be included for the following types of cables:

• Extruded cables with aluminum tape screen (only for the Country listed in table Table 6)
• Extruded cables with copper wires screen

Furthermore, for processing steps that require the use of a special tool, the description of these operations
shall be accompanied by the Distribution Companies of Enel Group material code/type code4 for the tool and
a color photograph.

Additionally a QR code shall be included in the instructions to provide a web-link to demonstration videos and
tutorials on the related termination. They shall be in the local language of the Country of delivery.

Installing instruction and templates shall be in the local language of the Country of delivery and shall be
approved by Distribution Companies of Enel Group.