FE-1500-FX Tech Data Sheet
FE-1500-FX Tech Data Sheet
PCI CONTROLS
INCORPORATED
Technical Data Sheet
FE-1500-FX
DUCT
MOUNTED
AIRFLOW
MEASURMENT
STATION
DESCRIPTION Features
Low signal-to-noise ratio
The FE-1500-FX airflow measurement station consists of single or Multiple total and static pressure sensing
multiple airflow elements, factory mounted and pre-piped in a ports along the length of the element
casing designed for flanged connection to the ductwork. The Factory mounted and pre-piped in a flanged
station also incorporates an airflow straightening section using duct section (casing)
honeycomb having a ½ inch opening by 3 inch depth. Standard Honeycomb airflow straightening section
materials consist of a G90 galvanized casing, 6063-T5 anodized ±2% accuracy throughout the velocity rages
of 100 fpm and over
aluminum flow sensors, and 3003 aluminum airflow straightner. Standard construction includes a galvanized
casing, 6063-T5 anodized aluminum flow
The FE-1500-FX airflow measurement station has been developed sensors, and 3003 aluminum airflow
for use in duct systems having a highly turbulent condition at the straightner
point of measurement. The airflow averaging element, utilized in Available in optional corrosive or high
temperature resistance materials including
the FE-1500-FX, is a head type device, which generates a Type 304L and 316L stainless steel,
differential (velocity) pressure signal similar to the orifice, venture, Hastelloy C-22, Type 1 PVC, and phenolic
and other head producing primary elements. The FE-1500-FX is and polyurethane enamel coatings
constructed so that strategically located sensing ports (based on Standard airflow stations can be operated
(in air) continuously in temperatures up to
duct size) continually sample the total and static pressures, when 350oF or intermittently in temperatures up
inserted normal to flow. The total pressures sensed by the upstream to 400oF
ports are continually averaged within the element in an isolated All airflow stations can be operated in
chamber. The static sensing ports (located where the influence of humidity ranges of 0 to 100%
Standard airflow stations have good salt air
the velocity head is zero) are averaged in a second isolation resistance and are suitable for most HVAC
chamber. Multiple elements are manifolded together for connection applications
to a differential measurement device (gauge, transmitter, etc.) for
flow measurement and indication purposes.
PARAGON
PCI CONTROLS
INCORPORATED
2
PARAGON
PCI CONTROLS
INCORPORATED
Rectangular Stations
Standard rectangular airflow measuring stations include a 16 gage galvanized casing, 8 inches long, with formed integral 90°
connecting flanges as listed below:
Oval Stations
Standard oval airflow measuring stations include a 18 gage galvanized casing, 8 inches long between beads with 1 inch connecting
sleeve on each end (10 inch overall length). Actual O.D. dimensions are ¼ inch less than specified duct I.D. dimensions.
3
PARAGON
PCI CONTROLS
INCORPORATED
FE-1500-FX Dimensions
Circular Stations
L" "F"
TOTAL PRESSURE
(T.P.) TAKEOFF
AIRFLOW
STATIC PRESSURE
"D"
(S.P.) TAKEOFF
3.250"
AIR STRAIGHTNER
Rectangular Stations
8.000"
"F" "W"
STATIC PRESSURE
AIRFLOW
(S.P.) TAKEOFF
"H"
TOTAL PRESSURE
(T.P.) TAKEOFF
3.250"
AIR STRAIGHTNER
4
PARAGON
PCI CONTROLS
INCORPORATED
STATIC PRESSURE
(S.P.) TAKEOFF
AIRFLOW
"H"
"L"
"W"
"L" + 212"
AIR STRAIGHTNER
FLOW FLOW
FLOW FLOW FLOW
D D/6
D
15° MAX 30 DEGREE MAXIMUM
D/6 TRANSITION ANGLE
D/4 4D D/6
2D D/2 D/6
D/4 2D 2.5D D D/2
D/2
Notes:
Round Ducts: Rectangular Ducts:
4 HW
D= Duct diameter D= H= Height W= Width
π
5
PARAGON
PCI CONTROLS
INCORPORATED
1000
100
0.001 0.01 0.1 1
Pre s s ure Drop (inche s w ate r colum n)
Protective Coatings
0 = No Coating
1 = Heresite VRL 500 phenolic coating
2 = Imron 333 polyurethane enamel
Element Material
A = 6063-T5 anodized aluminum (standard)
S = Type 316L stainless steel
P = Type 1 PVC
H = Hastelloy C22
Casing Material
1 = 16 ga G90 galvanized steel (standard)
2 = Type 304L stainless steel
3 = Type 316L stainless steel
4 = Hastelloy C22 (optional)
6
PARAGON
PCI CONTROLS
INCORPORATED
7
PARAGON
PCI CONTROLS
INCORPORATED
2
Where:
Q ⎛V ⎞ V = Velocity, in fpm C = 1096.7
V= PV = ⎜ ⎟ × ρ Q = Flow, in cfm ρ= Density of air, in lb/ft3
A ⎝C ⎠
A = Area, in ft2 PV = Velocity pressure, in inches H2O