HDL® BACNet Manual
1. Introduction
HDL-Bacnet module is a Bacnet HDL Data convertor, it can realize the control from
Bacnet system to HDL-BUS system.
Bacnet HDL-BUS
Data convertor
RJ45 BACNet system
( the manual is based on
BACNet client app )
HDL-BUS
………
.
2.HDL-BUS
HDL-Bacnet module configuration instruction
Relay Dimmer Sensor DLP Panel
HDL-BUS system devices should be setup inside HDL-BUS configuration software when
controlled by Bacnet client. Open HDL-BUS configuration software, search and set
parameters of the HDL-Bacnet module.
2.1 Basic information setting
0
HDL® BACNet Manual
HDL-Bacnet convertor embedded HDL-BUS IP
gateway function, need to set Ethernet
parameters firstly
Attention: the IP address of Ethernet parameters should be in the same Ethernet
segment with Bacnet client.
2.2 Parameters setting
Select to enable IP switch function
Default value, fixed
Control target ,
Maximum 150
(1) (2) (3) (4) (5)
(1) Bacnet ID includes different types: AI, AO, AV, BI, BO, BV, MI, MO, MV, other, not much
differences between different types, but for the convenience of management by client.
The value of ID is control point, it is user-defined, cannot be duplicate.
(2) The Hex value is auto generated according Bacnet ID type and ID value
(3) type of control target, It indicates the type of HDL-BUS controlled targets
(4) ID of HDL-BUS controlled devices.
(5) the parameter of controlled target, all supported parameters up to now, refer to below
table
1
HDL® BACNet Manual
3. Example setting
Take example of control the third ch of relay module
parameters setting in HDL-BUS configuration software:
Control ID of relay Controlled Remarks
target type module channel
Corresponding Setting in Bacnet client:
Double click to type the vale
Control target
Type 100, switch on the channel
Type 0, switch off the channel.
Addendum: supported parameter type and parameter settings
Configuration tab BACnet control parameters
2
HDL® BACNet Manual
HDL control BACNET WP Present Value
Parameter 1 Parameter 2
type definition and validation scope
0invalid switch xxx xxx invalid
Area Scene No.: 0-12
Scene control Device Area No. N/A “0” means switch off Scene,1-
12 is Scene No.
Sequence
Device Area No. N/A Area Sequence No.: 1-6
control
universal switch Switch No. N/A Switch status: 1: on, 0: off
single channel Device channel adjustment Intensity value of ch: 0-100
lighting No. time 0: off, 100: on
time switch Channel No. N/A Switch status: 1: on, 0: off
Curtain switch status: 0: stop,
curtain switch Curtain No. N/A
1: open, 2: close
Command Status: 0: invalid,
GPRS control Command No. N/A
1: SMS, 2: remote
Panel control IR Receiving
N/A 1: enable 0: disable
enabling
Panel locking N/A 1: lock 0: unlock
AC switch N/A 1: on 0: off
temperature value setting scope:
cooling
N/A 0-30 degree Celsius
temperature of AC
degrees Fahrenheit 32-86
0: Auto, 1: high,
Fan speed of AC N/A
2: Medium 3: low
0: cooling, 1: heating
AC mode N/A 2: Ventilaiton, 3: Auto,
4: dehumidification.
temperature value setting scope:
Heating
N/A 0-30 degree Celsius
temperature of AC
degrees Fahrenheit 32-86
temperature value setting scope:
Auto temperature
N/A 0-30 degree Celsius
of AC
degrees Fahrenheit 32-86
increase Temperature increasing Value :(1-
N/A
temperature 5℃/℉)
decrease Temperature decreasing Value :
N/A
temperature (1-5℃/℉)
Backlight switch N/A 1: on 0: off
AC locking N/A 1:lock 0:unlock
Backlight intensity N/A Backlight intensity value (0-100%)
3
HDL® BACNet Manual
status indicator Status indicator intensity value (0-
N/A
intensity 100%)
button shielding of
Button No. 0: shielded,1: unshielded
panel
page shielding of
Page No. 0: shielded,1: unshielded
panel
temperature value setting scope:
dehumidification
N/A 0-30 degree Celsius
temperature of AC
degrees Fahrenheit 32-86
heating switch N/A 0: off,1: on
Mode: (5: time,4: leaving mode,
Heating mode N/A
3: night, 2: daytime,1: normal)
increase heating Temperature increasing Value :(1-
N/A
temperature 5℃/℉)
decrease heating Temperature decreasing Value :
N/A
temperature (1-5℃/℉)
setting page
panel control N/A 1: lock 0: unlock
locking
broadcast scene All areas(255) N/A Scene No.: 0-12
broadcast All
N/A Intensity of light ch: 0-100
channel Channel(255)
Security modes(1-6):01:
Security Area Vacation, 02: leaving, 03: night,
Security module N/A
(1-8) 04: night party, 05: daytime,
06: disalarm