Reactive Capability Limitations of Doubly Fed Induction Generators
Reactive Capability Limitations of Doubly Fed Induction Generators
Reactive Capability Limitations of Doubly Fed Induction Generators
To cite this article: Bharat Singh & S. N. Singh (2009) Reactive Capability Limitations of Doubly-
fed Induction Generators, Electric Power Components and Systems, 37:4, 427-440, DOI:
10.1080/15325000802548905
Abstract In the new electricity grid code, reactive power generation by wind farms,
which must operate similarly to other conventional power plants, is a major concern
during both steady-state and fault conditions. This article presents the reactive power
capability of a doubly-fed induction generator through the use of performance capa-
bility curves. First, three steady-state models of doubly-fed induction generators are
derived in terms of (i) stator and rotor voltage (V S and V R ), (ii) stator voltage and
rotor current (V S and I R ), and (iii) stator voltage and stator current (V S and I S ),
to derive the limitations in the reactive power production caused by the rotor voltage,
rotor current, and stator current limits, respectively. Second, the reactive power
capability of the grid-side converter is included. Finally, a complete capability curve
of doubly-fed induction generators for stator voltages is developed by optimization of
rotor speed employing the maximum power point tracking algorithm. It is established
that the total reactive power production is limited by the rotor voltage limit for large
slips and then by rotor current limit, and the total reactive power consumption is
limited by the stator current limit for the entire operating region of the optimized slip.
The capability curve of the unified doubly-fed induction generator scheme is also
presented in this article.
1. Introduction
Wind power, which has been proved to be a potential source for generation of electricity
with minimal environmental impact, is the fastest-growing source for electric power
generation, and it is expected to remain so in the future. At the end of 2007, the wind-
installed capacity stands at over 94,112 MW worldwide, which is more than 20 GW from
the capacity in 2006 [1]. With the advancement of aerodynamic designs, wind turbines
can capture several megawatts of power, and this substantial amount of wind power can
supplement the base power demand when such wind energy conversion systems (WECSs)
are integrated into the grid.
Due to large penetration and mature technology, wind farms must fulfill almost
the same requirements as conventional power plants. According to new grid codes, wind
farms have to supply not only active power, but also to supply/consume the reactive power
to/from the grid. The requirements are defined with respect to the power factor as a func-
tion of the voltage at the point of common coupling (PCC) with the main grid. Thus, the
reactive power management becomes an integral issue in the grid-connected wind farms.
Received 23 April 2008; accepted 15 September 2008.
Address correspondence to Bharat Singh, Department of Electrical Engineering, Indian
Institute of Technology, Kanpur, U.P., 208 016, India. E-mail: [email protected]
427
428 B. Singh and S. N. Singh
Nomenclature
CPOPT power coefficient at optimal tip-speed ratio (TSR)
K! wind-turbine-dependent coefficient
LM magnetizing inductance
LS , LR stator and rotor inductance, respectively
LS , LR stator and rotor leakage inductance, respectively
PE , QE total active and reactive power supplied to grid, respectively
PMOPT power at optimal TSR
PR , QR rotor active and reactive power, respectively
PS , QS stator active and reactive power, respectively
QGSC grid-side converter reactive power
R rotor radius
s slip
V S, IS, S
stator voltage, current, and flux linkage phasors, respectively
V R, I R, R
rotor voltage, current, and flux linkage phasors, respectively
ı phase angle between stator and rotor voltage
phase angle between stator voltage and rotor current
MOPT optimal TSR
AIR air density
phase angle between stator voltage and current
!M rotational speed
!S , !R stator and rotor angular frequency, respectively
power capability from the GSC is derived and included. Finally, a complete P-Q diagram
of a DFIG is developed by optimization of rotor speed employing the maximum power
point tracking (MPPT) algorithm. The effect of stator voltage variation on capability
curves is also demonstrated.
Voltage equations:
V s D j!S S
; (1)
V r D RR I R C j.!S !R / R
: (2)
Flux equations:
S
D LS I S C LM I R ; (3)
R
D LR I R C LM I S ; (4)
The equivalent circuit corresponding to Eqs. (5) and (6) is illustrated in Figure 2.
PS C jQS D 3V S I S : (7)
Reactive Capability of Induction Generators 431
By eliminating the stator currents in Eq. (7) and using Eq. (5), we obtain
LM Vs
PS C jQS D 3V S j I R : (8)
LS LM !S
Let ı be the power angle taken between V S and V R . On solving for IR using Eqs. (5)
and (6), we get
LM
0 1
B VR .cos ı C j sin ı/ s LS Vs C
IR D B C .RR js!S LSC /; (9)
@ RR2 C .s!S LSC /2 A
L2
where LSC D .LR LMS /.
On eliminating I R from Eq. (8) using Eq. (9) and separating out the real and
imaginary parts, the expressions of the stator side active and reactive powers in terms of
stator and rotor voltages only, are obtained as
0 1
2
LM sRR LM B sin.ı C ıK /
PS D 3VS2 3VS VR A (10)
C
LS 2 2 LS
@q
RR C .s!S LSC / RR2 C .s!S LSC /2
and
!
3VS2 .s!S LM /2 LSC
LM cos.ı C ıK /
QS D 1C 2 3VS Vr p I (11)
!S LS RR C .s!S LSC /2 LS Rr2 C .swLSC /2
i.e.,
PS D asynchronous active power C synchronous active power, and
QS D absorbed reactive power with short-circuited rotor C synchronous reactive power,
The total active power (PE ) supplied from the DFIG to the grid is the sum of power
supplied from the stator to the grid (i.e., PS ) and the power exchanged with the converter
at the rotor slip rings (i.e., PR ). The total reactive power (QE ) exchanged between the
DFIG and the grid is equal to the reactive power in the stator, i.e., QS . Here, it is assumed
that the GSC exchanges active power only with the grid and usually operates at a power
factor equal to one, i.e., QGSC D 0. Later, in section 6, the reactive power capability of
the GSC will also be considered. Now, PE and QE can be given as
PE D PS C PR ; (14)
QE D QS : (15)
432 B. Singh and S. N. Singh
CPOPT 3
PMOPT D 0:5AIR R5 … 3
!M D K! !M ; (26)
M
OPT
where
Figure 4. P-Q curves for constant rotor voltage magnitude for different values of slip (VS D 1 p.u.,
VR D 0:3 p.u.).
Figure 5. P-Q curves for constant rotor current magnitude for different values of slip (VS D 1 p.u.,
IR D 1 p.u.).
Reactive Capability of Induction Generators 435
Figure 6. P-Q curves for constant stator current voltage magnitude for different values of slip
(VS D 1 p.u., IS D 1 p.u.).
the equal values of positive and negative slips. Nose points depict the maximum values
of the total power output of the DFIG for a given slip. Moreover, the real power output
is more for the negative slip compared to the same value of the positive slip.
P-Q curves for rotor current limitation during the optimized slip are calculated using
Eqs. (19) and (20) for variation in angle , as shown in Figure 5. It can be seen from
Figure 5 that total real power output of the DFIG decreases with a decrease in the slip.
P-Q curves for constant stator current limitation during the optimized slip are
calculated using Eqs. (24) and (25) for variation in angle ˆ, as shown in Figure 6.
The capability curve for the DFIG is obtained by calculating the minimum absolute
value of the limiting curves of three variables—i.e., rotor voltage, rotor current, and
stator current—for the entire operating region of the optimized slip, as shown in Figure 7.
Figure 7 shows the capability curve of a DFIG whose parameters are given in Appendix A.
It can be seen that the DFIG absorbs reactive power at low power generation. The
reactive power generation at a lower slip is limited by rotor current, whereas absorption
of reactive power is limited by stator current. Maximum reactive power generation is
always less than the maximum reactive power absorption at any power output of a DFIG.
The maximum real power output is limited by mechanical power limit constraints.
where VGSC and IGSC are AC side voltage and current of the GSC.
436 B. Singh and S. N. Singh
Figure 7. Capability curve of DFIG for entire operating region of optimized slip.
The rating of the converter is limited due to speed range and, hence, to the slip power.
In this work, ˙30% speed range is assumed as the converter rating is approximately 30%
of the DFIG stator rating. At VGSC D VS D 1 p.u., the reactive power capability supplied
by the GSC will be limited by the current rating of the converter, i.e., IGSC .
Depending on the operating conditions, the reactive power capability of the GSC may
vary from the maximum positive slip to the maximum negative slip values. At s D sMAX ,
QGSC will be equal to 0 p.u., and at s D 0, QGSC will be maximum in magnitude
(˙sMAX p.u.). From Eq. (27), it can be seen that QGSC is dependent on the rotor power
(PR ). If the rotor power is large (for large absolute values of slips), the capability of the
GSC to supply reactive power is less and vice versa. Hence, significant reactive power
support to the grid can be provided by the GSC during the low absolute values of the slip.
PE D PS C PR ; (28)
QE D QS C QGSC : (29)
Figure 8. Complete capability curve of DFIG considering reactive power capability of GSC.
Considering GSC reactive power, the limit for total reactive power production
always remains positive (Figure 8 only) for the complete operating region of the
optimized slip.
Without GSC reactive power support, the DFIG cannot produce reactive power at
high slip.
During the complete operating region of the optimized slip, rotor power (PR )
remains considerably small, and hence, the reactive power capability of the GSC
can be utilized.
During normal and abnormal conditions, the GSC (termed a parallel GSC [PGSC])
facilitates the normal power processing capabilities for both sub-synchronous and super-
synchronous modes of operation of the DFIG. During normal operating conditions,
the SGSC facilitates only reactive power capability, and during abnormal conditions, the
SGSC injects series voltage and phase angle for necessary compensation required for
secure and stable operation. The SGSC is sized to meet the desired reactive power
capability, enabling it to ride through the worst conditions. In both normal and extreme
conditions, the SGSC provides reactive power injection to the grid [10].
Utilization of an extra converter with associated controls and transformer will in-
crease the cost of whole system, but at the same time, it will facilitate the low voltage
ride-through (LVRT) capability and additional reactive power support. The cost of the
converter depends on the rating; hence, the rating of the SGSC must be chosen wisely
for economical operation. In this article, the rating of the SGSC is taken as 15% of the
DFIG stator rating.
In this section, only static performance, such as injection/absorption of reactive power
to/from grid during abnormal/normal conditions, is discussed. The dynamic performance
achieved with the series injection scheme is not explored. For reactive power support,
the injection of series voltage must be in phase quadrant with the stator (or line)
current. Hence, the injection of series voltage will not change the stator terminal voltage
substantially. Stator terminal voltage will always be the addition of grid voltage and series
injected voltage. The capability curve for UA, as shown in Figure 11, can be obtained by
adding the reactive power from the SGSC. It is assumed that stator voltage (VS ) remains
constant and equal to 1 p.u.
10. Conclusions
With the increased installation of large DFIG wind turbines, in the system having a new
electricity grid code where a wind power generator must fulfill the same requirements
as conventional power plants, it is necessary to develop a reactive power capability limit
constrained by machine operating limits. The main operating limits of a DFIG are the
rotor voltage, rotor current, and stator current.
It is observed that total reactive power production is limited by the rotor voltage limit
for large slips and then by rotor current limit. The total reactive power consumption is lim-
ited by the stator current limit for the entire operating region of the optimized slip. Also,
during the operating region of the optimized slip, the rotor power (PR ) remains consider-
ably small, and hence, the reactive power capability of the GSC can be utilized. The reac-
440 B. Singh and S. N. Singh
tive power capability of a unified DFIG having three converters is investigated. It is found
that during steady state, the converter can be utilized to provide the required capability.
Acknowledgment
The financial support obtained from the CPRI (Project No. CPRI/EE/20070101), Banga-
lore, India, is greatly acknowledged.
References
1. Global Wind Energy Council, available at: http://www.gwec.net.
2. Tapia, A., Tapia, G., Ostolaza, J. X., and Saenz, J. R., “Modeling and control of a wind
urbine driven doubly fed induction generator,” IEEE Trans. Energy Conversion, Vol. 18, No. 2,
pp. 194–204, June 2003.
3. Mustafa, K., and Milanovic, J. V., “Reactive power control strategies for DFIG-based plants,”
IEEE Trans. Energy Conversion, Vol. 22, No. 2, pp. 389–396, June 2007.
4. Lund, T., Sørensen, P., and Eek, J., “Reactive power capability of a wind turbine with doubly
fed induction generator,” Wind Energy, Vol. 10, No. 4, pp. 379–394, July/August 2007.
5. Peterson, A., Analysis Modeling and Control of Doubly-Fed Induction Generators for Wind
Turbines, Ph.D. Thesis, Chalmers University of Technology, Goteborg, Sweden, 2005.
6. Boldea, I., Variable Speed Generators, Boca Raton, FL: CRC Press, 2006.
7. Akhmatov, V., “Variable-speed wind turbines with doubly-fed induction generators Part 1:
Modelling in Dynamic Simulation Tools,” Wind Eng., Vol. 26, No. 2, pp. 85–108, March 2002.
8. Datta, R., and Ranganathan, V. T., “Variable-speed wind power generation using doubly fed
wound rotor induction machine—a comparison with alternative schemes,” IEEE Trans. Energy
Conversion, Vol. 17, No. 3, pp. 414–421, September 2002.
9. Flannery, P., and Venkataramanan, G., “A grid fault tolerant doubly fed induction genera-
tor wind turbine via series connected grid side converter,” WINDPOWER 2006 Conference,
Pittsburgh, PA, 4–7 June 2006.
10. Singh, B., Emmoji, V., and Singh, S. N., “Performance evaluation of series and parallel
connected grid side converters of DFIG,” IEEE PES General Meeting 2008, Pittsburgh, PA,
20–24 July 2008.
Appendix A
Parameters of simulated DFIG