Pamphlet On - Measurement of Soil Resistivity
Pamphlet On - Measurement of Soil Resistivity
Pamphlet On - Measurement of Soil Resistivity
CAMTECH/E/2021-22/EP-01/Soil Resistivity/1.0
June, 2021
• The measure of the resistance offered by the soil in the flow of electricity is
called the soil resistivity. The resistivity of the earth varies within extremely
wide limits, between 1 and 10000 ohm meters.
• Soil resistivity plays a vital role in the design of an earthing system. For
safety at substations i.e. the touch and step potentials are greatly influenced
by soil resistivity.
• The resistance to earth of a given electrode also depends upon the resistivity
of the soil in which it is installed. The flow of current into the grounds
depends on the resistivity of the soil in which the earth electrode is placed.
• For example, as per para 14.2.2 of IS 3043 : 2018, the resistance of a pipe or
rod electrode is given by:
Where,
ρ = resistivity of the soil, in Ω-m (assumed uniform),
l = length of rod or pipe, in cm, and
d = diameter of rod or pipe, in cm,
• The soil resistivity is affected by the moisture content of the soil, chemical
composition, concentration of salts dissolved in the contained water and
other factors like grain size, distribution, and closeness of packing etc.
Many of these factors vary locally and some seasonally so that the table
should only be taken as a general guide. Therefore, local values of soil
resistivity should be verified by actual measurement of soil resistivity.
• The soil resistivity varies over a wide range depending on its moisture
content. It is, therefore, advisable to conduct earth resistivity tests during
the dry season in order to get conservative results.
The types of soil largely determines its resistivity and examples are given in below table:
(Table 3 of IS 3043:2018.)
Sr. Type of soil Probable Climate Condition
No. value of
resistivity Normal and high Low rainfall and Underground
Ω.m rainfall (for desert condition waters
Example, Greater (for example, (Saline)
than 500 mm a less than 250
year) mm a year)
vii. Clay slates and slatey 1000 300 to 3000 1000 upwards 30 to 100
shales
This is a simpler test than the full Wenner’s test and may be used for
distribution substations. When this method is used at the planning stage the
rod may be installed in a position where it can be included in the final
electrode installation.
3.1 Test Procedure
Drive a single earth rod into the ground for a known depth (a depth of 2.4 m
is sufficient for most distribution substations) as shown below in fig. 3.
Make the connection as shown below using three terminal resistance meter (or
4 terminals with C1 and P1 shorted).
Where
R = the resistance to earth of a vertical rod,
L = the length of the electrode, in meters (m),
d = the diameter in meters (m),
ρ = the resistivity of the soil (assumed uniform), in ohm meters (Ω.m)
Hence,
The soil resistivity measured using above formula gives the average
value.
The soil resistivity measured using above formula gives the average
value. If it is difficult to drive 2.4 meter earth rod to its full depth, it is
an indication that there is a layer of high resistivity ground below the
immediate surface. In this case wenner’s four point method is suitable.
The most popular and user friendly method is Wenner’s Four Point
Method. This is done without any excavation, by injecting a current and
measuring the voltage drop at different spacing. Wenner’s method is more
time consuming than the “One Rod Method”. But it is helpful to decide on
deep or shallow earths when conditions are difficult.
Material Required:
One four-terminal earth megger with four rods (electrodes) & connecting
leads with clamps.
Fig.3: Eight equally spaced directions from the center of the site
Figure: 5
Generally, the earth tester used for these tests directly read the resistance (R).
The resistivity may be calculated from the equation as given in table below:
If spacing between the rods (s) is If spacing between the rods (s) is less than
more than 20 times of depth of 20 times of depth of burial (e) i.e. s < 20e
burial (e) i.e. s > 20e
For example, if spacing between the rods (s)
(In this depth of burial of the is 300 cm and depth of burial (e) is more
electrodes (e) in the ground is than 15 cm, below formula to be used:
negligible compared to the
spacing (s) between the
electrodes)
For example, if spacing between
the rods (s) is 300 cm and depth of
burial (e) is less than 15 cm,
below formula to be used:
Where
Plot a closed curve on the graph sheet jointing all the resistivity points
plotted to get the polar resistivity curve as shown in fig. 5 (Green).
Measure the area inside the polar resistivity curve and find out the
equivalent circle (fig. 5 Blue) of the same area. The radius of this
equivalent circle is the average resistivity of the site under
consideration.
The average resistivity thus obtained may be
used for the design of the earthing grid and
other computations and the results will be
reasonably accurate when the soil is
homogeneous.