Thermodynamics Lab1
Thermodynamics Lab1
Refrigeration System
Engineering Thermodynamics
Nazarbayev University
53, Kabanbay batyr Ave.,
Astana, 010000, Kazakhstan
Prepared by
Ilyas Ibragimov
Aisar Abdrakhmanov
Saltanat Yermakhanova
Elmira Kadyrova
Zhanibek Maratov
Alina Abdikadyr
Engineering Thermodynamics
2
Table of contents
Summary 2
1 Introduction 3
3 Experimental Procedure 4
3.1 Experimental Procedure A 6
3.2 Experimental Procedure C 6
3.3 Experimental Procedure D 7
3.4 Experimental Procedure F 7
5 Result Description 7
5.1 Result Description A 7
5.2 Result Description C 8
5.3 Result Description D 12
5.4 Result Description F 14
6 Discussion and Engineering Analysis of Results 15
6.1 Discussion A 15
6.2 Discussion C 16
6.3 Discussion D 16
6.4Discussion F 17
7 Conclusions & Recommendations 17
7.1 Conclusion A 17
7.2 Conclusion C 18
7.3 Conclusion D 18
7.4 Conclusion F 19
3
1. Introduction
Refrigeration cycle is the one of the widely used basic processes in thermodynamics. To
examine various thermodynamic properties we need to carry out numerous experiments using a
refrigeration cycle. In this particular laboratory work we use the RA1 refrigeration unit which is
process variables using an integral USB interface device. We can break down this system to four
core components: condenser, expansion valve, evaporator and compressor. In condenser vapour
refrigerant condenses to liquid through heat transfer to the cooler surroundings. After that, this
liquid refrigerant expands to the evaporator pressure in the expansion valve. Then, in the
relatively high temperature and pressure, requiring work input from outside and completes the
thermodynamic cycle.
driven by a three-phase electric motor with an inverter drive. Due to implemented Torque Vector
Control in the inverter, speed and the torque of the motor can be measured and logged by PC.
Temperature, pressure and refrigerant flow rate can also be measured and logged. Both
condenser and evaporator consist of brazed plate heat exchangers. To minimize changes in water
temperature a large reservoir of water is utilized by both condenser and evaporator. Operators
can set the speed of the flow of water through each exchanger using the PC. RA1 unit requires
only connection to electrical supply and a PC, in other aspects this unit is self-contained.
4
Figure 1: View of a Computer screen using PC Software
5
2. Experimental procedure
Experimental procedure A
1. Set the condenser water pump and evaporator water pump to 50% and 70%
respectively.
2. Check FM1 and FM2 on the RA1 unit to ensure there is flow of water through
3. Set the speed of the compressor motor to 80% and check FM3 to ensure that
5. Configure the sample options as ‘manual’ and click the “GO” button to log the
6. Verify that all readings have been logged by looking at the table of results.
Experimental procedure C
1. Set the condenser and evaporator water pump speeds to 100% and 70%
respectively
2. Check that flow rates through the condenser (FM1) and evaporator (FM2) are
3. Set the compressor motor speed to 80% and run the system until the temperatures
4. For each iteration, reduce the speed of the condenser water pump by 5%
6
Experimental procedure D
1. Set the condenser water pump speed and evaporator water pump to 50% and 70%
respectively.
2. Check that flow of water through the condenser (FM1) and evaporator ( FM2) are
3. Set the compressor motor speed to 100%. Check the area flow meter FM3 to ensure that
4. Let the system run until the temperature and pressure become stable.
6. When the refrigerant flow rate becomes irregular, return the compressor speed to 80%
Experimental procedure F
1. Using the data from experimental procedure A analyse the performance of the
refrigeration system.
3. Results
Results A
7
T7, [°C] 3.0
Results C
𝑄𝑖𝑛
𝐶𝑂𝑃 = 𝑊
(1)
𝑄 = 𝑚 × 𝑐 × (𝑇2 − 𝑇1) (2
4.3
𝑚(𝑘𝑔/𝑠) = 60
(𝑙/𝑠) × 1. 203(𝑘𝑔/𝑙) = 0. 086215 𝑘𝑔/𝑠
*The same calculations are used for sample numbers from 2 to 18.
8
2 2.6 17.1 920.3 226.8 4.06 0.0882 1088.591 4.7998 4.4
9
Fig.3 Flow rate (l/min) vs Time (min)
10
Fig.5 Coefficient of performance vs Flow rate (l/min)
11
Results D
Table 3. Critical Data
12
Fig 7 CoP over compressor speed
13
Results F
𝑊𝑜𝑟𝑘 = 𝑚 * 1000 * (ℎ2 − ℎ1) = 0. 0003342 * 1000 * (262. 08 − 241. 99) = 6. 714𝑊
Speed:
𝑆𝑝𝑒𝑒𝑑 = 120 * (𝐶𝑆/100 * 𝐹)/𝑛 = 120 * (80/100 * 50)/6 = 800 𝑟𝑝𝑚
Mechanical power or Compressor work:
𝑊 = 2 * π * 𝑆𝑝𝑒𝑒𝑑/60 * τ = 2 * π * 800/60 * 2. 21 = 185 𝑊
Compressor Efficiency:
𝐸𝑓𝑓𝑖𝑐𝑖𝑒𝑛𝑐𝑦 = 𝑊𝑜𝑟𝑘/𝑊 * 100 = 6. 714/185 * 100 = 3. 63
Sensible Heat Change in Condenser:
Heat removed from Refrigerant:
𝐻𝑒𝑎𝑡𝑜𝑢𝑡 = 𝑚 * (ℎ3 − ℎ2) * 1000 = 0. 0003342 * 1000 * (91. 78 − 262. 08) =− 56. 914𝑊
Condenser Efficiency:
𝐸𝑓𝑓𝑖𝑐𝑖𝑒𝑛𝑐𝑦 = 𝑄𝑜𝑢𝑡/𝐻𝑒𝑎𝑡𝑜𝑢𝑡 * 100 = 56. 914/910 * 100 = 6. 254
Heat Absorbed:
𝐻𝑒𝑎𝑡𝑖𝑛 = 𝑚 * (ℎ1 − ℎ4) * 1000 = 0. 0003342 * (241. 99 − 91. 78) * 1000 = 50. 2 𝑊
Evaporator Efficiency :
𝐸𝑓𝑓𝑖𝑐𝑖𝑒𝑛𝑐𝑦 = 𝑄𝑖𝑛/𝐻𝑒𝑎𝑡𝑖𝑛 * 100 = 50. 2/931 * 100 = 5. 392
14
4. Discussion
Discussion A
As it was already mentioned in the introduction, the refrigeration cycle goes through four main
processes, which can be seen in Fig 9. First, we start with the saturated vapour at temperature
T3=20.9 °C and pressure P1=2.2 bar, which is compressed and superheated to a temperature
T4=42.6 °C, above saturation temperature, with pressure P2 = 7.1 bar. Then the superheated
vapour at a constant pressure of P2 enters the condenser, where it is cooled down to the
temperature of T5=30.4 °C and condensed into a liquid at a constant pressure and temperature.
15
The liquid refrigerant is then passed through the expansion valve, expanding and greatly
decreasing both pressure (back to P1 = 2.2 bar) and temperature (T7 = 3.0 °C) creating a
increasing temperature back to T3 = 20.9 °C. The saturated vapour goes back to the compressor,
Discussion C
From Fig 3. The flow rate is reduced by decreasing the speed of the evaporator water
pump. Effects of refrigerant flow rate to the evaporator on the coefficient of performance are
illustrated in Fig 5 with both experimental and theoretical values. According to the graph, with a
decrease in flow rate to the evaporator, the coefficient of performance also declines due to its
linear proportionality to the heat (equation 1). Moreover, it can be seen immediately apparent
from Fig 4 that the heat energy absorbed from the air also decreases because of the flow rate. In
addition, according to Fig 6, the flow rate is inversely proportional to the difference in
In the graphs, there are some errors between theoretical and experimental values.
Probably, the error occurs due to electrical power supplied to a system, some amount of heat is
Discussion D
As it was stated in the manual it is important to understand the effect of the difference of
flow rate of the refrigerant to achieve desirable results with maximum efficiency. In this part the
different data was recorded that could show a trend with the change of the flow rate of
16
refrigerant. A higher mass flow rate of the refrigerant with the increase of compressor speed may
be responsible for a better distribution of the fluid through the channels and an increase in the
rate of heat transfer. Compressor is used in order to increase the pressure of the refrigerant
accordingly increasing the flow rate. But at the same time those components that increase the
flow rate require higher power input to work so the Coefficient of Productivity should not see
any big difference across different speeds, which exactly happens according to the graphs from
Results of part D.
Discussion F
The values for all efficiencies (condenser efficiency, compressor efficiency, evaporator
efficiency) have a value lower than 10 percent in the calculation part because of the
irreversibilities such as the uncontrolled expansion, heat loss through the walls of the pipe to the
atmosphere outside of the system, and the effect of frequency to the flow. Also, it is possible that
the calculated efficiency values from the experiment can be the result of friction in flow through
the pipe.
Conclusion A
condensation, expansion and evaporation. All these processes were previously discussed in the
refrigeration cycle, because typical range of CoP for refrigeration cycle is somewhere between
17
3.0 and 6.0. It means that more heat is exchanged in comparison to work input in the
compressor.
Conclusion C
The performance and size of the evaporator play a key role in improving the total cooling
capacity and the performance of the system. The performance of the evaporator can be improved
through the flow rate adjustments because it is more challenging to predict the value of the
enthalpy due to a two-phase state flow in the evaporator. According to the data acquired from
this experiment, there was an obvious correlation between the adjustment of flow rate and the
performance of the evaporator. To improve the performance of the evaporator, the flow rate
should be increased. However, due to a negative slope in the curve, a larger flow rate leads to
less temperature difference between a refrigerant and the secondary fluid [1]. Therefore, in this
study, it is suggested to increase the flow rate from 160 to 190 L/h.
In addition, an inclination angle of the tube also influences the heat transfer coefficient.
For example, considering vertical low flow, the highest heat transfer coefficient can be achieved
◦
only at 90 angle. Regarding the horizontal flow, the highest heat transfer coefficient is attained at
◦
− 30 [2].
Conclusion D
As it was stated in the discussion, the flow rate of refrigerant is the most important aspect
of the refrigeration system. With increase in compressor speed it is expected that flow rate of
refrigerant increases as well. But, the side effect is that sequentially the higher speed requires a
higher amount of power. Accordingly, the Coefficient of Productivity does not change from
18
compressor speed, which are represented in Fig 7 and Fig 8 with dependent inputs being the
Conclusion F
As it is mentioned above, all of the efficiency values were considerably low. Even If the
efficiency values are less than 10%, the efficiency value for evaporator, compressor, and
condenser was not higher than 100% (not possible to get this efficiency value). The reason for a
small value of the efficiency might be the incorrect readings taken by the measuring instruments.
Recommendations to increase the efficiency of the system can be the use of a good insulation to
minimize the heat loss into buildings and outside nature, to use the highest temperature possible
in a cooling process.
19
Bibliography
[1] “6.7 operating point,” SWEP. [Online]. Available:
https://www.swep.net/refrigerant-handbook/6.-evaporators/asas4/. [Accessed: 17-Oct-2021].
20