Technical Specification of LT Current Transformer

The document provides the technical specifications for a set of 4 resin cast ring type LT current transformers (LTCTs) with ratios of 400/5A, 600/5A, and 800/5A. The LTCTs comply with Indian Standard IS 16227 and have a class of accuracy of 0.5. They are designed for indoor use in metering boxes and have a rated voltage of 415V, 50Hz. Each LTCT will have rating plates with manufacturer and rating details.

Uploaded by

Sristi Mitra
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
387 views3 pages

Technical Specification of LT Current Transformer

The document provides the technical specifications for a set of 4 resin cast ring type LT current transformers (LTCTs) with ratios of 400/5A, 600/5A, and 800/5A. The LTCTs comply with Indian Standard IS 16227 and have a class of accuracy of 0.5. They are designed for indoor use in metering boxes and have a rated voltage of 415V, 50Hz. Each LTCT will have rating plates with manufacturer and rating details.

Uploaded by

Sristi Mitra
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 3

Technical specification of LT Current Transformer of ratio (a set of 4 nos.

LTCTs)

1. SCOPE

Specification covers resin cast ring type LT Current Transformers confirming to IS- or the latest version
thereof are of class 0.5 accuracy for use in conjunction with -/5A energy meters. CTs will be design for
indoor use to install in the metering box.

2. APPLICABLE STANDARDS:

LT CTs will comply with the Indian Standard Specification IS: 16227 and the latest version thereof.

3. TYPE AND RATING OF L.T.CURRENT TRANSFORMERS:

LT CTs will be of the following type and ratings:


Sr. No. Particulars Requirement
1. Type Resin Cast Ring type CT
2. a) Rated Voltage 415 V, 50 Hz ( Phase to phase)
b) No. of Cores One
c) Primary Current / Ratio 400/5A, 600/5A, 800/5,
d) Rated Output Burden. As per IS:16227 or latest version there of
e) Rated Continuous Thermal current
temperature rise over ambient 1.2 times of rated current
f) One Minute withstand Power
Frequency Voltage for Primary & 3 KV
secondary winding
g) ISF Less than 5
h) Rated Short Time Current 5 kA for 1 Second

3. Class of Accuracy 0.5


4. Material
i. Core High-grade non-ageing electrical low loss core
ii. Conductor Super enameled copper wire of requisite
diameter.
iii. Insulation Resin cast
5. Primary & secondary Terminals
i. Primary Primary Conductor (Cable/ Bus Bar) will pass
through Ring type CT. Proper marking will be
provided for current direction identification.
ii. Secondary terminal Secondary Terminals S1 & S2 will be clearly
marked.

4. RATING PLATE:
Each C.T. would have self adhesive, laminated, printed label having following details:
(i) Manufacturer's name
(ii) Manufacturing month & year
(iii) Ratio
(iv) VA burden
(v) Type of C.T. & serial no.
(vi) Line Voltage, frequency
(vii) Insulation level
(viii) Property of XXXX ( To be confirm along with PO )
Guaranteed Technical Particulars of LT Current Transformer of ratio (a set of 4 nos. LTCTs)

Sr. No Characteristics Bidders data


1) Make of CT
2) Type/ Capacity
3) (a) Rated Voltage
(b) Highest system voltage
(c) No of cores
(d) Rated output
(e) Rated Continuous Thermal Current
temperature rise over ambient

4) Class of Accuracy – 0.5

5) VA Burden

6) Dimension in mm
Inner dia of CT
a. 400/5A
b. 600/5A
c. 800/5A

7) Material:
(a) Core
(b) Conductor
(c) Insulation
8) Secondary termination
- Stud type terminals along with Nut &
washer with marking of S1 & S2 terminal