Design of Continuous Roof Beam

This document summarizes the design of a continuous roof beam (RB-1) with the following key details: - The beam is 200mm x 300mm and interior longitudinal. Design criteria include specifications, material properties, and loadings from roofing, ceilings, partitions, and live loads. - Loads were computed including dead loads from roofing, ceilings, self-weight, and live loads. The total uniform load was 4.96 kN/m. - A fixed-end moment distribution analysis was performed for the multi-span beam considering the stiffness of each member. Shear and bending moment diagrams were drawn. - The maximum negative moment of 6.48 kNm gover
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
262 views8 pages

Design of Continuous Roof Beam

This document summarizes the design of a continuous roof beam (RB-1) with the following key details: - The beam is 200mm x 300mm and interior longitudinal. Design criteria include specifications, material properties, and loadings from roofing, ceilings, partitions, and live loads. - Loads were computed including dead loads from roofing, ceilings, self-weight, and live loads. The total uniform load was 4.96 kN/m. - A fixed-end moment distribution analysis was performed for the multi-span beam considering the stiffness of each member. Shear and bending moment diagrams were drawn. - The maximum negative moment of 6.48 kNm gover
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

Design of Continuous Roof Beam, RB-1, Interior Longitudinal (200 mm x 300 mm)

1. Design Criteria

1.1. Specifications:
1.1.1. Design References
NSCP Volume I, Fourth Edition 2015
1.1.2. Design Aids
Microsoft Excel

1.2. Material Property:


1.2.1. Concrete
Compressive strength for concrete, f'c = 20.70 MPa
Modulus of Elasticity for concrete, Ec = 21,384.00 MPa
Unit Weight of concrete, Yc = 24.00 KN/cu.m

1.2.2. Steel
Yield Strength, fy = 273.00 MPa
Modulus of Elasticity for steel, Es = 200,000.00 MPa

1.2.3. Factors
Compressive block depth, β = 0.85
Reduction factor (Flexure), Φ = 0.90
Reduction factor (Shear), Φ = 0.85

1.3. Loadings:

1.3.1. Dead load:

Roofing
G.I. Rib type 0.10 KPa
Purlins 0.20 KPa

Floor finishes
Ceramic tile = 1.10 KPa

Ceiling finishes
Suspended steel channel = 0.10 KPa
Gypsum board = 0.05 KPa
Electrical wirings = 0.10 KPa

Partition Load
Partition 1.50 KPa
Weight of wall and parapet 3.50 KPa

1.3.2 Live load:

Basic Floor Area 1.90 KPa


Roof 0.60 KPa

1.4. Assumed member dimension

Beam assumed section:


b= 200.00
h= 300.00
Column assumed section
x= 300.00
y= 300.00

15
2. Load Computation

2.1. Roof beam along F

2.1.1. Due to Roofing


wr = 0.72 KN/m

2.1.2. Due to Ceiling


wc = 0.60 KN/m

2.1.3. Due to beam self weight


wb = 1.73 KN/m

2.1.4. Due to roof live load


wb = 1.92 KN/m

2.1.5. wt = 4.96 KN/m

16
3. Analysis

w = 4.96 KN/m

3.1. Compute k = I / L
k col = 0.000211
k 2-4 = k 4-2 = 0.000129
k 4-5 = k 5-4 = 0.000188
k 5-6 = k 6-5 = 0.000113

3.2. Compute Distribution Factor


Joint 2: ∑ k 2 = (k col) + (k 2-4) 0.000340
DF col 2 = 0.621
DF 2-4 = 0.379

Joint 4: ∑ k 4 = (k 4-2) + (k col) + (k 4-5) = 0.000527


DF 4-2 = 0.244
DF col 4 = 0.400
DF 4-5 = 0.356

Joint 5: ∑ k 5 = (k 5-4) + (k col)+ (k 5-6) = 0.000511


DF 5-4 = 0.367
DF col 5 = 0.413
DF 5-6 = 0.220

Joint 6: ∑ k 6 = (k 6-5) + (k col) = 0.000323


DF k 6-5 = 0.348
DF col 6 = 0.652

3.3. Compute Fixed end moments (FEM)


FEM 2-4 = FEM 4-2 = (w)(L^2) / 12 = 5.07 KNm

FEM 4-5 = FEM 5-4 =(w)(L^2) / 12 = 2.38 KNm

FEM 5-6 = FEM 6-5 = (w)(L^2) / 12 = 6.62 KNm

17
Joint 2 4 5 6
member col 2 - dn 2-4 4-2 col 4 - dn 4-5 5-4 col 5 - dn 5-6 6-5 col 6 - dn
DF 0.621 0.379 0.244 0.400 0.356 0.367 0.413 0.220 0.348 0.652
FEM -5.07 5.07 -2.38 2.38 -6.62 6.62
BAL 3.15 1.92 -0.65 -1.07 -0.96 1.55 1.75 0.93 -2.30 -4.32
CO -0.33 0.96 0.78 -0.48 -1.15 0.47
BAL 0.20 0.12 -0.42 -0.70 -0.62 0.60 0.67 0.36 -0.16 -0.30
CO -0.21 0.06 0.30 -0.31 -0.08 0.18
BAL 0.13 0.08 -0.09 -0.14 -0.13 0.14 0.16 0.09 -0.06 -0.12
CO -0.04 0.04 0.07 -0.06 -0.03 0.04
BAL 0.03 0.02 -0.03 -0.04 -0.04 0.03 0.04 0.02 -0.01 -0.03
CO -0.01 0.01 0.02 -0.02 -0.01 0.01
BAL 0.01 0.01 -0.01 -0.01 -0.01 0.01 0.01 0.01 0.00 -0.01
CO 0.00 0.00 0.01 0.00 0.00 0.00
BAL 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FEM 3.52 -3.52 4.94 -1.97 -2.97 3.85 2.64 -6.48 4.77 -4.77

18
3.4. Shear and Moment

span 2-4

w (KN/m)
3.52 4.94

2 L (m) 4
L= 3.50 m
w= 4.96
RL= 8.28
RR= 9.09
x x= 1.67 m

Shear
V 2L = 0.00
V 2R = 8.28
V 4L = -9.09
V 4R = 0.00

Moment
M 2L = -3.52
Mx= 3.39
M 4L = -4.94

span 4-5

w (KN/m)
2.97 3.85

4 L (m) 5
L= 2.40 m
w= 4.96
RL= 5.59
RR= 6.32
x x= 1.13 m

Shear
V 4L = 0.00
V 4R = 5.59
V 5L = -6.32
V 5R = 0.00

19
Moment
M 4L = -2.97
Mx= 0.18
M 5L = -3.85

span 5-6

w (KN/m)
6.48 4.77

5 L (m) 6
L= 4.00 m
w= 4.96
RL= 10.35
RR= 9.50
x x= 2.09 m

Shear
V 5L = 0.00
V 5R = 10.35
V 6L = -9.50
V 6R = 0.00

Moment
M 5L = -6.48
Mx= 4.32
M 6L = -4.77

M max negative = -6.48 kNm


M max positive = 4.32 kNm
R max = 16.68 kN

20
3.5. Design of Reinforcement
d=h-c= 240.00

3.5.1 Negative Reinforcement


Moment due to loads, MV = 6.48
Moment due to earthquake, MEQ = 5.18
MD = 0.75 (MV + ME) 8.75 USE

Mu = (Ф)(f'c)(b)(da^2)(ω)(1-0.59ω)
solve for ω
ω2 - 1.69ω + 0.0691 =0
ω= 0.0418

Actual steel ratio, ρ act


ρ act = (ω)(f'c/fy) = 0.0032 Non-Compliant

Minimum steel ratio, ρ min


ρ min = 1.4/fy = 0.0051 Use for design

Maximum steel ratio, ρ max


ρ bal = {(0.85)(β1)(f'c)/fy}{600/(600+fy)} = 0.0377
ρ max = 0.75(ρ bal) = 0.0282 Compliant

Therefore use, ρ govern = 0.0051 Singly Reinforced

Steel area, As
As = ρ (b)(d) = 246.15 sq.mm

Using ø 12 mm
n= 3.00

Use 3.00 pc of ø 12.00 mm

3.5.2. Positive Reinforcement


+ Mu = 4.32
Mu = (Ф)(f'c)(b)(da^2)(ω)(1-0.59ω)
solve for ω
ω2 - 1.69ω + 0.03408 =0
ω= 0.0204

Actual steel ratio, ρ act


ρ act = (ω)(f'c/fy) = 0.0015 Non-Compliant

Minimum steel ratio, ρ min


ρ min = 1.4/fy = 0.0051 Use for design

Maximum steel ratio, ρ max


ρ bal = {(0.85)(β1)(f'c)/fy}{600/(600+fy)} = 0.0377
ρ max = 0.75(ρ bal) = 0.0282 Compliant

Therefore use, ρ govern = 0.0051 Singly Reinforced

Steel area, As
As = ρ (b)(d) = 246.15 sq.mm

Using ø 12 mm
n= 3.00

Use 3.00 pc of ø 12.00 mm

21
3.5.3. Stirrups (Consider Shear)

Vu = V - (wt)(d) = 15.49 KN

Actual Vc = (Vu*1000) / [(ø)(b)(d)] = 0.38 MPa

Allow Vc = .17 (√ f'c) = 0.77 MPa Not Needed

Steel area, Av
Bar Diameter = 10.00 mm
area = 78.54 mm ²

S= -
Smax = d / 2 = 120.00
600 = 600.00

mm ø spaced
Use 10.00 120.00 mm O.C.
at

4. Summary

4.1. Reinforcement @ Support

200 mm
3 pcs of 12 mm diameter Top Bars
300 mm

3 pcs of 12 mm diameter Bottom Bars

4.2. Reinforcement @ Midspan

200 mm
3 pcs of 12 mm diameter Top Bars
300 mm

3 pcs of 12 mm diameter Bottom Bars

4.3. Beam Dimension


Continuous Roof Beam, RB-1
b= 200.00 mm
h= 300.00 mm

22