GE Power Electronics Brochure
GE Power Electronics Brochure
VAT2000
Approvals
CE compliance
UL approval (UL 508C) 400V series
drive only.
GE Power Controls
Multi-mode vector drive
Mode 1: Mode 3:
V/F control for constant torque loads with advanced Sensorless vector control
torque control There are many drives which claim to offer sensorless
This mode uses auto-tuning to give voltage vector vector control but we feel that this term is misused and
control in open loop. describes a control system similar to our standard
The main features of this mode are: Advanced Torque Control. We define true Sensorless
1. Built-in PID controller eliminates the requirement - and Vector Control as Flux Vector Control without encoder.
cost- of a separate device. Closed loop vector control requires the use of an
2. Tripless operation. This safe and convenient feature is encoder so that shaft position can be used in order to
a combination of: calculate and control phase angle and shaft speed.
- the availability to dynamically extend ramp times Because of this, all settings within a closed loop
during operation if the load is likely to demand a too environment relate to actual shaft rotation rather than
VAT2000
high current or regenerate a higher current than the output frequency.
programmed limit. Developing a method whereby the shaft rotation can be
- automatic limiting of the IGBT switching frequency if calculated by very closely monitoring the waveform and
the heatsink temperature rises too high feedback at the three output phases of the drive. All of
- the ability to limit current transients caused by the settings the VAT2000 in sensorless vector mode are
shock loads therefore set using rotational speed and not output
- alarms and controlled shutdown in the event of a frequency.
fault which is non-life threatening of the drive motor. In addition, incorporate two current loops to control
«Motor Loss Braking» is a system which reduces magnetising current independently. Thus, the VAT2000
motor efficiency during regenerative braking can perform almost as well as a closed loop system
allowing some of the braking energy to be and uniquely provide torque at zero speed.
dissipated from the motor as heat, so reducing the
size (or even eliminating) the brake resistor. Mode 4:
Cloosed Loop Vector Control
Mode 2: This advanced mode enables motor speed to be varied
V/F control for variable torque loads with advanced across a 1000 : 1 speed range, with 0.01% accuracy up
torque control to 6 times faster than conventional drives (30Hz
This mode uses auto-tuning to give voltage vector
control in open loop with the added benefit that,
response time)
In addition to outstanding torque performance, this
N
because of a higher continuous current rating than in mode contains a new feature whereby the loss of the 7
constant torque mode, an inverter of one size lower encoder signal will cause the drive to automatically
may be used in order to reduce the purchase cost. switch into Sensorless Vector mode. The drive then
Features include: issues an alarm signal which can be used as an
1. Special energy saving features for fans and pumps indication or as a shutdown signal.
where V/F ratios are dynamically controlled to Closed Loop Vector Control requires an Encoder
optimise the power usage. Feedback card.
2. The drive can auto-tune to two independent motors,
so that one inverter can be used in applications such Mode 5:
as pumping where a main and standby pump are fed PM Motor Control
by the same source.
3. Multi-pump control. This is a logic control system This mode enables the use of ultraefficient PM motors
commonly used where two or more pumps maintain for energy conservation.
pressure in a system, one being variable speed and
the others being brought in as required.
VAT2000
VAT2000
DC supply drives for common bus operation
We can supply VAT2000 drives for common bus operation DC supply 270-360 VDC or 520 - 720 VDC.
Please ask your dealer for more information
GE Power Controls
Optional PCBs Cards
Description Cat. No. Code
VAT2000
Encoder interface 12V A/B phase 60kHz; 6V single phase 20kHz, U2KV23DN1 168087
12VDC 100mA supply output
5V A/B phase differential 250kHz; 5VDC 200mA U2KV23DN2 168088
supply output
5V 6phase (A, B, Z, U, V, W) 250Hz for permanent U2KV23DN3 168089
magnet motors; 5VDC 200mA supply output
N
9
Accesories
Extension cable for keypad U2KV23W103 168102
Extension cable for software tool U2KV23W10 168104
Programming software tool U2KV23SOFT –
VAT2000
Technical Data
Frequency control
Control method All digital control sine wave approximation PWM
Carrier frequency
Mono-sound mode 1 to 15 kHz (1kHz increments)
Variable Speed Drives
Voltage frequency control Constant torque, constant output and reduction torque set in range from 3 to 440Hz.
Torque Boost: Manual and automatic
Max. torque boost: Alows improved V/f control
Vector control Sensorless With Sensor For PM motors
Control range 1 : 100 1 : 1000 1 : 100
GE Power Controls
Technical Data (continued)
Operation functions
Multi speed 8 fixed speed selectable with independent acceleration/deceleration ramps for each speed
Ratio interlock Output frequency or speed is operating according
Y = Ax + B + C
x : frequency or speed setting
A : (gain) 0.000 to ±10.000
B : 0.00 to ± 440Hz (0 to ±7200min-1 with max:120Hz in Vector control mode
C : Auxiliary input (AUX)
Upper and lower limits available
Frequency jump Up to three areas / Width can be varied between 0.0 and 10Hz
VAT2000
Slip compensation Slip compensation gain for V/f operation only from 0.0 to 20.0%
Auto-run funtion 10-step automatic run function / Synchronous / Asynchronous selective
Others PID, Pick-up, Auto-start, Traverse, Multipump control, reverse run protection and Restart after
instantaneous power failure
External I/O
Operation keypad Detachable IP54 unit with 7 digit LED display and eight status LED signals. Includes three set keys
and fast tuning knob system. Door mountable by 3 m extension cable
Input sequence Three fixed inputs and five programmable to more than 30 functions
Output sequence One fixed dry contact (fault), one dry contact and three open collector outputs all programmable to
more than 20 functions, like speed detection precharging, reverse run, speed reached, direction,
current reached, speed, acceleration, fault code, etc.
Frequency settings FSV: 0 to 10V / 0 to 5V / 1 to 5V
FSI: 4 to 20mA / 0 to 20mA
AUX: 0 to ±10V / 0 to ±5V / 1 to 5V
Source potentiometer: 10VDC (2hOhms)
Meter outputs Two 0-10V programmable with output frequency,
voltage, current, DC voltage, etc
N
11
Protection features
Prevention Overcurrent and Overvoltage limit, Overload warning signal
Trip Overcurrent, overvoltage, undervoltage, IGBT fault, overload, temperature rise, ground fault, other
self-diagnosis
Fault history The last four faults are recorded including in each:
Main cause, secondary cause, output current and output frequency at the fault time.
Overload level CT: 150% for 1 minute, 170% for 2,5 seconds ( 50% of these values for 3Hz and less )
VT: 120% for 1 minute, 125% for 1 seconds ( 75% of these value for 3Hz and less )
Retry Automatic reset after a fault. Adjustable from 0-10 tries
Operating environment
Installation Indoor, with atmosphere free from corrosive or explosive gases, dust, steam or oil mist
Working temperature -10 to +50ºC
Relative humidity 95% RH, non-condensing
Altitude 1000 m max.
Vibrations 3m/s2
VAT2000
I / O Wiring
DBR driving unit (option) (3)
Variable Speed Drives
MCCB MOTOR
POWER
SUPPLY
N ANALOGUE INPUT
Frequency
12 setting
(voltage)
2kΩ, 2W (5) Voltage
output
Aux. setting (0-10V)
DC ± 10V load max.
DC 0-10V 1mA
(5) (5)
DIGITAL INPUT
Max. 1A 250V AC To comply
or 30Vdc with UL
use at
30VAC/DC
Max. 0,4A 250V AC or lower
or 1A 30VDC
Standard setting
Free voltage
input
(5mA per
signal)
Open collector
Max. 30VDC 30mA
RY0V) (4)
GE Power Controls
Notes
VAT2000
N
13
VAT2000
ON during operation, the VAT2000 is led into a stopping sequence (ramp down stop or coast-
to-stop are available. It is also possible to output this signal as a fault (FLT).
RESET Fault reset A faulty condition is reset. With this signal, a fault status output (FLT LED, FAULT relay
operation) is turned OFF and operation becomes possible
RUN Forward run This is a command for forward run. Run/Reverse mode by permanent or pulse command can
be selected
Analogue inputs FSV Voltage/Frequency This is mainly used for setting frequency (speed). The maximum speed setting is available at
10V input. This input is valid when VFS function is ON
FSI Current/Frequency This is mainly used for setting frequency (speed). The maximum speed is available at 20mA
input. This input is valid when IFS function is ON
AUX Auxiliary input This is mainly used for setting frequency (speed). The maximum speed setting is available at
±10V input. This setting is valid when AUX function is ON
COM Analogue input comm. This is a common terminal for FSV, FSI and AUX signals
Analogue outputs FM Frequency meter This is a voltage output signal for a frequency meter. In a standard mode, a 10V output is
available at the maximum frequency. This output voltage can be adjusted to 0.2 to 2.0 times
10V (max output is, however, approximately 11V). Internal parameters other than those of
frequency can also be output (C13-0, C14-0)
AM Ammeter This is a voltage output signal for ammeter. In a standard arrangements, an output of 5V is
available for the rated current. This output voltage adjustment of 0.2 to 2.0 times of 5V is also
available. Internal parameters other than those of current can also be output.
COM Analogue output comm. This is a common terminal for a frequency meter and ammeter
P10 FSV source This is a 10V source used when a potentiometer is connected to the FSV input circuit. The
potentiometer should be of 2W and 2kΩ.
Digital outputs RC, RA RUN Dry relay contact assigned to RUN function as default. Programmable to other functions as well
FC, FA, FB FAULT Dry relay contact assigned to FAULT function. It operates when a fault occur.
PS01 READY Programmable open collector output assigned to READY function as default
PS02 Current detection Programmable open collector output assigned to current detection function as default
PS03 Frequency (speed) Programmable open collector output assigned to speed detection as default attainment
PS0E Open collector This is a common terminals for the PS01, 2 and 3 outputs
output common All digital outputs can be set to any of output sequence functions.
GE Power Controls
I / O terminal board specifications (continued)
Terminals Function Description
VAT2000
EC0~EC3 Fault code 0 to F After a fault this outputs the fault code with a 4-bit binary format.
ACC Acceleration This turns ON during acceleration.
DCC Deceleration This turns ON during deceleration.
AUXDV Dual selection This turns ON when the secondary drive parameter setting is validated
ALM Minor fault This turns ON during a minor fault.
FAN Fan control This turns ON during running, jogging, pre-excitation and DC braking. A three minute off delay
is provided, so even if the above operations turn OFF, this control will not turn OFF for three
minutes. This is used for external fan control.
ASW Auto- start wait This is ON while Auto-start delay time. (C08-0)
ZSP Zero speed This turns ON when the output frequency (speed) is below the level set with (C15-4)
LLMT PID lower limit These turns ON when the feedback value exceeds the limit value ( <B43-3) or (>B3-4)
ULMT PID upper limit during PID operation
N
15
VAT2000
Soft sound
Run the drive
(run the tuning)
OK
Auto-Tuning is complete
N
16
Mono sound
B00/1-0 Input voltage (V)
B00/1-1 Motor rated output voltage (kW)
B00/1-2 Number of motor poles (Pole)
B00/1-4 Max. speed (min-1)
B00/1-5 Base speed (min-1)
B00/1-6 Motor rated current (A)
B00/1-7 Carrier frequency
B00/1-8 Number of encoder pulses (P/R)
GE Power Controls
Vector control system. Speed block diagram
The VAT2000 performs an high-end Vector control system,
which allows speed accuracy up to 0.01% using encoder
feedback, and up to 0.5% in sensorless. The dynamic
response is excellent in all cases.
The speed control block diagram is given bellow
VAT2000
I Control Current Speed
Gain detection detection
Torque
Command
Disturbance
observer Detected
motor speed
Excite
current
control Flux
Estimated motor speed Observer
& Speed
Sensorless estimation
Motor vector control
speed
Vector control
with sensor
Interlock ratio
Allows full control of speed setting and motor output’s
ratio.
Variable Speed Drives
Multi-pump control
One pump is variable speed controlled and up to six
more controlled ON/OFF by the digital outputs provided
in the VAT2000. The water pressure in the pipe system
is controlled to be constant according the setting input
in the VAT2000´s PID.
The pumps are automatically shifted in order they work
at the same time
As standard the drive provide control up to 3 ON/OFF
controlled pumps. By using optional card U2KV23RYO,
then operation is allowed up to 5 pumps
Pressure
setting Speed controlled
pump
ON / OFF pump 1
ON / OFF pump 2
ON / OFF pump 3
N ON / OFF pump 4
Pressure transducer
18
ON / OFF pump 5
PID - Control
This function allows control of external conditions by
using a feedback signal. Useful for slow process control
like water pressure or flow, temperature by fans etc.
Pressure sensor
Pump
Pump
C12-4 (gain)
COM AUX/FSI
R
Converter
GE Power Controls
Frequency jump
Selectable function which jumps up to three
programmable motor speed regions. It is useful to
avoid vibrations caused by mechanical resonance.
(Valid only during V/F control.)
Pattern run
Up to ten steps automatic operation. Useful for
machines working in a repeated cycle
VAT2000
Frequency (Speed)
Time
N
19
RUN
Traverse
Usefull function for winding textil equipment.
The traverse centre frequency, can be selected from either analog
input setting, keypad setting or programmable fixed speeds
Centre frequency (speed)
Energy saving
Selectable function which automatically varies the
voltage when the motor operates under partial or no-
load conditions, thereby obtaining maximum efficiency.
Variable Speed Drives
Retry
Allows automatic restart after a fault. Provides up to
10 programmable re-tries with programmable time
between tries.
Output frequency
Motor speed
Time
Internal
FLT
Communications
N Built-in standard ASCII based communication feature.
20 Optional Profibus DP (others communication cards in
development).
Fault history
The last four faults are coded and saved in a internal
buffer.
Trace back
This is an optional feature which allows recording of up
to four motor or drive signals, while the VAT2000 is
operating. The last 30 samples of each signal can be
monitored after a fault.
GE Power Controls
Dimensional drawings and Weights
VAT2000
Cat. No. Dimensions Main Weight
Supply Supply A B C D E Ød circuit
200-230V 400-460V terminal kg
X05K5 216 275 169 201 260 7 M4 6
X07K5 216 275 169 201 260 7 M4 6
N05K5 216 275 169 201 260 7 M5 6
N07K5 16 275 169 201 260 7 M5 6
X11K0 265 360 228 245 340 7 M5 13
X15K0 265 360 228 245 340 7 M5 13
X18K5 265 360 228 245 340 7 M5 13
N11K0
N15K0
265
265
360
360
228
228
245
245
340
340
7
7
M6
M6
13
13
N
21
External accessories
Absorber
U2KN18K5S 18.5 400 100 CL07
U2KN22K0S 22 500 150 CL09
U2KN30K0S 30 500 150 CL10
U2KN37K0S 37 600 200 CK75
Built-in PCB option U2KX00K4S 0.4 10 5 CL00
U2KX00K7S 0.75 10 5 CL00
U2KX01K5S 1.5 20 5 CL00
U2KX02K2S 2.2 30 5 CL00
U2KX04K0S 4.0 50 15 CL00
Stand-alone options U2KX05K5S 5.5 60 20 CL00
U2KX07K5S 7.5 90 30 CL02
Noise filter oooo
U2KF-oooo This device suppresses the
oooo
PR-oooo electromagnetic noise generated by U2KX11K0S 11 110 40 CL04
the inverter. It may be required for U2KX15K0S 15 125 40 CL04
EMC compliance (CE) U2KX18K5S 18.5 175 50 CL04
U2KX22K0S 22 225 50 CL06
U2KX30K0S 30 250 75 CL06
N DBR unit oo
U2KV23DBU-oo This module provides dynamic
braking capacity to drives larger
U2KX37K0S
U2KX45K0S
37
45
300
400
100
100
CL07
CL09
22 than 7.5kW (U2KN07K5S or
U2KX07K5S) Always install
Variable torque ratings
appropriate braking resistor.
VAT2000 Losses Fuses MCCB Line
Cat. No. W (1) (A) (2) (A) MC
ACL oooo
ACR-oooo If the line impedance is too low the U2KN00K4S 0.75 20 5 CL00
current ripple trough input rectifier U2KN00K7S 1.5 50 10 CL00
become excessive and may result U2KN01K5S 2.2 60 15 CL00
in inverter damage. This may U2KN02K2S 4.0 110 20 CL01
happen when the power supply U2KN04K0S 5.5 125 30 CL02
transformer exceeds 10 times the U2KN05K5S 7.5 225 40 CL04
inverter unit capacity, so always U2KN07K5S 11 225 75 CL04
install reactors in this case.
U2KN11K0S 15 250 75 CL06
Reactors are also effective U2KN15K0S 18.5 400 100 CL07
improving the power factor and
U2KN18K5S 22 500 150 CL09
suppressing the current high har-
monics. The power factor will be U2KN22K0S 30 500 150 CL10
approx. 0.9. U2KN30K0S 37 600 200 CK75
U2KN37K0S 45 600 200 CK75
U2KX00K4S 0.75 10 5 CL00
DCL oooo
DCR-oooo Same benefits than ACL reactors,
U2KX00K7S 1.5 20 5 CL00
note however that ACL provides
U2KX01K5S 2.2 30 5 CL00
additional protection to input
rectifier U2KX02K2S 4.0 50 15 CL00
U2KX04K0S 5.5 60 20 CL00
Surge absorber oooo &
ACR-oooo This device protects the motor U2KX05K5S 7.5 90 30 CL02
N11P34018 against surge voltage. It is applica- U2KX07K5S 11 110 40 CL04
ble to 400-460V systems, and may U2KX11K0S 15 125 40 CL04
be required if output wiring to motor U2KX15K0S 18.5 175 50 CL04
exceeds of 40m length. U2KX18K5S 22 225 50 CL06
The surge absorber is composed by U2KX22K0S 30 250 75 CL06
one output reactor and a RC filter. U2KX30K0S 37 300 100 CL07
U2KX37K0S 45 400 100 CL09
U2KX45K0S 55 400 150 CL09
GE Power Controls
EMC Dynamic Braking INPUT Surge Absorber (4)
Filter Braking Module Resistors (3) AC Reactor DC Reactor Reactor RC Filter
U2KF3016MD1 Built in VAT2000 TLR405P200 ACR4A2H5 - - -
U2KF3016MD1 Built in VAT2000 TLR216P200 ACR6A2H5 - - -
U2KF3016MD1 Built in VAT2000 TLR108P200 ACR9A1H3 - - -
U2KF3030MD1 Built in VAT2000 TLR74P200 ACR12A0H84 - - -
U2KF3030MD1 Built in VAT2000 TLR44P600 ACR18A0H56 - - -
U2KF3060MD2 Built in VAT2000 TLR29P600 ACR27A0H37 DCR32A0H78 - -
U2KF3060MD2 Built in VAT2000 TLR22P600 ACR35A0H27 DCR45A0H55 - -
VAT2000
U2KF3094MD3 U2KV23DBUL1 TLR15P1000 ACR55A0H18 DCR60A0H4 - -
U2KF3094MD3 U2KV23DBUL1 TLR11P1200 ACR70A0H14 DCR80A0H3 - -
PR3120STD U2KV23DBUL1 TLR8,8P1500 ACR80A0H14 DCR100A0H24 - -
PR3120STD U2KV23DBUL2 TLR7,4P1800 ACR97A0H11 DCR120A0H2 - -
PR3150STD U2KV23DBUL2 TLR5P2500 ACR140A0H072 DCR150A0H17 - -
PR3180STD U2KV23DBUL3 TLR4P3000 ACR180A0H056 DCR180A0H14 - -
U2KF3016MD1 Built-in VAT2000 TLR864P200 ACR3A8H1 ACR3A0H05 N11P34018
U2KF3016MD1 Built-in VAT2000 TLR864P200 ACR3A8H1 - ACR3A0H05 N11P34018
U2KF3016MD1 Built-in VAT2000 TLR432P200 ACR4A5H1 - ACR4A0H05 N11P34018
U2KF3016MD1 Built-in VAT2000 TLR295P200 ACR6A3H4 - ACR6A0H05 N11P34018
U2KF3016MD1 Built-in VAT2000 TLR175P600 ACR10A2H - ACR10A0H05 N11P34018
U2KF3032MD2 Built-in VAT2000 TLR118P600 ACR14A1H4 DCR18A2H9 ACR14A0H05 N11P34018
U2KF3032MD2 Built-in VAT2000 TLR86P600 ACR18A1H1 DCR25A2H1 ACR18A0H05 N11P34018
U2KF3058MD3 U2KV23DBUH1 TLR59P1000 ACR27A0H75 DCR32A1H6 ACR27A0H05 N11P34018
U2KF3058MD3 U2KV23DBUH1 TLR43P1000 ACR35A0H58 DCR40A1H2 ACR35A0H05 N11P34018
U2KF3058MD3 U2KV23DBUH1 TLR35P1500 ACR38A0H58 DCR50A0H96 ACR38A0H05 N11P34018
U2KF3096MD4 U2KV23DBUH2 TLR29P1800 ACR45A0H45 DCR60A0H82 ACR45A0H05 N11P34018
U2KF3096MD4 U2KV23DBUH2 TLR22P2500 ACR70A0H29 DCR80A0H58 ACR62A0H05 N11P34018
PR3110STD
PR3150STD
U2KV23DBUH3
U2KV23DBUH3
TLR18P3000
TLR15P3700
ACR90A0H22
ACR115A0H18
DCR100A0H49
DCR140A0H32
ACR90A0H05
ACR115A0H05
N11P34018
N11P34018
N
23
N
24
GE Power Controls
External dynamic braking units
VAT2000
U2KV23DBUH2 168085 1.7
U2KV23DBUH3 168086 1.7
Braking resistors
Reactors
Fig. 1 Fig. 4
Variable Speed Drives
Fig. 2 Fig. 5
N
26
Fig. 3
GE Power Controls
Reactors (continued)
VAT2000
ACR97A0H11 129988 39 2 280 190 210 80 250 9 20
ACR140A0H072 129925 40 3 280 220 210 90 250 9 22
ACR180A0H056 129926 42 3 280 230 210 100 250 9 27
ACR200A0H051 129927 47 3 280 245 210 115 250 9 29
ACR3A8H1 129989 8 1 137 146 103 125 102 7 2.8
ACR4A5H1 129990 9 1 137 146 103 125 102 7 2.9
ACR6A3H4 129991 11 1 137 146 103 125 102 7 3.2
ACR10A2H 129992 14 1 137 146 113 125 102 7 4
ACR14A1H4 129993 19 1 173 167 118 146 127 7 8
ACR18A1H1 129994 21 1 173 167 133 146 127 7 10
ACR27A0H75 129995 23 1 205 200 145 176 174 7 12
ACR35A0H58 129996 25 1 205 200 155 176 174 7 13
ACR38A0H58 129997 32 1 205 200 170 176 174 7 14
ACR45A0H45 129998 35 1 205 200 170 176 174 7 14
ACR70A0H29 129928 40 2 280 200 210 90 250 9 22
ACR90A0H22 129700 42 2 280 210 210 100 250 9 27
ACR115A0H18 129701 47 2 280 225 210 115 250 9 29
ACR3A0H05 168262 9 1 137 146 103 125 102 7 2.9
ACR4A0H05 168263 9 1 137 146 103 125 102 7 2.9
ACR6A0H05
ACR10A0H05
168264
168265
9
9
1
1
137
137
146
146
103 125
103 125
102
102
7
7
2.9
2.9
N
ACR14A0H05 168266 10 1 137 146 103 125 102 7 2.9 27
ACR18A0H05 168267 10 1 137 146 103 125 102 7 2.9
ACR27A0H05 168268 11 1 137 146 103 125 102 7 2.9
ACR35A0H05 168269 11 1 137 146 103 125 102 7 2.9
ACR38A0H05 168270 11 1 137 146 103 125 102 7 2.9
ACR45A0H05 168271 11 1 137 146 103 125 102 7 2.9
ACR62A0H05 168272 14 1 137 146 113 125 102 7 4
ACR90A0H05 168273 21 1 173 167 133 146 127 7 10
ACR115A0H05 168274 32 1 205 200 170 176 174 7 14
DCR32A0H78 168371 13 4 150 200 145 176 102 7 7
DCR45A0H55 168372 13 4 150 200 145 176 102 7 7
DCR60A0H4 168373 14 4 150 200 155 176 102 7 8
DCR80A0H3 168374 17 4 150 200 170 176 102 7 9
DCR100A0H24 168375 17 4 150 200 170 176 102 7 9
DCR120A0H2 168376 17 5 190 200 215 90 160 9 15
DCR150A017 168377 21 5 190 210 215 100 160 9 17
DCR180A0H14 168378 26 5 240 200 265 96 210 9 21
DCR220AH11 168379 27 5 240 200 265 96 210 9 21
DCR18A2H9 168380 13 4 125 167 118 146 89 7 5
DCR25A2H1 168381 14 4 125 167 118 146 89 7 5
DCR32A1H6 168382 15 4 125 167 133 146 89 7 6
DCR40A1H2 168383 17 4 125 167 133 146 89 7 6
DCR50A0H96 168384 16 4 150 200 145 176 102 7 7
DCR60A0H82 168385 17 4 150 200 155 176 102 7 8
DCR80A0H58 168386 21 4 150 200 170 176 102 7 9
DCR100A0H49 168286 23 4 150 200 170 176 102 7 9
DCR125A0H40 168287 27 5 190 200 215 90 160 9 15
DCR140A0H32 168288 29 5 190 200 215 90 160 9 15
VAT2000
Surge absorbers
Reactor
Variable Speed Drives
RC - Filter
N
28
GE Power Controls
Notes
VAT2000
N
29
VAT20
Power Electronics
N. 2 Micro Variable Speed Drives - VAT20
N. 3 Ordering codes
N. 3 Dimensions
N. 6 Three-phase variable Speed Drives - VAT2000
N. 8 Ordering codes
N. 10 Technical data
N. 12 I/O Wiring
N. 14 I/O terminal board specifications
N. 16 Functions
N. 21 Dimensions
N. 22 External accessories
N.
N.
30
31
Soft Starters - ASTAT SD
Ordering codes N
N. 32 Basic diagrams 1
N. 34 Dimensions
N. 36 Solid state soft Starters - ASTATplus
N. 39 Ordering codes
N. 40 I/O Wiring
N. 41 Thermal characteristics
N. 42 Basic diagrams
N. 45 Installation
N. 46 Dimensions
VAT20
VAT20
Variable Speed Drives
Technical data
Control specifications
Control system Sinusoidal wave PWM inverter
Output frequency 0-200Hz (*)
Voltage / Frequency Constant torque. Constant power. Torque boost.
Six selectable pre-set patterns.
Overload capacity 150%, 60 sec
Carrier frequency Selectable 4-16kHz (*)
Frequency setting resolution
Digital 0.1Hz(0-99.9Hz), 1Hz(100-200Hz) (*)
N Analogic 0.1Hz/ 60Hz
2 Acceleration/deceleration 0.1 - 999 sec. Acceleration and deceleration set individually
Operating system Two mode selection: forward run by FWD input, Reverse run by REV
input Run by FWD input, forward / reverse command by REV input
Stopping system Selectable either ramp down or coast to stop
DC braking DC brake starting frequency 1-10Hz
DC braking level 1- 20%, DC braking time 0- 25.5 sec
Frequency limit Upper limit ( 1-200 Hz ) (*), lower limit ( 0-200 Hz) (*)
Other functions Auto re-start, Auto reset flying start, Jog, Slow speeds.
V/F Pattern 6 selectable patterns
I / O Configuration
Operation panel 3 digit, 7 segment display with 5 operations keys
Sequence input Four digital inputs ( 2 are programmable )
Sequence output One programmable relay output
Frequency setting input One analogue either 0-10Vm 4-20mA or 0-20mA configurable
Source for potentiometer 10V DC source for 2-10kΩ potentiometer
Meter output 0-10V DC analog output for frequency metering
Protection features
Prevention Overcurrent limitation, Overvoltage limitation, Stall prevention
Trip Overload, Overvoltage, Undervoltage, Powerloss,
Output short-circuit, grounding fault and overtemperature
Fault history The last three faults are recorded
Operating environment
Installation Indoor, with atmosphere free from corrosive or explosive gases, dust, steam or oil mist.
Protection degree IP 20
Temperature range -10 to 50 ºC
Humidity 0-95% non-condensing
Vibrations Under 1G (9,8 m/s2)
Standards UL, CSA,CE
* For drives U20N0K2S, U20N0K4S and U20N0K7S,
the carrier frequency is 1-8 kHz and the max. frequency is 120 Hz
GE Power Controls
VAT20 - Ordering Codes
Input voltage Input power Output current Maximum Cooling Cat. No. Code
motor power convection
kVA A kW (1)
VAT20
(1) Ratings for standard three-phase induction motors with four poles
(2) Units including Dynamic Braking function. An external braking resistor is needed to perform operation. Check table on N.4.
(3) Voltage range: + 10%, -15%, 50/60 Hz ( +/- 5%)
I / O Wiring
VAT20
Power Supply
Single phase drives: L1-L2 or L1-L3
Three phase drives: L1-L2-L3
Multifunction
Multifunction input option
For factory
N
test only 3
2.5 - 10k
Grounding
Digital inputs
12V Common digital inputs 12V DC supply for all digital inputs
FWD Forward run Used for forward run command
REV Reverse run Used for reverse run command
SP1 Multifunction input This is a programmable digital input.
Either jog, slow speed, emergency stop, output shut off or reset function are allowed
RST Fault reset This is a programmable input set to reset function as default.
Either jog, slow speed, emergency and output shut off are allowed as well
Digital outputs
Trip relay Multifunction output This is a programmable output relay set to Fault function as default.
Run status and frequency reached are allowed as well
Analog inputs
MVI Frequency setting Programmable analogue frequency signal input. O-10V, 4-20mA or 0-20mA allowed
0V Common analog I/O
Analog outputs
FM Frequency output Analogue frequency output 0-10V. May be used as speed meter
0V Common analog I/O
VAT20
Cat. No. A B C D E B D
U20AF0K7 156 76 25 60 145
U20AF2K2 170 221 38 108 156
U20AF2K2X 170 221 38 108 156 A
GE Power Controls
Dimensional drawings and Weights
Frame 1
VAT20
Frame 2
143.1
127.5
140
TM2
TM1
TM2
Ground 3 x Ø4.5
N
5
TM1
171.7
U20N2K2S 1.76
U20X0K7S 1.60
108 U20X1K5S 1.60
118 U20X2K2S 1.63
ASTAT SD
Soft starters
ASTAT SD
- Solid state soft starter for 3ph motors up to 20 kW
- Working voltage up to 500VAC
- Built-in with analogue operation panel
- Three phase - full wave control
- Excellent pacht of basic functions
Soft Starters
30 GE Power Controls
Environmental conditions
Temperature 0 to +55ºC
(derate output current by 1.5% / ºC above 45ºC)
Relative humidity 95% without condensation
Maximum altitude 3000 m
(derate output current by 1% / 100 m above 1000 m)
Mounting position Vertical
Description of the terminals
1L1, 3L2, 5L3 Power supply (max. 440V or 500V)
2T1, 4T2, 6T3 Outputs to motor
A1/A2, B1/B2 Command supply inputs (110/120V - 220/240V AC)
11, 14 Internal relay output (1 NO)
ASTAT SD
1, 57 Run command input
2, 57 Stop command input
Output contacts specifications
Maximum usage voltage 380VAC
Thermal current Ith 8A
Usage specifications
AC15 220V / 3A - 380V / 1A
DC15 Max. 30V / 3.5A
Input voltage
A
5
A
25
kW
1.1
kW
2.2
kW
2.2
kW kW
1.1
kW
2.2
kW
2.2
kW
Natural QS1BNA 120460 N
220 - 440 VAC 9 45 2.2 4 4 2.2 4 4 Natural QS1DNA 120462
31
12 60 3 5.5 6.3 3 5.5 6.3 Natural QS1FNA 120464
16 80 4 7.5 7.5 3.7 6.3 7.5 Natural QS1GNA 120466
22 110 5.5 10 11 5.5 10 11 Natural QS1HNA 120468
34 170 7.5 15 18.5 7.5 15 17 Natural QS1INA 120470
Input voltage 5 25 1.1 2.2 2.2 3 1.1 2.2 2.2 3 Natural QS2BNA 120461
220 - 500 VAC 9 45 2.2 4 4 5.5 2.2 4 4 5.5 Natural QS2DNA 120463
12 60 3 5.5 6.3 7.5 3 5.5 6.3 7.5 Natural QS2FNA 120465
16 80 4 7.5 7.5 10 3.7 6.3 7.5 10 Natural QS2GNA 120467
22 110 5.5 10 11 13 5.5 10 11 13 Natural QS2HNA 120469
34 170 7.5 15 18.5 20 7.5 15 15 20 Natural QS2INA 120471
UL ratings Current Maximum Light duty Heavy duty Cooling Cat. No. Code
rating starting (3 x Ir, 30 sec.) (4.5 x Ir, 30 sec.) convection
Ir current 200V 230V 460V 200V 230V 460V
A A HP HP HP HP HP HP
Input voltage 5 25 1 1 1 1 Natural QS1BNA 120460
200 - 230 V 9 45 2 2 2 2 Natural QS1DNA 120462
12 60 3 3 3 3 Natural QS1FNA 120464
16 80 3 5 3 5 Natural QS1GNA 120466
22 110 5 7.5 5 7.5 Natural QS1HNA 120468
34 170 10 10 7.5 7.5 Natural QS1INA 120470
Start / Stop
I/ 0
Control voltage
220/240V AC
Soft Starters
Control by push-buttons
Control voltage
110/120V AC
Start Stop
N Control voltage
220/240V AC
32
(1) These contacts allow for direct action on contactors up to type CL06 at 220VAC.
(2) The Astad SD has no overload function, so always use an external overload
relay to protect the motor.
GE Power Controls
Permanent command with line contactor
Control voltage
110/120V AC Control
voltage
Start / Stop
Control voltage
220/240V AC
ASTAT SD
Pulse function with line contactor
Control voltage
110/120V AC Control
voltage
Start Stop
Control voltage
220/240V AC N
33
N
34
GE Power Controls
Notes
ASTAT SD
N
35
ASTATplus
ASTATplus
- Solid state soft starter for 3ph AC motors up to 850 KW
- Working voltage up to 500V
- Built-in digital operation panel
- ASCII and Modbus RTU communications
- High end features and functions
Soft Starters
GE Power Controls
Running
External Control Start - Stop
Acceleration phase Adjustable time
Permanent time Energy savings/ Override choice
Stop phase Power cut-off / Ramp / DC braking / Pump control
Inputs / Outputs
External Control 4 digital optocoupled
Two fixed (Start, Stop), and 2 programmable (I3, I4)
1 analogue 0-5V DC for tachogenerator input feedback
Outputs 3 programmable relays (1r, 2r, 3r)
1 analogue 0-10V DC output for current metering
Communications
ASTATplus
ASCII and ModBus RTU as standard
Profibus DP and DeviceNet by optional external modules
Protections
Current limit Adjustable from 1 ln to 7 ln
Overload IEC class 10 and 20 ( selectable )
NEMA class 10, 20 and 30 ( selectable )
Cool-down time after
overload trip 300 s for reset
Loss on input phase Trip at 3 s
Thyristor short circuit Trip at 200 ms
Heatsink overheating Trip at 200 ms
Motor thermistor Trip at 200 ms
Loss on output phase Trip at 3s
Stalled rotor Trip at 200 ms
Supply frequency error If f < 45Hz or f > 65 Hz,
Overcurrent 100 to 150% ln; trip time adjustable from 0 to 99s
Undercurrent 0 to 99% ln; trip time adjustable from 0 to 99s N
Overvoltage 100% to 130% Un; trip time adjustable from 0 to 99s 37
Undervoltage 0 to 50% Un; trip time adjustable from 0 to 99s
Error ( CPU ) 60 ms
Memory 4 former errors
Long start time 2s x ta ( ta= acceleration ramp time )
Long slow speed time 120s
Enviromental conditions
Temperature 0 to +55º C
( derate ouput current by 1.5% /ºC above 40ºC )
Relative humidity 95% without condensation
Maximun altitude 3000 m
( derate output current by 1%/ 100 m above 1000 m )
Mountig position Vertical
Protection degree IP 00, UL open
Standards
CE, cUL, UL CE conforming IEC 947-4-2
UL, cUL conformig to UL 508
Conducted & radiated Conforming to IEC 947-4-2, Class A
emissions
Electrostatic discharges Conforming to IEC 1000-4-2, level 3
Radioelectric interference Conforming to IEC 1000-4-6, level 3 and
to IEC 1000-4-3, level 3
Inmunity to fast trasients Conforming to IEC 1000-4-4, level 3
Inmunity to surge voltage Conforming to IEC 1000-4-5, level 3
ASTATplus
Input voltage 17 4 7.5 7.5 11 14 3 5.5 7.5 7.5 natural QC2FDP 129729
220- 500 V 21 5.5 11 11 13 17 4 7.5 7.5 11 natural QC2GDP 129731
27 7.5 13 15 15 22 5.5 11 11 15 natural QC2HDP 129733
38 10 18.5 22 25 32 7.5 15 18.5 22 natural QC2I DP 129735
58 15 25 30 37 48 13 22 22 30 by fan QC2JDP 129737
75 22 37 45 45 63 15 30 37 37 by fan QC2KDP 129739
86 25 45 50 50 72 20 37 37 45 by fan QC2LDP 129741
126 37 63 75 80 105 30 55 55 75 by fan QC2MDP 129743
187 55 90 110 132 156 40 75 90 110 by fan QC2NDP 129745
288 80 150 165 200 240 63 110 132 160 by fan QC2QDP 129747
378 110 200 220 250 315 90 160 200 220 by fan QC2RDP 129749
444 132 220 250 315 370 110 200 220 250 by fan QC2SDP 129751
570 160 300 355 400 475 150 250 250 335 by fan QC2TDP 129753
732 220 400 450 500 610 200 315 400 400 by fan QC2UDP 129755
1020 300 560 600 750 850 250 450 530 600 by fan QC2VDP 129757
1290 395 715 750 850 1075 355 600 670 750 by fan QC2XDP 129759
UL ratings Light duty Heavy duty
N Current Maximum
rating
Ir
starting
current
(3 x Ir, 30 sec.)
200V 230V 460V
(4.5 x Ir, 30 sec.)
200V 230V 460V
Cooling
convection
Cat. No. Code
38 A A HP HP HP HP HP HP
Input voltage 14 70 3 3 - 3 3 - natural QC1FDP 129728
200- 230 V 17 85 3 3 - 3 3 - natural QC1GDP 129730
22 110 5 7.5 - 5 7.5 - natural QC1HDP 129732
34 170 10 10 - 7.5 7.5 - natural QC1I DP 129734
48 240 15 15 - 10 15 - by fan QC1JDP 129736
63 315 20 20 - 15 20 - by fan QC1KDP 129738
72 360 20 25 - 20 20 - by fan QC1LDP 129740
105 525 30 30 - 30 30 - by fan QC1MDP 129742
156 780 50 60 - 40 50 - by fan QC1NDP 129744
240 1200 75 75 - 60 75 - by fan QC1QDP 129746
315 1575 100 125 - 75 100 - by fan QC1RDP 129748
370 1850 125 150 - 100 125 - by fan QC1SDP 129750
500 2500 150 200 - 150 150 - by fan QC1TDP 129752
630 3150 200 250 - 200 200 - by fan QC1UDP 129754
850 4250 300 350 - 250 300 - by fan QC1VDP 129756
GE Power Controls
I / O terminal board specifications
Terminals Function Description
Power I / O terminals
1L1, 3L2, 5L3 Mains input 3ph input voltage according ASTATplus voltage
2T1, 4T2, 6T3 Motor output Output terminals to 3ph AC motor
A1, A2, B1, B2 110/120V AC, +10%, -15% 220/240V AC, +10%, -15%
Input control voltage
Digital inputs
57 Common for digital inputs This is a common terminal for the digital input terminals specified below
ASTATplus
1 Run Run order. Command signal may be provided by one NO dry momentary contact to terminals
1 and 57
2 Stop Stop order. Command signal may be provided by one NC dry momentary contact to terminals
2 and 57
NOTE: Run/Stop permanent command is allowed linking 1-57 and using one dry NO contact to
2-57 terminals
3 Programmable input I3 These two inputs are programmable. Can be assigned to the following internal functions:
4 Programmable input I4 - soft stop - DC brake - linear ramp
- pump control - slow speed control - dual ramp selection
- kick start - reverse slow speed - bypass function
- override - local / remote control
Command signal should be provided by one NC dry contact to terminals 57-3 or terminals 57-4.
By switching this contact ON/OFF it is possible to enable or disable the assigned function.
Digital outputs
11, 12, 14 Programmable relay 1r 11-12 = NC, 11-14 = NO dry contacts
This relay can be assigned to several internal output functions. As default assigned to
function RUN
23, 24 Programmable relay 2r 23-24 = NO dry contact
This relay can be assigned to several internal output functions. As default assigned to
function EOR
33, 34 Programmable relay 3r 33-34 = NO dry contact
This relay can be assigned to several internal output functions. As default assigned to
function DC BRAKE
Common for all relay output contacts: Maximum usage voltage 380V AC (B300 - UL) N
Thermal current 8A
AC-15 220V / 3A, 380V / 1A
39
DC-15 30V max. / 3.5A
Programable relays can be asigned to following functions:
- End of Ramp - RUN
- DC Brake - Slow speed
- Fault - Undercurrent
- Undervoltage - Overcurrent
- Overvoltage
Analogue I / O
8 Analog input common (-) This is a common terminal for the analogue input terminal number 7, and analogue output
terminal number 9
7 TG feedback input (+) 0-5V analogue input for speed feedback. It should be provided by a DC tacho-generator
coupled to the motor.
This speed feedback signal is required when the «linear ramp» function is used
9 Current output (+) 0-10V DC analog output for current measurement purpose.Ir correspond to 2Vdc.
Rated current is 2VDC.
Load impedance 10kΩ or higher
Motor thermistor terminals
5, 6 Motor thermistor input This input allows a motor thermistor with a response value from 2.8 to 3.2kW, and a reset
value from 0.75 to 1kW to control motor temperature.
When the motor thermistor is not used, a link must be used in terminals 5-6
Communications
SG, TD, RD Gr, Tx, Rx data - RS 232C, 3 wires, half duplex. Maximum cable lengths 3 m (10 feet)
- Asynchronous data transmission, 9600 bauds, 1 bit start, 8 bits data, 1 bit stop, no parity
- Supported ASCII and Modbus RTU ( selectable by user ) (*)
- Optional DeviceNet and Profibus by external moduls (*)
* Modbus RTU, DeviceNet, Profibus in development stage.
ASTATplus
I / O wiring
Control voltage
110/120V AC
Serial Comm.
RS232C 1
Control voltage 1
220/240V AC
Soft Starters
1r 2r 3r
Programmable relay outputs 3
Programmable inputs 2
I3 I4
Start / Stop
(permanent command)
4
N Start Stop
(command by push-buttons) 4
40
4
1 Control and mains wiring recommendations, see page 17 3 The programmable relay outputs are assigned to the following functions as default:
Relay 1r : RUN (RUN status)
2 The programmable inputs I3, I4 are not assigned to any function Relay 2r : EOR (End Of Ramp)
by default. Check ASTATplus user manual Relay 3r : DCBR (DC Braking Control)
Equipment installation
When installing equipment, keep the following points in mind:
! The equipment should be installed vertically and should hang over a platform or bars. The vertical position is
essential for proper cool air circulation.
! Environmental conditions are in accordance with the following ranges and maximum values:
- Operating temperature ................................................... 0 to +55ºC
- Relative humidity (without condensation) ................................ 95%
- Maximum altitude ................................................................ 3000 m.
Reduce usage intensity with 1.5% / ºC from 40ºC and 1% / 100 m. from 1000 m.
! Do not install equipment in environments containing explosive or flammable gases, or near important heat
sources.
! Equipment should be well ventilated, at least keeping clearance as indicated in illustration. (left)
! When the equipment is to be removed on a platform subject to strong vibrations, there should be an elastic base
to protect the equipment.
GE Power Controls
Thermal characteristics
The ASTATplus allows motor protection according IEC Class 10 or Class 20 and NEMA 10, 20 or 30, free
selectable by parameter «o» (overload).
ASTATplus
COLD
COLD
HOT HOT
Ir / In Ir / In
NEMA 10 NEMA 20
Time (s) Time (s)
COLD
COLD
N
41
HOT
HOT
Ir / In Ir / In
Thermal memory
NEMA 30
Time (s) If the control voltage is not removed, the unit has a cool
down characteristic, the time for cool down is 300 sec.
after the overload trip.
If the control voltage is removed after tripping, wait at
least 2 minutes before the unit can be restarted.
1
Control voltage
220/240V AC
Soft Starters
3
1r 2r 3r
Programmable relay outputs
Programmable inputs
I3 I4
1 2 3 4
The isolation contactor In this example, Start and The output relays allow for The ASTATplus is provided Use an external overload
DC1, is not required to Stop command is enabled direct action on contactors with an electronic motor protection if required by local
perform operation to the by push-buttons. according ratings specified. overload protection, which codes or to protect the motor
motor. Be aware however Permanent command is should be adequate against current unbalance.
that DC1 provides galvanic allowed as well, wiring 1, 2 protection for most of the
isolation from the incoming and 57 terminals applications.
line increasing the safety. accordingly.
1
Control voltage
220/240V AC
3
1r 2r 3r
Programmable relay outputs
Programmable inputs 3
I3 I4
Start / Stop 4
permanent
command 2 By-pass 5 Motor thermistor
1 2 3 4 5
The isolation contactor In this example, Start and The output relays allow for CAUTION: By-pass control is allowed
DC1, is not required to Stop command is enabled direct action on contactors In by-pass mode, an using external contactor
perform operation to the by push-buttons. according ratings specified. external overload relay DC2 and setting function
motor. Be aware however Permanent command is protection must be used. «2xxx» to ON
that DC1 provides galvanic allowed as well, wiring 1, 2 As alternative by-pass can
isolation from the incoming and 57 terminals be controlled from the
line increasing the safety. accordingly. outside if «zxxx» is set to
one programmable input.
GE Power Controls
Basic diagram with jog (slow speed) function
Control voltage
110/120V AC
Control voltage
1
Control voltage
220/240V AC
ASTATplus
3
1r 2r 3r
Programmable relay outputs
Programmable inputs 3
I3 I4
1 2 3 5
The isolation contactor In this example, Start and The output relays allow for protection for most of the Slow speed for forward or reverse operation
DC1, is not required to Stop command is enabled direct action on contactors applications. Use an external using programmable inputs I3, I4.
perform operation to the by push-buttons. according ratings specified. overload protection if Jog (slow speed) function:
motor. Be aware however Permanent command is required by local codes or to The slow speed function is enabled by setting
4 The ASTATplus is
that DC1 provides galvanic allowed as well, wiring 1, 2 protect the motor against «Jxxx» to I3.
isolation from the incoming and 57 terminals provided with an electronic current unbalance. For more information, check with ASTATplus
line increasing the safety. accordingly. motor overload protection,
User´s Manual.
which should be adequate
1
Control voltage
220/240V AC
3
1r 2r 3r
Programmable relay outputs
Programmable inputs 3
I3 I4
5
Start / Stop 4
permanent
command 2 Motor thermistor
1 2 3 4 5
The isolation contactor In this example, Start and The output relays allow for The ASTATplus is provided DC brake at stopping time DC brake function.
DC1, is not required to Stop command is enabled direct action on contactors with an electronic motor is provided by the DC brake The DC brake function may
perform operation to the by push-buttons. according ratings specified. overload protection, which function and external be enabled by setting
motor. Be aware however Permanent command is should be adequate contactor DC3. «Bxxx» to ON.
that DC1 provides galvanic allowed as well, wiring 1, 2 protection for most of the CAUTION: The 3 contacts For more information,
isolation from the incoming and 57 terminals applicationsUse an external of DC3 must be connected check with ASTATplus
line increasing the safety. accordingly. overload protection if in parallel. Mandatory User´s Manual.
required by local codes or between 2T1 and 4T2
to protect the motor against phases, otherwise a short-
current unbalance. circuit can occur.
ASTATplus
Control voltage
220/240V AC
Soft Starters
1r 2r 3r
Programmable relay outputs
Programmable inputs 3
I3 I4
1 2 3 4 5
The isolation contactor In this example, Start and The output relays allow for The ASTATplus is provided Linear ramp provided by
DC1, is not required to Stop command is enabled direct action on contactors with an electronic motor «Dxxx» function. A tacho
perform operation to the by push-buttons. according ratings specified. overload protection, which generator must be used as
motor. Be aware however Permanent command is should be adequate feedback.
that DC1 provides galvanic allowed as well, wiring 1, 2 protection for most of the Linear ramp function.
isolation from the incoming and 57 terminals applications. The linear ramp function
line increasing the safety. accordingly. Use an external overload may be enabled by setting
N protection if required by
local codes or to protect
«Dxxx» to ON. In this case,
linear ramp is independent
44 the motor against current of the load. This function
unbalance. needs the speed feedback
provided by an external
tacho generator.
For more information,
check with ASTATplus
User´s Manual.
GE Power Controls
Fuses, contactors and supply wiring
IEC Class 10 ratings
Cat. No. In Total Fuses Fuses Fuses Control voltage Contactor Conductor
losses aM FERRAZ type BUSSMANN type DC 1 DC 3 section
100% In (F1) (XX=according (Typower Sicu 660V~) Fuse Consumpt. (1)
A W A mech. design) Size In A VA mm2
QC _ F DP 17 67 25 6.600 CP URC 14.51/40 00 40 1 18 CL02 CL02 4
QC _ G DP 21 78 32 6.6 URD 30 XX 0063 00 50 1 18 CL03 CL03 4
QC _ H DP 27 88 40 6.6 URD 30 XX 0080 00 80 1 18 CL04 CL03 6
QC _ I DP 38 116 63 6.6 URD 30 XX 0100 00 100 1 18 CL45 CL04 10
QC _ J DP 58 208 80 6.6 URD 30 XX 0125 00 125 2 55 CL07 CL45 16
QC _ K DP 75 277 100 6.6 URD 30 XX 0160 00 160 2 55 CL08 CL06 25
ASTATplus
QC _ L DP 86 302 125 6.6 URD 30 XX 0160 00 200 2 55 CL09 CL06 35
QC _ M DP 126 389 200 6.6 URD 30 XX 0250 00 250 2 55 CK75 CL07 50
QC _ N DP 187 719 250 6.6 URD 30 XX 0315 00 315 2 78 CK08 CL10 95
QC _ Q DP 288 1097 400 6.6 URD 31 XX 0500 2 550 2 78 CK95 CK85 185
QC _ R DP 378 1286 500 6.6 URD 31 XX 0630 2 630 4 118 CK10 CK85 240
QC _ S DP 444 1374 630 6.6 URD 32 XX 0800 2 800 4 118 CK11 CK95 Busbar (2)
QC _ T DP 570 2086 800 6.6 URD 33 XX 1000 3 1000 4 118 CK12 CK10 Busbar (2)
QC _ U DP 732 2352 1000 6.6 URD 33 XX 1250 3 1250 4 248 CK12 CK10 Busbar (2)
QC _ V DP 1020 3000 1250 6.6 URD 233 XX 2000 - - 4 248 CK13 CK11 Busbar (2)
QC _ X DP 1290 3839 2x800 6.6 URD 233 XX 2000 - - 4 248 CK13 CK12 Busbar (2)
N
46
GE Power Controls
Dimensional drawings and Weights (continued)
ASTATplus
Terminals
Terminals
Cat. No. Cat. No. Cat. No. Cat. No. A Cat. No.
QC _ NDP QC _ RDP QC _ TDP QS _ UDP 6 QC _ XDP
QC _ QDP QC _ SDP QS _ VDP 10
ASTATplus
Notes
Soft Starters
N
48
GE Power Controls