Power System Protection (Directional)
Power System Protection (Directional)
Figure 10.21: Directional relay block and trip regions in the complex plane
The contacts of the overcurrent relay OC & the directional relay D are connected in series in
Figure 10.20, so that the breaker trip coil is energized only when the CT secondary current:
o Exceeds the OC relay pickup value
o In the forward tripping direction
Although construction details differ, the operating principle of an electromechanical directional
relay is similar to that of a watt hour meter.
o There are two input coils (i.e. voltage coil & current coil), both located on a stator, and there
is a rotating disc element.
o Suppose that the reference voltage is passed through a phase-shifting element to obtain
V1 V1 90
o If V1 and I = IΦ are applied to a watt-hour meter, the torque on the rotating element is
*Given V and I values, use the formula to calculate T value to determine whether relay contact
close or open. For fault in forward direction, use (Φ1 – Φ) = 90º. While for fault in reverse direction,
use (Φ1 – Φ) = -90º
b) When fault occurs at P2. Verify that the relays are either trip or not when the secondary sides
of VT is 500 300 V and CT is 10001200 A.
c) Yes, the directional overcurrent relays also protect the system against bus faults.
If the fault is at bus 2, relays at B21 and B23 will not operate, but B12 and B32 will operate
to clear the fault. B1 and B21 will operate to clear a fault at bus 1. B3 and B23 will clear a
fault at bus 3.
Zones of Protection
A fundamental concept in protection is the division of a system into protective zones.
If a fault occurs anywhere within zone, action will be taken to isolate that zone from the rest of
the system.
Zones are defined for:
o Generators
o Transformers
o Buses
o Transmission and distribution lines
o Motors
Figure 10.23 illustrates the protective zone concept.
o Each zone is defined by a closed, dashed line. For e.g.
- Zone 1 contains a generator & connecting leads to a transformer
o It may contain more than one component. For e.g.
- Zone 3 contains a generator transformer unit & connecting leads to a bus
- Zone 10 contains a transformer & a line
Since isolation during faults is done by circuit breakers, they should be inserted between
equipment in a zone and each connection to the system.
o That is breakers should be inserted in each overlap region.
o As such, they identify the boundaries of protective zones.