FR100 Series User Manual EN V1.320150325

Download as pdf or txt
Download as pdf or txt
You are on page 1of 121

FR100 Series Multifunctional Compact Inverter

FR100series inverters fast installation and commissioning guide

Step 1. Checking the inverter model No.

FR100□-4T-0.7B
Master series code of
product:
FR100:Multifunctional Brake unit:
Compact Inverter B: Built-in brake unit

Industry-specific series Adaptable Motor (kW)And


code: Type of
None:Standard Machine Motor:0.7:0.75kW(General
A~Z:Industry-specific type)
retention

Input voltage: Input voltage phases:


2:220V(-15%~+30%) S:Single-phase
4:380V(-15%~+30%) T:Three-phase

Figure 1 Produce Model No. Naming Rule


Step 2. Wirings
By step 1 to check and confirm that the purchased inverter is what user need, and
then wirings as below:
1. Main circuit wiring
Braking Resistor(Optional spares)

MCCB
(+) PB U
L1
Power L2 V M
Inverter
L3 W

Figure 2 Main Circuit Wirings


Terminal marks Designation and function of terminals.
AC power input terminals for connecting to 3-phase AC380V power
R/L1、S/L2、T/L3
supply.

U/T1、V/T2、W/T3 AC output terminals of inverter for connecting to 3-phase induction motor.

(+)、(-) Positive and negative terminals of internal DC bus.


Positive and negative terminals of internal DC bus. Connecting terminals
PB
of braking resistor. One end connected to + and the other to PB.
Grounding terminal.
2. Control circuit wirings
Different control circuit wirings for different applications, for FRECON product
quick-menu, here take some normal-used wirings as example below:

-1-
FR100 Series Multifunctional Compact Inverter

DI1 DI2 DI3 DI4 DI7/HI GND 485+ 485- R1A R1B R1C
+24V GND Y1 +10V AI1 AI2 AO1 PE

Figure 3 FR100 series Control Terminal Diagrams


2.1 Frequency given by keypad potentiometer, start or stop the machine controlled by
RUN and STOP button on keypad. Control circuits no need to be wired, directly work with
power on.
2.2 Frequency given by external potentiometer, start or stop the machine controlled by
external switch, Control circuit wirings as below:
FWD/STOP

DI1
REV/STOP

DI2

GND

Inverter
GND

Potentiometer AI1

+10V

Figure 4 Control terminal wirings


Parameters need to be set as below:
F01.01 Main frequency source given mode 2: AI1 2
F02.00 Start/stop command source selection 1: External terminal (LED light turn on) 1
2.3 Frequency given by PID, start/stop controlled by external switch, take constant
pressure water supply as an example, control wirings as below:

FWD/STOP
DI1
REV/STOP
DI2
GND

+10V
Inverter
400R

Resistance type
pressure gauge AI1

GND

Figure 5 Control Terminal Wirings

-2-
FR100 Series Multifunctional Compact Inverter
Parameters need to be set as below:
F01.01 Main frequency source given mode 6: Process PID 6
1: External terminal (LED light
F02.00 Start/stop command source selection 1
turn on)
F13.01 PID Digital Given 0.0~100.0% 25.0%
F13.08 Proportional Gain Kp1 0.0~100.0 1.0
F13.09 Integration Time Ti1 0.01~10.00s 0.10s

3. Integrated Wirings Diagram


In many cases, besides the above control wirings, inverter’s fault signal and frequency signal
need to be transferred to upper machine, control signal output and fault reset function added
base on figure 2.2 application mode, inverter’s integrated wirings diagram as below:
Braking resistor(Optional spare)

MCCB P
(+) U
L1 B

Power L2 V M
L3 W

FWD/STOP Inverter
DI1
REV/STOP
DI2
Fault reset AO1
DI3
Analog
voltmeter
GND
GND

GND R1A
Potentiometer AI1 R1B
Fault output
R1C
+10V

Figure 6 Integrated Wirings

Step 3 Operations and Display Interface Introduction


Operation panel is a Human-Machine-Interface (HMI), which can change the inverter
function parameter, monitor the inverter work situation, control the inverter run/stop, etc.
The appearance and functional area as below:

Figure 7 Operation panel diagram


3.1 Operation panel button and potentiometer function
There are 8 buttons and 1 analog potentiometer, functions of every button as table 1.
-3-
FR100 Series Multifunctional Compact Inverter
Table 1 Operation Panel Buttons Function Table
Symbol Name Function
Escape Enter or exit Level I menu
Enter the menu interfaces level by level, and
Enter
confirm the parameter setting
Increment Increase data or function code

Decrement Decrease data or function code


Select the displayed parameters in turn in the stop
Shift or running state, and select the digit to be modified
when modifying parameters
Perform function switchover (such as jog run and
quick switchover of
Multifunction
command source or direction) according to the
setting of F16.00
potentiometer With the same function as AI1/AI2

Run Start the inverter in the keypad control mode


Stop the inverter when it is in the running state and
perform the reset operation when it is in the fault
Stop/Reset
state. The functions of this key are restricted in
F16.01.
The inverter will free stop when the run and stop
+ Key combinations
key are pressed simultaneously
3.2 Quick-menu (user customized parameters) instruction
For ease of normal-used parameters quick setting, FR series inverters software
version higher than V1.07, factory menu mode changed to quick-menu (F00.01=1),
default quick parameters refer to schedule.
Display difference between quick menu and basic menu (F00.01=0) is 2nd grade, for
ease of user distinguish the difference and switch method as below:
Menu Mode Quick Menu Basic Menu
Display
Difference
F01.01. F01.01 Function code last digit
Function code last
(2nd) digit with decimal point, no flash. no decimal point, flash.

1、Press or , set 1、Press or , switch up or


function code switch up or down down according to order of function
Functional according to F17 group. code 01, 02…
Distinction
2、 Press can’t go back 1st 2、Press can go back to 1st grade
grade menu. F01
menu.( )
Method 1, switch to basic menu Method 1, switch to quick menu by
by changing F00.01=0. changing F00.01=1.
Method 2, when show 2nd menu, Method 2, when show 2nd menu, keep
Inter-switch
keep press button, press button, auto-switch to
auto-switch to basic menu. quick-menu.

If the default quick-parameters can’t meet the user demand, user can self-define
the quick-parameters according to the actual situation; detailed method is to change F17
group function code.
F17 group supply max 30 groups of user customized parameters, F17 group
parameter show value 00.00, means the user function code is null. When entering
-4-
FR100 Series Multifunctional Compact Inverter
user-defined parameter mode, displayed function code defined by F17-00~F17-29, order
keep the same with F17 group, skip on 00.00. Two digits in left side of decimal point mean
function code group, right side mean the position of the function code group. For example:
05.15 means F05.15. F00~F20 group corresponds to decimal point left side two digits
00~20, U00 and U01 group corresponds to 48 and 49. Set as 21~46 mean the user
function code null. When right side 2 digits per group more than setting group function
code number, also mean user function code null.
Appendix:shortcut menu factory parameter
Param. Parameter Name Setting Range Default Attr
Setting of User
F00.00 0~65535 0 ×
Password
0: Display all parameters
1: Only display F00.00, F00.01 and
Display of user-defined parameters
F00.01 1 ×
Parameters F17.00~F17.29
2: Only display A0-00, A0-01, and the
parameters different with factory default
0:Master digital setting (F01.02)
1: keypad potentiometer
2: Analog input AI1
3: Communication
Master Frequency
F01.01 4: Multi-reference 1 ×
Command Source
5: PLC
6: Process PID output
7: X7/HI pulse input
8:AI2
0: Keypad control (LED off)

F02.00 Run command 1: Terminal control (LED on) 0 ×


2: Communication control (LED
blinking)
0: Forward
F02.01 Running direction 0 △
1: Reverse
0: Ramp to stop
F02.12 Stop mode 0 ×
1: Coast to stop

F03.00 Accel time 0 0.0~6000.0s 15.0s △

F03.01 Decel time 0 0.0~6000.0s 15.0s △


Function of
F04.00 0: No function 1 ×
terminal DI1
Function of
F04.01 1: Running forward (FWD) 2 ×
terminal DI2
Function of
F04.02 2: Running reverse (REV) 7 ×
terminal DI3
Function of
F04.03 3: Three-wire control 13 ×
terminal DI4
-5-
FR100 Series Multifunctional Compact Inverter
Relay 1 output
F05.02 2: Fault output 2 ×
function
Power rating of Model
F08.01 0.1~1000.0kW ×
motor 1 defined
Rated voltage of Model
F08.02 60~660V ×
motor 1 defined
Rated current of Model
F08.03 0.1~1500.0A ×
motor 1 defined
Rated frequency Model
F08.04 20.00~Fmax ×
of motor 1 defined
Rated speed of Model
F08.05 1~30000 ×
motor 1 defined
0: No autotuning
Autotuning of 1: Static autotuning of async motor
F08.30 0 ×
motor 1
2: Rotary autotuning of async motor

Unit's place: Bus undervoltage


0: Fault reported and coast to stop
1: Stop according to the stop mode
2: Fault reported but continue to run

Protection action 3: Fault protection disabled


F11.10 03000 ×
1 Ten's digit :Power input phase
Loss (Err09)(Same as unit's place )
Hundred's digit :Power output
phase loss(Err10)(Same as unit's place )
Thousand's digit:Motor overload
(Err11)(Same as unit's place )
Ten thousand's digit:Inverter
overload(Err11)(Same as unit's place )
0: F13.01 digital setting
1:keypad potentiometer
2:AI1
F13.00 PID setting 3: Communication 0 ×
4:Multi-Reference
5: DI7/HI pulse input
6: AI2

F13.01 PID digital setting 0.0~100.0% 50.0% △

0:AI1
F13.02 PID feedback 1:AI2 0 ×
2: Communication
Proportional gain
F13.08 0.0~100.0 1.0 △
Kp1
Integration time
F13.09 0.01~10.00s 0.10s △
Ti1

-6-
FR100 Series Multifunctional Compact Inverter

Preface

Thank you for choosing FRECON developed and produced FR100 series
multifunctional compact inverter.
FR100 Series multifunction compact inverter is a compact, feature-rich, and highly
price-competitive models.Particularly suitable for electronic equipment, food packaging, woodworking,
treadmills and other small power transmission applications. This user manual presents a detailed
description of FR100 series multifunction compact inverter product characterization, structural features,
parameter setting, operation and commissioning, maintenance inspection, and other contents. Make
sure to carefully read the safety precautions before application, and use this product on the premise
that personnel and equipment safety is ensured.

IMPORTANT NOTES
◆To illustrate the details of some of the products ,in this manual have outer casing or safety
shields be removed picture .When using this product, please be sure to install a good outer
casing or covering, and in accordance with the contents of the manual operation.
◆The illustrations this manual for illustration only and may vary with different products you have
ordered.
◆The company is committed to continuous improvement of products, product features will
continue to upgrade, the information provided is subject to change without notice.
◆If you are using have questions, please contact our regional agents or our customer service
center. Customer Service Tel 0755 -33067999.
◆The company's other products please visit our website.http://www.frecon.com.cn

-7-
FR100 Series Multifunctional Compact Inverter

-8-
FR100 Series Multifunctional Compact Inverter

Table of Contents

Preface .......................................................................................................................................................... - 7 -
Table of Contents ....................................................................................................................................... - 9 -
Chapter 1 Safety Precautions ................................................................................................................ - 11 -
1.1 Safety Considerations .................................................................................................................... - 11 -
1.2 Precautions ...................................................................................................................................... - 12 -
Chapter 2 Product Information .............................................................................................................. - 14 -
2.1 Nameplate information ................................................................................................................... - 14 -
2.2 Information of FR100 Product Model ........................................................................................... - 15 -
2.3 Technical Features of FR100 ........................................................................................................ - 15 -
2.4 Parts Drawing .................................................................................................................................. - 17 -
2.5 External Dimensions of Keypad .................................................................................................... - 18 -
2.6 Configuration, Mounting Dimensions and Weight....................................................................... - 18 -
Chapter 3 Installation and Wiring ......................................................................................................... - 20 -
3.1 Installation Environment ................................................................................................................. - 20 -
3.2 Installation Direction, Space and Cooling .................................................................................... - 20 -
3.3 Fixed manner .................................................................................................................................. - 20 -
3.4 Remove & Mount Keypad and Cover ........................................................................................... - 21 -
3.5 Dust cover installation and removal(Optional accessories).................................................. - 22 -
3.6 Configuration of Peripheral Devices ............................................................................................. - 23 -
3.7 Wiring way ....................................................................................................................................... - 24 -
3.8 Terminal Configuration ................................................................................................................... - 25 -
3.9 EMI Solutions .................................................................................................................................. - 30 -
Chapter 4 Operation and display .......................................................................................................... - 32 -
4.1 Introduction of Keypad ................................................................................................................... - 32 -
4.2 Viewing and Modifying Function Codes ....................................................................................... - 34 -
4.3 Viewing Status Parameters............................................................................................................ - 35 -
4.4 Motor Auto-tuning ........................................................................................................................... - 35 -
4.5 Password Setting ............................................................................................................................ - 35 -
4.6 Keypad lock ..................................................................................................................................... - 35 -
4.7 Shortcut menus function code description................................................................................... - 36 -
Chapter 5 List of Parameter ................................................................................................................... - 37 -
5.1 Standard Function Parameters ..................................................................................................... - 38 -
Chapter 6 Specification of Parameters ................................................................................................ - 58 -
Group F00 System Parameters ........................................................................................................... - 58 -
Group F00 Frequency command ........................................................................................................ - 60 -
Group F02 Start/Stop Control Start/Stop Control ............................................................................... - 63 -
Group F03 Accel/Decel Parameters ................................................................................................... - 66 -
Group F04 Digital Input......................................................................................................................... - 68 -
Group F05 Digital Output ..................................................................................................................... - 75 -
Group F06 Analog and Pulse Input ..................................................................................................... - 79 -
Group F07 Analog and Pulse Output .................................................................................................. - 82 -
Group F08 Parameters of Motor 1 ...................................................................................................... - 82 -
Group F09 V/f Control Parameters of Motor 1 ................................................................................... - 83 -

-9-
FR100 Series Multifunctional Compact Inverter
Group F11 Protection Parameters...................................................................................................... - 88 -
Group F12 Multi-Reference and Simple PLC Function.................................................................... - 92 -
Group F13 Process PID ....................................................................................................................... - 96 -
Group F14 Swing Frequency, Fixed Length,Count and Wakeup ................................................... - 98 -
Group F15 Communication Parameters .......................................................................................... - 101 -
Group F16 Keys and Display of Keypad Parameters .................................................................... - 102 -
Group F17 User-defined Display Parameters ................................................................................. - 102 -
Group U00 Status Monitoring ............................................................................................................ - 103 -
Group U01 Fault Record.................................................................................................................... - 105 -
Chapter 7 Maintenance and Troubleshooting ................................................................................. - 106 -
Chapter 8 Maintenance and Inspection .............................................................................................- 110 -
8.1 Inspection .......................................................................................................................................- 110 -
8.2 Maintenance .................................................................................................................................. - 111 -
Appendix A: Modbus Communication Protocol ..............................................................................- 113 -
Appendix B: Accessories......................................................................................................................- 119 -
B.1 Braking Resistor............................................................................................................................- 119 -
B.2 Uploading and Downloading Module..........................................................................................- 119 -

- 10 -
FR100 Series Multifunctional Compact Inverter

Chapter 1 Safety Precautions

Safety Precautions
Safety signs in this manual:
DANGER: indicates the situation in which the failure to follow operating requirements may result
in fire or serious personal injury or even death.
CAUTION: indicates the situation in which the failure to follow operating requirements may cause
moderate or slight injury and damage to equipment.
Users are requested to read this chapter carefully when installing, commissioning and repairing
this product and perform the operation according to safety precautions as set forth in this chapter
without fail. FRECON will bear no responsibility for any injury and loss as a result of any violation
operation.
1.1 Safety Considerations
Safety
The use phase Considerations
class
◆Do not install the product if the package is with water, or
component is missing or broken.
Danger ◆Do not install the product if the label on the package is not
identical to that on the inverter.
Before ◆Be careful of carrying or transportation. Risk of devices
Installation damage.
◆Do not use damaged product or the inverters missing
Caution component .Risk of injury.
◆Do not touch the parts of control system with bare hands. Risk
of ESD hazard.
◆Installation base shall be metal or other non-flammable
material. Risk of fire.
◆Do not install inverter in an environment containing explosive
Danger gases, otherwise there is danger of explosion.
◆Do not unscrew the fixing bolts, especially the bolts with red
mark.
Installation
◆Do not leave cable strips or screws in the inverter. Risk of
inverter damage.
◆Install the product at the place with less vibration and no direct
Caution sunlight.
◆Consider the installation space for cooling purpose when two
or more inverters are placed in the same cabinet.
◆Wiring must be performed by authorized and qualified
personnel. Risk of danger.
◆Circuit-breaker should be installed between inverter and the
mains. Risk of fire.
◆Make sure the input power supply has been completely
disconnected before wiring. Failure to comply may result in
personnel injury and/or equipment damage.
◆Since overall leakage current of this equipment may be bigger
Wiring than 3.5mA, for safety's sake, this equipment and its associated
Danger
motor must be well grounded so as to avoid risk of electric
shock.
◆Never connect the power cables to the output terminals (U/T1、
V/T2、W/T3) of the AC drive. Pay attention to the marks of the
wiring terminals and ensure correct wiring. Failure to comply will
result in damage to the AC drive.
◆Install braking resistors at terminals (+)and PB only. Failure to
- 11 -
FR100 Series Multifunctional Compact Inverter
comply may result in equipment damage.
◆AC 220V signal is prohibited from connecting to other
terminals than control terminals R1A、R1B、R1C andR2A、R2B、
R2C. Failure to comply may result in equipment damage.
◆Since all adjustable frequency AC drives from FRECON have
been subjected to hi-pot test before delivery, users are
prohibited from implementing such a test on this equipment.
Failure to comply may result in equipment damage.
◆Signal wires should to the best of the possibility be away from
Caution main power lines. If this cannot be ensured, vertical
cross-arrangement shall be implemented, otherwise interference
noise to control signal may occur.
◆If motor cables are longer than 100m, it is recommended
output AC reactor be used. Failure to comply may result in faults.
◆Inverter shall be power-on only after the front cover is
Danger assembled. Risk of electrical hazard.
◆Verify that the input voltage is identical to the rated voltage of
Before
product, correct wiring of input terminals R/L1, S/L2, and T/L3
Power-on
and output terminals U/T1, V/T2, and W/T3, wiring of inverter
Caution
and its peripheral circuits, and all wires should be in good
connection. Risk of inverter damage.
◆Do not open the cover after power.Rick of electrical hazard.
◆Do not touches any input/output terminals of inverter with bare
Danger
hands. Rick of electrical hazard.
After Power-on
◆If auto tuning is required, be careful of personal injury when
motor is running. Risk of accident.
Caution ◆Do not change the defaults of parameters. Risk of devices
damage.
◆Non-professionals shall not detect signals during operation.
Risk of personal injury or device damage.
Danger ◆Do not touch the fan or the discharging resistor to check the
During temperature. Failure to comply will result in personal burnt.
Operation ◆Prevent any foreign items from being left in the devices during
operation. Risk of device damage.
Caution ◆Do not control start/stop of inverter by ON/OFF of contactor.
Risk of device damage.
◆Maintenance and inspection can only be performed by
professionals . Risk of personal injury.
◆Maintain and inspect devices after power is off. Risk of
electric hazard.
◆Repair or maintain the AC drive only ten minutes after
the AC drive is powered off. This allows for the residual
Maintenance
Danger voltage in the capacitor to discharge to a safe value.
Failure to comply will result in personal injury.
◆All pluggable components can be inserted or pulled out
only when power has been turned off.
◆Set and check the parameters again after the AC drive
is replaced.
1.2 Precautions
1.2.1 Motor Insulation Inspection
When the motor is used for the first time or when the motor is reused after being kept, or when
periodical inspection is performed, insulation inspection shall be conducted with motor so as to avoid
damaging the inverter because of the insulation failure of the motor windings. The motor wires must be
disconnected from the inverter during the insulation inspection. It is recommended to use the 500V
mega meter, and the insulating resistance measured shall be 5MΩ at least.
1.2.2 Motor Thermal Protection
If the motor rating does not match that of the inverter, especially when the rated power of the

- 12 -
FR100 Series Multifunctional Compact Inverter
inverter is higher than that of the motor, adjust motor protection parameters in the inverter or install
thermal relay to protect motor.
1.2.3 Operating with the Frequency Higher than Grid Power Frequency
Output frequency of FR100 is 0.00Hz~600.00Hz. If FR100 is required to operate above 50.00Hz,
please take the endurance of mechanical devices into consideration.
1.2.4 Mechanical Vibrations
Inverter may encounter mechanical resonance point of the load device at certain output
frequencies which can be avoided by setting the skip frequency parameters of the inverter.
1.2.5 Motor Heat and Noise
Since output voltage of inverter is PWM wave and contains a certain amount of harmonics, so
that the temperature, noise and vibration of the motor will be higher than those when the inverter runs
at grid power frequency.
1.2.6 Voltage-sensitive device or capacitor on output side of the AC drive
Do not install the capacitor for improving power factor or lightning protection voltage-sensitive
resistor on the output side of the AC drive because the output of the AC drive is PWM wave.
Otherwise, the AC drive may suffer transient over-current or even be damaged.
1.2.7 Contactor at the I/O terminal of the AC drive
When a contactor is installed between the input side of the AC drive and the power supply, the AC
drive must not be started or stopped by switching the contactor on or off. If the AC drive has to be
operated by the contactor, ensure that the time interval between switching is at least one hour since
frequent charge and discharge will shorten the service life of the capacitor inside the AC drive.
When a contactor is installed between the output side of the AC drive and the motor, do not turn off the
contactor when the AC drive is active. Otherwise, modules inside the AC drive may be damaged.
1.2.8 Applied with the Rated Voltage
Apply FR100 with the rated voltage. Failure to comply will damage inverter. If required, take a
transformer to boost or step-down voltage.
1.2.9 Do Not Apply a 3-Phase Input Inverter to 2-Phase Input Applications
Do not apply a 3-phase input FR inverter to 2-phase input applications. Otherwise, it will result in
faults or damage inverter.
1.2.10 Lightning Protection
FR100 has integrated lightning over-current protection device which has certain self-protection
capacity against the lightning. Additional protection devices have to be installed between inverter
and power supply in the area where lightning occurs frequently.
1.2.11 Altitude De-rating
In places where the altitude is above 1000 m and the cooling effect reduces due to thin air, it is
necessary to de-rate the AC drive. Contact FRECON for technical support.
1.2.12 Some Special Usages
If wiring that is not described in this manual such as common DC bus is applied, contact the agent
or FRECON for technical support.
1.2.13 Cautions for Inverter Disposal
The electrolytic capacitors on the main circuit and PCBA may explode when they are burnt.
Emission of toxic gas may be generated when the plastic parts are burnt. Please dispose inverter as
industrial wastes.
1.2.14 Adaptable Motor
The standard adaptable motor is adaptable four-pole squirrel-cage asynchronous induction motor
or PMSM. For other types of motor, select a proper AC drive according to the rated motor current.
The cooling fan and rotor shaft of non-variable-frequency motor are coaxial, which results in
reduced cooling effect when the rotational speed declines. If variable speed is required, add a more
powerful fan or replace it with variable-frequency motor in applications where the motor overheats
easily.
The standard parameters of the adaptable motor have been configured inside the AC drive. It is
still necessary to perform motor auto-tuning or modify the default values based on actual conditions.
Otherwise, the running result and protection performance will be affected.
The AC drive may alarm or even be damaged when short-circuit exists on cables or inside the
motor. Therefore, perform insulation short-circuit test when the motor and cables are newly installed or
during routine maintenance. During the test, make sure that the AC drive is disconnected from the
tested parts.

- 13 -
FR100 Series Multifunctional Compact Inverter

Chapter 2 Product Information

2.1 Nameplate information

Fig.2-1 Nameplate information

Model Explanation
Model show on product nameplate contains information below

FR100□-4T-0.7B
Master series code of
product:
FR100:Multifunctional Brake unit:
Compact Inverter B: Built-in brake unit

Industry-specific series Adaptable Motor (kW)And


code: Type of
None:Standard Machine Motor:0.7:0.75kW(General
A~Z:Industry-specific type)
retention

Input voltage: Input voltage phases:


2:220V(-15%~+30%) S:Single-phase
4:380V(-15%~+30%) T:Three-phase

Fig.2-2 Model Explanation

- 14 -
FR100 Series Multifunctional Compact Inverter
2.2 Information of FR100 Product Model
Table 2-1 FR100 Product model and technical data
Power Rated Input Rated output
Applicable motor
Model No. capacity current current
kW HP
KVA A A
Single-Phase:220V,50/60Hz Range:-15%~+30%
FR100-2S-0.2B 0.5 4.9 1.6 0.18、0.2、0.25 0.25
FR100-2S-0.4B 1.0 6.5 2.5 0.37、0.4 0.5
FR100-2S-0.7B 1.5 9.3 4.2 0.75 1.0
FR100-2S-1.5B 3.0 15.7 7.5 1.5 2
FR100-2S-2.2B 4.0 24 9.5 2.2 3
3-Phase:380V,50/60Hz Range:-15%~+30%
FR100-4T-0.7B 1.5 3.4 2.5 0.75 1
FR100-4T-1.5B 3.0 5.0 4.2 1.5 2
FR100-4T-2.2B 4.0 5.8 5.5 2.2 3
FR100-4T-4.0B 6.0 11 9.5 3.7、4 5
2.3 Technical Features of FR100
Table 2-2 Technical features of FR100
Project Specifications
Rated input Single-Phase 220V(-15%~+30%)
voltage (V) 3-phase 380 V (-15%~+30%)
Rated input
See table 2-1
Power input current (A)
Rated input
frequency 50Hz/60Hz,tolerance±5%
(Hz)
Applicable
See table 2-1
motor(kW)
Rated output
See table 2-1
current(A)
The
maximum
Power output output 0~rated input voltage, error<±3%
voltage(V)
The
maximum
output 0.00~600.00 Hz,unit0.01Hz
frequency
(Hz)
V/f control
V/f patterns Sensor-less vector control 1
Sensor-less vector control 2
1:50 (V/f control)
Speed range 1:100 (sensor-less vector control 1)
1:200 (sensor-less vector control 2)
Control Speed ±0.5% (V/f control)
characteristics accuracy ±0.2% (sensor-less vector control 1、2 )
Speed
±0.3% (sensor-less vector control 1、2 )
fluctuation
Torque
< 10ms (sensor-less vector control 1、2 )
response
Starting 0.5Hz: 180% (V/f control, sensor-less vector control 1)
torque 0.25Hz:180%(sensor-less vector control 2)
Basic functions Carrier
0.7kHz~16kHz
frequency
- 15 -
FR100 Series Multifunctional Compact Inverter
Overload G Model:150% Rated Current 60s,180% Rated Current
capability 10s,200% Rated Current 1s.
Automatic torque boost;Manual torque boost 0.1%~
Torque boost
30.0%
Three ways:Three ways: straight; multi-point type; N
V/F Curve Th-type V / F curve(1.2 Th -type、1.4 Th -type、1.6 Th
-type、1.8 Th -type、2 Th -type)
Acceleration Line or curve acceleration and deceleration mode.
and
Four kinds of acceleration and deceleration time,Ramp
deceleration
Curve Time Range :0.0~6000.0s
DC brake start frequency: 0.00~600.00Hz
DC brake DC brake time:0.0s~10.0s
DC brake current:0.0%~150.0%
Jog frequency range:0.00Hz~50.00Hz.
Jog brake
Jog deceleration time: 0.0s~6000.0s.
Simple PLC、 Through the built-in PLC or control terminal to achieve up
Multi-speed to 16 speed running
Facilitate the realization of process control loop control
Built-in PID
system
Basic functions Automatic
voltage When the grid voltage changes, can automatically
adjustment maintain a constant output voltage
(AVR)
Fast current
Minimize over current fault protection inverter running
limit function
Over voltage System automatically limits of current and voltage during
Over current operation to prevent frequent
Command Given the control panel, control terminal, serial
source communication port given.
Sevkeinradlswoafysfrtoeqsuweintcchy sources: digital
setting, keyboard potentiometer setting, analog
Frequency
Voltage, given analog current reference pulse is given,
given
the serial port is given, multi-speed given, PLC is given,
the process PI D reference. There are several ways to
Run switch
5Switch input terminals, one way to make high-speed
Input
pulse input.
terminal
2-channel analog inputs,1-way voltage and current
options,1- way to support input
1-way switch output terminal
output
1 relay output terminals
terminal
1 analog output terminal, and optional voltage and
current.
Parameter copy 、parameter backup 、flexible parameter displayed &
hidden. Common DC bus(Contains below 30 KW).
Various master & auxiliary command and switchover.
Reliable speed search started.
A variety of Accel / Decel curves programmable.
Featured
Timing control、 fixed length control、count function.
functions
Three faults recorded.
Over excitation brake、overvoltage stall protection programmable、under
voltage stall protection programmable、restart upon power loss.
Four kinds of Accel/Decel time.
Motor thermal protection.
Flexible fan control.
- 16 -
FR100 Series Multifunctional Compact Inverter
Process PID control、simple PLC、16-step speed control programmable.
Wobble frequency control.
Multi-functional key programmable、field-weakening control.
High-precision torque control、V/f separated control、torque control at
sensor-less vector control.
Protection Provide fault protection dozen:Overcurrent、Overvoltage、Undervoltage、
function Overtemperature、Overload Etc Protection.
LED Display Display Parameters
Key lock and
Realize some or all of the keys locked, scope definition
function
Display and section keys to prevent misuse
selection
keyboard
Run and stop
In the run or stop can be set to monitor U00 group four
monitoring
objects were.
information
Indoors, no direct sunlight, free from dust, corrosive
Place of gases,
operation flammable gases, oil mist, water vapor, water drop and
salt, etc.
0~2000m
Altitude De-rate 1% for every 100m when the altitude is above
1000 meters
Environment
Ambient
-10℃~40℃
temperature
Relative
5~95%, no condensation
humidity
Vibration Less than 5.9m/s2 (0.6g)
Storage
-20℃~+70℃
temperature
Efficiency Rated power≥93%
Installation Wall-mounted or DIN-rail mounting
Others IP grade IP20
Cooling
Fan cooled
method

2.4 Parts Drawing


DIN-rail release button

Cooling air outlet Mounting holes

Upper case
Dust cover
(Optional accesories)

Keypad
Nameplate

Lower case
Terminals cover

Fan cover

Fig 2-3 Outline example

- 17 -
FR100 Series Multifunctional Compact Inverter
2.5 External Dimensions of Keypad

Fig 2-4 Keyboard size diagram


External keyboard installation instruction:
1. first install the panel according to inverter’s power range corresponding to the size of hole as shown
on scheme 2-5, After that insert keyboard pad into the mounting panel and then insert the keyboard
module into the keyboard pad.(Before removing the keyboard pad, first remove the keyboard, then
remove as shown in the scheme)

+0.5 Keypad assembly Keypad tray Mounting plate


64-0
(The thickness of the
1 plate can`t be more
2 than 1.5 mm)
+0.5
99-0

Press 4 hooks on both sides of the


Hole size of mounting plate mounting ,the keypad tray will be get out

Fig 2-5 External keyboard installation whole size diagram


2.6 Configuration, Mounting Dimensions and Weight

Fig 2-6 Product size chart


- 18 -
FR100 Series Multifunctional Compact Inverter
Table 2-3 Configuration, mounting dimensions and weight
External and installation dimensions(mm)
N.W
Model Install Install (Kg)
W H D W1 W2 H1 H2 H3 H4 Hole Hole
d1 d2

Single-Phase:220V,50/60Hz
FR100-2S-0.2B

FR100-2S-0.4B 95 162 120 85 11 151.5 152 110.8 130 4.5 4.5 1.1

FR100-2S-0.7B
FR100-2S-1.5B
110 173 135 100 11 163 163 121.8 140.5 4.5 5 1.5
FR100-2S-2.2B

3-Phase:380V,50/60Hz
FR100-4T-0.7B
FR100-4T-1.5B
110 173 135 100 11 163 163 121.8 140.5 4.5 5 1.5
FR100-4T-2.2B

FR100-4T-4.0B

- 19 -
FR100 Series Multifunctional Compact Inverter

Chapter 3 Installation and Wiring

3.1 Installation Environment


1) Ambient temperature in the range of -10℃~50℃.
2) Drive should be installed on surface of flame retardant object, with adequate surrounding space for
heat dissipation.
3) Installation should be performed where vibration is less than 5.9m/s2 (0.6g).
4) Avoid from moisture and direct sunlight.
5) Protect the cooling fan by avoiding oil, dust and metal particles.
6) Do not expose to an atmosphere with flammable gases, corrosive gases, explosive gases or other
harmful gases.
7) Prevent drilling residues, wire ends and screws falling into drive.
8) Ventilation part of the drive should be installed outside from harsh environment (e.g. Textile facilities
with fiber particles and chemical facilities filled with corrosive gases or Loaded dust cover).
3.2 Installation Direction, Space and Cooling
A fan is integrated in FR100 for forced air cooling. FR100 has to be installed vertically for the purpose
of good cooling circulation. Sufficient spaces have to be left between FR100 and its peripheral objects.
Multi- FR100 can be installed in parallel horizontally e and vertically. See followings for specific space
requirement, heat dissipating capacity and mass airflow.
>100mm

>100mm

>100mm
>100mm

Air outlet Direction

>50mm >50mm >100mm


>100mm

(a)Inverter transversely-mounted diagram (b)Inverter vertical-mounted diagram


Fig 3-1 Installation methods
3.3 Fixed manner
a.Four-hole fixation
Size of four holes (Hole a) refer to product dimensions and installation dimensions,as the figure
below 3-2(a), drilling four holes in the mounting surface and put inverter against the mounting surface
with four holes level,and then insert screws into four holes and fixed (any two of the four holes on the
cross installed is available, all four holes screwed for enhanced installation, screw size is M4*L(Length
L longer than 12mm,torque 1N.m±10%).
b.Three-hole fixation
Size of three holes (Hole b) refer to product dimensions and installation dimensions,as the figure
below 3-2(b), drilling three holes in the mounting surface and insert three screws into mounting surface,
no tight, reserving an appropriate distance between screw washer and mounting surface (7.5~9mm),
and then hang the inverter from top to bottom with 3 screws(M4*L, length L longer than 16mm, torque
1N.m±10%) and tight two screws at the lower end.
c.DIN Slot Rail fixation(Using 35mm DIN Rail)
- 20 -
FR100 Series Multifunctional Compact Inverter
Installation size of DIN rail mounting refer to product dimension and installation dimension. Install
or remove the inverter as figure 3-2(c), please press the buckle release key of DIN rail when installing
or removing the inverter.
Hole A Hole A

Hole B

DIN-rail

Hole A Hole A Hole B Hole B

(a)Four-hole fixation (b)Three-hole fixation (c)DIN Slot Rail fixation


Fig3-2 Fixation

Do not take the sunken screws as shown in the


picture. Otherwise, inverter may be damaged

Take screws combined with springs and plain gaskets to


Install inverter.

3.4 Remove & Mount Keypad and Cover


a. Remove keypad: Disassemble keypad. See following Figure: 3-3(a)Push the buckle on
the keypad in Direction 1 first, and then lift up the keypad in Direction 2.
b. Mount keypad: Assemble keypad. See following Figure:3-3(b) Place keypad in the slot in
Direction 1, and then press the keypad in Direction 2 until it clicks into right place.
c. Disassembly of Terminal Cover:loosen the captive cover screws as shown in Fig.3-3(c),then
remove terminal cover in the direction as shown in the Figure below.
d. Assemble of Terminal Cover: See following Figure: 3-3(d)Place the upper buckle of the terminal
cover in the slot of upper housing in Direction 1, and then press the two lower buckle of terminal cover
I Direction 2 until it clicks into right place of upper housing. , then Tighten the screws as shown in
Fig.3-3

2
1

1
1

Fig.3-3 (a) Remove keypad Fig.3-3 (b) Mount keypad

- 21 -
FR100 Series Multifunctional Compact Inverter

1
2
(c)Disassembly of Terminal Cover (d)Assemble of Terminal Cover
Fig.3-3 Remove & Mount Keypad and Cover
3.5 Dust cover installation and removal(Optional accessories)
a. Install dust cover:The dust cover shown in Fig3-4 parallel to the housing assembly(No cock
around is installed).
b. Removing dust cover:cording to the dust cover arrow direction, at one end of the dust cover
and hard to lift the dust cover under the desirable.

Fig.3-4Dust cover installation and removal

- 22 -
FR100 Series Multifunctional Compact Inverter
3.6 Configuration of Peripheral Devices
power source

circuit breaker

contactor FR100 Inverter

+/PB Braking
U/V/W resistor
Input chokes

R/S/T Output filter

Input filter
Output AC
reactor

motor

Fig.3-5 Standard configuration of peripheral device


Table 3-1 Instructions of peripheral devices
Picture Device Instructions
Cable Transmitting electrical signals.
Purpose: disconnect power supply and protect the
equipments in case of abnormal overcorrect occurs
Type selection: breaking current of circuit breaker is
Circuit
defined to be 1.5~2 times the rated current of the
breaker
drive Breaking time characteristic of circuit breaker
should be selected based on
overload protection time characteristic of the drive
Improve power factor Reduce the impact of
imbalanced three-phase input AC power supply on
the system Suppress higher harmonics and reduce
Input chokes
the conducted and radiated interference to peripheral
devices Restrict the impact of impulse current on
rectifier bridges
Reduce conducted interference from power supply to
the drive, improve the immunity of the drive from noise
Input filter
Reduce conducted and radiated interference of the
drive to peripheral device
Braking Purpose: consume motor feedback energy to attain
resistor quick brake

- 23 -
FR100 Series Multifunctional Compact Inverter
Output filter and radiated interference of the drive to
Output filter
peripheral devices
Avoid the motor insulation damage result from
harmonic voltage Reduce frequent protection from the
Output AC
drive caused by leakage current In case the cable
reactor
connecting drive and motor is over 100 meters, output
AC reactor recommended
3.6.1 Selection of Peripheral Devices
Table 3-2 Selection of peripheral devices
Cable(mm2) Circuit
contactor
Model L1、L2、L3 (+)、(-)、 breaker
(A)
U、V、W PE (A)
PB
Single-Phase:220V
FR100-2S-0.2B 1.5 1.5 1.5 1.5 10 10
FR100-2S-0.4B 2.5 1.5 1.5 1.5 16 10
FR100-2S-0.7B 2.5 1.5 1.5 1.5 16 10
FR100-2S-1.5B 4 2.5 2.5 2.5 20 16
FR100-2S-2.2B 4 2.5 2.5 2.5 32 16
3-Phase:380V
FR100-4T-0.7B 2.5 2.5 2.5 2.5 6 10
FR100-4T-1.5B 2.5 2.5 2.5 2.5 10 10
FR100-4T-2.2B 2.5 2.5 2.5 2.5 16 10
FR100-4T-4.0B 2.5 2.5 2.5 2.5 16 10
3.7 Wiring way
3.7.1Single-phase 220V inverter typical wiring diagram
Braking resistor

MCCB
Single-phase (-) (+) PB U
L1
220V
50/60Hz L2 V M
W
FR100

24V

Switch input 1 AO1


DI1 Analog Output 0~10V
Switch input 2 GND
DI2 Operation Panel
Switch input 3
DI3 24V
Switch input 4 Open collector
DI4 output 1
Y1
High-speed
pulse input HI DI7/HI
R1A
GND
Relay output 1
R1B
250V AC/3A
30V DC1A
+10V R1C

DC 0~10V
AI1 AI2 485+
1kΩ~5kΩ RS485
I ON
DC 0~10V or 0~20mA
AI2 485-
V RS485
OFF GND Communication
GND

PE

Uploading and
UP/DOWNLOAD downloading module

Fig.3-6 Single-phase 220V Inverter wiring diagram

- 24 -
FR100 Series Multifunctional Compact Inverter
Remarks:
1)◎refers to main circuit terminals.,○refers to control circuit terminals.
2)User selects braking resistor based on real needs,Please refer to the braking resistor Selection
Guide.
3)Signal cable and power cable should be separated. Try to cross control cable and
power cable in 90°if needed. The best selection of analog signal lines shielded twisted pair,Power
cables use shielded three-core cable(The specifications of the motor cable than ordinary freshman
profile)or Comply with manual drive.
3.7.2 Three-phase 380V inverter typical wiring diagram
Braking resistor

MCCB
Three-phase (-) (+) PB U
L1
380V
50/60Hz L2 V M
W
L3 FR100

24V

Switch input 1 AO1


DI1 Analog Output 0~10V
Switch input 2 GND
DI2 Operation Panel
Switch input 3
DI3 24V
Switch input 4 Open collector
DI4 output 1
Y1
High-speed
pulse input HI DI7/HI
R1A
GND
Relay output 1
R1B
250V AC/3A
30V DC1A
+10V R1C

DC 0~10V
AI1 AI2 485+
1kΩ~5kΩ RS485
I ON
DC 0~10V or 0~20mA
AI2 485-
RS485
V OFF GND Communication
GND

PE

Uploading and
UP/DOWNLOAD downloading module

Fig.3-7Three-phase 380V Inverter wiring diagram


3.8 Terminal Configuration
3.8.1 Main Circuit Terminals
a: Single-phase 0.2~0.75KW Main Circuit Terminals

L1 L2 (+) (-) U V W

Fig.3-8 0.2~0.75kW main circuit terminals

- 25 -
FR100 Series Multifunctional Compact Inverter

b: three-phase 380V 0.75~4.0 KW Main Circuit Terminals

L1 L2 L3 (+) (-) U V W

Fig.3-9 three-phase 380V 0.75~4.0 KW Main Circuit Terminals

Table 3-5 main circuit terminal functions


Terminal marks Designation and function of terminals.
AC power input terminal, connects to three-phase 380V or 220V AC
L1、L2、L3 power (For the machine with single-phase 220V: L1、L2 connect to
single-phase 220V AC power, L3 terminal left unconnected)

U、V、W AC output terminals of inverter for connecting to 3-phase induction motor.

(+)、(-) Positive and negative terminals of internal DC bus.


Positive and negative terminals of internal DC bus. Connecting terminals
PB
of braking resistor. One end connected to + and the other to PB.
Grounding terminal.
Remarks: No phase sequence requirements on wiring of the input side of inverter. Wiring
Precautions:
1)Power input terminals L1、L2 、L3
◆ The cable connection on the input side of the AC drive has no phase sequence requirement.
2)DC bus (+)、(-)
◆ Terminals (+) and (-) of DC bus have residual voltage after the AC drive is switched off. After
indicator CHARGE goes off, wait at least 10 minutes before touching the equipment Otherwise, you
may get electric shock.
◆ Do not connect the braking resistor directly to the DC bus. Otherwise, it may damage the AC drive
and even cause fire.
3)Braking resistor connection terminals (+)、PB
◆ The cable length of the braking resistor shall be less than 5 m. Otherwise, it may damage the AC
drive.
4)AC drive output terminals U、V、W
◆ The capacitor or surge absorber cannot be connected to the output side of the AC drive. Otherwise,
it may cause frequent AC drive fault or even damage the AC drive.
If the motor cable is too long, electrical resonance will be generated due to the impact of distributed
capacitance. This will damage the motor insulation or generate higher leakage current, causing the AC
drive to trip in overcurrent protection. If the motor cable is greater than 100 m long, an AC output
reactor must be installed close to the AC drive.
5)Terminal PE
◆ This terminal must be reliably connected to the main earthing conductor. Otherwise, it may cause
electric shock, mal-function or even damage to the AC drive.
◆ Do not connect the earthing terminal to the neutral conductor of the power supply.

- 26 -
FR100 Series Multifunctional Compact Inverter
3.8.2 Control circuit terminals

D I 1 DI2 DI3 DI4 DI7/HI GND 485+ 485- R1A R1B R1C
+24V GND Y1 +10V AI1 AI2 AO1 PE
Fig.3-10 Control circuit terminals
Table 3-4 FR100 Description of control circuit terminals
Type Terminal Name Function Description
Provide +10 V power supply to
external unit.
External +10 V Generally, it provides power supply to
+10V-GND
power supply external potentiometer with resistance
range of 1–5 kΩ.
Power supply Maximum output current: 10 mA
External +24V
Provide +24 V power supply to
power
external unit.
supply Applying
+24V-COM Generally, it provides power supply to
to Overvoltage
DI/Do terminals and external sensors.
Category II
Maximum output current: 200 mA
circuit
Input voltage range:DC 0~10V/0~
AI1-GND Analog input 1 20mA,decided by toggle switches
Analog input
AI1、AI2 on the control board
AI2-GND Analog input 2 Impedance: 250 kΩ (voltage input),
250 Ω (current input)
Switch input
DI1- GND
terminals 1
Switch input Maximum input frequency:200Hz
DI2- GND
terminals 2 Impedance:2.4kΩ
Switch input Voltage range for level input:9V~
DI3- GND
terminals 3 30V
Switch input
Switch input
DI4- GND
terminals 4
Switch input
Besides features of DI1–DI4, it can be
terminals 7 OR
DI7/HI-COM used for high-speed pulse input.
High-speed
Maximum input frequency: 100 kHz
pulse input
Analog Analog output Output voltage range:0~10V
AO1-GND
output terminal 1 Impedance requirements≥10kΩ
Open collector Voltage range:0~24V
Switch output Y1-GND
output 1 Current range:0~50mA
Normally open Contact driving capacity:
R1A-R1C
Relay output terminal
AC250V,3A,COSØ=0.4.
Normally
R1B-R1C DC 30V,1A
closed terminal
485 Rate:
485
485+-485- Communication 4800/9600/19200/38400/57600/
Communication
Terminals 115200bps

- 27 -
FR100 Series Multifunctional Compact Inverter
485 Termination resistor is set by the
Communication toggle switch on the control panel
GND
shielded RS485
ground
Shield PE Shield Ground Ground terminal for shield
External
Use standard network cable
operation
Auxiliary Maximum cable distance: 50m
panel interface
Interface
Parameter
UP/DOWNLOAD
copy interface

1、Description of Wiring of Signal Terminals:


1)Description Use the analog input terminal
Weak analog voltage signals are easy to suffer external interference, and therefore the shielded cable
must be used and the cable length must be less than 20 m, as shown in following figure. When the
analog input signal to an external power supply,AI1 Terminal wiring as shown in Fig 3-12(a).When
the input analog voltage signal is potentiometer,AI1 Terminal wiring as shown in Fig 3-12(b).
<20m
<20m
+10V
+10V
FR100
FR100
DC 0~10V AI1
AI1

1kΩ~5kΩ DC 0~10V

GND GND

PE PE

(a) (b)
Fig.3-11 Analog input terminal wiring diagram
2)Instructions of Digital Input/output Terminals
Digital input & output signals cables should be as short as possible, shielded, and their shielded layers
should be properly grounded close to the side of drive. The cables should not exceed 20m. When
active drive is selected, take necessary filtering measures against power crosstalk, for which dry
contact control is recommended.
Control cables shall be kept no less than 20cm away from main circuit and strong current lines (e.g.
power lines, motor lines, relay lines and contactor lines) and should not be arranged in parallel with
strong current lines. In case it is inevitable to intersect strong current line, vertical wiring is
recommended to avoid drive faults as a result of noise. Operating instructions for switching value input
terminal
A: Dry contact
External
controller
FR100
+5V
+24V
Optocoupler
- +
1 DI1

GND
+5V
+24V
Optocoupler
- +
7 DI7/HI

GND

GND

Fig.3-12 Dry contact


B: Open collector NPN connection

- 28 -
FR100 Series Multifunctional Compact Inverter
External FR100
controller
+5V
+24V
Optocoupler
- +
1 DI1

GND
+5V
+24V
Optocoupler
- +
7 DI7/HI

GND

GND

Fig.3-13 Open collector NPN connection


3)Instructions of digital output terminal

FR100
24V +24V
+5V
Optocoupler Y1
Pull-up
resistor

GND

Fig.3-14 wiring when Y2 and HO output with pull-up resistors

FR100
24V +24V
+5V
Optocoupler Y1,2
Relays

GND

Fig.3-15 Wiring diagram when Y2 and HO drive relay


ATTENTION:
When relay coil voltage is lower than 24V, a resistor as voltage divider should be mounted between
relay and output terminal, based on coil impedance.
4)Wiring instruction of relay output terminal
Control boards of FR100 series drives are provided with one programmable relay dry contact outputs.
Relay contacts are R1A/R1B/R1C, whose R1Aand R1C are normally open, while R1B and R1C are
normally closed. See parameter F05.02 for details.
ATTENTION:
In case inductive load (e.g. electromagnetic relay or contactor) is to be driven, a surge voltage
absorbing circuit such as RC absorbing circuit (note that its leakage current shall be less than holding
current of controlled contactor or relay), piezoresistor or fly-wheel diode etc. shall be mounted (be sure
to pay close attention to polarity in case of DC electromagnetic circuit). Absorbing devices should be
mounted close to the ends of relay or contactor.
5) Instruction of Signal Switch

- 29 -
FR100 Series Multifunctional Compact Inverter
AI2 RS485
I ON

V OFF
Factory
Terminal Function
default
AI2 I: current input (0~20mA); V: voltage input (0~10V) 0~10V
No
Selection of 485 termination resistor; ON :120Ω termination
RS485 termination
resistor provided; OFF: no termination resistor
resistor

3.9 EMI Solutions


Due to its working principle, the drive will inevitably produce certain noise that may influence and
disturb other equipment. Moreover, since the internal weak electric signal of drive is also susceptible
to the interference of drive itself and other equipment, EMI problems shall be inevitable. In order to
reduce or avoid the interference of drive to external environment and protect drive against interference
from external environment, this section makes a brief description of noise abatement, ground handling,
leakage current suppression and the application of power line filters.
3.9.1 Noise Abatement
When peripheral equipment and drive share the power supply of one system, noise from drive
may be transmitted to other equipment in this system via power lines and result in misoperation
and&or faults. In such a case, the following measures could be taken:
1) Mount input noise filter at input terminal of the drive;
2) Mount power supply filter at power input terminal of affected equipment;
3) Use isolation transformer to isolate the noise transmission path between other equipment and the
drive.

leakage current of inverter will cause equipment misoperation and/or faults.


Disconnect the grounding connection of equipment may avoid this misoperation and/or faults

cable
could be put into metallic conduits between which the distance shall be no less than 20cm, and shall
be kept as far away from drive and its peripheral devices, cables as possible. Never make signal lines
in parallel with power lines or bundle them up.

-thick pipelines or buried


cement groove, also, power lines can be put into metallic conduit and grounded well with shielded
cables.
-core motor cables of which one is grounded at close side of the drive and the other side is
connected to motor enclosure.
ar noise
filter. For example, ferrite common mode choke can restrain radiation noise of power lines.
3.9.2 Grounding
Recommended ground electrode is shown in the figure below:

Drive
变频器 变频器
Drive 变频器
Drive 变频器
Drive 变频器
Drive 变频器
Drive

Fig.3-17v
Use to the fullest extent the maximum standard size of grounding cables to reduce the impedance of
grounding system;
Grounding wires should be as short as possible;
Grounding point shall be as close to the drive as possible;
- 30 -
FR100 Series Multifunctional Compact Inverter
-core motor cables shall be grounded at the drive side and connected to grounding
terminal of motor at the other side. Better effect will be achieved if motor and drive are provided with
dedicated ground electrodes;
When grounding terminals of various parts of system are linked together, leakages current turns into
a noise source that may influence other equipment in the system, thus, grounding terminals of the
drive and other vulnerable equipment should be separated.
e kept away from inlet & output of noise-sensitive equipment.
3.9.3 Leakage Current Suppression
Leakage current passes through the line-to-line and ground distributed capacitors at input & output
sides of drive, and its size is associated with the capacitance of distributed capacitor and the carrier
frequency. Leakage current is classified into ground leakage current and line-to-line leakage current.
Ground leakage current not only circulates inside drive system, but may also influence other
equipment via ground loop. Such a leakage current may result in malfunction of RCD and other
equipment. The higher the carrier frequency of drive is, the bigger the ground leakage current would
be. The longer the motor cables and the bigger the parasitic capacitances are, the bigger the ground
leakage current would be. Therefore, the most immediate and effective method for suppression of
ground leakage current is to reduce carrier frequency and minimize the length of motor cables.
The higher harmonics of line-to-line leakage current that pass through between cables at output
side of drive will Accel the aging of cables and may bring about malfunction of other equipment. The
higher the carrier frequency of drive is, the bigger the line-to-line leakage current would be. The longer
the motor cables and the bigger the parasitic capacitances are, the bigger the line-to-line leakage
current would be. Therefore, the most immediate and effective method for suppression of ground
leakage current is to reduce carrier frequency and minimize the length of motor cable. Line-to-line
leakage current can also be effectively suppressed by mounting additional output reactors.
3.9.4 Use of Power Supply Filter
Since AC drives may generate strong interference and are also sensitive to outside interference,
power supply filters are recommended. Pay close attention to the following instructions during the use:
Enclosure of the filter needs to be reliably grounded;
Input lines of the filter shall be kept as far away from output lines as possible so as to avoid mutual
coupling;
Filter shall be as close to the drive side as possible;
Filter and drive must be connected to the same common ground.

- 31 -
FR100 Series Multifunctional Compact Inverter

Chapter 4 Operation and display

4.1 Introduction of Keypad


As a human-machine interface, you can modify the parameters, monitor the working status and
start or stop the inverter by operating the keypad. Its appearance and function area as shown in the
following figure:

Fig.4-1 Keypad
4.1.1 Key and potentiometer Functions on keypad
There are 8 keys and a potentiometer on the keypad, whose functions are as shown in Table 4-1.
Table 4-1 Key functions on keypad
Symbol Name Function
Escape Enter or exit Level I menu
Enter the menu interfaces level by level, and
Enter
confirm the parameter setting
Increment Increase data or function code

Decrement Decrease data or function code


Select the displayed parameters in turn in the stop
Shift or running state, and select the digit to be modified
when modifying parameters
Perform function switchover (such as jog run and
quick switchover of
Multifunction
command source or direction) according to the
setting of F16.00

potentiometer With the same function as AI1/AI2

Run Start the inverter in the keypad control mode


Stop the inverter when it is in the running state and
perform the reset operation when it is in the fault
Stop/Reset
state. The functions of this key are restricted in
F16.01.
The inverter will free stop when the run and stop
+ Key combinations
key are pressed simultaneously

- 32 -
FR100 Series Multifunctional Compact Inverter
4.1.2 Keypad Indicators
There are 8 Indicators on the keypad, whose descriptions are as shown in Table 4-2.
Table 4-2 Description of indicators
Indicator Name Meaning
ON: currently displayed parameter is
Hz Frequency
frequency
V Voltage ON:currently displayed parameter is voltage
Unit A Current ON:currently displayed parameter is current
ON:currently displayed parameter is
% Percentage
percentage
All off Other unit Other unit or no unit
ON:the drive is running reverse
Forward or
FWD/REV OFF:the drive is running forward
reverse
Flash:dormant state
Keypad, ON:Terminal control
LOC/REM terminals or OFF:Keypad control
State communication Flash:Communication control
ON:Running state
Running state OFF:Stopped state
(Green border) Flash:In process of stop
ON:Fault state
Fault state OFF:Normal state
(Red border) Flash:Warning state

4.1.3 Keypad digital display


The keypad has five LED (digital) display, it can display a given frequency, output frequency and
other parameters, monitoring data and alarm code. Table 4-3 shows meanings of the characters
displayed on Keypad.

Table 4-3 Meanings of displayed characters


Displayed Character Displayed Character Displayed Character Displayed Character
character Meaning character Meaning character Meaning character Meaning

0 A I S
1 b J T
2 C K t
3 c L U
4 d N u
5 E n y
6 F o -
7 G p 8.
8 H q .
9 h r

- 33 -
FR100 Series Multifunctional Compact Inverter
4.1.4 Message status
A message appears when the state of completion of certain operations. Prompt message
characters and their meanings are specified in Table 4-4.
Table 4-4 Prompt characters
Prompt symbol Meaning Prompt symbol Meaning
Motor parameter
Err00~Err99 Fault type TUNE identification in
process
A00~A99 Alarm type -END- Write parameter
4.2 Viewing and Modifying Function Codes
The keypad of the FR100 adopts three-level menu.
The three-level menu consists of function code group (Level I), function code (Level II), and function
code setting value (level III), as shown in the figure 4-2.
If there is a blinking digit,press
Level-I menu
Status parameter
(Select the function to modify the digit
(default display)
code group)
ESC

50.00 Switch menu


F00 ENT
ESC

Return
Enter
Switch
Status parameter
Level-II menu
(Select the function ESC
code)
F00.04 ENT
F00.05 ENT

Return Enter

11.2 Enter
ENT
Next function

0
Level-III menu code
(Set the value of ESC
To save the
the function code) Not to setting
Save the
setting
Fig.4-2 Operation procedure on the keypad
Explanation:In the level III menu, you can press the ESC key or ENT key to return to the level II
menu. The difference is: If you do not have to modify the function code setting, press ENT will be
automatically transferred to the next function code; If the function code settings are modified, it will
display munu "-END-" 1 second when press ENT key, and redisplay the current function code settings,
and it will be automatically transferred to the next function code when press the ENT key again. Press
the ESC key to abandon the current parameter changes directly returns the current function code in
level II.
Here is an example of changing the value of F1-02 to 15.00 Hz.
ESC ESC ENT
50.00 F00.00 F00 F01 F01.00
ESC
ESC
F01 F01.02 F01.02
ESC ESC ENT
ENT ENT
F01.03 15.00 15.00 10.00 10.00
Fig.4-3 Example of changing the parameter value
In Level III menu, if the parameter has no blinking digit, it means that the parameter cannot be
modified. This may be because:
(1)Such a function code is only readable, such as, AC drive model, actually detected parameter
and running record parameter.
(2)Such a function code cannot be modified in the running state and can only be changed at
stop.

- 34 -
FR100 Series Multifunctional Compact Inverter
4.3 Viewing Status Parameters
There are stop state parameters and running state parameters.
It has 4 status parameters in the stop or running state .You can press “>>” on the keypad to display
status parameters. Which parameters are displayed is determined by the values of F16.03~F16.06
(Running state parameters 1~4) 、F16.07~F16.10(stop state parameters1~4),it can select the
U00 group.
4.4 Motor Auto-tuning
Tuning is valid only when the keyboard command mode. Set tuning mode (stationary or rotating),
press the ENT key to confirm, the keyboard will display TUNE, then press the RUN key, the inverter
will drive motor acceleration and deceleration, positive inversion operation,and the run indicator lights.
Tuning duration of about two minutes, when the display TUNE message disappears, returning to
normal parameter display status, which means that the tuning is completed.
4.5 Password Setting
The inverter provides password protection function, it is set a user's password when F00.00 set to
nonzero.If five minutes without operating the keypad, the password protection is effective, and the
keypad will show “-----”, then the user must enter the correct password to enter the regular menu,
otherwise inaccessible.
There are three ways a user password into force:
Method 1: Set F00.00 parameter to nonzero, then press the ESC + ENT key.
Method 2: Set F00.00 parameter to nonzero, then do not use the keypad within five minutes.
Method 3: Set F00.00 parameter to nonzero, then completely power down and then power.
If you want to cancel the password protection functions, only through a password to enter, and set
F00.00 to 0.
4.6 Keypad lock
4.6.1 Keypad lock
The following three methods to any one immediately lock all or part of the keypad buttons; see the
definition of the function code F16.02.
Method 1:Set F16.02parameter to nonzero, then press the ESC + ENT key.
Method 2:Set F16.02 parameter to nonzero, and then do not use the keypad within five minutes.
Method 3:Set F16.02 parameter to nonzero, then completely power down and then power.
4.6.2 Keypad unlock
Press the ESC + >> keys to unlock.Unlocking operation does not change the value of F16.02,
That means when Meet the keypad locking conditions, the keypad will be locked again. If you want the
control panel no longer be locked, after unlocking the F16.02 must change the value to 0.

- 35 -
FR100 Series Multifunctional Compact Inverter
4.7 Shortcut menus function code description
Factory setting mode is changed to be shortcut menu mode (F00.01=1) in the software
version above V1.07, group 17 is for the parameters of shortcut menu.
The difference of display between shortcut manual and basic menu is in the second level
menu, please refer to below the details of difference and the switching method.
Menu mode Shortcut menu Basic menu

F01.01. F01.01
Display F01.01 function code is
difference The last digit of F01.01. function
code is with radix point, no without radix point, and flashing
flashing

1. Press or for
1. Press or up-down switch in
up-down switch in F17 function
Function sequency
code
difference
2. Press return back to first level
2. can’t return back to
menu
first level menu
Method 1. Setting F00.01=0 to
basic menu Method 1. Setting F00.01 to shortcut menu

Switch Method 2. Long Press Method 2. Long press when display


when display second level second level menu, switch to shortcut menu
menu, switch to basic menu automatically
automatically

If the shortcut menu is not enough, user can reset the shortcut menu, refer to group F17 for details.

- 36 -
FR100 Series Multifunctional Compact Inverter

Chapter 5 List of Parameter

Group F00~F16 are standard function parameters. Group U00 is status monitoring parameters.
Group U01 is fault record parameters.
The symbols in the function code table are described as follows:
"△ " means the value of this parameter can be modified in stop and running status of drive;
"×" means the value of this parameter cannot be modified when drive is running;
"⊙" means this parameter is a measured value that cannot be modified;
Default: The value when restored to factory default. Neither measured parameter value nor
recorded value will be restored.
Setting Range: the scope of setting and display of parameters
FR100 parameter groups are listed below:

Category Parameter Group


System Parameters F00: System Parameters
F01: Frequency Command
Basic Parameters F02: Start/Stop Control Start/Stop Control
F03: Accelerate/Decelerate Parameters
F04: Digital Input
F05: Digital Output
Input & Output Terminals
F06: Analog and Pulse Input
F07: Analog and Pulse Output
F08: Parameters of Motor 1
Motor and Control Parameters F09: V/f Control Parameters of Motor 1
F10: Vector Control Parameters of Motor 1
Protection Parameters F11: Protection Parameters
F12: Multi-Reference and Simple PLC Function
Application Parameters F13: Process PID
F14: Swing Frequency, Fixed Length , Count and
Wakeup
Communication Parameters F15: Communication Parameters
Keys and Display of Keypad
F16:Keys and Display of Keypad Parameters
Parameters
User-defined Display Parameters F17:User-defined Display Parameters
U00:Status monitoring
Monitoring Parameters
U01:Fault record

- 37 -
FR100 Series Multifunctional Compact Inverter
5.1 Standard Function Parameters
Table 5-1 Standard Function Parameters
At
Param. Parameter Name Setting Range Default
tr
Group F00: System Parameters
Setting of User
F00.00 0~65535 0 ×
Password
0:Display all function code
1:Display F00.00、F00.01 and user
F00.01 Function code display setting function code 1 ×
2. Display F00.00、F00.01 and the
function code different with factory
setting
0: All parameter programmable
F00.02 Parameter Protection 1: Only F00.02 and this parameter 0 ×
programmable
0: No operation
1: Restore all parameters to factory
default (excluding motor
F00.04 Parameter Initialization parameters) 0 ×
2: Clear fault record
3: Restore user backup parameters
4: Back up currentuser parameters
0: No operation
1: Upload parameter
2: Download parameter (excluding
F00.05 Copy of Parameters 0 ×
motor parameters)
3: Download parameter (including
motor parameters)
0:Editable via keypad and
Parameter RS485
F00.06 0 ×
editing mode 1:Editable via keypad
2:Editable via RS485
0: Voltage/Frequency (V/F)
control
F00.08 Motor 1 control mode 1 ×
1:Sensor-less vector control 1
2: Sensor-less vector control 2
0:Digital input terminal 7
F00.09 DI7/HI input mode 0 ×
1: Pulse input
Unit's place: PWM modulation
mode
0: Fixed carrier
1: Random carrier
2: Derating of fixed carrier
3: Derating of random carrier
Decade: PWM modulation mode
0: Seven-segment mode
F00.12 PWM optimization 100 ×
1: Five-segment mode
2: Five-segment and
seven-segment automatic
switchover
Hundreds place: over-modulation
adjustment
0: Disabled
1: Enabled

- 38 -
FR100 Series Multifunctional Compact Inverter
Model
F00.13 Carrier frequency 0.700~16.000kHz △
defined
Upper carrier
F00.14 0.700~16.000kHz 8.000kHz ×
frequency
Lower carrier
F00.15 0.700~16.000kHz 2.000kHz ×
frequency
F00.16 Output voltage 5.0~100.0% 100.0% ×
0: Disabled
1: Enabled
2: AVR is disabled if the DC
F00.17 AVR bus voltage > the rated 1 ×
voltage of DC bus, and it will be
enabled if the DC bus voltage≤the
rated voltage of DC bus.
0: Run at power-on
F00.18 Fan control 1 ×
1: Fan working during running
F00.19 Factory password 0~65535 0 ×
Model
F00.20 Inverter rated power 0.2~710.0kW ⊙
defined
Model
F00.21 Inverter rated voltage 60~660V ⊙
defined
Model
F00.22 Inverter rated current 0.1~1500.0A ⊙
defined
Model
F00.23 Software version 0.00~655.35 ⊙
defined
F00.24 Dealer 0~65535 0 ×
F00.25 Setting operation time 0~65535h (0:Invalid) 0h ×
0:General purpose application
F00.26 Inverter application 0 ×
1:Fireworks machine
Group F01: Frequency Command
0: Master frequency source
1: Auxiliary frequency source
2: Master +Auxiliary
Frequency source 3: Master - Auxiliary
F01.00 0 ×
selection 4: MAX{Master, Auxiliary }
5: MIN {Master, Auxiliary }
6: AI1*( Master + Auxiliary)
7: AI2*( Master +Auxiliary)
0:Master digital setting (F01.02)
1: keypad potentiometer
2: Analog input AI1
3: Communication
Master Frequency
F01.01 4: Multi-reference 1 ×
Command Source
5: PLC
6: Process PID output
7: X7/HI pulse input
8: Analog input AI2
Digital Setting of Master
F01.02 0.00~Fmax 0.00Hz △
Frequency
0: Auxiliary digital setting
(F01.04)
Auxiliary Frequency 1: keypad potentiometer
F01.03 0 ×
Command Source 2: Analog input AI1
3: Communication
4: Multi-reference

- 39 -
FR100 Series Multifunctional Compact Inverter
5: PLC
6: Process PID output
7: X7/HI pulse input
8: Analog input AI2
Digital setting of
F01.04 0.00~Fmax 0.00Hz △
auxiliary frequency
Range of auxiliary 0: Relative to maximum frequency
F01.05 0 ×
frequency 1: Relative to master frequency
Coeff of auxiliary
F01.06 0.0~150.0% 100.0% △
frequency
F01.07 Jog frequency 0.00~Fmax 5.00Hz △
F01.08 Maximum frequency 20.00~600.00Hz 50.00Hz ×
Fdown~Fmax
F01.09 Upper limit frequency Lower limit frequency~maximum 50.00Hz ×
frequency
F01.10 Lower limit frequency 0.00~Fup 0.00Hz ×
Operation when command 0: Run at lower limit frequency
F01.11 frequency lower than 1: Run at 0 Hz would be activated 0 ×
lower limit frequency after the time delay set by F01.12
Lower limit frequency
F01.12 0.0~6000.0s 60.0s ×
running time
Group F02: Start/Stop Control
0: Keypad control (LED off)
1: Terminal control (LED on)
F02.00 Run command 0 ×
2: Communication control (LED
blinking)
0: Forward
F02.01 Running direction 0 △
1: Reverse
0: Reverse enabled
F02.02 Reverse-proof action 0 ×
1: Reverse disabled
Dead time between
F02.03 0.0~6000.0s 0.0s ×
forward and reverse
0: From start frequency
F02.04 Start mode 0 ×
1: Rotational speed tracking restart
F02.05 Start frequency 0.00~10.00Hz 0.00Hz ×
Startup frequency holding
F02.06 0.0~100.0s 0.0s ×
time
F02.07 Startup DC brakin current 0.0~150.0% 0.0% ×
F02.08 DC braking time at start 0.0~100.0s 0.0s ×
F02.09 Speed search current 0.0~180.0% 100.0% △
F02.10 Sped search decel time 0.0~10.0s 1.0s ×
F02.11 Sped search coefficient 0.01~5.00 0.30 △
0: Ramp to stop
F02.12 Stop mode 0 ×
1: Coast to stop
Initial frequency of stop
F02.13 0.01~50.00Hz 2.00Hz ×
DC braking
F02.14 Stop DC braking current 0.0~150.0% 0.0% ×
Waiting time of stop DC
F02.15 0.0~30.0s 0.0s ×
braking
F02.16 Stop DC braking time 0.0~30.0s 0.0s ×
0: Disabled
1: Enabled
F02.17 Dynamic brake 0 ×
2: Enabled at running
3: Enabled at deceleration
- 40 -
FR100 Series Multifunctional Compact Inverter
Dynamic Brake
F02.18 480~800V 700V ×
Voltage
F02.19 Brake use ratio 5.0~100.0% 100.0% ×
0:No voltage output
F02.20 0Hz output selection 0 ×
1:Voltage output
Group F03: Accel/Decel Parameters
F03.00 Accel time 0 0.0~6000.0s 15.0s △
F03.01 Decel time 0 0.0~6000.0s 15.0s △
F03.02 Accel time 1 0.0~6000.0s 15.0s △
F03.03 Decel time 1 0.0~6000.0s 15.0s △
F03.04 Accel time 2 0.0~6000.0s 15.0s △
F03.05 Decel time 2 0.0~6000.0s 15.0s △
F03.06 Accel time 3 0.0~6000.0s 15.0s △
F03.07 Decel time 3 0.0~6000.0s 15.0s △
F03.08 Jog accel time 0.0~6000.0s 15.0s △
F03.09 Jog decel time 0.0~6000.0s 15.0s △
0: Linear Accel/Decel
F03.10 Accel/Decele curve 0 ×
1: S-curve Accel/Decel
F03.11 S curve Time 0 0.0~6000.0s 0.0s ×
Acceleration and 0:0.1s
F03.12 0 ×
deceleration time unit 1:0.01s
Frequency switchover
point
F03.13 between acceleration time 0.00~Fmax 0.00Hz ×
0
and acceleration time 1
Frequency switchover
point
F03.14 between deceleration time 0.00~Fmax 0.00Hz ×
0
and deceleration time 1
F03.15 S curve Time 1 0.0~6000.0s 0.0s ×
F03.16 S curve Time 2 0.0~6000.0s 0.0s ×
F03.17 S curve Time 3 0.0~6000.0s 0.0s ×
Group F04 Digital Input
F04.00 Function of terminal DI1 0: No function 1 ×
F04.01 Function of terminal DI2 1: Running forward (FWD) 2 ×
F04.02 Function of terminal DI3 2: Running reverse (REV) 7 ×
F04.03 Function of terminal DI4 3: Three-wire control 13 ×
4: JOG forward 0 ×
5: JOG reverse 0 ×
6: Coast to stop 0 ×
7: Fault reset (RESET) 0 ×
8: Running suspended
0 ×
9: External fault input
10: Terminal UP
11: Terminal DOWN
F04.06 Function of terminal D17 12: UP/DOWN (including ∧/∨
key) adjustment clear
13: Multi-step frequency terminal 1 0 ×
14: Multi-step frequency terminal 2
15: Multi-step frequency terminal 3
16: Multi-step frequency terminal 4
17: Accel/Decel time determinant 1
18: Accel/Decel time determinant 1
- 41 -
FR100 Series Multifunctional Compact Inverter
19: Accel/Decel disabled(ramp
stop not inclusive)
20: Switch to auxiliary speed
Setting
21: PLC status reset
22: Simple PLC paused
23: Simple PLC paused
24: PID adjustment direction
25: PID integration paused
26: PID parameter switch
27: Swing frequency pause(output
the currentfrequency)
28: Swing frequency reset(output
the central frequency)
29: Run command switched to
keypad contro
30: Run command switched to
terminal control
31: Run command switched to
communication control
32: Count input
33: Count clear
34: Length count
35: Length clear
36: DC brake input command at
Stop
37~99:reserved
Filtering time of digital
F04.10 0.000~1.000s 0.010s △
input terminalD11~D17
Delay time of terminal
F04.11 0.0~300.0s 0.0s △
DI1
Delay time of terminal
F04.12 0.0~300.0s 0.0s △
DI2
DI4、DI3、DI2、DI1
0: Positive logic(Terminals are on
Terminal DI1~DI4
F04.13 at 0V/off at 24V) 0000 ×
positive/negative logic
1: Negative Logic (Terminals are
off at 0V/on at 24V)
Reserved DI7
Terminal
F04.14 0: Positive logic 00 ×
DI7positive/negative logic
1: Negative Logic
0: Two-wire mode 1
1: Two-wire mode 2
FWD/REV terminal 2: Three-wire mode 1
F04.15 0 ×
control mode
3: Three-wire mode 2
4:Pulse operation stop
Unit's place: action when stop 000 ×
0: Clear
1: Holding
Terminal UP/DOWN Decade: action on power loss
F04.16 frequency adjustment 0: Clear
control 1: Holding
Hundreds place: integral function
0: No integral function
1: Integral function enabled
Terminal UP/DOWN 1.00Hz/
F04.17 0.00~50.00Hz 0.00:Disabled △
frequency change step 200ms
- 42 -
FR100 Series Multifunctional Compact Inverter
size
Terminal action selection 0:Level effective
F04.18 0 ×
when power on 1:Edge trigger +Level effective
Group F05 Digital Output
F05.00 Y1 output function 0: No output 1 ×
2: Fault output 2 ×
3: Frequency-level detection FDT1
output
4: Frequency-level detection FDT2
output
5: Drive in 0Hz running 1(no output
at stop)
6: Drive in 0Hz running 2(output at
stop)
7: Upper limit frequency attained
8: Lower limit frequency attained
9: Frequency attained
10: Inverter is ready to work
F05.02 Relay 1 output function 11: Drive (motor) overloaded alarm
11 ×
12: Inverter overheat warning
13: Current running time attained
14: Accumulative power-on time
attained
15: Consecutive running time
attained
16: PLC cycle completed
17: Set count value attained
18: Designated count value
attained
19: Length attained
20: Under load alarm
21:Brake output
F05.04 Y1 output delay time 0.0~6000.0s 0.0s △
F05.06 R1 output delay time 0.0~6000.0s 0.0s △
Unit's place: Y1
0: Positive logic
1: Negative logic
Enabled state of digital Decade: Y2 (same as unit's place)
F05.08 0000 ×
output Hundreds place: Relay 1 output
(same as unit's place)
Thousands place: Relay 2 output
(same as unit's place)
Detection width of
F05.09 0.00~20.00Hz 5.00Hz ×
frequency attained
F05.10 FDT1 upper bound 0.00~Fmax 30.00Hz ×
F05.11 FDT1 lower bound 0.00~Fmax 30.00Hz ×
F05.12 FDT2 upper bound 0.00~Fmax 30.00Hz ×
F05.13 FDT2 lower bound 0.00~Fmax 30.00Hz ×
Consecutive running
F05.14 0.0~6000.0Min 0.0:Disabled 0.0Min ×
time
Accumulative power-on
F05.15 0~65535h 0:Disabled 0h ×
time setting
Accumulative running
F05.16 0~65535h 0:Disabled 0h ×
time setting
0: Disabled
F05.17 Brake control selection 0 ×
1: Enabled

- 43 -
FR100 Series Multifunctional Compact Inverter
F05.18 Brake opened frequency Closed frequency ~30.00Hz 2.50Hz ×
F05.19 Brake opened current 0.0~200.0% 0.0% △
F05.20 Brake open waiting time 0.00~10.00s 0.00s ×
F05.21 Brake open operating time 0.00~10.00s 0.50s ×
F05.22 Brake closed frequency 0.00Hz~opened frequency 2.00Hz ×
F05.23 Brake close waiting time 0.00~10.00s 0.00s ×
F05.24 Brake close operating time 0.00~10.00s 0.00s ×
Group F06 Analog and Pulse Input
Minimum input of curve 0.0%~input of inflection point1
F06.00 0.0% △
AI1 of curve AI1
Set value corresponding
F06.01 to minimum input of -100.0~100.0% 0.0% △
curve AI1
Input of inflection point Minimum input of curve AI1~Input
F06.02 25.0% △
1 of curve AI1 of inflection point 2 of curve AI1
Set value corresponding
F06.03 to input of inflection -100.0~100.0% 25.0% △
point 1 of curve AI1
Input of inflection point Input of inflection point 1 of curve
F06.04 75.0% △
2 of curve AI1 AI1~Maximum input of curve AI1
Set value corresponding
F06.05 to input of inflection -100.0~100.0% 75.0% △
point 2 of curve AI1
Maximum input of curve Input of inflection point 2 of curve
F06.06 100.0% △
AI1 AI1~100.0%
Set value corresponding
F06.07 to maximum input of -100.0~100.0% 100.0% △
curve AI1
Minimum input of curve 0.0%~input of inflection point1 of
F06.08 0.0% △
AI2 curve AI2
Set value corresponding
F06.09 to minimum input of -100.0~100.0% 0.0% △
curve AI2
Input of inflection point Minimum input of curve AI1~Input
F06.10 25.0% △
1 of curve AI2 of inflection point 2 of curve AI2
Set value corresponding
F06.11 to input of inflection -100.0~100.0% 25.0% △
point 1 of curve AI2
Input of inflection point Input of inflection point 1 of curve
F06.12 75.0% △
2 of curve AI2 AI2~Maximum input of curve AI2
Set value corresponding
F06.13 to input of inflection -100.0~100.0% 75.0% △
point 2 of curve AI2
Maximum input of curve Input of inflection point A of curve
F06.14 100.0% △
AI2 AI2~100.0%
Set value corresponding
F06.15 to maximum input of -100.0~100.0% 100.0% △
curve AI2
Minimum input of curve 0.0~Maximum input of curve
F06.24 0.1% △
keypad potentiometer keypad potentiometer
Set value corresponding
to minimum input of
F06.25 -100.0~100.0% 0.0% △
curve keypad
potentiometer
F06.26 Maximum input of curve Minimum input of curve keypad 99.9% △

- 44 -
FR100 Series Multifunctional Compact Inverter
keypad potentiometer potentiometer~100.0
Set value corresponding
to maximum input of
F06.27 -100.0~100.0% 100.0% △
curve keypad
potentiometer
F06.28 AI1 terminal filtering time 0.000~10.000s 0.100s △
F06.29 AI2 terminal filtering time 0.000~10.000s 0.100s △
Keypad potentiometer
F06.31 0.000~10.000s 0.100s △
filtering time
0.00 kHz~Maximum input of curve
F06.32 Minimum input of curve HI 0.00kHz △
HI
Set value corresponding to
F06.33 -100.0~100.0% 0.0% △
minimum input of curve HI
Minimum input of curve HI~
F06.34 Maximum input of curve HI 50.00kHz △
100.00kHz
Set value corresponding to
F06.35 -100.0~100.0% 100.0% △
maximum input of curve HI
F06.36 HI terminal filtering time 0.000~10.000s 0.100s △
Group F07 Analog and Pulse Output
0: No output
1: Output frequency
2: Command frequency
3: Output current
4: Output voltage
5: Output power
6: Bus voltage
F07.00 AO1 output function 1 ×
7:+10V
8: keypad potentiometer
9:AI1
10:AI2
12:HI
13: Reserved
14:Communication given output
F07.03 AO1 offset -100.0~100.0% 0.0% △
F07.04 AO1 gain -2.000~2.000 1.000 △
F07.05 AO1 filtering time 0.000~10.000s 0.000s △
Group F08 Parameters of Motor 1
Model
F08.01 Power rating of motor 1 0.1~1000.0kW ×
defined
Model
F08.02 Rated voltage of motor 1 60~660V ×
defined
Model
F08.03 Rated current of motor 1 0.1~1500.0A ×
defined
Rated frequency of Model
F08.04 20.00~Fmax ×
motor 1 defined
Model
F08.05 Rated speed of motor 1 1~30000 ×
defined
Stator resistance R1 of Model
F08.08 0.001~65.535Ω ×
async motor 1 defined
Rotor resistance R2 of Model
F08.09 0.001~65.535Ω ×
async motor 1 defined
Leakage inductance L1 Model
F08.10 0.01~655.35mH ×
of async motor 1 defined
Mutual inductance L2 of Model
F08.11 0.1~6553.5mH ×
asynchronous motor 1 defined

- 45 -
FR100 Series Multifunctional Compact Inverter
No-load current of Model
F08.12 0.1~1500.0A ×
async motor 1 Defined
Field weakening coeff 1
F08.13 0.0~100.0 87% ×
of async motor 1
Field weakening coeff 2
F08.14 0.0~100.0 75% ×
of async motor 1
Field weakening coeff 3
F08.15 0.0~100.0 70% ×
of async motor 1
0: No autotuning
1: Static autotuning of async motor
F08.30 Autotuning of motor 1 0 ×
2: Rotary autotuning of async
motor
Group F09 V/f Control Parameters of Motor 1
0: Linear V/f
1: Multi-stage V/f
2: 1.2nd power V/F
3: 1.4th power V/F
F09.00 V/f curve setting 4: 1.6th power V/F 0 ×
5: 1.8th power V/F
6: 2.0nd power V/F
7: V/F complete separation
8: V/F half separation
0.1%–30.0% 0.0% (fixed torque
F09.01 Torque boost 0.0% △
boost)
Cut-off frequency of torque
F09.02 0.00~Fmax 50.00Hz △
boost
Multi-point V/F frequency
F09.03 0.00~F09.05 0.00Hz △
1(F1)
Multi-point V/F voltage 1
F09.04 0.0~100.0 0.0% △
(V1)
Multi-point V/F frequency
F09.05 F09.03~F09.05 5.00Hz △
2(F2)
Multi-point V/F voltage 2
F09.06 0.0~100.0 14.0% △
(V2)
Multi-point V/F frequency
F09.07 F09.05~F09.09 25.00Hz △
3(F3)
Multi-point V/F voltage 3
F09.08 0.0~100.0 50.0% △
(V3)
Multi-point V/F frequency
F09.09 F09.07~rated motor frequency 50.00Hz △
4(F4)
Multi-point V/F voltage 4
F09.10 0.0~100.0 Ue=100.0% 100.0% △
(V4)
V/F slip compensation
F09.11 0.0~300.0% 80.0% △
gain
Stator voltagedrop
F09.12 0.0~200.0% 100.0% △
compensation gain
F09.13 Excitation boost gain 0.0~200.0% 150.0% △
F09.14 Oscillation Suppression 0.0~300.0% 100.0% △
Group F10 Vector Control Parameters of Motor 1
0: speed control
F10.00 Speed/torque control 0 ×
1: torque control
ASR low-speed
F10.01 0.0~100.0 30.0 △
proportional gain Kp1
ASR low-speed
F10.02 0.01~10.00s 0.50s △
integration time Ti1
F10.03 ASR switching 0.00~F10.06 5.00Hz △

- 46 -
FR100 Series Multifunctional Compact Inverter
frequency 1
ASR high-speed
F10.04 1~100.0 10.0 △
proportional gain Kp2
ASR high-speed
F10.05 0.01~10.00s 0.100s △
integration time Ti2
ASR switching
F10.06 F10.03~Fmax 10.00Hz △
frequency 2
F10.07 ASR input filtering time 0.0~500.0ms 0.3ms △
F10.08 ASR output filtering time 0.0~500.0ms 0.0ms △
F10.09 Vector control slip gain 50~200% 100% △
Digital setting of torque
F10.10 upper limit in speed control 80.0~200.0% 165.0% ×
mode
Excitation adjustment
F10.11 0.00~10.00 0.50 △
proportional gain Kp1
Excitation adjustment
F10.12 0.0~3000.0ms 10.0ms △
integral gain Ti1
Torque adjustment
F10.13 0.00~10.00 0.50 △
proportional gain Kp2
Torque adjustment integral
F10.14 0.0~3000.0ms 10.0ms △
gain Ti2
F10.15 reserved
0: Set by F10.17
1:Keypad potentiometer
Torque setting source 2:AI1
F10.16 0 ×
under torque control 3:AI2
5: Pulse setting ( DI7/HI )
6: Communication setting
F10.17 Digital setting of torque -200.0~200.0% 150.0% △
Forward speed limited
F10.18 0.00~Fmax 50.00Hz △
value under torque control
Reverse speed limited
F10.19 0.00~ Fmax 50.00Hz △
value under torque contro
F10.20 Set torque accel time 0.0~6000.0s 0.0s △
F10.21 Set torque decel time 0.0~6000.0s 0.0s △
Static friction torque
F10.22 0.0~100.0% 5.00% △
compensation
Static friction frequency
F10.23 0.00~20.00Hz 1.00Hz △
range
Sliding friction torque
F10.24 0.0~100.0% 1.0% △
compensation
Rotary inertia
F10.25 50.0~200.0% 100.0% △
compensation coeff
0: Set by F10.18 & F10.19
1:Keypad potentiometer
Max Frequency source
F10.26 2:AI1 0 ×
under torque control
3:AI2
5: Pulse setting ( DI7/HI )
Group F11 Protection Parameters
0: Current limit disabled
F11.00 Current limit control 1: Current limit mode 1 2 ×
2: Current limit mode 2
F11.01 Current limit 100.0~200.0% 150.0% ×
Frequency decreasing
F11.02 0.0~6000.0s 5.0s △
time(limit current in

- 47 -
FR100 Series Multifunctional Compact Inverter
constant speed operation)
Current limit mode 2
F11.03 0.1~100.0% 3.0% △
proportion gain
Current limit mode 2
F11.04 0.00~10.00s 10.00s △
integral time
0: Overvoltage stall disabled
F11.05 Overvoltage Stall Control 1: Overvoltage stall mode 1 1 ×
2: Overvoltage stall mode 2
Overvoltage Stall
F11.06 600~800V 700V ×
Voltage
Overvoltage Stall
F11.07 0.1~100.0% 3.0% △
Mode 2 Proportion Gain
Overvoltage Stall
F11.08 0.00~10.00s 10.00s △
Mode 2 Integral Time
Unit's place: Bus undervoltage
0: Fault reported and coast to stop
1: Stop according to the stop mode
2: Fault reported but continue to
run
3: Fault protection disabled
Ten's digit :Power input phase
Loss (Err09)(Same as unit's
F11.10 Protection action 1 place ) 03000 ×
Hundred's digit :Power output
phase loss(Err10)(Same as unit's
place )
Thousand's digit:Motor overload
(Err11)(Same as unit's place )
Ten thousand's digit:Inverter
overload(Err11)(Same as unit's
place )
External equipment fault(Err13)
0: Fault reported and coast to stop
1: Stop according to the stop mode
2: Fault reported but continue to
run
Ten's digit: EEPROM read/write
fault (Err15) (Same as unit's place)
F11.11 Protection action 2 Hundred's digit: Communication 00000 ×
overtime error (Err18) (Same as
unit's place)
Thousand's digit: PID feedback
loss (Err19) (Same as unit's place)
Ten thousand's digit: Continuous
running time reached (Err20)
(Same as unit's place)
Unit's place: Module temperature
detection disconnection(Err24)
0: Fault reported and coast to stop
F11.12 Protection action 3 1: Stop according to the stop mode 00030 ×
2: Fault reported but continue to
run
Ten's digit: Load becoming 0
(Err25) (Same as unit's place)
Frequency selection for 0: Current running frequency
F11.14 0 ×
continuing to run upon 1: Set frequency

- 48 -
FR100 Series Multifunctional Compact Inverter
fault 2: Frequency upper limit
3: Frequency lower limit
4: Backup frequency upon
Abnormality
Backup frequency upon
F11.15 0.00~Fmax 0.00Hz ×
abnormality
Motor overload protection
F11.17 30.0~300.0s 60.0s ×
time
Unit's place: detection option:
0: Always detect
1: Detect at constant speed only
F11.18 Overload alarm 00 ×
Ten's digit : compared object
0: Rated current of motor
1: Rated current of drive
F11.19 Overload alarm threshold 20.0~200.0% 130.0% ×
Overload alarm
F11.20 activated time that 0.1~60.0s 5.0s ×
exceeding threshold
Inverter overheat warning Base on
F11.21 50.0℃~over heat temperature ×
threshold model
Detection level of power
F11.22 5.0~100.0% 20.0% ×
loss
Detection time of power
F11.23 0.1~60.0s 5.0s ×
loss
0: Disabled
Action selection at
F11.24 instantaneous power 1: Deceleration 1 ×
failure 2: Bus voltage constant control
Decel time at
F11.25 instantaneous power 0.0~6000.0s 5.0s △
failure
0: Disabled
F11.26 Rapid current limit 0 ×
1: Enabled
Times of automatic
F11.27 0~20 0 ×
reset
Interval of automatic
F11.28 0.1~100.0s 1.0s ×
reset
DO action during fault auto 0: Not act
F11.29 0 ×
reset 1: Act
Instantaneous power off Range:60.0%~F11.31 80.0%
F11.30 △
bus voltage
Instantaneous power off Range:F11.30~100.0% 85.0%
F11.31 △
recovery voltage
Instantaneous power off Range:0.01~10.00s 0.10s
F11.32 △
voltage judge time
Instantaneous power off Range:0.1~100.0% 40.0%
F11.33 △
gain Kp
Instantaneous integration Range:0.00~10.00s(0.00: 0.10s
F11.34 △
time Ti Integration invalid)
Group F12: Multi-Reference and Simple PLC Function
F12.00 Reference 0 -100.0~100.0% 0.0% △
F12.01 Reference 1 -100.0~100.0% 0.0% △
F12.02 Reference 2 -100.0~100.0% 0.0% △
F12.03 Reference 3 -100.0~100.0% 0.0% △

- 49 -
FR100 Series Multifunctional Compact Inverter
F12.04 Reference 4 -100.0~100.0% 0.0% △
F12.05 Reference 5 -100.0~100.0% 0.0% △
F12.06 Reference 6 -100.0~100.0% 0.0% △
F12.07 Reference 7 -100.0~100.0% 0.0% △
F12.08 Reference 8 -100.0~100.0% 0.0% △
F12.09 Reference 9 -100.0~100.0% 0.0% △
F12.10 Reference 10 -100.0~100.0% 0.0% △
F12.11 Reference 11 -100.0~100.0% 0.0% △
F12.12 Reference 12 -100.0~100.0% 0.0% △
F12.13 Reference 13 -100.0~100.0% 0.0% △
F12.14 Reference 14 -100.0~100.0% 0.0% △
F12.15 Reference 15 -100.0~100.0% 0.0% △
0: Digital setting(F12.00)
1:keypad potentiometer
2:AI1
F12.16 Reference 0 source 0 ×
3: Process PID output
4: X7/HI pulse input
5:AI2
Unit's place: PLC running mode
0: Stop after a single cycle
1: Continue to run with the last
frequency after a single cycle
2: Repeat cycles
Decade: started mode
0: Continue to run from the step of
stop (or fault)
1: Run from the first step
Running mode of simple “multi-step frequency 0”
F12.17 0000 ×
PLC 2:Restart from eighth step
3:Restart from eighth step
Hundreds place:power loss
memory
0: Memory disabled on power loss
1: Memory enabled on power loss
Thousands place: unit of simple
PLC running time
0: Second (s)
1: Minute (min)
F12.18 Running time of step 0 0.0~6000.0s(h) 0.0s(h) △
F12.19 Running time of step 1 0.0~6000.0s(h) 0.0s(h) △
F12.20 Running time of step 2 0.0~6000.0s(h) 0.0s(h) △
F12.21 Running time of step 3 0.0~6000.0s(h) 0.0s(h) △
F12.22 Running time of step 4 0.0~6000.0s(h) 0.0s(h) △
F12.23 Running time of step 5 0.0~6000.0s(h) 0.0s(h) △
F12.24 Running time of step 6 0.0~6000.0s(h) 0.0s(h) △
F12.25 Running time of step 7 0.0~6000.0s(h) 0.0s(h) △
F12.26 Running time of step 8 0.0~6000.0s(h) 0.0s(h) △
F12.27 Running time of step 9 0.0~6000.0s(h) 0.0s(h) △
F12.28 Running time of step 10 0.0~6000.0s(h) 0.0s(h) △
F12.29 Running time of step 11 0.0~6000.0s(h) 0.0s(h) △
F12.30 Running time of step 12 0.0~6000.0s(h) 0.0s(h) △
F12.31 Running time of step 13 0.0~6000.0s(h) 0.0s(h) △

- 50 -
FR100 Series Multifunctional Compact Inverter
F12.32 Running time of step 14 0.0~6000.0s(h) 0.0s(h) △
F12.33 Running time of step 15 0.0~6000.0s(h) 0.0s(h) △
Acceleration/deceleration
F12.34 time of simple PLC 0~3 0 △
reference 0
Acceleration/deceleration
F12.35 time of simple PLC 0~3 0 △
reference 1
Acceleration/deceleration
F12.36 time of simple PLC 0~3 0 △
reference 2
Acceleration/deceleration
F12.37 time of simple PLC 0~3 0 △
reference 3
Acceleration/deceleration
F12.38 time of simple PLC 0~3 0 △
reference 4
Acceleration/deceleration
F12.39 time of simple PLC 0~3 0 △
reference 5
Acceleration/deceleration
F12.40 time of simple PLC 0~3 0 △
reference 6
Acceleration/deceleration
F12.41 time of simple PLC 0~3 0 △
reference 7
Acceleration/deceleration
F12.42 time of simple PLC 0~3 0 △
reference 8
Acceleration/deceleration
F12.43 time of simple PLC 0~3 0 △
reference 9
Acceleration/deceleration
F12.44 time of simple PLC 0~3 0 △
reference 10
Acceleration/deceleration
F12.45 timeof simple PLC 0~3 0 △
reference 11
Acceleration/deceleration
F12.46 time of simple PLC 0~3 0 △
reference 12
Acceleration/deceleration
F12.47 time of simple PLC 0~3 0 △
reference 13
Acceleration/deceleration
F12.48 time of simple PLC 0~3 0 △
reference 14
Acceleration/deceleration
F12.49 time of simple PLC 0~3 0 △
reference 15
Group F13 Process PID
0: F13.01 digital setting
1:keypad potentiometer
2:AI1
F13.00 PID setting 0 ×
3: Communication
4:Multi-Reference
5: DI7/HI pulse input
- 51 -
FR100 Series Multifunctional Compact Inverter
6: AI2
F13.01 PID digital setting 0.0~100.0% 50.0% △
0:AI1
1:AI2
2: Communication
3:AI1+AI2
F13.02 PID feedback 0 ×
4:AI1-AI2
5:Max{AI1,AI2}
6:Min{AI1,AI2}
7: DI7/HI pulse input
PID setting feedback
F13.03 0~60000 1000 △
range
0: Forward action
F13.04 PID action direction 0 ×
1: Reverse action
Filtering time of PID
F13.05 0.000~10.000s 0.000s △
setting
Filtering time of PID
F13.06 0.000~10.000s 0.000s △
feedback
Filtering time of PID
F13.07 0.000~10.000s 0.000s △
output
F13.08 Proportional gain Kp1 0.0~100.0 1.0 △
F13.09 Integration time Ti1 0.01~10.00s 0.10s △
F13.10 Differential time Td1 0.000~10.000s 0.000s △
F13.17 PID offset limit 0.0~100.0% 1.0% ×
PID output frequency lower limit~
PID output frequency
F13.22 100.0%(100.0% corresponds to 100.0% ×
upper limit
maximum frequency )
PID output frequency –100.0%~PID output frequency
F13.23 0.0% ×
lower limit lower limit
Detection value of 0.1~100.0%
F13.24 0.0% ×
PID feedback loss 0.0%: Not judging feedback loss
Detection time of
F13.25 0.0~30.0s 1.0s ×
PID feedback loss
0: No PID operation at stop
F13.26 PID operation at stop 0 ×
1: PID operation at stop
Group F14: Swing Frequency, Fixed Length , Wakeup and Count
0: Relative to the setting
Swing frequency setting frequency
F14.00 0 ×
mode 1: Relative to the maximum
frequency
Swing frequency
F14.01 0.0~100.0% 0.0% △
amplitude
F14.02 Jump frequency amplitude 0.0~50.0% 0.0% △
Rising Time of Swing
F14.03 0.0~6000.0s 5.0s △
frequency
Dropping Time of Swing
F14.04 0.0~6000.0s 5.0s △
frequency
F14.05 Set length 0m~65535m 1000m ×
Number of pulses per
F14.06 0.1~6553.5 100.0 ×
meter
Command when the 0: Not stop
F14.07 0 ×
length attained 1: Stop
F14.08 Set count value 1~65535 1000 ×
F14.09 Designated count value 1~65535 1000 ×
- 52 -
FR100 Series Multifunctional Compact Inverter
Dormant frequency (F14.12)~
F14.10 Wakeup frequency 0.00Hz △
Fmax
F14.11 Wakeup delay time 0.0~6000.0s 0.0s △
F14.12 Dormant frequency 0.00~Wakeup frequency 0.00Hz △
F14.13 Dormant delay time 0.0~6000.0s 0.0s △
0:Frequency
F14.14 Wake up mode selection 0 ×
1:Pressure
0:Frequency
F14.15 Dormancy mode selection 0 ×
1:Pressure
0:AI1
F14.16 Voltage feedback source 1:AI2 0 ×
2:DI7/HI pulse input
F14.17 Wake up pressure 0.0%~Dormancy pressure 10.0% △
F14.18 Dormancy pressure Wake up pressure~100.0% 50.0% △
Group F15: Communication Parameters
0:4800bps
1:9600bps
2:19200bps
F15.00 Baud rate 1 ×
3:38400bps
4:57600bps
5:115200bps
No check, data format (1-8-N-2) for
RTU
1: Even parity check, data format
(1-8-E-1) for RTU
F15.01 Data format 0 ×
2: Odd Parity check, data format
(1-8-O-1) for RTU
3: No check, data format(1-8-N-1)
for RTU
F15.02 Local address 1~247 0: Broadcast address 1 ×
F15.03 Communication timeout 0.0~60.0s 0.0s ×
F15.04 Response time delay 0~200ms 1ms ×
Master-slave 0:The inverter is the slave
F15.05 0 ×
Communication Mode 1:The inverter is the master
The Master 0: Set frequency
F15.06 Communication 0 ×
Sending Data 1: Current running frequency
F15.07 Informaion return when Range:0~1
1 △
communication error
Group U00.00 output 0:Positive and negative value
F15.08 frequency numerical 0 △
attribute 1:Absolute value
Group F16 Keys and Display of Keypad Parameters
0: No function
1: Jog
F16.00 MF.K key setting 1 ×
2: Forward/reverse switchover
3: Run command sources shifted
0: STOP/RST key valid only when
Function of STOP/RST under keypad control
F16.01 1 ×
key 1: STOP/RST key valid under any
run command source
0: Not locked
F16.02 Keys locked option 0 ×
1: Full locked

- 53 -
FR100 Series Multifunctional Compact Inverter
2: Keys locked other than RUN,
STOP/RST
3: Keys locked other than
STOP/RST
4: Keys locked other than >>
LED displayed parameters 0~99(correspond U00.00~
F16.03 0 △
setting 1 on running status U00.99)
LED displayed parameters 0~99(correspond U00.00~
F16.04 6 △
setting 2 on running status U00.99)
LED displayed parameters 0~99(correspond U00.00~
F16.05 3 △
setting 3 on running status U00.99)
LED displayed parameters 0~99(correspond U00.00~
F16.06 2 △
setting 4 on running status U00.99)
LED displayed parameters 0~99(correspond U00.00~
F16.07 1 △
setting 1 on stop status U00.99)
LED displayed parameters 0~99(correspond U00.00~
F16.08 6 △
setting 2 on stop status U00.99)
LED displayed parameters 0~99(correspond U00.00~
F16.09 15 △
setting 3 on stop status U00.99)
LED displayed parameters 0~99(correspond U00.00~
F16.10 16 △
setting 4 on stop status U00.99)
Group F17 User-defined Display Parameters
User-defined Display
F17.00 00.00~49.99 00.03 △
Parameter 0
User-defined Display
F17.01 00.00~49.99 01.01 △
Parameter 1
User-defined Display
F17.02 00.00~49.99 01.02 △
Parameter 2
User-defined Display
F17.03 00.00~49.99 01.08 △
Parameter 3
User-defined Display
F17.04 00.00~49.99 01.09 △
Parameter 4
User-defined Display
F17.05 00.00~49.99 02.00 △
Parameter 5
User-defined Display
F17.06 00.00~49.99 02.01 △
Parameter 6
User-defined Display
F17.07 00.00~49.99 02.12 △
Parameter 7
User-defined Display
F17.08 00.00~49.99 03.00 △
Parameter 8
User-defined Display
F17.09 00.00~49.99 03.01 △
Parameter 9
User-defined Display
F17.10 00.00~49.99 04.00 △
Parameter 10
User-defined Display
F17.11 00.00~49.99 04.01 △
Parameter 11
User-defined Display
F17.12 00.00~49.99 04.02 △
Parameter 12
User-defined Display
F17.13 00.00~49.99 04.03 △
Parameter 13
User-defined Display
F17.14 00.00~49.99 05.02 △
Parameter 14
User-defined Display
F17.15 00.00~49.99 08.01 △
Parameter 15
User-defined Display
F17.16 00.00~49.99 08.02 △
Parameter 16
- 54 -
FR100 Series Multifunctional Compact Inverter
User-defined Display
F17.17 00.00~49.99 08.03 △
Parameter 17
User-defined Display
F17.18 00.00~49.99 08.04 △
Parameter 18
User-defined Display
F17.19 00.00~49.99 08.05 △
Parameter 19
User-defined Display
F17.20 00.00~49.99 08.30 △
Parameter 20
User-defined Display
F17.21 00.00~49.99 11.10 △
Parameter 21
User-defined Display
F17.22 00.00~49.99 13.00 △
Parameter 22
User-defined Display
F17.23 00.00~49.99 13.01 △
Parameter 23
User-defined Display
F17.24 00.00~49.99 13.02 △
Parameter 24
User-defined Display
F17.25 00.00~49.99 13.08 △
Parameter 25
User-defined Display
F17.26 00.00~49.99 13.09 △
Parameter 26
User-defined Display
F17.27 00.00~49.99 00.00 △
Parameter 27
User-defined Display
F17.28 00.00~49.99 00.00 △
Parameter 28
User-defined Display
F17.29 00.00~49.99 00.00 △
Parameter 29
Group U00 Status Monitoring
U00.00 Running frequency 0.00~Fup 0.00Hz ⊙
U00.01 Set frequency 0.00~Fmax 0.00Hz ⊙
U00.02 Output voltage 0~660V 0.0V ⊙
U00.03 Output current 0.0~3000.0A 0.0A ⊙
U00.04 Output power 0.0~3000.0kW 0.0kW ⊙
Estimated Motor
U00.05 0~60000rpm 0rpm ⊙
Speed
U00.06 Bus voltage 0~1200V 0V ⊙
U00.07 Synchronous Frequency 0.00~Fup 0.00Hz ⊙
U00.08 PLC step 0~15 0 ⊙
U00.09 Program Operation Time 0.0~6000.0s(h) 0.0s(h) ⊙
U00.10 PID set 0~60000 0 ⊙
U00.11 PID feedback 0~60000 0 ⊙
Status of DI1~DI5 digital
U00.12 DI5 DI4 DI3 DI2 DI1 00000 ⊙
input terminal
Status of DI6~DI7 digital
U00.13 DI7 DI6 00 ⊙
input terminal
Status of digital output
U00.14 R2 R1 Y2 Y1 0000 ⊙
terminal
U00.15 AI1 input 0.0~100.0% 0.0% ⊙
U00.16 AI2 input 0.0~100.0% 0.0% ⊙
Keypad potentiometer
U00.18 0.0~100.0% 0.0% ⊙
input
U00.19 HI input 0.00~100.00kHz 0.00kHz ⊙
U00.20 AO1 output 0.0~100.0% 0.0% ⊙
U00.23 Temperature of inverter -40.0℃~120.0℃ 0.0℃ ⊙
U00.24 Accumulative power-on 0~65535min 0min ⊙

- 55 -
FR100 Series Multifunctional Compact Inverter
time
U00.25 Accumulative running time 0~6553.5min 0.0min ⊙
Cumulative power-on
U00.26 0~65535h 0h ⊙
time
U00.27 Cumulative running time 0~65535h 0h ⊙
U00.28 Count value 0~65535 0 ⊙
U00.29 Length value 0~65535m 0m ⊙
Group U01 Fault Record
Err00:No fault
Err01:Accel overcurrent
Err02:Decel overcurrent
Err03:Constant-speed overcurrent
Err04:Accel overvoltage
Err05:Decel overvoltage
Err06:Constant-speed overvoltage
Err07:Bus undervoltage
Err08:Short circuit
Err09:Power input phase loss
Err10:Power output phase loss
Err11:Motor overload
Err12:Inverter overload
Err13:External equipment fault
Err14:Module overheat
Err15:EEPROM read/write fault
Err16:Motor auto-tuning cancelled
U01.00 Code of the latest fault Err17:Motor auto-tuning fault Err00 ⊙
Err18:Communication overtime
error
Err19:PID feedback loss
Err20:Continuous running time
reached
Err21:Parameter upload fault
Err22:Parameter download fault
Err23:Braking unit fault
Err24:Module temperature
detection disconnection
Err25: Load becoming 0
Err26:With-wave current limit fault
Err27:Inverter soft-start relay is off
Err28:EEPROM version is not
compatible
Err29:reserved
Err30:reserved
Err31:reserved
Running frequency
U01.01 when the latest fault 0.00~Fup 0.00Hz ⊙
occurred
Output current when the
U01.02 0.0~3000.0A 0.0A ⊙
latest fault occurred
Bus voltage when the
U01.03 0~1200V 0V ⊙
latest fault occurred
U01.04 Cumulative running time 0~65535h 0h ⊙
- 56 -
FR100 Series Multifunctional Compact Inverter
when the latest fault
occurred
U01.05 Code of previous fault Same as U01.00 Err00 ⊙
Running frequency
U01.06 when previous fault 0.00~Fup 0.00Hz ⊙
occurred
Output current when
U01.07 0.0~3000.0A 0.0A ⊙
previous fault occurred
Bus voltage when
U01.08 0~1200V 0V ⊙
previous fault occurred
Cumulative running time
U01.09 when previous fault 0~65535h 0h ⊙
occurred
Before-previous fault
U01.10 Same as U01.00 Err00 ⊙
code
Running frequency
U01.11 when before-previous 0.00~Fup 0.00Hz ⊙
fault occurred
Output current when
U01.12 before-previous fault 0.0~3000.0A 0.0A ⊙
occurred
Bus voltage when
U01.13 before-previous fault 0~1200V 0V ⊙
occurred
Cumulative running time
U01.14 when before-previous 0~65535h 0h ⊙
fault occurred
Previous 3 categories of
U01.15 The same with U01.00 Err00 ⊙
faults
Previous 4 categories of
U01.16 The same with U01.00 Err00 ⊙
faults
Previous 5 categories of
U01.17 The same with U01.00 Err00 ⊙
faults
Previous 6 categories of
U01.18 The same with U01.00 Err00 ⊙
faults
Previous 7 categories of
U01.19 The same with U01.00 Err00 ⊙
faults
Previous 8 categories of
U01.20 The same with U01.00 Err00 ⊙
faults
Previous 9 categories of
U01.21 The same with U01.00 Err00 ⊙
faults
Previous 10 categories of
U01.22 The same with U01.00 Err00 ⊙
faults
Previous 11 categories of
U01.23 The same with U01.00 Err00 ⊙
faults
Previous 12 categories of
U01.24 The same with U01.00 Err00 ⊙
faults
Previous 13 categories of
U01.25 The same with U01.00 Err00 ⊙
faults

- 57 -
FR100 Series Multifunctional Compact Inverter

Chapter 6 Specification of Parameters

Group F00 System Parameters


F00.00 Setting of user password Range: 0~65535 Default: 0
Setting of password:
A non-zero number could be set as a user password by entering this password into F00.00 and
pressing ENT key to confirm once, the password setting will take effect as long as there is no
operation on keypad within 2 minutes, or cutting the power off and power up again . After a password
has been set and taken effect, you must enter the correct password in order to enter the menu. If the
entered password is incorrect you cannot view or modify parameters.
Change password:
Access F00.00 after entering the original password (at this point, F00.00 displays setting of user
password) and set the new password following the above-noted procedure.
Password clearance:
Access F00.00 after entering the original password (at this point, F00.00 displays setting of user
password); F00.00 is set to 0 and press ENT key to make confirmation. In this way, password is
successfully cleared and the password protection function is disabled.
F00.01 Function code display Range:0~2 Default:1
0:Display all function code。
1:Display F00.00、F00.01 and user setting function code。
2:Display F00.00、F00.01 and the function code different with factory setting
F00.02 Parameter protection Range: 0~1 Default: 0
0: All parameter programming allowed
1: Only this parameter programming allowed
F00.04 Parameter initialization Range:0~4 Default: 0
0: No operation
1: Restore all parameters to factory default (excluding motor parameters)
If F00.04 is set to 1, most function codes are restored to the default settings except motor
parameters, fault records, accumulative running time, and accumulative power-on time.
2: Clear fault record
If F00.04 is set to 2, all fault record of Group U01 will be cleared.
3: Back up current user parameters
If F00.04 is set to 3, the current parameter settings are backed up, helping you to restore the
setting if incorrect parameter setting is performed.
4: Restore all parameters to backup parameters
If F00.04 is set to 4, the previous backup user parameters are restored.
F00.05 Copy of parameter Range:0~3 Default: 0
0: No operation
1: Upload all parameters other than Group U to UP/DOWNLOAD
2: Download all parameters of UP/DOWNLOAD other than F08~F09 to drive
3: Download all parameters of UP/DOWNLOAD to drive
*:UP/DOWNLOAD is optional parts
F00.06 Parameter editing mode Range:0~2 Default: 0
0: Editable via keypad and RS485
1: Editable via keypad
2: Editable via RS485
F00.08 Motor 1 control mode Range:0~1 Default:1
0: V/f control
Constant voltage&frequency ratio control. Applicable to such cases in which the performance
Requirement to the drive is not rigorous, or using one drive to drive several motors, or it is difficult to
identify motor parameters correctly, etc. When motor 1 under V/f control is selected, need to set
related parameters Group F09 well.
1: Sensor-less vector control 1
- 58 -
FR100 Series Multifunctional Compact Inverter
This helps achieve high-performance control without encoder and provides strong adaptability of
load. Under this selection, please correctly set parameters Group F08 and F09.
2: Sensor-less vector control 2
This helps achieve high-performance control without encoder. This control technique is superior
to sensor-less vector control 1. Under this selection, please correctly set motor parameters of Group
F08 and vector control parameters of Group F10.

F00.09 DI7/HI input mode Range:0~1 Default: 0


0: Digital input terminal 7
1: Pulse input
F00.12 PWM optimization Range:000~103 Default:100
Unit's place: PWM modulation mode
0: Fixed carrier
Carrier of inverter is a fixed value set by F00.12.
1: Random carrier
Inverter carrier will vary with output frequency in linear variation. Upper/Lower carrier frequencies
are under control of F00.14 and F00.15.
2: Derating of fixed carrier
Inverter can adjust carrier value based on F00.12, carrier temperature and carrier current,
protecting itself against overtemperature.
3: Derating of random carrier
Inverter can adjust carrier value based on random carrier, carrier temperature and carrier current,
protecting itself against overtemperature.
Decade: PWM modulation mode
0: Seven-segment mode
Hundreds place: over-modulation adjustment
0: Disabled
1: Enabled
At low grid voltage or long-term heavy-duty operation, over-modulation can improve the voltage
utilization and enhance the maximum voltage output capacity of the drive. This parameter takes effect
only for V/f control, while over-modulation is enabled all the time under SVC pattern.
Default: Model
F00.13 Carrier frequency Range:0.700~16.000kHz
defined
At lower carrier frequency, output current of the drive produces higher harmonics, motor loss
increases, and temperature and motor noise rise, but drive temperature, drive leakage current, and
drive interference to external devices are lower or less.
With higher carrier frequency, drive temperature will rise, drive leakage current is bigger, and
drive interference to external devices is bigger. However, motor loss and noise will be lower, and
motor temperature will drop.
PWM carrier frequency setting method:
1) When the motor line is too long, reduce carrier frequency.
2) When torque at low speed is unstable, reduce carrier frequency.
3) If the drive produces severe interference to surrounding equipment, reduce carrier frequency.
4) Leakage current of the drive is big, reduce carrier frequency.
5) Drive temperature rise is relatively high, reduce carrier frequency.
6) Motor temperature rise is relatively high, increase carrier frequency.
7) Motor noise is relatively big, increase carrier frequency.
ATTENTION:
Increasing carrier frequency can reduce motor noise and heat, but it will increase temperature of
inverter. When the carrier frequency is higher than the default, inverter rated power shall be decreased
by 5% for every additional 1 kHz carrier frequency.
F00.14 Upper carrier frequency Range:0.700~16.000kHz Default:8.000 kHz
F00.15 Lower carrier frequency Range:0.700~16.000kHz Default:2.000 kHz
Inverter carrier will vary with output frequency in linear variation. Upper/Lower carrier frequencies
are under control of F00.14 and F00.15.
F00.16 Output voltage Range:5.0~100.0% Default:100.0%
Adjust the percentage of output voltage to input voltage.

- 59 -
FR100 Series Multifunctional Compact Inverter
F00.17 AVR Range:0~2 Default: 1
0: Disabled
1: Enabled
2: AVR is disabled if the DC bus voltage > the rated voltage of DC bus, and it will be enabled if the
DC bus voltage≤the rated voltage of DC bus.
F00.18 Fan control Range:0~1 Default:1
After power is on, the fan runs per the control mode after running for 2 minutes regardless of the
working status of inverter.
0: The fan runs directly after inverter is power-on.
1: the fan works when the AC drive is in running state. When the AC drive stops, the cooling fan
works if the heat sink temperature is higher than 42°C, and stops working if the heat sink temperature
is lower than 38°C.
F00.19 Factory password Range:0~65535 Default: 0
Factory parameter
Default: Model
F00.20 Inverter rated power Range:0.2~710.0kW
defined
Default: Model
F00.21 Inverter rated voltage Range:220~380V
defined
Default: Model
F00.22 Inverter rated current Range:0.1~1500.0A
defined
Default: Model
F00.23 Software version Range:0.01~99.99
defined
The parameters are only for reference and cannot be edited.
F00.24 Dealer password Range:0~65535 Default:0
Range:0~65535h(0:
F00.25 Using time Default:0
Invaild)
When total running time ≥F00.25, inverter will not work. When setting F00.24, need to unlock
F00.24 dealer passport, after time setting, need to input dealer passport to lock
★:Setting this parameter may cause that the inverter can’t work normally,please set carefully.
F00.26 Inverter application Range:0~1 Default:0
Inverter application
0:General purpose application
1:Fireworks machine

Group F00 Frequency command


Switched by
Terminal UP/DOWN terminal Switched by
terminal
0
+
Master frequency
source
Command frequency

Auxiliary 1
frequency source
2
+ Jog
frequency
3
-

4
Max

5
Min

+
6
x
AI1

+
x 7
AI2

Fig. 6-1

- 60 -
FR100 Series Multifunctional Compact Inverter
Frequency source
F01.00 Range:0~7 Default: 0
selection
0: Master frequency source
The frequency source is determined by master frequency source F01.01.
1: Auxiliary frequency source
The frequency source is determined by auxiliary frequency source F01.03.
2: Master + Auxiliary
The frequency source is determined by Master + Auxiliary.
3: Master - Auxiliary
The frequency source is determined by Master - Auxiliary.
4: MAX {Master, Auxiliary}
The frequency source is determined by MAX {Master, Auxiliary}.
5: MIN {Master, Auxiliary}
The frequency source is determined by MIN {Master, Auxiliary}.
6: AI1*(Master + Auxiliary)
The frequency source is determined by AI1*(Master + Auxiliary).
7: AI2*(Master + Auxiliary)
The frequency source is determined by AI2*(Master + Auxiliary).
F01.01 Master frequency source selection Range:0~8 Default:1
0: Digital setting (F01.02)
When the inverter is powered on, the value of F01.02 is taken as the master frequency source.
1: Keypad potentiometer
2: Analog input AI1
AI1 and AI2 are (0~10V) voltage input and (0~20mA) current input programmable. Voltage or
current input can be selected through toggle switches AI1 and AI2 on control board.
3: Communication
Upper computer is the master frequency command source of the drive through standard RS485
communication interface on the drive. Refer to Group F15 and appendix on this manual for further
information aboutcommunication protocol, and programming, etc.
4: Multi-reference
In multi-reference mode, combinations of different DI terminal states correspond to different set
frequencies. The FR100 supports a maximum of 16 speeds implemented by 16 state combinations of
four DI terminals (allocated with functions 13 to 16) in Group F04. The multiple references indicate
percentages of the value of F01.08 (Maximum frequency).
If a DI terminal is used for the multi-reference function, you need to perform related setting in
group F04.
5: PLC
Master frequency command is determined by simple PLC. See parameter Group F12 for details.
6: Process PID output
Master frequency command is determined by process closed-loop PID computation result. See
parameter Group F13 for details.
7: DI7/HI pulse input
If this parameter value selected, command frequency will be determined by pulse frequency input
via terminal DI7/HI only. In such a case, F00.09 should be set to 1. Corresponding relation between
pulse frequency and command frequency is specified in F06.32~F06.35.
8:AI2
Master frequency command is determined by analog input AI2.
Note:
AI2 are(0~10)V voltage input or (0~20) mA current input optional for AI2. Voltage or current input
can be selected by the toggle switch on control panel input and(0~20mA), correspondence between
analog value and frequency please refer to the specific instructions of function codeF06.00~F06.15.
When using external analog directly input, the connection diagram of voltage/current analog input
shown as figure 6-2.

- 61 -
FR100 Series Multifunctional Compact Inverter

Analog input AI1


AI1
Analog
input AI2
AI2
Inverter

GND

Figure 6-2 Diagram for analog input with external power supply
When using the inverter with 10V power built-in combined with potentiometer, connection diagram
shown as figure 6-3, note that the toggle switch must keep voltage input side at this moment.

+10V

AI(i) Adjustable
Inverter (i=1,2) resistor

GND

Figure 6-3 Diagram for internal 10V power analog input


Note:
The final set frequency of FR100 series inverter mainly frequency can be stacked by keypad
UP/DOWN button or the function of UP/DOWN terminal, while no such a function for the final setted
frequency of auxiliary frequency source.

Digital setting of master


F01.02 Range:0.00~FmaxHz Default:0.00Hz
frequency
When master frequency source selection F01.01 is set to 1, this parameter value will be the initial
value of master frequency command.
Auxiliary frequency command
F01.03 Range:0~9 Default: 0
source
0: Digital setting (F01.04)
When the inverter is powered on, the value of F01.02 is taken as the master frequency source.
1: Keypad potentiometer
Auxiliary frequency command is determined by keypad potentiometer.
2: Analog input AI1
Auxiliary frequency command is determined by analog input AI1.
3: Communication
Upper computer is the auxiliary frequency command source of the drive through standard RS485
communication interface on the drive.
4: Multi-reference
Auxiliary frequency command is determined by multi-reference. See parameter Group F04 for
details.
5: PLC
Auxiliary frequency command is determined by simple PLC. See parameter Group F12 for details.
6: Process PID output
Auxiliary frequency command is determined by process PID computation result. See parameter
Group F13 for details.
7: DI7/HI pulse input
Auxiliary frequency command is determined by DI7/HI pulse input.
8:AI2

- 62 -
FR100 Series Multifunctional Compact Inverter
Auxiliary frequency command is determined by analog input AI2.
Digital setting of auxiliary
F01.04 Range:0.00~Fmax Default:0.00Hz
frequency
When auxiliary frequency command F01.03 is set to 0, this parameter value should be the initial
value of auxiliary frequency command.
F01.05 Range of auxiliary frequency Range:0~1 Default: 0
0: Relative to maximum frequency
1: Relative to master frequency
See F01.06 specification for details.
F01.06 Coeff of auxiliary frequency Range:0.0~150.0% Default:100.0%
F01.05 and F01.06 will determine the final output value of auxiliary frequency command.
When F01.05 is set to 0 (relative to maximum frequency):
The auxiliary frequency= the auxiliary frequency *F01.06.
When F01.05 is set to 1 (relative to master frequency):
The setting range of the auxiliary frequency varies according to the master frequency.
The auxiliary frequency= the auxiliary frequency *F01.06*abs (the master frequency)/F01.08.
F01.07 Jog frequency Range:0.00~Fmax Default:5.00Hz
This parameter sets the running frequency during jog.
F01.08 Maximum frequency Range:20.00~600.00 Default:50.00Hz
Maximum frequency of F01.08 is the maximum allowable output frequency of drive.
F01.09 Upper limit frequency Range:Fdown~Fmax Default:50.00Hz
F01.10 Lower limit frequency Range:0.00~Fup Default:50.00Hz
F01.09upper limit frequency is the user-defined maximum allowable running frequency; F01.10
lower limit frequency is user-defined minimum allowable running frequency.
ATTENTION:
1. Fup and Fdown shall be set as per motor nameplate parameters and working conditions. Motor
shall not work in low frequency for a long time. Otherwise, motor service lifespan will be shortened due
to overheating.
2. Correlation of Fmax, Fup and Fdown: 0.00Hz ≤Fdown ≤Fup≤Fmax ≤600.00Hz
Operation when command
F01.11 frequency lower than lower Range:0~1 Default: 0
limit frequency
Lower limit frequency
F01.12 Range:0.0~6000.0s Default:0.0s
running time
0: Run at lower limit frequency
In case command frequency is lower than lower limit frequency, the running should be at lower
limit frequency.
1: Run at 0 Hz would be activated after the time delay
If frequency command is lower than lower limit frequency, run at 0 Hz would be activated after the
time delay set by F01.12. When lower limit frequency is 0, this limitation is invalid.
Group F02 Start/Stop Control Start/Stop Control
F02.00 Run command Range:0~2 Default: 0
This parameter sets run command source. Run commands include "start, stop, forward ,
reverse,jog", etc.
0: Keypad control (LED off)
Control run command through RUN, STOP/RESET and MF.K keys on keypad (set multifunction
key MF.K to JOG by F16.00). Refer to Chapter 4 about the operation of keypad.
1: Terminal control (LED on)
Controls run command via DI terminals. Perform FORWARD and REVERSE by DI terminals. The
control modes are two-wire mode and three-wire mode selectable. See Group F04 for details of
designation and wiring regulation of DI terminals.
2: Communication control (LED blinking)
Master device is able to control run command through built-in RS485 serial communication
interface of drive. Refer to parameters Group F15 and appendix for further information about
programming.
Run command from keypad, terminals and communication can be switched by terminals "run

- 63 -
FR100 Series Multifunctional Compact Inverter
command switched to keypad control", "run command switched to terminal control" and "run command
switched to communication control".
Multifunction key MF.K can be set to "run command sources shifted" key through parameter
F16.00. When MF key is pressed under this setting; run command will be shifted during keypad control,
terminal control and communication control circularly.
F02.01 Running direction Range:0~1 Default: 0
0: Forward
1: Reverse
You can change the rotation direction of the motor just by modifying this parameter without
changing the motor wiring. Modifying this parameter is equivalent to exchanging any two of the motor's
U, V, W wires.
Note:
The motor will resume running in the original direction after parameter initialization. Do not use
this function in applications where changing the rotating direction of the motor is prohibited after
system commissioning is complete.
F02.02 Reverse-proof action Range:0~1 Default: 0
0: Reverse enabled
1: Reverse disabled
In some applications, reverse is likely to result in equipment damage. This parameter is used to
prevent reverse running.
Dead time of forward and
F02.03 Range:0.0~6000.0s Default:0.0s
reverse
The dead time with 0Hz output during the transition from forward to reverse, or from reverse to forward. As shown
in Fig. 6-4.

Output frequency(Hz)

Time(S)

Dead time of forward Dead time of forward


and reverse and reverse
Fig. 6-4
F02.04 Start mode Range:0~1 Default: 0
0: From start frequency
If the DC braking time(F02.08) is set to 0, the AC drive starts to run at the startup
frequency(F02.05) and keeps this frequency for a period of time set by F02.06, and then accelerated
to command frequency in accordance with the accel method and time..
If the DC braking time (F02.08)is not 0, the AC drive performs DC braking first and then starts to
run at the startup frequency. It is applicable to small-inertia load application where the motor is likely to
rotate at startup.
1: Rotational speed tracking restart
The AC drive judges the rotational speed and direction of the motor first and then starts at the
tracked frequency. Such smooth start has no impact on the rotating motor. It is applicable to the restart
upon instantaneous power failure of large-inertia load. To ensure the performance of rotational speed
tracking restart, set the motor parameters correctly.
F02.05 Start frequency Range:0.00~10.00Hz Default:0.00Hz
F02.06 Startup frequency holding time Range:0.0~100.0s Default:0.0s
To ensure the motor torque at AC drive startup, set a proper startup frequency. In addition, to build
excitation when the motor starts up, the startup frequency must be held for a certain period.
The startup frequency (F02.05) is not restricted by the frequency lower limit. If the set target
frequency is lower than the startup frequency, the AC drive will not start and stays in the standby state.
During switchover between forward rotation and reverse rotation, the startup frequency holding
- 64 -
FR100 Series Multifunctional Compact Inverter
time is disabled. The holding time is not included in the acceleration time but in the running time of
simple PLC.
F02.07 Startup DC braking current Range:0.0~150.0% Default:0.0
F02.08 Startup DC braking time Range:0.0~100.0s Default:0.0
Startup DC braking is generally used during restart of the AC drive after the rotating motor stops.
Pre-excitation is used to make the AC drive build magnetic field for the asynchronous motor before
startup to improve the responsiveness.
Startup DC braking is valid only for direct start (f02.05 = 0). In this case, the AC drive performs DC
braking at the set startup DC braking current. After the startup DC braking time, the AC drives starts to
run. If the startup DC braking time is 0, the AC drives starts directly without DC braking. The larger the
startup DC braking current is, the larger the braking force is.
F02.09 Speed search current Range:0.0~180.0 Default:100.0%
100% corresponds to rated current of the drive. When output current of drive is less than this
parameter value, it will be deemed that the output frequency of drive has been kept in step with motor
speed and the search action finished.
F02.10 Sped search decel time Range:0.0~10.0 Default:1.0s
This parameter sets the output frequency Decel time of speed search action. This time means the
time required for Decel from maximum frequency to 0.The shorter the speed search Decel time is, the
faster the search will be. However, excessively rapid search may bring about inaccuracy of search
result.
F02.11 Sped search coefficient Range:0.01~5.00 Default:0.30
Sped search coefficient
F02.12 Stop method Range:0~1 Default: 0
0: Ramp to stop
Upon the receipt of stop command, drive will gradually decrease output frequency according to
the set Decel time, and stop when frequency attains 0.
1: Coast to stop
Upon the receipt of stop command, drive will immediately lock the output and the motor will stop
with its mechanical inertia.
Initial frequency of stop DC
F02.13 Range:0.00~50.00Hz Default:2.00Hz
braking
F02.14 Stop DC braking current Range:0.0~150.0% Default:0.0%
Waiting time of stop DC
F02.15 Range:0.0~30.0s Default:0.0s
braking
F02.16 Stop DC braking time Range:0.0~30.0s Default:0.0s
Initial frequency of stop DC braking:
During the process of decelerating to stop, the AC drive starts DC braking when the running
frequency is lower than the value set in F02.13.
Stop DC braking current:
This parameter specifies the output current at DC braking and is a percentage relative to the base
value.
If the rated motor current is less than or equal to 80% of the rated AC drive current, the base value
is the rated motor current.
If the rated motor current is greater than 80% of the rated AC drive current, the base value is 80%
of the rated AC drive current.
Waiting time of stop DC braking:
When the running frequency decreases to the initial frequency of stop DC braking, the
AC drive stops output for a certain period and then starts DC braking. This prevents faults such as
over current caused due to DC braking at high speed.
Stop DC braking time:
This parameter specifies the holding time of DC braking. If it is set to 0, DC braking is cancelled.
ATTENTION:
If there is a DC brake signal of external terminal at stop, then the DC brake time takes the bigger
value between the active time of the terminal and the setting time of F02.16.

The stop DC braking process is shown in the following figure.


Figure 6-5 Stop DC braking process
- 65 -
FR100 Series Multifunctional Compact Inverter
Output frequency(Hz)

Initial frequency of stop


DC braking
Time(S)

Waiting time of stop


DC braking

Output voltage
RMS
Time(S)

Stop DC braking
Run command time
Fig. 6-5
F02.17 Dynamic brake Range:0~3 Default: 0
When dynamic brake is enabled, the electric energy generated during Decel shall be converted
into heat energy consumed by brake resistor, so as to attain rapid Decel. This brake method applies to
brake of high-inertia load or the situations that require quick stop. In such a case, it is necessary to
select appropriate dynamic brake resistor and break unit. The AC drives equal and below 30kW is
provided with a standard built-in brake unit. Built-in brake unit is optional for AC drive 37kW~75kW.
0: Disabled
1: Enabled
2: Enabled at running
3: Enabled at deceleration
Dynamic brake threshold
F02.18 Range:480~800V Default:700V
voltage
This parameter takes effect only to the drives with built-in brake unit.
When bus voltage of AC drive attains the value of F02.18, dynamic brake shall perform. The
energy shall be rapidly consumed through brake resistor. This value is used to regulate the brake
effect of brake unit.
F02.19 Brake use ratio Range:5.0~100.0% Default:100.0%
It is valid only for the AC drive with internal braking unit and used to adjust the duty ratio of the
braking unit. The larger the value of this parameter is, the better the braking result will be. However,
too larger value causes great fluctuation of the AC drive bus voltage during the braking process.
F02.20 0Hz Output selection Range:0~1 Default:0
0: No voltage output
1: Voltage output
Group F03 Accel/Decel Parameters
F03.00 Accel time 0 Range:0.0~6000.0s Default:15.0s
F03.01 Decel time 0 Range:0.0~6000.0s Default:15.0s
F03.02 Accel time 1 Range:0.0~6000.0s Default:15.0s
F03.03 Decel time 1 Range:0.0~6000.0s Default:15.0s
F03.04 Accel time 2 Range:0.0~6000.0s Default:15.0s
F03.05 Decel time 2 Range:0.0~6000.0s Default:15.0s
F03.06 Accel time 3 Range:0.0~6000.0s Default:15.0s
F03.07 Decel time 3 Range:0.0~6000.0s Default:15.0s
Accel time means required time for drive to Accelerate to maximum frequency F01.08 from zero
frequency, while Decel time refers to the time required for drive to Decelerate to zero frequency from
maximum frequency F01.08.

- 66 -
FR100 Series Multifunctional Compact Inverter
These four types of Accel/Decel time can be selected through the ON/OFF combination of
DI terminals" Accel/Decel time determinant 1" and "Accel/Decel time determinant 2". See the following
table.
Accel/Decel time Accel/Decel time
Accel/Decel time
determinant 2 determinant 1
OFF OFF Accel/Decel time 1(F03.00、F03.01)
OFF ON Accel/Decel time 2(F03.02、F03.03)
ON OFF Accel/Decel time 3(F03.04、F03.05)
ON ON Accel/Decel time 4(F03.06、F03.07)

F03.08 Jog accel time Range:0.0~6000.0s Default:15.0s


F03.09 Jog decel time Range:0.0~6000.0s Default:15.0s
F03.08 and F03.09 set the rate of Accel/Decel of Jog, similar with F03.00~F03.07.
F03.10 Accel/Decele curve Range:0~1 Default: 0
F03.11 S curve Time 0 Range:0.0~6000.0s Default:0.0s
F03.15 S curve Time 1 Range:0.0~6000.0s Default:0.0s
F03.16 S curve Time 2 Range:0.0~6000.0s Default:0.0s
F03.17 S curve Time 3 Range:0.0~6000.0s Default:0.0s
0: Linear Accel/Decel
Accel/Decel is in linear mode.
1: S-curve Accel/Decel
The 1st section and the last section in accelerating or decelerating are in smooth transition. The
acceleration/deceleration curve is similar to S curve. When it is in S curve, the final
acceleration/deceleration time= S curve time+ Linear acceleration/deceleration time. See Figure 6-13
for 2 acceleration/deceleration modes.
See Figure 6-6 for 2 acceleration/deceleration modes.

Output frequency(Hz)
Fmax

Fset

0
① ① ① ① T

② ③
Setting acceleration Setting
time deceleration time
①S section curve time
②Time required for linear acceleration time
③Time required for linear deceleration time
Figure 6-6
Acceleration and 0:0.1s
F03.12 0 ×
deceleration time unit 1:0.01s
To select the time unit of acceleration and deceleration
0:0.1s
All acceleration and deceleration time unit is 0.1s, the decimal point of function code 4 step acc/dec
time((F03.00~F03.07)、Inching acc/dec time (F03.08、F03.09)、4 step S curve time (F03.11、F03.15~
F03.17) is one bit.
1:0.01s

- 67 -
FR100 Series Multifunctional Compact Inverter
All acceleration and deceleration time unit is 0.01s, the decimal point of function code 4 step acc/dec
time((F03.00~F03.07)、Inching acc/dec time (F03.08、F03.09)、4 step S curve time (F03.11、F03.15~
F03.17) is 2 bit.
Frequency switchover point
F03.13 between acceleration time 1 and Range:0.00~Fmax Default:0.00Hz
acceleration time 2
Frequency switchover point
F03.14 between deceleration time 1 and Range:0.00~Fmax Default:0.00Hz
deceleration time 2
This function is valid when motor 1 is selected and acceleration/deceleration time switchover is
not performed by means of DI terminal. It is used to select different groups of acceleration/deceleration
time based on the running frequency range rather than DI terminal during the running process of the
AC drive.
During acceleration, if the running frequency is smaller than the value of F03.13, acceleration time
2 is selected. If the running frequency is larger than the value of F03.13, acceleration time 1 is
selected.
During deceleration, if the running frequency is larger than the value of F03.14, deceleration time
1 is selected. If the running frequency is smaller than the value of F03.14, deceleration time 2 is
selected.
Figure 6-7 Acceleration/deceleration time switchovers.

Output frequency(Hz)

Set frequency

F03.13

F03.14

Time

Acceleration Acceleration Deceleration Deceleration


time 2 time 1 time 1 time 2

Figure 6-7
Group F04 Digital Input
F04.00 Function of terminal DI1 Range:0~99 Default:1
F04.01 Function of terminal DI2 Range:0~99 Default:2
F04.02 Function of terminal DI3 Range:0~99 Default:7
F04.03 Function of terminal DI4 Range:0~99 Default:13
F04.06 Function of terminal DI7 Range:0~99 Default:0

Value Function Description


0 No function Set 0 for reserved terminals to avoid malfunction.
Forward RUN
1 Terminals control forward running and reverse running of the
(FWD)
drive. Refer to F04.15 for enabled conditions on initial power
Reverse RUN
2 up.
(REV)
The terminal determines three-line control of the AC drive. For
3 Three-wire control
details, see the description of F04.15.
Forward JOG FJOG indicates forward JOG running, while RJOG indicates
4
(FJOG) reverse JOG running. The JOG frequency, acceleration time

- 68 -
FR100 Series Multifunctional Compact Inverter
Reverse JOG and deceleration time are described respectively in F01.07,
5
(RJOG) F03.08 and F03.09.
The AC drive blocks its output, the motor coasts to rest and is
6 Coast to stop not controlled by the AC drive. It is the same as coast to stop
described in F02.12.
The terminal is used for fault reset function, the same as the
7 Fault reset (RESET) function of RESET key on the operation panel.Remote fault
reset is implemented by this function.
The AC drive decelerates to stop, but the running parameters
are all memorized, such as PLC, swing frequency and PID
8 RUN pause
parameters. After this function is disabled, the AC drive
resumes its status before stop.
Normally open (NO) If this terminal becomes ON, the AC drive reports Err13 and
9 input performs the fault protection action. For more details, see the
of external fault description of F11.11.
10 Terminal UP If the frequency is determined by external terminals, the
Terminals with the two functions are used as increment and
11 Terminal DOWN decrement commands for frequency modification.
If the frequency source is master frequency source setting, the
UP and DOWN
terminalis used to clear the modification by using the
setting
12 UP/DOWN function or the increment/decrement key on the
clear (terminal,
keypad, returning the set frequency to the value of master
keypad)
frequency source setting.
Multi-reference
13
terminal 1
Multi-reference
14 The setting of 16 speeds or 16 other references can be
terminal 2
implemented through combinations of 16 states of these four
Multi-reference
15 terminals.
terminal 3
Multi-reference
16
terminal 4
Terminal 1 for
acceleration/
17
deceleration time
Totally four groups of acceleration/deceleration time can be
selection
selected through combinations of two states of these two
Terminal 2 for
terminals.
acceleration/
18
deceleration time
selection
When "Accel/Decel disabled" terminal is enabled, the drive
Acceleration/Decele maintains the present output frequency and no longer
19 ration responds to the change of command frequency. But it will
prohibited still perform ramp-down stop when receiving stop command.
This terminal is disabled during normal ramp-down stop.
Switch to auxiliary
Switch integrated frequency source setting mode to auxiliary
20 frequency source
frequency source setting mode.
setting
When simple PLC is running and this terminal is enabled. The
status (running time and step) of PLC will be cleared and the
21 PLC status reset
output frequency is step 0. When this terminal is disabled
again, the drive resumes PLC running from step 0.
When simple PLC is running and this terminal is enabled, the
current PLC status (running time and step) will be memorized,
22 Simple PLC paused
and the drive will run at 0Hz. When this terminal is disabled,
the drive restores its running from the memorized moment.
When this terminal is enabled, PID adjustment is paused, and
23 PID pause the drive will maintain current output frequency. After this
terminal becomes disabled, PID adjustment recovers.
- 69 -
FR100 Series Multifunctional Compact Inverter
Reverse PID action After this terminal becomes ON, the PID action direction is
24
direction reversed to the direction set in F13.04.
After this terminal becomes ON, the integral adjustment
25 PID integral pause function pauses. However, the proportional and differentiation
adjustment functions are still valid.
When PID parameter switch is set to "2: switched by terminal",
this terminal could be used to realize the switching between
PID parameter two groups of PID parameters. When this terminal is enabled,
26
switchover PID parameters are Kp1 and Ti1, Td1.
When this terminal is disabled, PID parameters are Kp2, Ti2
and Td2.
Swing frequency
The AC drive outputs the current frequency, and the swing
27 pause(output the
frequency function pauses.
current frequenc)
Swing frequency
The AC drive outputs the central frequency, and the swing
28 reset(output the
frequency function pauses.
central frequency)
Run comman This terminal should be enabled by trigger edge. When this
29 switched to keypad terminal status is switched from OFF to ON, run command will
control be switched to keypad control.
Run comman This terminal should be enabled by trigger edge. When this
30 switched to terminal terminal status is switched from OFF to ON, run command will
control be switched to terminal control.
Run comman
This terminal should be enabled by trigger edge. When this
switched to
31 terminal is switched from OFF to ON, run command will be
communication
switched to communication control.
control
The maximum frequency at count pulse input terminal is
200Hz, and the count value can be memorized in case of
power loss. With the setting of F14.07 (set count value) and
32 Count input
14.08 (designated count value), this terminal can control
digital output "set count value attained" and "designated count
value attained".
33 Count clear Used with "count input" terminal, to clear pulse count value.
It is used for fixed-length control, and only takes effect on
digital input terminal DI7/HI. The length is calculated via
pulse input. Please refer to specification of parameters
34 Length count
14.04~F14.06 for details. When the length is attained, digital
output terminal "length attained" shall output effective signal.
The current length value will be memorized on power loss.
Used with "length count" terminal, to clear the length
35 Length clear
calculated.
When inverter is in the process of ramp-to-stop, and running
frequency < DC brake frequency (Set by F02.13) at stop, if the
terminal is ON, DC brake starts, until the terminal is OFF, DC
DC brake input
36 brake ends.
command at stop
If the terminal is ON, and DC brake setting time is effective,
take the bigger value between time when terminal is ON and
DC brake setting time at stop.
37~
Reserved
99
The four multi-reference terminals have 16 state combinations, corresponding to 16 reference values,
as listed in the following table.
Table 1 State combination of the four multi-reference terminals

- 70 -
FR100 Series Multifunctional Compact Inverter
Multi-reference Multi-reference Multi-reference Multi-referenc Reference Corresponding
terminal 4 terminal 3 terminal 2 e terminal 1 Setting Parameter
Reference
OFF OFF OFF OFF F12.16
0
Reference
OFF OFF OFF ON F12.01
1
Reference
OFF OFF ON OFF F12.02
2
Reference
OFF OFF ON ON F12.03
3
Reference
OFF ON OFF OFF F12.04
4
Reference
OFF ON OFF ON F12.05
5
Reference
OFF ON ON OFF F12.06
6
Reference
OFF ON ON ON F12.07
7
Reference
ON OFF OFF OFF F12.08
8
Reference
ON OFF OFF ON F12.09
9
Reference
ON OFF ON OFF F12.10
10
Reference
ON OFF ON ON F12.11
11
Reference
ON ON OFF OFF F12.12
12
Reference
ON ON OFF ON F12.13
13
Reference
ON ON ON OFF F12.14
14
Reference
ON ON ON ON F12.15
15

Table 2 State combinations of two terminals for acceleration/deceleration time selection


Acceleration/Deceler Acceleration/Deceler
Acceleration/Deceleratio Corresponding
ation time ation time
n Time Selection Parameters
determinant 2 determinant 1
Acceleration/Deceleratio
OFF OFF F03.00、F03.01
n time 1
Acceleration/Deceleratio
OFF ON F03.02、F03.03
n time 2
Acceleration/Deceleratio
ON OFF F03.04、F03.05
n time 3
Acceleration/Deceleratio
ON ON F03.06、F03.07
n time 4

Filtering time of digital


F04.10 Range:0.000~1.000s Default:0.010s
input terminal
Set the filtering time of DI1~DI7 (when DI7/HI is used as ordinary low-speed terminal), AI1, AI2
(when used as digital input terminal). Interference immunity of digital input terminals can be improved
by appropriate filtering time. However, the response time of digital input terminal will become slower
when filtering time is increased.
ATTENTION:
This filtering time takes no effect on DI7/HI when DI7/HI terminal is used as DI high-speed input
terminal, while the filtering time of DI is determined by parameter F06.36.

- 71 -
FR100 Series Multifunctional Compact Inverter
F04.11 Delay time of terminal DI1 Range:0.0~300.0s Default:0.0s
F04.12 Delay time of terminal DI2 Range:0.0~300.0s Default:0.0s
The delayed response time of digital input terminals DI1 and DI2 is set by these two parameters.
ATTENTION:
Terminal delay time F04.11and F04.12 can be set with filtering time F04.10 at the same time. The
drive will respond after the signals via DI1 and DI2 go through filtering time, and then delay time.
Terminals DI3~DI7 have no delay time function.
Terminal DI1~DI5
F04.13 Range:00000~11111 Default:00000
positive/negative logic
These parameters are used to set the valid mode of DI terminals.
Unit's place: DI1
0: Positive logic
The DI terminal is valid when being connected with COM, and invalid when being disconnected
from COM.
1: Negative Logic
The DI terminal is invalid when being connected with COM, and invalid when being disconnected
from COM.
Ten's digit: DI2 (same as DI1)
Hundred's digit: DI3 (same as DI1)
Thousand's digit: DI4 (same as DI1)
Ten thousand's digit: reserved
Terminal DI6~AI2
F04.14 Range:00000~11111 Default:00000
positive/negative logic
Use for setting the valid situation mode of input terminal
Unit's place: DI1
0: Positive logic
The DI terminal is valid when being connected with COM, and invalid when being disconnected
from COM.
1: Negative Logic
The DI terminal is invalid when being connected with COM, and invalid when being disconnected
from COM.
F04.15 Terminal command mode Range:0~4 Default: 0
This parameter is used to set the mode in which the AC drive is controlled by external terminals.
The following uses DI1, DI2 and DI3 among DI1 to DI7 as an example, with allocating functions of DI1,
DI2 and DI3 by setting F4-00 to F4-02.
0: Two-line mode 1
It is the most commonly used two-line mode, in which the forward/reverse rotation of the motor is
decided by DI1 and DI2. The parameters are set as below:
Function Code Parameter Name Value Function Description
F04.15 Terminal command mode 0 Two-line 1
F04.00 DI1 function selection 1 Forward RUN (FWD)
F04.01 DI2 function selection 2 Reverse RUN (REV)

K1
FWD FWD REV RUN command
Inverter OFF OFF Stop
K2
OFF ON Reverse RUN
REV
ON OFF Forward RUN
ON ON Stop
GND

Figure 6-8 setting of two-line mode 1

- 72 -
FR100 Series Multifunctional Compact Inverter
As shown in the preceding figure, when only K1 is ON, the AC drive instructs forward rotation.
When only K2 is ON, the AC drive instructs reverse rotation. When K1 and K2 are ON & OFF
simultaneously, the AC drives stops.
1: Two-line mode 2
In this mode, DI1 is RUN enabled terminal, and DI2 determines the running direction.
The parameters are set as below:
Function Code Parameter Name Value Function Description
F04.15 Terminal command mode 1 Two-line 2
F04.00 DI1 function selection 1 Forward RUN (FWD)
F04.01 DI2 function selection 2 Reverse RUN (REV)

FWD REV RUN command


OFF OFF Stop
K1 OFF ON Stop
FWD ON OFF Forward RUN
Inverter
K2 ON ON Reverse RUN
REV

GND

Figure 6-9 setting of two-line mode 2


As shown in the preceding figure, if K1 is ON, the AC drive instructs forward rotation when K2 is
OFF, and instructs reverse rotation when K2 is ON. If K1 is OFF, the AC drives stops.
2: Three-line mode 1
In this mode, DI3 is RUN enabled terminal, and the direction is decided by DI1 and DI2.
The parameters are set as below:

Function Code Parameter Name Value Function Description


F04.15 Terminal command mode 2 Three-line 1
F04.00 DI1 function selection 1 Forward RUN (FWD)
F04.01 DI2 function selection 2 Reverse RUN (REV)
F04.02 DI3 function selection 3 Three-line control

SB1
Three-line
control DIi
SB2
FWD
SB3
Inverter
REV

GND

Figure 6-10 setting of three-line mode 1


As shown in the preceding figure, if SB1 is ON, the AC drive instructs forward rotation when SB2
is pressed to be ON and instructs reverse rotation when SB3 is pressed to be ON. The AC drives
stops immediately after SB1 becomes OFF. During normal startup and running, SB1 must remain ON.
The AC drive's running state is determined by the final actions on SB1, SB2 and SB3.
3: Three-line mode 2
In this mode, DI3 is RUN enabled terminal. The RUN command is given by DI1 and the direction
is decided by DI2. The parameters are set as below:
- 73 -
FR100 Series Multifunctional Compact Inverter

Function Code Parameter Name Value Function Description


Terminal command Three-line 2
F04.15 3
mode
F04.00 DI1 function selection 1 Forward RUN (FWD)
F04.01 DI2 function selection 2 Reverse RUN (REV)
F04.02 DI3 function selection 3 Three-line control

SB1
Three-line
control DIi
SB2
FWD

Inverter K
REV

GND

Figure 6-11 setting of three-line mode 2


As shown in the preceding figure, if SB1 is ON, the AC drive starts running when SB2 is pressed
to be ON; the AC drive instructs forward rotation when K is OFF and instructs reverse rotation when K
is ON. The AC drives stops immediately after SB1 becomes OFF. During normal startup and running,
SB1 must remain ON. The AC drive's running state is determined by the final actions of SB1, SB2 and
K.
4:Pulse operation stop
This model is using one touch control, to start and stop inverter by pulse, motor forward and
reverse operation is determined by DI1 and DI2
Function code setting:
Function Setting
Name Function description
code value
FWD/REV terminal
F04.15 4 Pulse operation stop
control mode selection
F04.00 DI1 function selection 1 Forward operation(FWD)
F04.01 DI2 function selection 2 Reverse operation(REV)

SB
1
FWD FWD ↑ ↑
SB
Operation
2 FWD Stop
Inverter REV command
REV ↑ ↑
Operation
COM REV Stop
command

Figure 6-12 Pulse operation stop control diagram

Press SB1, inverter forward operation, press SB1 again inverter stop; Press SB2, inverter reverse
operation, press SB2 again, inverter stop

- 74 -
FR100 Series Multifunctional Compact Inverter
Press the SB1 button inverter run clockwise, press the SB1 button to stop the SB2 button is
pressed again converter; inverter reverse operation, press the SB2button to stop again inverter

Terminal UP/DOWN frequency


F04.16 Range:00~11 Default:00
adjustment treatment
Unit's place: action when stop
0: Clear
Terminal UP/DOWN frequency adjustment value is cleared when the drive stops.
1: Holding
Terminal UP/DOWN frequency adjustment value is maintained when the drive stops.
Ten's digit: action on power loss
0: Clear
Terminal UP/DOWN frequency adjustment value is cleared in case of power loss.
1: Holding
Terminal UP/DOWN frequency adjustment value is saved in case of power loss.
Hundred's digit: integral function
0: No integral function
Adjustment step size is kept constant during terminal UP/DOWN adjustment, in compliance with
F04.17.
1: Integral function enabled
When frequency is adjusted through terminal UP/DOWN, initial step size is set by F04.17.
With the effective lasting time of the terminals, adjustment step size will increase gradually.
Terminal UP/DOWN
F04.17 Range:0.00~50.00Hz Default:1.00Hz/200ms
frequency change step size
It is used to adjust the rate of change of frequency when the frequency is adjusted by means of
terminal UP/DOWN.
F04.18 Power on running terminal Range:0~1 Default:0
action selection
It is only valid to running command terminal which is set in number 1,2,4,5(Running forward,
running reverse, JOG forward, JOG reverse), and only valid for the first running after power on
0:Electrial level effective
When terminal is given running command, running terminal is detected to be ON, inverter start to
run. Please ensure the terminal statue before power on.
1:Edge trigger + Electrical level effective
When terminal is given running command, the terminal is detected to jump from OFF to ON and
maintain ON, inverter start to run.

Group F05 Digital Output


F05.00 Y1 output function Range:0~99 Default:1
F05.02 Relay 1 output function Range:0~99 Default:2

Corresponding
Setting Description
function
0 No output Output terminal is disabled, and there is no output.
The output is ON when the drive is running, and output is
1 Drive is running
OFF when drive stopped.
2 Fault output When the drive is in fault, outputs ON.
Frequency-level
3 detection FDT1 Refer to the descriptions of F05.10 and F05.11.
output
Frequency-level
4 detection FDT2 Refer to the descriptions of F05.12 and F05.13.
output
Drive in 0Hz
When be running at 0Hz, this corresponding terminal
5 running 1(no
outputs ON signal. No ON signal will be output at stop.
output at stop)
6 Drive in 0Hz Outputs ON signal when is running at 0Hz and also outputs
- 75 -
FR100 Series Multifunctional Compact Inverter
running 2(output ON signal at stop.
at stop)
Upper limit When output frequency attains F01.09 (upper limit
7
frequency attained frequency), outputs ON.
Lower limit When output frequency attains F01.10 (lower limit
8 frequency attained frequency), outputs ON. In the stop state, the terminal
(no output at stop) becomes OFF.
Frequency
9 Refer to the descriptions of F05.09.
attained
If the AC drive main circuit and control circuit become
10 Ready for RUN stable, and the AC drive detects no fault and is ready for
RUN, the terminal becomes ON.
In case drive output current exceeds F11.19 (overload
alarm threshold) and its last time exceeds F11.20 (overload
Drive (motor) alarm activated time that exceeding threshold), outputs ON.
11
overloaded alarm
Refer to parameters F11.18~ F11.20 for information with
regard to drive (motor) overloaded alarm.
Drive overheat When drive internally detected temperature exceeds F11.21
12
alarm (Drive overheat alarm threshold), ON signal will be output.
When current running time attains the value of F05.14,
Current running
13 corresponding terminal outputs ON. Current running time is
time attained
cleared when stop.
Accumulative When accumulative power-on time attains the value of
14 power-on time F05.15, corresponding terminal outputs ON. Accumulative
attained power-on time is maintained when stop.
Accumulative When accumulative running time attains the value of
15 running time F05.16, corresponding terminal outputs ON. Accumulative
attained running time is maintained when stop.
PLC cycle Upon the completion of a cycle of simple PLC running, ON
16
completed signal with a width of 250ms will be output.
Set count value The terminal becomes ON when the count value reaches
17
attained the value set in F14.07.
The terminal becomes ON when the count value reaches
Designated count
18 the value set in F14.08. Refer to the specification of
value attained
parameter F14.07 and F14.08.
The terminal becomes ON when the detected actual length
19 Length attained exceeds the value set in F14.04. Refer to the specification
of parameter F14.05~F14.07.
20 Under load alarm When inverter under load, output ON signal
When the brake function selection is effective and reach
21 Brake Output
brake open condition, output signal ON
22~99 Reserved

Define the functions of digital output terminals Y1 and relay R1. Output terminal function selections
are as follows:

F05.04 Y1 output delay time Range:0.0~6000.0s Default:0.0s


F05.06 Relay 1 output delay time Range:0.0~6000.0s Default:0.0s
These two parameters define the delay response time of digital output terminals Y1 and relay R1.
Enabled state of digital
F05.08 Range:0000~1111 Default:0000
output
Unit's place: Y1
0: Positive logic; ON when current passes through
1: Negative logic; ON when no current passes through

0: Positive logic; ON when there is coil excitation


- 76 -
FR100 Series Multifunctional Compact Inverter
1: Negative logic; ON when there is no coil excitation

Relay
24V

Inverter
Y1

GND

Fig. 6-12
Detection width of
F05.09 Range:0.0~20.0Hz Default:5.0Hz
frequency attained
This parameter should be set with digital output terminal "frequency attained". When the
difference between output frequency and command frequency is less than this value, terminal
"frequency attained" a outputs ON. See Fig. 6-13:
Output frequency(Hz)

FAR

FAR

Time(S)

Valid Valid

Time(S)

Fig. 6-13
F05.10 FDT1 upper bound Range:0.00~Fmax Default:30.00Hz
F05.11 FDT1 lower bound Range:0.00~Fmax Default:30.00Hz
These parameters should be set with digital output terminals "FDT1" and "FDT2".
Take FDT1 for example, the drive outputs ON signal when output frequency exceeds upper
bound of FDT1 and will not output OFF signal unless output frequency drops to below lower bound of
FDT1. Please set F05.10 to be larger to some certain extent than F05.11, avoiding status change
frequently. See Fig. 6-14:
Output frequency(Hz)

FDT upper bound


FDT lower bound

Time(S)
Y1
Valid

0 Time(S)

- 77 -
FR100 Series Multifunctional Compact Inverter
Fig. 6-14
F05.14 Consecutive running time Range:0.0~6000.0Min Default: 0.0Min
This parameter should be set with digital output terminal “Consecutive running time attained".
When current running time attains the value of F05.14, corresponding terminal outputs ON. Current
running time is cleared when stop. When this parameter value is set to 0.0, this function is invalid.
F05.15 Accumulative power-on time Range:0~65535h Default: 0h
This parameter should be set with digital output terminal “Accumulative power-on time attained".
When accumulative power-on time attains the value of F05.15, corresponding terminal outputs ON.
Accumulative power-on time is maintained when stop. When this parameter value is set to 0, this
function is invalid.
F05.16 Accumulative running time Range:0~65535h Default: 0h
This parameter should be set with digital output terminal “Accumulative running time attained".
When accumulative running time attains the value of F05.16, corresponding terminal outputs ON.
Accumulative running time is maintained when stop. When this parameter value is set to 0, this
function is invalid.
F05.17 Brake control selection Range: 0~1 Default value: 0
0:Disabled
1:Enabled
Default value:
F05.18 Brake open frequency Range: 0.00~20.00Hz
2.50Hz
F05.19 Brake open current Range: 0.0~200.0% Default value:
0.0%
F05.20 Brake open waiting time Range: 0.00~10.00s Default value:
0.00s
F05.21 Brake open operating time Range: 0.00~10.00s Default value:
0.50s
F05.22 Brake closed frequency Range: 0.00~20.00Hz Default value:
2.00Hz
F05.23 Brake close waiting time Range: 0.00~10.00s Default value: 0.00s
F05.24 Brake close operating time Range: 0.00~10.00s Default value: 0.50s
Scheme of brake control process:
Frequency

F05.18

F05.22

FWD/REV

Internal
operating

Brake

F05.2 F05.2 F05.2 F05.2


0 1 3 4

Current

F05.19

Fig 6-15 Break control logic scheme

- 78 -
FR100 Series Multifunctional Compact Inverter
1)After inverter receives a run command, accelerate the run to set F05.18 brake open frequency.
2)After the frequency reaches F05.18 set frequency, inverter keeps constant running and the
duration reaches the F05.20 set brake open waiting time, inverter running constant speed continue to
the F05.20 set brake open waiting time, switching output “brake output” terminal output OFF signal.
3)After reaching the break open waiting time, if inverter current is more than or equal with the
F05.19 set brake open current, at this time switching output "brake output" terminal output signal ON,
inverter continue working on the F05.18 set frequency, when operating time reaches the F05.21set
time, running starts acceleration up to set frequency.
4)After inverter receives the stop command, running decelerate to the F05.22 set brake closing
frequency, and then operate on the constant frequency.
5)After running frequency reaches the F05.22 set frequency, after delay the F05.23 set brake
closing delay time, this period of time, "Brake Output" output ON signal.
6)After reaching the F05.23 set time, “Brake Output "terminal output OFF signal, the inverter
output frequency keeps the F05.22 set value, after delaying reach the F05.24 set value, inverter blocks
output, get into stopped state.

Group F06 Analog and Pulse Input


Range:0.0%~input of
F06.00 Minimum input of curve AI1 Default:0.0%
inflection point1 of curve AI1
Set value corresponding
F06.01 to minimum input of curve Range:-100.0~100.0% Default:0.0%
AI1
Range:Minimum input of
Input of inflection point
F06.02 curve AI1~Input of inflection Default:25.0%
1 of curve AI1
point 2 of curve AI1
Set value corresponding
F06.03 to input of inflection Range:-100.0~100.0% Default:25.0%
point 1 of curve AI1
Range:Input of inflection point
Input of inflection point
F06.04 1 of curve AI1~Maximum Default:75.0%
2 of curve AI1
input of curve AI1
Set value corresponding
F06.05 to input of inflection Range:-100.0~100.0% Default:75.0%
point 2 of curve AI1
Maximum input of curve Range:Input of inflection point
F06.06 Default:100.0%
AI1 2 of curve AI1~100.0%
Set value corresponding to
F06.07 Range:-100.0~100.0% Default:100.0%
maximum input of curve AI1
Curve AI1 is defined by above-noted 8 parameters.
Input values F06.00、F06.02、F06.04、F06.06:
AI1~AI2 are 0~10V or 0~20mA programmable by jumper on control board.
If 0~10V is selected: 0V corresponds to 0%, while 10V corresponds to 100%.
If 0~20mA is selected: 0mA corresponds to 0%, while 20mA corresponds to 100%.
Corresponding set values F06.01、F06.03、F06.05、F06.07:
When the corresponding set value is frequency: 100% is the maximum frequency, while
-100% is the maximum negative frequency.
When corresponding set value is torque: 100% means 2 times the rated torque, while -100%
Means negative "2 times the rated torque".
When the corresponding set value is output voltage (e.g. the voltage setting in case of V/f
separated pattern): 100% corresponds to rated voltage of motor. "Less than or equal to 0%"
corresponds to 0V voltage.
Curve diagram is shown as below:
For Instance:
Following description is taken AI1 as the example.
(1) Parameter setting

- 79 -
FR100 Series Multifunctional Compact Inverter
Table 6-3(1) Parameter setting 1 Table 6-3(2) Parameter setting 2
Code Value Code Value Code Value Code Value
-100 F06.01 100% F06.00 0%
F06.01 %
F06.00 0.0%
F06.03 70% F06.02 40%
F06.03 -50% F06.02 25.0%
F06.05 -50% F06.04 75%
F06.05 70% F06.04 75.0%
100
100 100.0 F06.07 -100% F06.06
F06.07 F06.06 %
% %
See Figure 6-15 (1) and Figure 6-15 (2) for input/output bias of Table 6-3(1) and Table 6-3(2)
respectively.
Set frequency
F06.07 Fmax
100%

F06.05
70%

2.5V 7.5V 10V Analog input


0.0% 25% 75% 100%
F06.00 F06.02 F06.04 F06.06

F06.03
-50%

F06.01
-100%

Figure 6-16(1)
Set frequency
F06.07 Fmax
100%

F06.05
70%

4V 7.5V 10V Analog input

0.0% 40% 75% 100%


F06.00 F06.02 F06.04 F06.06
F06.03
-50%

F06.01
-100%
Figure 6-16 (2)
Range:0.0%~input of
F06.08 Minimum input of curve AI2 Default:0.0%
inflection point1 of curve AI2
Set value corresponding to
F06.09 Range:-100.0~100.0% Default:0.0%
minimum input of curve AI2
Range:Minimum input of
Input of inflection point
F06.10 curve AI2~Input of inflection Default:25.0%
1 of curve AI2
point 2 of curve AI2
Set value corresponding
F06.11 to input of inflection Range:-100.0~100.0% Default:25.0%
point 1 of curve AI2

- 80 -
FR100 Series Multifunctional Compact Inverter
Range:Input of inflection
Input of inflection point
F06.12 point 1 of curve AI2~ Default:75.0%
2 of curve AI2
Maximum input of curve AI2
Set value corresponding
F06.13 to input of inflection Range:-100.0~100.0% Default:75.0%
point 2 of curve AI2
Maximum input of curve Range:Input of inflection
F06.14 Default:100.0%
AI2 point 2 of curve AI2~100.0%
Set value corresponding to
F06.15 Range:-100.0~100.0% Default:100.0%
maximum input of curve AI2
Curve AI2 defined as AI1.
Range:0.0~Maximum input
Minimum input of curve
F06.24 of curve keypad Default:0.0%
keypad potentiometer
potentiometer
Set value corresponding to
F06.25 minimum input of curve Range:-100.0~100.0% Default:0.0%
keypad potentiometer
Range: Minimum input of
Maximum input of curve
F06.26 curve keypad Default:100.0%
keypad potentiometer
potentiometer~100.0%
Set value corresponding to
F06.27 maximum input of curve Range:-100.0~100.0% Default:100.0%
keypad potentiometer
Curve keypad potentiometer is defined by above-noted 4 parameters.
Input values F06.24、F06.26:
keypad potentiometer is 0~5V on control board. 0V corresponds to 0%, while 5V corresponds to
100%.
Corresponding set values F06.25、F06.27:
When the corresponding set value is frequency: 100% is the maximum frequency, while -100% is
the maximum negative frequency.
When corresponding set value is torque: 100% means 2 times the rated torque, while -100%
means negative "2 times the rated torque".
When the corresponding set value is output voltage (e.g. the voltage setting in case of V/f
separated pattern): 100% corresponds to rated voltage of motor. "Less than or equal to 0%"
corresponds to 0V voltage. The difference is that curve keypad potentiometer is a straight line while
curve AI1~AI2 is a broken line with two inflection points.
F06.28 AI1 terminal filtering time Range:0.000~10.000s Default:0.100s
F06.29 AI2 terminal filtering time Range:0.000~10.000s Default:0.100s
Keypad potentiometer
F06.31 Range:0.000~10.000s Default:0.100s
filtering time
F06.28~F06.31 define the filtering time of analog input terminals AI1, AI2 and Keypad
potentiometer. Long filtering time results in strong immunity from interference but slow response, while
short filtering time brings rapid response but weak immunity from interference.
Range:0.00kHz~Maximum
F06.32 Minimum input of curve HI Default:0.00kHz
input of curve HI
Set value corresponding to
F06.33 Range:-100.0~100.0% Default:0.0%
minimum input of curve HI
Range: Minimum input of
F06.34 Maximum input of curve HI Default:100.00kHz
curve HI~100.00kHz
Set value corresponding to
F06.35 Range:-100.0~100.0% Default:100.0%
maximum input of curve HI
Curve HI is defined by above-noted 4 parameters.
Input values F06.32、F06.34:
HI is 0~100kHz.
Corresponding set values F06.33、F06.35:

- 81 -
FR100 Series Multifunctional Compact Inverter
When the corresponding set value is frequency: 100% is the maximum frequency, while -100% is
the maximum negative frequency.
When corresponding set value is torque: 100% means 2 times the rated torque, while -100%
means negative "2 times the rated torque".
When the corresponding set value is output voltage (e.g. the voltage setting in case of V/f
separated pattern): 100% corresponds to rated voltage of motor. "Less than or equal to 0%"
corresponds to 0V voltage.
ATTENTION:
When pulse input is selected as the frequency command, DI7/HI terminal shall be set to "pulse
input" function (F00.09 is set to 1).
F06.36 HI terminal filtering time Range:0.000~10.000s Default:0.100s
F06.36 defines the filtering time of pulse input terminals DI7/HI. Long filtering time results in
strong immunity from interference but slow response, while short filtering time brings rapid response
but weak immunity from interference.
Group F07 Analog and Pulse Output
F07.00 AO1 output function Range:0~99 Default:1
AO1 and AO2 are analog output terminals, output voltage is (0~10)V.
Value Function Range
0 No output No output
1 Output frequency 0.00~Fmax
2 Command frequency 0.00~Fmax
3 Output current 0~2 times the rated current of inverter
4 Output voltage 0~2 times the rated voltage of motor
5 Output power 0~ 2 times the rated power
6 Bus voltage 0~1000V
7 +10V +10V
8 Keypad potentiometer 0~5V
9 AI1 0~10V/0~20mA
10 AI2 0~10V/0~20mA
11 Reserved
12 Pulse input 0.01kHz~100.00kHz
13 Reserved 0~2 times the rated torque
14 Communication given 0.0~100.0%

F07.03 AO1 offset Range:-100.0~100.0% Default:0.0%


F07.04 AO1 gain Range:-2.000~2.000 Default:1.000
When users need to chang AO1 measuring range or correct the error of meter, it can be realized
by setting of F07.03 and F07.04. When using factory default set: 0~10V (or 0~20mA) of AO1
corresponds to “0~maximun”. By expressing standard output of AO1 as x, the adjusted AO1 output
as y, the gain as k, and the offset as b (100% of offset corresponds to 10V or 20mA), there is the
equation:
y=kx+b
Example:
Set F07.00 to 1: output frequency. Standard AO1 output: AO1 outputs 0V when output frequency
is 0, and outputs 10V when output frequency is maximum frequency. If AO1 is requested to output 2V
when output frequency is 0.00Hz, and requested to output 8V when output frequency is the maximum
frequency. There is: 2=k*0+b; 8=k*10+b. Through these two equations, we obtain: k = 0.6, b = 2V, i.e.
F07.03 is set to 20.0% while F07.04 is set to 0.600.
F07.05 AO1 filtering time Range:0.000~10.000s Default:0.000s
Define output filtering time of AO1 terminal.
Group F08 Parameters of Motor 1
F08.01 Power rating of motor 1 Range:0.1~1000.0kW Default: Model defined
F08.02 Rated voltage of motor 1 Range:60~660V Default: Model defined

- 82 -
FR100 Series Multifunctional Compact Inverter
F08.03 Rated current of motor 1 Range:0.1~1500.0A Default: Model defined
F08.04 Rated frequency of motor 1 Range:20.00~Fmax Default: Model defined
F08.05 Rated speed of motor 1 Range:1~60000rpm Default: Model defined
Set the parameters according to the motor nameplate no matter whether V/F control or vector
control is adopted.
To achieve better V/F or vector control performance, motor auto-tuning is required. The motor
auto-tuning accuracy depends on the correct setting of motor nameplate parameters.
Stator resistance R1 of
F08.08 Range:0.001~65.535Ω Default: Model defined
async motor 1
Rotor resistance R2 of
F08.09 Range:0.001~65.535Ω Default: Model defined
async motor 1
Leakage inductance L1 of
F08.10 Range:0.001~65.535mH Default: Model defined
async motor 1
Mutual inductance L2 of
F08.11 Range:0.1~6553.5mH Default: Model defined
asynchronous motor 1
No-load current of async
F08.12 Range:0.1~1500.0A Default: Model defined
motor 1
Field weakening coeff 1 of
F08.13 Range:0.0~100.0% Default:87%(1.1)
async motor 1
Field weakening coeff 2
F08.14 Range:0.0~100.0% Default:75%(1.6)
of async motor 1
Field weakening coeff 2
F08.15 Range:0.0~100.0% Default:70%(3)
of async motor 1
The parameters in F08.08 to F08.15 are asynchronous motor parameters. These parameters are
unavailable on the motor nameplate and are obtained by means of motor auto-tuning. Only F08.08 to
F08.10 can be obtained through static motor auto-tuning. Through complete motor auto-tuning,
encoder phase sequence and current loop PI can be obtained besides the parameters in F08.08 to
F08.12.Each time "Rated motor power" (F08.01) or "Rated motor voltage" (F08.02) is changed, the AC
drive automatically restores values of F08.08 to F08.12 to the parameter setting for the common
standard Y series asynchronous motor.
If it is impossible to perform motor auto-tuning onsite, manually input the values of these
parameters according to data provided by the motor manufacturer.
F08.30 Autotuning of motor 1 Range:0~2 Default: 0
0: No auto-tuning, auto-tuning is prohibited.
1: Asynchronous motor static auto-tuning
It is applicable to scenarios where complete auto-tuning cannot be performed because the
asynchronous motor cannot be disconnected from the load.Before performing static auto-tuning,
properly set the motor type and motor nameplate parameters of F08.00 to F08.07 first. The AC drive
will obtain parameters of F08.08 to F08.10 by static auto-tuning.Set this parameter to 1, and press
RUN. Then, the AC drive starts static auto-tuning.
2: Asynchronous motor complete auto-tuning
To perform this type of auto-tuning, ensure that the motor is disconnected from the load. During
the process of complete auto-tuning, the AC drive performs static auto-tuning first and then
accelerates to 80% of the rated motor frequency within the acceleration time 4. The AC drive keeps
running for a certain period and then decelerates to stop within deceleration time 4
Before performing complete auto-tuning, properly set the motor type, motor nameplate
parameters of F08.00 to F08.07.
The AC drive will obtain motor parameters of F08.08 to F08.12 by complete auto-tuning.
Set this parameter to 2, and press RUN. Then, the AC drive starts complete auto-tuning.
ATTENTION:
1) Please make sure the motor is in a stationary status before autotuning, or autotuning cannot be
performed normally.
2) Keypad displays "TUNE", and RUN indicator is lighting during autotuning. RUN indicator
turns off upon the completion of autotuning.
3) If autotuning failed, the fault code “Err17" shall be displayed.
Group F09 V/f Control Parameters of Motor 1
F09.00 V/f curve setting Range:0~6 Default: 0
- 83 -
FR100 Series Multifunctional Compact Inverter
Set the relation between output voltage and output frequency of the drive when motor 1 is under
V/f control.
0: Linear V/f
Applies to general constant-torque load.When drive output frequency is 0, output voltage will be 0,
while when output frequency is rated frequency of motor, the output voltage would be rated voltage of
motor.
1: Broken line V/f (determined by F09.03~F09.10)
Applies to spin drier, centrifuge, industrial washing machine and to other special loads. When
drive output frequency is 0, output voltage will be 0, while when output frequency is rated frequency of
motor, the output voltage would be rated voltage of motor. What is different is this pattern can set 4
inflection points by F09.03~F09.10.
2: 1.2nd power
3: 1.4th power
4: 1.6th power
5: 1.8th power
6: 2.0th power
Parameter values 2~6 apply to torque-dropped loads such as fans and water pumps. See Fig.
6-16.
2.0 power
1.8 power
Output voltage (V) 1.6 power
1.4 power
1.2 power
Rated voltage of motor

SL V/F

Output frequency(Hz)
0 Rated frequency of motor

Fig. 6-17
F09.01 Torque boost Range:0.0~30.0% Default: 0.0%
Cut-off frequency of torque
F09.02 Range:0.0~Fmax Default:50.0Hz
boost
Torque boost:
Under V/f pattern, output voltage at low frequency can be compensated by this parameter,
improving the torque output. 0.0% corresponds to automatic torque boost, and drive output voltage is
automatically compensated via detection of load current. Automatic torque boost is valid only for linear
V/f pattern. 100% of torque boost corresponds to rated voltage of motor. A non-zero value means the
output voltage rises on the basis of V/f curve and this takes effect at parameter values 0~6 of F09.00.
It is suggested this parameter value be gradually increased from zero until the starting requirement is
met. Boost value is not suggested to be set to a relatively big one, as it is likely to bring about a bigger
drive current and higher motor temperature.
Cut-off frequency of torque boost:
F09.02 specifies the frequency under which torque boost is valid. Torque boost becomes invalid
when this frequency is exceeded, as shown in the following figure.

- 84 -
FR100 Series Multifunctional Compact Inverter
Output voltage (V)

Rated voltage of motor

Torque boost

Output frequency(Hz)

0 Cut-off frequency of
Rated frequency of motor
torque boost

Fig. 6-18
F09.03 Multi-point V/F frequency 1(F1) Range:0.0~F09.05 Default:0.00Hz
F09.04 Multi-point V/F voltage 1(V1) Range:0.0~100.0% Default:0.0%
F09.05 Multi-point V/F frequency 2(F2) Range:F09.03~F09.07Default:5.00Hz
F09.06 Multi-point V/F voltage 2(V2) Range:0.0~100.0% Default:14.0%
Default:25.00H
F09.07 Multi-point V/F frequency 3(F3) Range:F09.05~F09.09
z
F09.08 Multi-point V/F voltage 3(V3) Range:0.0~100.0% Default:50.0%
Range:F09.07~rated motor Default:50.00H
F09.09 Multi-point V/F frequency 4(F4)
frequency z
F09.10 Multi-point V/F voltage 4(V4) Range:0.0~100.0% Default:100.0%
F09.03~F09.10 is used for broken line V/f mode. Voltage value 100% corresponds to rated
voltage of motor. Please rationally set the values of frequency and voltage at knees on the basis of
characteristics of motor and load. Improper setting may rise output current even burn the motor. Figure
6-18 setting of multi-point V/F curve.
Output voltage (V)

Rated voltage of motor


V4

V3

V2

V1

Output frequency(Hz)
0 F1 F2 F3 F4 Rated frequency of motor

Fig. 6-19
ATTENTION:
The multi-point V/F curve is set based on the motor's load characteristic. The relationship
between voltages and frequencies is:V1≤V2≤V3≤V4,F1≤F2≤F3≤F4.At low frequency, higher voltage
may cause overheat or even burnt out of the motor and overcurrent stall or overcurrent protection of
the AC drive.
F09.11 V/F slip compensation gain Range:0.0~300.0% Default: 0.0%
This parameter is valid only for the asynchronous motor.
It can compensate the rotational speed slip of the asynchronous motor when the load of the motor
increases, stabilizing the motor speed in case of load change.
Stator voltagedrop
F09.12 Range:0.0~200.0% Default:100.0%
compensation gain
- 85 -
FR100 Series Multifunctional Compact Inverter
Stator voltagedrop compensation is to compensate voltagedrop produced by stator resistance
and connecting cable.
F09.13 Excitation boost gain Range:0.0~200.0% Default:100.0%
F09.14 Oscillation Suppression Range:0.0~300.0% Default: 100.0%
Set this parameter to a value as small as possible in the prerequisite of efficient oscillation
suppression to avoid influence on V/F control.Set this parameter to 0 if the motor has no oscillation.
Increase the value properly only when the motor has obvious oscillation. The larger the value is, the
better the oscillation suppression result will be.
When the oscillation suppression function is enabled, the rated motor current and no-load current
must be correct. Otherwise, the V/F oscillation suppression effect will not be satisfactory.
Group F10 Vector Control Parameters of Motor 1
F10.00 Speed/torque control Range:0~1 Default: 0
Sensor-less vector control 2 and close-loop vector control support torque control. Under these two
control patterns, speed control and torque control can be programmed by this parameter.Added to this,
the switchover between speed control and torque control can also be realized by digital input terminal
"speed/torque control switch". The relation of the switchover via terminal and parameter is shown in
the following table:
Speed/torque control
F10.00 Control mode
switch terminal
0 OFF Speed control
0 ON Torque control
1 OFF Torque control
1 ON Speed control
Under speed control, output torque of motor will match load automatically. In order to avoid
overcurrent fault caused by excessive output torque, it is necessary to set appropriate torque limit
value and keep output torque of motor within this limit. Please refer to the specification of F10.10 for
torque limited information.
Under torque control, torque can be set by different sources, by F10.16. Under torque control,
motor speed is determined by the difference between set torque and load torque. When the set torque
is bigger than load torque, motor will be accelerated continuously. When the set torque is smaller than
load torque, motor will be decelerated continuously. When the set torque is matching load torque well,
the speed of motor will be maintained. Therefore, it is necessary to set limit value of forward or reverse
speed during torque control so as to prevent over-run caused by continuous acceleration of motor.
Please set the speed limits in F10.18~F10.19 under torque control.
ATTENTION:
Jog mode will run in the manner of speed control, and torque control is disabled.

F10.01 ASR low-speed proportional


Range:0.0~100.0 Default:30.0
gain Kp1
F10.02 ASR low-speed integration
Range:0.00~10.00s Default:0.50s
time Ti1
F10.03 ASR switching frequency 1 Range:0.0~F10.06 Default:5.0Hz
F10.04 ASR high-speed
Range:0.0~100.0 Default:15.0
proportional gain Kp2
F10.05 ASR high-speed integration
Range:0.00~10.00s Default:1.00s
time Ti2
F10.06 ASR switching frequency 2 Range:F10.03~Fup Default:10.0Hz
Speed loop PI parameters vary with running frequencies of the AC drive.
If the running frequency is less than or equal to "Switchover frequency 1" (F10.03), the speed loop
PI parameters are F10.00 and F10.01.
If the running frequency is equal to or greater than "Switchover frequency 2" (F10.06), the speed
loop PI parameters are F10.04 and F10.05.
If the running frequency is between F10.03 and F10.03, the speed loop PI parameters are
obtained from the linear switchover between the two groups of PI parameters.
The speed dynamic response characteristics in vector control can be adjusted by setting
theproportional gain and integral time of the speed regulator.To achieve a faster system response,

- 86 -
FR100 Series Multifunctional Compact Inverter
increase the proportional gain and reduce the integral time. Be aware that this may lead to system
oscillation.
The recommended adjustment method is as follows:
If the factory setting cannot meet the requirements, make proper adjustment. Increase the
proportional gain first to ensure that the system does not oscillate, and then reduce the integral time to
ensure that the system has quick response and small overshoot.
ATTENTION:
Improper PI parameter setting may cause too large speed overshoot, and overvoltage fault may
even occur when the overshoot drops.
F10.07 ASR input filtering time Range:0.0~500.0ms Default:0.3ms
F10.08 ASR output filtering time Range:0.0~500.0ms Default:0.3ms
Sets the input/output filtering time of ASR.No need to modify its default setting if not have special
requirement.
F10.09 Vector control slip gain Range:50~200% Default:100%
For SFVC, it is used to adjust speed stability accuracy of the motor. When the motor with load
runs at a very low speed, increase the value of this parameter; when the motor with load runs at a very
large speed, decrease the value of this parameter.
For CLVC, it is used to adjust the output current of the AC drive with same load.
Digital setting of torque upper
F10.10 Range:50.0~200.0% Default:100%
limit in speed control mode
In the speed control mode, the maximum output torque of the AC drive is restricted by F10.10.

Excitation adjustment
F10.11 Range:0.00~10.00 Default:0.50
proportional gain Kp1
Excitation adjustment integral
F10.12 Range:0.0~3000.0ms Default:10.0ms
gain Ti1
Torque adjustment
F10.13 Range:0.00~10.00 Default:0.50
proportional gain Kp2
Torque adjustment integral
F10.14 Range:0.0~3000.0ms Default:10.0ms
gain Ti2
These are current loop PI parameters for vector control. These parameters are automatically
obtained through "Asynchronous motor complete auto-tuning" or "Synchronous motor no-load
auto-tuning", and need not be modified.

Torque setting source under


F10.16 Range:0~6 Default:0
torque control
F10.17 Digital setting of torque Range:-200~200% Default:150.0%
F10.16 is used to set the torque setting source. There are a total of 6 torque setting sources.
The torque setting is a relative value. 100.0% corresponds to the AC drives rated torque. The
setting range is -200.0% to 200.0%, indicating the AC drive's maximum torque is twice of the AC
drive's rated torque.
If the torque setting is positive, the AC drive rotates in forward direction. If the torque setting is
negative, the AC drive rotates in reverse direction.
0: Digital setting (F10.17)
The target torque directly uses the value set in F10.17.
1: Keypad potentiometer
2: AI1
3: AI2
5: Pulse setting (DI7/HI)
The target torque is set by DI7/HI (high-speed pulse). The pulse setting signal specification is
9–30 V (voltage range) and 0–100 kHz (frequency range). The pulse can only be input via DI7.
6: Communication setting
The target torque is set by means of communication.
Forward speed limited value
F10.18 Range:0.0~Fmax Default:50.0Hz
under torque control
Reverse speed limited value
F10.19 Range:0.0~Fmax Default:50.0Hz
under torque control

- 87 -
FR100 Series Multifunctional Compact Inverter
When F00.26=0,Two parameters are used to set the maximum frequency in forward or reverse
rotation in torque control mode.
In torque control, if the load torque is smaller than the motor output torque, the motor's rotational
speed will rise continuously. To avoid runaway of the mechanical system, the motor maximum rotating
speed must be limited in torque control.
You can implement continuous change of the maximum frequency in torque control dynamically
by controlling the frequency upper limit.
F10.20 Set torque accel time Range:0.0~6000.0s Default:0.0s
F10.21 Set torque decel time Range:0.0~6000.0s Default:0.0s
In torque control, the difference between the motor output torque and the load torque determines
the speed change rate of the motor and load. The motor rotational speed may change quickly and this
will result in noise or too large mechanical stress. The setting of acceleration/deceleration time in
torque control makes the motor rotational speed change softly.
However, in applications requiring rapid torque response, set theacceleration/deceleratio time in
torque control to 0.00s.
For example, two AC drives are connected to drive the same load. To balance the load allocation,
set one AC drive as master in speed control and the other as slave in torque control. The slave
receives the master's output torque as the torque command and must follow the master rapidly. In this
case, the acceleration/deceleration time of the slave in torque control is set to 0.0s.
Static friction torque
F10.22 Range:0.0~100.0% Default:5.0%
compensation
F10.23 Static friction frequency range Range:0.0~20.0Hz Default:1.0Hz
This parameter takes effect only in torque control. To compensate the static friction of system at
the start, additional torque might be needed. When the motor runs, static friction torque compensation
is disabled. 100% corresponds to rated torque of motor.
Sliding friction torque
F10.24 Range:0.0~100.0% Default:1.0%
compensation
This parameter takes effect only in torque control. To compensate the sliding friction during
running, additional torque might be needed. 100% corresponds to rated torque of motor.

Rotary inertia compensation


F10.25 Range:50.0~200.0% Default:100.0%
coeff
This parameter takes effect only in torque control. This parameter value is to compensate
mechanical rotary inertia during acceleration/deceleration.
0: Set by F10.18 & F10.19
1:Keypad potentiometer
Max Frequency source
F10.26 2:AI1 0 ×
under torque control
3:AI2
5: Pulse setting ( DI7/HI )
This parameter takes effect only in torque control. F10.26 is used to set the Max frequency source
under torque control.
Group F11 Protection Parameters
F11.00 Current limit control Range:0~2 Default:2
F11.01 Current limit Range:100.0~200.0% Default:150.0%
Frequency decreasing time (limit
F11.02 Range:0.0~6000.0s Default:5.0s
current in constant speed operation)
F11.03 Current limit mode 2 proportio gain Range:0.1~100.0% Default:3.0%
F11.04 Current limit mode 2 integral time Range:0.00~10.00s Default: 10.00s
F11.00=0:Current limit disabled
F11.00=1:Current limit mode 1
During acceleration and deceleration, if output current exceeds current limit (F11.01), inverter
stops acceleration/deceleration and remains at present running frequency, and will
accelerate/decelerate as per previous acceleration/deceleration time after output current decreased.
During steady state, after output current exceeds the current limit (F11.01), inverter decelerates
as per the decreasing time (F11.02) of constant speed current frequency, and the minimum

- 88 -
FR100 Series Multifunctional Compact Inverter
deceleration could reach lower limit frequency (F01.10). After output current decreases, inverterwill
accelerate to setting frequency as per setting acceleration time, see Figure 6-19.
Output current (A)

Current limit

Time
Output frequency(Hz)

Acceleration Constant speed Deceleration Time


process process process
Figure 6-20
F11.00=2: Current limit mode 2
Current limit mode 2 is applied to the applications which are sensitive to acceleration/ deceleration
time. In this mode, the motor current is automatically adjusted by regulating the output frequency as
per the PI parameterse set in F11.03 and F11.04.
For load with larger inertia if overcurrent occurs during acceleration, the propotional gain may be
increased. For overcurrent during deceleration, the proportional gain may be decreased. For load with
smaller inertia, the propotional gain may be kept smaller. Integral time can be adjusted for fine tunning
in both cases

F11.05 Overvoltage stall control Range:0~2 Default:1


F11.06 Overvoltage stall voltage Range:600~800V Default:700V
Overvoltage stall mode 2
F11.07 Range:0.1~100.0% Default:3.0%
proportion gain
Overvoltage stall mode 2
F11.08 Range:0.00~10.00s Default: 10.00s
integral time

F11.05=0: Overvoltage Stall Disabled.


F11.05=1: Overvoltage Stall Mode 1
In deceleration process, after DC bus voltage exceeds overvoltage stall voltage (F11.06), inverter
stops deceleration process, and remains at present running frequency. After DC bus voltage
decreases, inverter will decelerate as per previous deceleration time, see Figure 6-20.
DC bus voltage(V)

Overvoltage stall level

Time
Output frequency(Hz)

Acceleration Constant speed Deceleration Time


process process process

- 89 -
FR100 Series Multifunctional Compact Inverter
Figure 6-21
F11.05=1: Overvoltage Stall Mode 2
Overvoltage stall mode 2 is applied to the applications which are sensitive to acceleration/
deceleration time. In this mode, the motor frequency is automatically adjusted by DC bus voltage as
per the PI parameters set in F11.07 and F11.08.
For load with larger inertia if overvoltage stall occurs during deceleration, the propotional gain may
be increased. For load with smaller inertia, the propotional gain may be kept smaller. Integral time can
be adjusted for fine tunning in both cases.
Overvoltage stall protective voltage setting 100% corresponds to base values.
Voltage Class Corresponding Base Value
Single-phase 220 V 311V
Three-phase 380 V 537V

F11.10 Protection action 1 Range:00000~33333 Default:03000


Unit's place: Bus undervoltage(Err07)
0: Fault reported and coast to stop
1: Stop according to the stop mode
2: Fault reported but continues to run
3: Fault protection disabled
Ten's digit: Power input phase Loss (Err09) (Same as unit's place)
Hundred's digit: Power output phase loss (Err10) (Same as unit's place)
Thousand's digit: Motor overload (Err11) (Same as unit's place)
Ten thousand's digit: Inverter overload (Err11) (Same as unit's place)
Note:
If "Coast to stop" is selected, the AC drive displays Err** and directly stops.
If "Stop according to the stop mode" is selected, the AC drive displays A** and stops according to
the stop mode. After stop, the AC drive displays Err**.
If "Continue to run" is selected, the AC drive continues to run and displays A**. The running
frequency is set in F11-14.
F11.11 Protection action 2 Range:00000~22222 Default:00000
Unit's place: External equipment fault(Err13)
0: Fault reported and coast to stop
1: Stop according to the stop mode
2: Fault reported but continues to run
Ten's digit: EEPROM read/write fault (Err15) (Same as unit's place)
Hundred's digit: Communication overtime error (Err18) (Same as unit's place)
Thousand's digit: PID feedback loss (Err19) (Same as unit's place)
Ten thousand's digit: Continuous running time reached (Err20) (Same as unit's place)
F11.12 Protection action 2 Range: 00~32 Default: 30
Unit's place: Module temperature detection disconnection(Err24)
0: Fault reported and coast to stop
1: Stop according to the stop mode
2: Fault reported but continues to run
Ten's digit: Load becoming 0 (Err25) (Same as unit's place)
Frequency selection for
F11.14 Range: 0~4 Default: 00
continuing to run upon fault
Backup frequency upon
F11.15 Range:0.0~Fmax Default: 0.0Hz
abnormality
0: Current running frequency
1: Set frequency
2: Frequency upper limit
3: Frequency lower limit
4: Backup frequency upon abnormality(F11.15)
Motor overload protection
F11.16 Range:0~1 Default:1
choice

0: Prohibited

- 90 -
FR100 Series Multifunctional Compact Inverter
No function of Motor overload protection, dangerous of overheating damage to Motor may existed,
thermal relay here suggested to configure between inverter and motor.
1: Allowed
Inverter judge the motor overload or not according to inverse time limit curve of Motor overload
protection.
F11.17 Motor overload protection time Range:30.0~300.0s Default:60s
The default is that inverter trips Err11 fault if 150% overload lasts for 1 minute at hot start, see
Figure 6-21 for motor overload protection time. During normal operation, motor overload protection
operates in the area between a cold start and a hot start.
Cold start: Motor protection operation time in response to an overload situation that was suddenly
reached when starting a stationary motor.
Hot start: Motor protection operation time in response to an overload situation that occurred
during sustained operation at rated current.
Operation time(Minutes)

7.8
Cold start

Hot start

0 100 150 200 Motor current(%)


Figure 6-22
F11.18 Overload alarm Range:00~11 Default:00
Unit's place: detection option
0: Always detect
Overload alarm works all the time during drive running.
1: Detect at constant speed only
Overload pre-alarm only works during constant-speed running of inverter.
Decade: compared object
0: Rated current of motor
Compared object is the rated current relative to motor, and display " A11" when the alarm is given
under this setting
1: Rated current of drive
Compared object is the rated current of drive, and display " A12" when the alarm is given under
this setting.
F11.19 Overload alarm threshold Range:20.0~200.0% Default:130.0%
When 0 is set at decade of F11.18, this set value is a percentage compared to rated current of
motor. When 1 is set of that, this set value is a percentage compared to rated current of drive.
Overload alarm activated time
F11.20 Range:0.1~60.0s Default:5.0s
that exceeding threshold
Set the lasting time that overload alarm is activated when output current of drive is bigger than the
threshold set by F11.19.

Inverter overheat warning Range:50℃~Over heat Model


F11.21
threshold temperature defined
Sets the threshold of drive t overheat alarm. When the maximum internal temperature of drive is
higher than this value, the drive displays thermal alarm code “A14", but won’t influence the running.
F11.22 Detection level of power loss Range:5.0~100.0% Default:20.0%
F11.23 Detection time of power loss Range:0.1~60.0s Default:5.0s

- 91 -
FR100 Series Multifunctional Compact Inverter
When the output current of the AC drive is lower than the detection level (F11.22) and the lasting
time exceeds the detection time (F11.23), fault reported (Err25)and coast to stop.
F11.24 Action selection at Range: 0~2 Defailt:0
instantaneous power failure
0:Disabled
1:Deceleration
After power off, bus voltage is less than instantaneous power off bus voltage F11.30, and keep
instantaneous power off voltage judge time F11.32, inverter start to reduce the running frequency via
decel time at instantaneous power failure, the motor is in the state of power generation, the power
feedback to maintain the bus voltage to ensure the normal running of inverter until the bus voltage is
bigger than the instantaneous power off recovery voltage F11.31, then continue to run till the target
frequency.
2:Bus voltage constant control
After power off, bus voltage is less than the instantaneous power off bus voltage F11.30, inverter
will adjust the output frequency via PI adjustment F11.33 automatically
Decel time at
F11.25 Range: 0.0~6000.0s Default:5.0s
instantaneous power failure
Instantaneous power off bus
F11.30 Range:60.0%~F11.31 Default:80.0%
voltage
Instantaneous power off
F11.31 Range:F11.30~100.0% Default:85.0%
recovery voltage
Instantaneous power off
F11.32 Range:0.01~10.00s Default:0.10s
voltage judge time
Instantaneous power off gain
F11.33 Range:0.1~100.0% Default:40.0%
Kp
Range : 0.00 ~ 10.00s
Instantaneous integration time
F11.34 ( 0.00 : Integration Default:0.10s
Ti
invalid)

Notice:
1. Proper adjustment of F11.25, can avoid production stop due tothe protection of the inverter
when power switch
2. Input phase lack protection function must be forbidden to enable this feature
F11.27 Times of automatic reset Range:0~20 Default: 0
It is used to set the times of fault auto resets if this function is used. After the value is exceeded,
the AC drive will remain in the fault state.
F11.28 Interval of automatic reset Range:0.1~100.0s Default:1.0s
It is used to set the waiting time from the alarm of the AC drive to fault auto reset.
DO action during fault auto
F11.29 Range:0~1 Default: 0
reset
0: Not act
1: Act
It is used to decide whether the DO acts during the fault auto reset if the fault auto reset function is
selected.
Group F12 Multi-Reference and Simple PLC Function
F12.00 Reference 0 Range:-100.0~100.0% Default:0.0%
F12.01 Reference 1 Range:-100.0~100.0% Default:0.0%
F12.02 Reference 2 Range:-100.0~100.0% Default:0.0%
F12.03 Reference 3 Range:-100.0~100.0% Default:0.0%
F12.04 Reference 4 Range:-100.0~100.0% Default:0.0%
F12.05 Reference 5 Range:-100.0~100.0% Default:0.0%
F12.06 Reference 6 Range:-100.0~100.0% Default:0.0%
F12.07 Reference 7 Range:-100.0~100.0% Default:0.0%
F12.08 Reference 8 Range:-100.0~100.0% Default:0.0%

- 92 -
FR100 Series Multifunctional Compact Inverter
F12.09 Reference 9 Range:-100.0~100.0% Default:0.0%
F12.10 Reference 10 Range:-100.0~100.0% Default:0.0%
F12.11 Reference 11 Range:-100.0~100.0% Default:0.0%
F12.12 Reference 12 Range:-100.0~100.0% Default:0.0%
F12.13 Reference 13 Range:-100.0~100.0% Default:0.0%
F12.14 Reference 14 Range:-100.0~100.0% Default:0.0%
F12.15 Reference 15 Range:-100.0~100.0% Default:0.0%
At most 16 steps of multi-feference can be set by different status combinations of
" multi-feference terminals 1~4" of digital input.
Multi-reference can be the setting source of frequency, V/F separated voltage and process PID.
The multi-reference is relative value and ranges from -100.0% to 100.0%.
As frequency source, it is a percentage relative to the maximum frequency. As V/F separated
voltage source, it is a percentage relative to the rated motor voltage. As process PID setting source, it
does not require conversion.
Multi-reference can be switched over based on different states of DI terminals. For details, see the
descriptions of group F4.
F12.16 Reference 0 source Range:0~6 Default: 0
0: Digital setting(F12.00)
1: keypad potentiometer
2:AI1
3: Process PID output
4: X7/HI pulse input
5:AI2
It determines the setting channel of reference 0. You can perform convenient switchover between
the setting channels. When multi-reference or simple PLC is used as frequency source, the switchover
between two frequency sources can be realized easily.
F12.17 Running mode of simple PLC Range:0000~1132 Default:000
Unit's place: PLC running mode
0: Stop after a single cycle
PLC stops upon the completion of one cycle and it won’t be started unless another run command
is given, shown as Fig. 6-22.
Output frequency(Hz)

f5
f4 a5

f3 a4
f2 f15
a3 d6 f14 a15
f1 a2
f0 a1 f13 a14 d15
f12 a13
a0 T7 T8 T9 T10 T11 a12
0 T0 T1 T2 T3 T4 T5 T6 a6 T12 T13T14 T15
f6 a7
f7
a8
a9 d12
f8
f9 a10
f10 a11
f11

Pulse length:250ms

PLC cycle completed

Run command
Fig. 6-23
1: Continue to run with the last frequency after a single cycle
After the completion of one cycle, PLC maintains the running frequency and direction of the last
step. See the figure below:

- 93 -
FR100 Series Multifunctional Compact Inverter
Output frequency(Hz)

f5
f4 a5

f3 a4
f2 f15
a3 d6 f14 a15
f1 a2
f0 a1 f13 a14

f12 a13
a0 T7 T8 T9 T10 T11 a12
0 T0 T1 T2 T3 T4 T5 T6 a6 T12 T13T14 T15
f6 a7
f7
a8
a9 d12
f8
f9 a10
f10 a11
f11

Pulse length:250ms

PLC cycle completed

Run command
Fig. 6-24
2: Repeat cycles
PLC automatically starts another cycle after finishing one until there is a stop command, shown
as Fig. 6-24.
Output frequency(Hz)

f5
f4 a5

f3 a4
f2 f15
a3 d6 f14 a15
f1 a2 d0
f0 a1 f13 a14

f12 a13 f0
a0 T7 T8 T9 T10 T11 a12
0 T0 T1 T2 T3 T4 T5 T6 a6 T12 T13T14 T15
f6 a7
f7
a8
a9 d12
f8
f9 a10
f10 a11
f11

Pulse length:250ms

PLC cycle completed

Run command

Fig. 6-25
Decade: started mode
0: Continue to run from the step of stop (or fault)
At the moment drive stop, the drive automatically records the running time of current step. When
restarted, the drive will gets into this step, continue to run the remanent time with the frequency of this
step.
1: Run from the first step “multi-step reference 0”
When restarted after stop, the drive will start to run from “step 0”.
2: Run from the Eighth step “multi-step reference 8”
When restarted after stop, the drive will start to run from “step 8”.
3: Run from the Fifteenth step “multi-step reference 15”
When restarted after stop, the drive will start to run from “step15”.
Hundreds place: power loss memory
0: Memory disabled on power loss
The drive does not memorize PLC running status on power loss and starts the running from step
0 after power up again.
1: Memory enabled on power loss

- 94 -
FR100 Series Multifunctional Compact Inverter
The drive saves PLC running status on power loss, including the running step, running frequency
and finished running time at the moment of power loss. After the next power up, the running will be
continued in accordance with the memorized status.
Thousands place: unit of simple PLC running time
0: Second
1: Hour
Set the unit of running time and Accel/Decel time of simple PLC.
F12.18 Running time of step 0 Range:0.0~6000.0s(h) Default:0.0s(h)
F12.19 Running time of step 1 Range:0.0~6000.0s(h) Default:0.0s(h)
F12.20 Running time of step 2 Range:0.0~6000.0s(h) Default:0.0s(h)
F12.21 Running time of step 3 Range:0.0~6000.0s(h) Default:0.0s(h)
F12.22 Running time of step 4 Range:0.0~6000.0s(h) Default:0.0s(h)
F12.23 Running time of step 5 Range:0.0~6000.0s(h) Default:0.0s(h)
F12.24 Running time of step 6 Range:0.0~6000.0s(h) Default:0.0s(h)
F12.25 Running time of step 7 Range:0.0~6000.0s(h) Default:0.0s(h)
F12.26 Running time of step 8 Range:0.0~6000.0s(h) Default:0.0s(h)
F12.27 Running time of step 9 Range:0.0~6000.0s(h) Default:0.0s(h)
F12.28 Running time of step 10 Range:0.0~6000.0s(h) Default:0.0s(h)
F12.29 Running time of step 11 Range:0.0~6000.0s(h) Default:0.0s(h)
F12.30 Running time of step 12 Range:0.0~6000.0s(h) Default:0.0s(h)
F12.31 Running time of step 13 Range:0.0~6000.0s(h) Default:0.0s(h)
F12.32 Running time of step 14 Range:0.0~6000.0s(h) Default:0.0s(h)
F12.33 Running time of step 15 Range:0.0~6000.0s(h) Default:0.0s(h)
Acceleration/deceleration time
F12.34 Range: 0~3 Default: 0
of simple PLC reference 0
Acceleration/deceleration time
F12.35 Range: 0~3 Default: 0
of simple PLC reference 1
Acceleration/deceleration time
F12.36 Range: 0~3 Default: 0
of simple PLC reference 2
Acceleration/deceleration time
F12.37 Range: 0~3 Default: 0
of simple PLC reference 3
Acceleration/deceleration time
F12.38 Range: 0~3 Default: 0
of simple PLC reference 4
Acceleration/deceleration time
F12.39 Range: 0~3 Default: 0
of simple PLC reference 5
Acceleration/deceleration time
F12.40 Range: 0~3 Default: 0
of simple PLC reference 6
Acceleration/deceleration time
F12.41 Range: 0~3 Default: 0
of simple PLC reference 7
Acceleration/deceleration time
F12.42 Range: 0~3 Default: 0
of simple PLC reference 8
Acceleration/deceleration time
F12.43 Range: 0~3 Default: 0
of simple PLC reference 9
Acceleration/deceleration time
F12.44 Range: 0~3 Default: 0
of simple PLC reference 10
Acceleration/deceleration time
F12.45 Range: 0~3 Default: 0
of simple PLC reference 11
Acceleration/deceleration time
F12.46 Range: 0~3 Default: 0
of simple PLC reference 12
Acceleration/deceleration time
F12.47 Range: 0~3 Default: 0
of simple PLC reference 13
Acceleration/deceleration time
F12.48 Range: 0~3 Default: 0
of simple PLC reference 14
Acceleration/deceleration time
F12.49 Range: 0~3 Default: 0
of simple PLC reference 15
- 95 -
FR100 Series Multifunctional Compact Inverter
Every segment of simple PLC has four kinds of acceler-deceleration time for choice.
Group F13 Process PID
The purpose of process PID control is to make feedback value consistent with the set value.
PID control diagram is as shown in Fig. 6-25.
F13.08\F13.11
P
PID positive and
negative adjustment Integration
F13.04 paused F13.09\F13. F13.18
F13.00 F13.05 F13.17 0 0 0 +
12
Filtering time + +
PID setting PID offset limit I
of PID setting -1
1 1 1 +

-
F13.02 F13.06 Last time Integration value
Filtering time
PID feedback F13.10\F13.13 PID differential limit F13.19
of PID fdback
D

PID output limit


F13.07 F13.22/F13.23
F13.21 0 Filtering time of
0 PID output
Output
frequency 1
1
F13.20 Last time PID
output
PID initial value

Fig. 6-26
F13.00 PID setting Range: 0~6 Default: 0
Select the setting source of PID control.
0: F13.01 digital setting
1: keypad potentiometer
2:AI1
3: Communication
4:Multi-Reference
5: DI7/HI pulse input
6: AI2
F13.01 PID digital setting Range:0.0~100.0% Default:50.0%
When F13.00 is set to 0, this parameter value is taken as set value of PID.
F13.02 PID feedback Range:0~7 Default:0
Select the feedback source of PID control.
0:AI1
1:AI2
2: Communication
3:AI1+AI2
4:AI1-AI2
5:Max{AI1,AI2}
6:Min{AI1,AI2}
7: DI7/HI pulse input
F13.03 PID setting feedback range Range:0~60000 Default:1000
This parameter is a non-dimensional unit. It is used for PID setting display (U00.11) and PID
feedback display (U00.12).Relative value 100% of PID setting feedback corresponds to the value of
F13.03.
If F13.03 is set to 1000 and PID setting is 50.0%, the PID setting display (U00.11) is 500.
F13.04 PID action direction Range:0~1 Default:0
0: Positive adjustment
1: Negative adjustment
This parameter can be used with digital input terminal "PID adjustment direction" to select positive
or negative adjustment of PID.
- 96 -
FR100 Series Multifunctional Compact Inverter

F13.04 PID adjustment direction terminal Adjustment


0 OFF Positive
0 ON Negative
1 OFF Negative
1 ON Positive
Positive adjustment:
When feedback signal is smaller than PID setting, output frequency of the drive will rise to reach
PID balance.
When feedback signal is bigger than PID setting, output frequency of the drive will drop to reach
PID balance.
Negative adjustment:
When feedback signal is smaller than PID setting, output frequency of the drive will drop to reach
PID balance.
When feedback signal is bigger than PID setting, output frequency of the drive will rise to reach
PID balance.
F13.05 Filtering time of PID setting Range:0.000~10.000s Default:0.000s
Filtering time of PID
F13.06 Range:0.000~10.000s Default:0.000s
feedback
F13.07 Filtering time of PID output Range:0.000~10.000s Default:0.000s
Set the filtering time of PID setting, feedback and output.
F13.08 Proportional gain Kp1 Range:0.0~100.0 Default:1.0
F13.09 Integration time Ti1 Range:0.01~10.00s Default:0.10s
F13.10 Differential time Td1 Range:0.000~10.000s Default:0.000s
Proportional gain Kp1:
It decides the regulating intensity of the PID regulator. The higher the Kp1 is, the larger the
regulating intensity is. The value 100.0 indicates when the deviation between PID feedback and PID
setting is 100.0%; the adjustment amplitude of the PID regulator on the output frequency reference is
the maximum frequency.
Integral time Ti1:
It decides the integral regulating intensity. The shorter the integral time is, the larger the regulating
intensity is. When the deviation between PID feedback and PID setting is 100.0%, the integral
regulator performs continuous adjustment for the time set in FA-06. Then the adjustment amplitude
reaches the maximum frequency.
Differential time Td1:
It decides the regulating intensity of the PID regulator on the deviation change. The longer the
differential time is, the larger the regulating intensity is. Differential time is the time within which the
feedback value change reaches 100.0%, and then the adjustment amplitude reaches the maximum
frequency.
F13.17 PID offset limit Range:0.0~100.0% Default:1.0%
If the offset between PID feedback and setting is more than this set value, PID regulator will
implement regulation. If the offset between PID feedback and setting is less than this set value, PID
will stop the regulation and the PID controller output will be kept unchanged. This function can improve
the stability of PID performance.
PID output frequency Range: PID output frequency
F13.22 Default:100.0%
upper limit lower limit~100.0%
PID output frequency Range:–100.0%~PID output
F13.23 Default:-100.0%
lower limit frequency upper limit
This function is used to limit PID output frequency.100.0% corresponds to maximum frequency.
Detection value of PID Range:0.0%~100.0% Default:0.0%
F13.24
feedback loss
Detection time of PID Range:0.0~30.0s Default:1.0s
F13.25
feedback loss
When offset between feedback and setting of PID is less than set value of F13.24 and the lasting
time attains the set time of F13.25, the drive reports fault “Err19". If F13.24 is set to 0.0, feedback loss
detection is disabled.
- 97 -
FR100 Series Multifunctional Compact Inverter
F13.26 PID operation at stop Range:0~1 Default:0
0: No PID operation at stop
1: PID operation at stop
It is used to select whether to continue PID operation in the state of stop. Generally, the PID
operation stops when the AC drives stops.
Group F14 Swing Frequency, Fixed Length,Count and Wakeup
The swing frequency function is applied to the textile and chemical fiber fields and the applications
where traversing and winding functions are required.
The swing frequency function indicates that the output frequency of the AC drive swings up and
down with the set frequency as the center. The trace of running frequency at the time axis is shown in
the following figure. The swing amplitude is set in F14.00 and F14.01. When F14.01 is set to 0, the
swing amplitude is 0 and the swing frequency does not take effect.
Output frequency (Hz)

Swing frequency upper limit


Jump frequency amplitude Swing
frequency
Set frequency Fset
amplitude

Swing frequency lower limit Jump frequency amplitude

Time
Accelerate by Dropping Rising Time of Decelerate by
acceleration time Time of Swing frequency deceleration
Swing time
Run frequency
command

Figure 6-27

Swing frequency setting


F14.00 Range:0~1 Default:0
mode
This parameter is used to select the base value of the swing amplitude.
0: Relative to the central frequency (group F01)
It is variable swing amplitude system. The swing amplitude varies with the central frequency (set
frequency).
1: Relative to the maximum frequency (F01.08maximum output frequency)
It is fixed swing amplitude system. The swing amplitude is fixed.
F14.01 Swing frequency amplitude Range:0.0~100.0% Default:0.0%
F14.02 Jump frequency amplitude Range:0.0~50.0% Default:0.0%
This parameter is used to determine the swing amplitude and jump frequency amplitude.
If relative to the central frequency (F14.00 = 0), the actual swing amplitude AW is the calculation
result of group F01 (Frequency source selection) multiplied by F14.01.
If relative to the maximum frequency (F14.00 = 1), the actual swing amplitude AW is the
calculation result of F01.08 (Maximum frequency) multiplied by F14.01.
Jump frequency = Swing amplitude AW x F14.02 (Jump frequency amplitude). If relative to the
central frequency (F14.00= 0), the jump frequency is a variable value.If relative to the maximum
frequency (F14.00= 1), the jump frequency is a fixed value.
The swing frequency is limited by the frequency upper limit and frequency lower limit.
Rising Time of Swing
F14.03 Range:0.0~6000.0s Default:5.0s
frequency
Dropping Time of Swing
F14.04 Range:0.0~6000.0s Default:5.0s
frequency
See Figure 6-26.
F14.05 Set length Range:0~65535m Default:1000m
F14.06 Number of pulses per meter Range:0.0~6553.5 Default:100.0
The preceding parameters are used for fixed length control.
- 98 -
FR100 Series Multifunctional Compact Inverter
The length information is collected by DI terminals. U00.27 (Actual length) is calculated by
dividing the number of pulses collected by the DI terminal by F14.06 (Number of pulses each meter).
When the actual length U00.27 exceeds the set length in F14.05, the DO terminal allocated with
function (Length reached) becomes ON.During the fixed length control, the length reset operation can
be performed via the DI terminal allocated with function 35. For details, see the descriptions of F04.00
to F04.09.
Allocate corresponding DI terminal with function 34 (Length count input) in applications. If the
pulse frequency is high, DI7/HI must be used.
F14.15
(Set length)
F05.00~F05.03=19
≥ (Length reached)
F04.06=34 F14.16
Length pulses input ÷ U00.29 After the length is
(Length pulses (Number of pulses
(Actual length) reached, the DO
input) permeter)
Reset becomes 1.
Clear to 0

Length reset F04.00~F04.06=35


(Length reset)

Length pulses input

1 2 3 4 5 6

U00.27=0
Length reset input
F14.15=6
U00.27=6
Length reached output

Figure 6-28
Command when the length
F14.07 Range:0~1 Default: 0
attained
0: Not stop
1: Stop
This parameter sets the action of the drive when actual length attains the length set by F14.05.
Actual length can be cleared through digital input terminal "length clear".
ATTENTION:
When actual length is detected to attain the set length, digital output terminal "length attained"
outputs ON signal no matter the drive is set to stop or not stop.
Actual length is saved at power loss and can be read in both stop and running.
F14.08 Set count value Range:1~65535 Default:1000
F14.09 Designated count value Range:1~65535 Default:1000
The count value needs to be collected by DI terminal. Allocate the corresponding DI terminal with
function 32 (Counter input) in applications. If the pulse frequency is high, DI7/HI must be used.
When the count value reaches the set count value (F14.08), the DO terminal allocated with
function 17 (Set count value reached) becomes ON. Then the counter stops counting.
When the counting value reaches the designated counting value (F14.09), the DO terminal
allocated with function 17 (Designated count value reached) becomes ON. Then the counter continues
to count until the set count value is reached.
F14.09 should be equal to or smaller than F14.08.
Figure 6-28 Reaching the set count value and designated count value

- 99 -
FR100 Series Multifunctional Compact Inverter

F14.08 After the designated


(Designated counting value is
counting value) F05.00~F05.03=17 reached, set the DO
(Designated terminal to 1.

counting value reached)
Counting pulses F04.00~F04.06=32 U00.28
(Counting pulses) (Counting value)
Reset F05.00~F05.03=18
F14.09 ≥ (Set counting
Clear to 0 (Set counting value reached) After the set counting
value) value is reached, set
Reset
the DO terminal to 1.
Counting reset F04.00~F04.06=33
(Counting reset)

Counting pulses input

1 2 3 4 5 6 7 8 9

U00.28=0
Counting reset input
F14.08=6
Designated counting U00.28=6
value reached output
F14.08=9
Set counting value
U00.28=9
reached output

Figure 6-29
ATTENTION:
Actual count value can be cleared through digital input terminal "count clear".
Actual count value is saved at power loss.

Range:Dormancy Default:0.00Hz
F14.10 Wake up frequency
frequency~Fmax
F14.11 Wake up delay time Range:0.0~6000.0s Default:0.0s
Range : 0.00 ~ Wake up Default:0.00Hz
F14.12 Dormancy frequency
frequency
F14.13 Dormancy delay time Range:0.0~6000.0s Default:0.0s
Range:0.0%~Dormancy Default:10.0%
F14.17 Wake up pressure
pressure
Range : Wake up Default:50.0%
F14.18 Dormancy pressure
pressure~100.0%
The parameters are used for the dormancy and wake up function in water supply application
During inverter operation, when F14.15 set to be “0”, and when setting frequency is lower than
F14.12, after delay time of F14.13, inverter entry dormancy and stop. When F14.15 set to be “1”, and
when pressure feedback is bigger than F14.18, after delay time of F14.13, inverter entry dormancy
and stop
During inverter dormancy, when F14.14 set to be “0”, and when setting frequency is bigger than
F14.10, after delay time of F14.11, inverter start to operate; When F14.14 set to be “1”, and when
pressure feedback is lower than F14.17, after delay time of F14.11, inverter start to operate
Usually, please set wake up frequency bigger than dormancy frequency. If wake up frequency and
dormancy frequency are set to be 0.00Hz, wake up and dormancy function is invalid.
When start dormancy function, if frequency source is PID, need to set F13.26 to be “1” PID
operation at stop
F14.14 Wake up mode selection Range:0~1 Default:0
0:Frequency
When inverter in dormancy, wake up mode is frequency wake up
1:Pressure
When inverter in dormancy, wake up mode is pressure wake up
F14.15 Dormancy mode selection Range:0~1 Default:0
0:Frequency
Inverter dormancy mode is frequency dormancy
1:Pressure
Inverter dormancy mode is pressure dormancy
F14.16 Pressure feedback source Range:0~3 Default:0
When voltage dormancy or wake up:

- 100 -
FR100 Series Multifunctional Compact Inverter
0:AI1
Pressure feedback given by AI1
1:AI2
Pressure feedback given by AI2
2:DI7/HI pulse input
Pressure feedback given by DI7/HI
Group F15 Communication Parameters
F15.00 Baud rate Range:0~5 Default:1
0:4800bps 1:9600bps
2:19200bps 3:38400bps
4:57600bps 5:115200bps
F15.01 Data format Range:0~3 Default:0
0: No check, data format (1-8-N-2) for RTU
1: Even parity check, data format (1-8-E-1) for RTU
2: Odd Parity check, data format (1-8-O-1) for RTU
3: No check, data format (1-8-N-1) for RTU
F15.02 Local address Range:1~247 Default:1
Set this drive address. 0 is broadcast address, while available addresses are 1~247.
F15.03 Communication timeout Range:0.0~60.0s Default:0.0s
This parameter sets communication error detection time. When it's set to 0.0, no communication
Error will be reported.
F15.04 Response time delay Range:0~200ms Default:1ms
Refer to the spacing interval between ending of inverter data receiving and sending response data
to upper computer.
As modbus protocol required, inverter judge whether ending of a frame of data receiving by
judging the minimum spacing interval between two bytes data higher than 3.5 byte time. Waiting time
of confirmation the end of data receiving on different baud rates as below chart:
Baud Rate Minimum spacing interval between two
bytes
4800bps 7ms
9600bps 4ms
19200bps 2ms
38400bps 1ms
So the final response time=minimum spacing interval between two bytes+F15.03
Set response time delay of this drive to the master.
Master-slave Communication
F15.05 Range:0~1 Default:0
Mode
0: The inverter is the slave
PC as master controls the drive. This supports all communication protocols.
1: The inverter is the master
This drive as master sends current running frequency data or set frequency data (F15.06) through
RS-485 port to 2001H. Data cannot be received but sent.
The Master Communication
F15.06 Range:0~1 Default:0
Sending Data
0: Set frequency
1: Current running frequency
F15.07 Informaion return when Range:0~1 Default:1
communication error
0: No return
1: Return
F15.08 Group U00.00 output Range:0~1 Default:0
frequency numerical attribute
0:Positive and negative value (Forward: Positive value,reverse: negative value)
1: Absolute value

- 101 -
FR100 Series Multifunctional Compact Inverter
Group F16 Keys and Display of Keypad Parameters
F16.00 MF.K key setting Range:0~2 Default:1
0: No function
1: Jog
2: Forward/reverse switchover
3: Run command sources shifted
F16.01 Function of STOP/RST key Range:0~1 Default:0
0: STOP/RST key valid only when under keypad control
1: STOP/RST key valid under any run command source
F16.02 Keys locked option Range:0~4 Default:0
0: Not locked
1: Full locked
2: Keys locked other than RUN, STOP/RST
3: Keys locked other than STOP/RST
4: Keys locked other than >>
LED displayed parameters
F16.03 Range:0~99 Default:0
setting 1 on running status
LED displayed parameters
F16.04 Range:0~99 Default:6
setting 2 on running status
LED displayed parameters
F16.05 Range:0~99 Default:3
setting 3 on running status
LED displayed parameters
F16.06 Range:0~99 Default:2
setting 4 on running status
Sets LED displayed parameters on running status. When a number of parameters are selected to
be displayed, skim- through could be performed using key >> on keypad. 0~99 corresponding
U00.00~U00.99.
LED displayed parameters
F16.07 Range:0~99 Default:1
setting 1 on stop status
LED displayed parameters
F16.08 Range:0~99 Default:6
setting 2 on stop status
LED displayed parameters
F16.09 Range:0~99 Default:15
setting 3 on stop status
LED displayed parameters
F16.10 Range:0~99 Default:16
setting 4 on stop status
Sets LED displayed parameters on stop status. When a number of parameters are selected to be
displayed, skim-through could be realized via key >> on keypad. 0~99 corresponding U00.00 ~
U00.99.
Group F17 User-defined Display Parameters
User-defined Display
F17.00 Range:00.00~49.99 Default:00.03
Parameter 0
User-defined Display
F17.01 Range:00.00~49.99 Default:01.01
Parameter 1
User-defined Display
F17.02 Range:00.00~49.99 Default:01.02
Parameter 2
User-defined Display
F17.03 Range:00.00~49.99 Default:01.08
Parameter 3
User-defined Display
F17.04 Range:00.00~49.99 Default:01.09
Parameter 4
User-defined Display
F17.05 Range:00.00~49.99 Default:02.00
Parameter 5
User-defined Display
F17.06 Range:00.00~49.99 Default:02.01
Parameter 6
User-defined Display
F17.07 Range:00.00~49.99 Default:02.12
Parameter 7
User-defined Display
F17.08 Range:00.00~49.99 Default:03.00
Parameter 8

- 102 -
FR100 Series Multifunctional Compact Inverter
User-defined Display
F17.09 Range:00.00~49.99 Default:03.01
Parameter 9
User-defined Display
F17.10 Range:00.00~49.99 Default:04.00
Parameter 10
User-defined Display
F17.11 Range:00.00~49.99 Default:04.01
Parameter 11
User-defined Display
F17.12 Range:00.00~49.99 Default:04.02
Parameter 12
User-defined Display
F17.13 Range:00.00~49.99 Default:04.03
Parameter 13
User-defined Display
F17.14 Range:00.00~49.99 Default:05.02
Parameter 14
User-defined Display
F17.15 Range:00.00~49.99 Default:08.01
Parameter 15
User-defined Display
F17.16 Range:00.00~49.99 Default:08.02
Parameter 16
User-defined Display
F17.17 Range:00.00~49.99 Default:08.03
Parameter 17
User-defined Display
F17.18 Range:00.00~49.99 Default:08.04
Parameter 18
User-defined Display
F17.19 Range:00.00~49.99 Default:08.05
Parameter 19
User-defined Display
F17.20 Range:00.00~49.99 Default:08.30
Parameter 20
User-defined Display
F17.21 Range:00.00~49.99 Default:11.10
Parameter 21
User-defined Display
F17.22 Range:00.00~49.99 Default:13.00
Parameter 22
User-defined Display
F17.23 Range:00.00~49.99 Default:13.01
Parameter 23
User-defined Display
F17.24 Range:00.00~49.99 Default:13.02
Parameter 24
User-defined Display
F17.25 Range:00.00~49.99 Default:13.08
Parameter 25
User-defined Display
F17.26 Range:00.00~49.99 Default:13.09
Parameter 26
User-defined Display
F17.27 Range:00.00~49.99 Default:00.00
Parameter 27
User-defined Display
F17.28 Range:00.00~49.99 Default:00.00
Parameter 28
User-defined Display
F17.29 Range:00.00~49.99 Default:00.00
Parameter 29
This function code is for user to customize parameter
User can select any function code of FR200 into FR17 group, for easy check and change.
FR17 group has total 30 customized parameters, if FR17 display 00.00, indicating function code is
empty.
The two bit in left indicate function code group, the two bit in right indicate the position in the group.
For example, 05.15 means F05.15. F00~F20 group equal to the two bit in left, U00~U01 equal 49 and
49. Setting 21~47 indicate the function code is empty.

Group U00 Status Monitoring


Group U00 is used to monitor the AC drive's running state. You can view the parameter values by
using keypad, convenient for on-site commissioning, or from the host computer by means of
communication (address: 0x3000~0x3020). Status monitoring parameters in the running and stop
state are defined by F16.03 and F16.103.

U00.00 Running frequency Range:0.00~Fup Default:0.00Hz


- 103 -
FR100 Series Multifunctional Compact Inverter
U00.01 Set frequency Range:0.00~Fmax Default:0.00Hz
U00.02 Output voltage Range:0~660V Default:0V
U00.03 Output current Range:0.0~3000.0A Default:0.0A
U00.04 Output power Range:-3000.0~3000.0kW Default:0.0kW
U00.05 Estimated Motor Speed Range:0~60000rpm Default:0rpm
U00.06 Bus voltage Range:0~1200V Default:0V
U00.07 Synchronous Range:0.00~Fup Default:0.00Hz
Frequency
U00.08 PLC step Range:1~15 Default:1
U00.09 Program Operation Range:0.0~6000.0s(h) Default:0.0s(h)
Time

U00.10 PID set Range:0~60000 Default:0


U00.11 PID feedback Range:0~60000 Default:0
They display the PID setting value and PID feedback value.
PID setting = PID setting (percentage) * F13.03
PID feedback = PID feedback (percentage) * F13.03
Status of DI1~DI4
U00.12 Range:00000~11111 Default:00000
digital input terminal
0 means terminal input status is OFF, while 1 means terminal input status is ON.
Unit's place:DI1
Decade:DI2
Hundreds place:DI3
Thousands place:DI4
Status of DI7 digital
U00.13 Range: 00~11 Default: 00
input terminal
Ten thousands place:Reserved
0 means terminal input status is OFF, while 1 means terminal input status is ON.
Unit's place:DI6
Decade:DI7
Status of digital output
U00.14 Range: 0000~1111 Default: 0000
terminal
0 means terminal input status is OFF, while 1 means terminal input status is ON.
Unit's place:Y1
Decade:Reserved
Hundreds place:R1
Thousands place:Reserved
U00.15 AI1 input Range: 0.0~100.0% Default: 0.0%
U00.16 AI2 input Range: 0.0~100.0% Default: 0.0%
Keypad potentiometer
U00.18 Range: 0.0~100.0% Default: 0.0%
input
U00.19 HI input Range: 0.00~100.00kHz Default: 0.00kHz
U00.20 AO1 output Range: 0.0~100.0% Default: 0.0%
Analog and Pulse Monitoring
U00.23 Temperature of inverter Range:-40.0~120.0℃ Default: 0.0℃
Accumulative power-on
U00.24 Range:0~65535min Default: 0min
time
U00.25 Accumulative running time Range:0~65535min Default: 0min
U00.26 Cumulative power-on time Range:0~65535h Default: 0h
U00.27 Cumulative running time Range:0~65535h Default: 0h
U00.28 Count value Range:0~65535 Default: 0
U00.29 Length value Range:0~65535m Default: 0m

- 104 -
FR100 Series Multifunctional Compact Inverter
Group U01 Fault Record
U01.00 Code of the latest fault Range:0~31 Default:Err00
Running frequency when the
U01.01 Range:0.00~Fup Default:0.0Hz
latest fault occurred
Output current when the latest
U01.02 Range:0.0~3000.0A Default:0.0A
fault occurred
Bus voltage when the latest
U01.03 Range:0~1200V Default:0V
fault occurred
Cumulative running time when
U01.04 Range:0~65535h Default:0h
the latest fault occurred
Check the information of the latest fault. See Chapter 7 for details of fault codes.
U01.05 Code of previous fault Range:0~31 Default:Err00
Running frequency when
U01.06 Range:0.00~Fup Default:0.0Hz
previous fault occurred
Output current when previous
U01.07 Range:0.0~3000.0A Default:0.0A
fault occurred
Bus voltage when previous fault
U01.08 Range:0~1200V Default:0V
occurred
Cumulative running time when
U01.09 Range:0~65535h Default:0h
previous fault occurred
Check the information of previous fault. See Chapter 7 for details of fault codes.
U01.10 Before-previous fault code Range:0~31 Default:Err00
Running frequency when
U01.11 Range:0.00~Fup Default:0.0Hz
before-previous fault occurred
Output current
U01.12 whenbefore-previous fault Range:0.0~3000.0A Default:0.0A
occurred
Bus voltage when
U01.13 Range:0~1200V Default:0V
before-previous fault occurred
Cumulative running time when
U01.14 Range:0~65535h Default:0h
before-previous fault occurred
Check the information of before-previous fault (the fault sequence: before-previous fault, previous
fault, latest fault). See Chapter 7 for details of fault code
U01.15 Previous 3 categories of faults The same with U01.00 Err00 ⊙
U01.16 Previous 4 categories of faults The same with U01.00 Err00 ⊙
U01.17 Previous 5 categories of faults The same with U01.00 Err00 ⊙
U01.18 Previous 6 categories of faults The same with U01.00 Err00 ⊙
U01.19 Previous 7 categories of faults The same with U01.00 Err00 ⊙
U01.20 Previous 8 categories of faults The same with U01.00 Err00 ⊙
U01.21 Previous 9 categories of faults The same with U01.00 Err00 ⊙
U01.22 Previous 10 categories of faults The same with U01.00 Err00 ⊙
U01.23 Previous 11 categories of faults The same with U01.00 Err00 ⊙
U01.24 Previous 12 categories of faults The same with U01.00 Err00 ⊙
U01.25 Previous 13 categories of faults The same with U01.00 Err00 ⊙
Check the information of 3~13 previous fault (the fault sequence: before-previous fault, previous fault,
latest fault). See Chapter 7 for details of fault code

- 105 -
FR100 Series Multifunctional Compact Inverter

Chapter 7 Maintenance and Troubleshooting

FR100 inverter provides a number of warning information and protection, when a fault occurs,
the protective function is activated, the inverter will stop output, inverter fault relay contact, and in the
inverter displays the fault code on the display panel. Before seeking service user can press the
self-examination tips in this section, analyze problems, and identify solutions. If the problem still
cannot be excluded, seek services, or contact the dealer you purchase the drive with my company.

Display Fault Name Possible Causes Solutions

1: The output circuit is


1: Eliminate external faults.
grounded or short circuited.
2: Increase the acceleration
2: The acceleration time is too
time.
short.
3: Adjust the manual torque
3: Manual torque boost or V/F
boost or V/F curve.
curve is not appropriate.
4: Adjust the voltage to
4: The voltage is too low.
Err01 Accel overcurrent normal range.
5: The startup operation is
5: Select rotational speed
performed on the rotating
tracking restart or start the
motor.
motor after it stops.
6: A sudden load is added
6: Remove the added load.
during acceleration.
7: Select an AC drive of
7: The AC drive model is of too
higher power class
small power class.
1: The output circuit is
grounded or short circuited. 1: Eliminate external faults.
2: The deceleration time is too 2: Increase the deceleration
short. time.
3: The voltage is too low. 3: Adjust the voltage to
Err02 Decel overcurrent
4: A sudden load is added normal range.
during deceleration. 4: Remove the added load.
5: The braking unit and 5: Install the braking unit and
braking resistor are not braking resistor.
installed.
1: The output circuit is
1: Eliminate external faults
grounded or short circuited.
2: Adjust the voltage to
2: The voltage is too low.
Constant-speed normal range.
Err03 3: A sudden load is added
overcurrent 3: Remove the added load
during operation.
4: Select an AC drive of
4: The AC drive model is of too
higher power class.
small power class.
1: The input voltage is too
1: Adjust the voltage to
high.
normal range.
2: An external force drives the
2: Cancel the external force
motor during acceleration.
or install a braking resistor.
Err04 Accel overvoltage 3: The acceleration time is too
3: Increase the acceleration
short.
time.
4: The braking unit and
4: Install the braking unit and
braking resistor are not
braking resistor.
installed.

- 106 -
FR100 Series Multifunctional Compact Inverter
1: The input voltage is too
1: Adjust the voltage to
high.
normal range.
2: An external force drives the
2: Cancel the external force
motor during deceleration.
Decel or install the braking resistor.
Err05 3: The deceleration time is too
overvoltage 3: Increase the deceleration
short.
time.
4: The braking unit and
4: Install the braking unit and
braking resistor are not
braking resistor.
installed.
1: Adjust the voltage to
1: The input voltage is too high
Constant-speed normal range.
Err06 2: An external force drives the
overvoltage 2: Cancel the external force
motor during deceleration.
or install the braking resistor.
1: Instantaneous power failure
occurs on the input power
supply.
2: The AC drive's input voltage
is not within the allowable 1: Reset the fault.
range. 2: Adjust the voltage to
Err07 Bus undervoltage 3: The bus voltage is normal range.
abnormal. 3: Contact the agent or
4: The rectifier bridge and Frecon.
buffer resistor are faulty.
5: The drive board is faulty.
6: The main control board is
faulty.
1: The output circuit is
grounded or short circuited.
1: Eliminate external faults.
2: The connecting cable of the
2: Install a reactor or an
motor is too long.
output filter.
3: The module overheats.
3: Check the air filter and the
4: The internal connections
Err08 Short circuit cooling fan.
become loose.
4: Connect all cables
5:The main control board is
properly.
faulty
5: Contact the agent or
6: The drive board is faulty.
Frecon.
7: The inverter module is
faulty.
1: The three-phase power
input is abnormal.
2: The drive board is faulty. 1: Eliminate external faults.
Power input
Err09 3: The lightening board is 2: Contact the agent or
phase loss
faulty. FRECON.
4: The main control board is
faulty.
1: The cable connecting the
AC drive and the motor is 1: Eliminate external faults.
faulty. 2: Check whether the motor
Power output 2: The AC drive's three-phase Three-phase winding is
Err10
phase loss outputs are unbalanced when normal.
the motor is running. 3: Contact the agent or
3: The drive board is faulty. Frecon.
4: The module is faulty.
1: F11-17 is set improperly. 1: Set F11-17 correctly.
2: The load is too heavy or 2: Reduce the load and
Err11 Motor overload locked-rotor occurs on the check the motor and the
motor. mechanical condition.
3: The AC drive model is of too 3: Select an AC drive of

- 107 -
FR100 Series Multifunctional Compact Inverter
small power class. higher power class.
1: The load is too heavy or 1: Reduce the load and
locked-rotor occurs on the check the motor and
Err12 Inverter overload motor. mechanical condition.
2: The AC drive model is of too 2: Select an AC drive of
small power class. higher power class.
External 1: External fault signal is input
Err13 Reset the operation.
equipment fault via DI.
1: The ambient temperature is 1: Lower the ambient
too high. temperature.
2: The air filter is blocked. 2: Clean the air filter.
3: The fan is damaged. 3: Replace the damaged
Err14 Module overheat 4: The thermally sensitive fan.
resistor of the module is 4: Replace the damaged
damaged. thermally sensitive resistor.
5: The inverter module is 5: Replace the inverter
damaged. module.
EEPROM The EEPROM chip is Replace the main control
Err15
read/write fault damaged. board.
Since the identification
Motor auto-tuning Press STOP / RST key to
Err16 process, press STOP / RST
cancelled reset
key
1: the motor and the inverter 1: check the connection
output terminals are not between the inverter and
Motor auto-tuning connected motor
Err17
fault 2: The motor does not 2: The motor is disengaged
disengage the load load
3: The electrical fault 3: Check the motor
1: The PC is not working
1: Check the PC Connection
properly
Communication 2: Check the communication
2: The communication line is
Err18 overtime cable
not normal
error 3: The communication
3: F15 set communication
parameters are set correctly
parameters set incorrectly
Check the PID feedback
PID feedback PID feedback set value is less
Err19 signal or set to an
loss than F13.24
appropriate value F13.24
Continuous
Set the running time to reach reference F05.14
Err20 running time
this function Description
reached
1: Is not installed or is not
1: a copy of the card is
plugged parameter copy card
properly installed
Parameter 2: Parameter copy card
Err21 parameters
upload fault anomalies
2: for technical support
3: The control board
3: for technical support
abnormalities
1: Is not installed or is not
1: A copy of the card is
plugged parameter copy card
properly installed
Parameter 2: Parameter copy card
Err22 parameters
download fault anomalies
2: For technical support
3: The control board
3: For technical support
abnormalities
1: The brake line failure or 1: Check the brake unit,
damage the brake pipe replace the brake pipe
Err23 Braking unit fault
2: An external braking resistor 2: Increasing the braking
is too small resistor

- 108 -
FR100 Series Multifunctional Compact Inverter
Module
temperature The temperature sensor
Err24 For technical support
detection failure or cable break
disconnection
Check that the load is
The AC drive running current disconnected or the setting
Err25 Load becoming 0
is lower than F11.22 F11-22 and F11-23 is
correct.
1: The load is too heavy or 1: Reduce the load and
locked rotor occurs on the check the motor and
With-wave
Err26 motor. mechanical condition.
current limit fault
2: The AC drive model is of too 2: Select an AC drive of
small power class. higher power class.
1: Check the grid voltage
Inverter soft-start 1: The grid voltage is too low
Err27 2: Demand for technical
relay is off 2: Rectifier module failure
support
1: The upper and lower
transmission module
Software version re-upload module
Err28 parameters in the parameter
compatibility fault parameters to pass down
version of the control panel
version mismatch.

The setting Running time more than


Err40 1. Contact the dealer
running time ends F00.25

- 109 -
FR100 Series Multifunctional Compact Inverter

Chapter 8 Maintenance and Inspection

8.1 Inspection
Frequency semiconductor devices, passive electronic components, and the movement device is
configured, these devices have life, even under normal working conditions, if over the useful life, some
devices may have characteristic changes or failure. In order to prevent this phenomenon leads to
failure and must be checked daily, periodic inspection, parts replacement and other preventative
maintenance checks. After the machine installation is recommended every 3 to 4 months to conduct
an inspection. If any of the following situations, please check to shorten the cycle.
High-temperature, high-altitude environment;
Frequent starting and stopping the environment;
The presence of AC power or load greater volatility environment;
Environment existed large vibration or shock;
The existence of environmental dust, metal dust, salt, sulfuric acid, chlorine element;
Storage environment is very bad.
8.1.1 Daily inspection
To avoid damage and shorten the life of the inverter, please confirm the following items daily.
item contents Strategies
Check the supply voltage meets the
requirements phase power supply
Power supply Press nameplate asked to solve.
and the presence of the
phenomenon.
Installation environment meets the Confirm the source and properly
Surroundings
requirements of Table 3-1. resolve
Confirm whether the overload,
Whether the inverter and the motor
tighten the screws, if the inverter
Cooling System
heatsink fan is dirty confirm
and cooling fan status.
whether the stall.
Tightening mechanical and
Whether the motor is abnormal
Motor electrical connections and do
vibration and abnormal noise.
lubricated mechanical parts.
Inverter output current is higher than Confirm whether there is an
Load conditions the rating of the motor or inverter overload condition occurs confirm
and lasted for some time. the correct drive selection
Note: Do not relate jobs in the state power is turned on, otherwise there is danger of electric
and make sure the
main circuit DC voltage has dropped to a safe level, five minutes before the related operations.
8.1.2 Regularly check
Under normal circumstances, every three months to four months to conduct a periodic inspection
is appropriate, but in the actual case, combined with the use of each machine and the working
environment, to determine the actual inspection cycle.

- 110 -
FR100 Series Multifunctional Compact Inverter
item contents Strategies
● fastening and replace bad parts;
● Insulation resistance check;
Overall ● Clean improving operating
● environmental inspections.
environment.
● Are there wires and connection
● Replace damaged wires;
portion discolored insulation for
● tighten loose terminals and
Electrical damage, cracks, discoloration and
replace the damaged terminal;
connection aging signs;
● measure ground resistance and
● connection terminals for wear,
tighten the corresponding ground
damage, loose;
terminal.
● ground checks.
Mechanical ● whether there is abnormal vibration ● tightening, lubrication,
connection and noise, fixed loose. replacement of bad parts.
Semiconduct ● Clean the operating
or devices ● Are there significant changes in environment;
appearance. ● Replace damaged parts.
Electrolytic ● whether the leaks, discoloration,
capacitor cracking, safety is exposed, swelling, ● Replace damaged parts.
cracking or leakage.
Peripheral ● peripherals appearance and
equipment insulation inspection. damaged parts.
● Fastening;
Printed circuit ● Are there odor, discoloration, severe ● Clean the printed circuit board;
board rust connector is correct and reliable. ● Replace damaged printed circuit

● whether the cooling fan is broken and


stall phenomenon;
Cooling ● fins are not stained with garbage and ● Clean the operating
System dirt, dirty; environment;
● air intake and exhaust ports are ● Replace damaged parts.
clogged or contaminated with foreign
matter.
● Are there broken keyboard and
Keyboard ● Replace damaged parts.
display incomplete phenomenon.
● fastening mechanical and
● The motor is abnormal vibration and
Motor electrical connections, and the
abnormal noise.
motor shaft lubrication.
Note: Do not relate jobs in the state power is turned on, otherwise there is danger of electric
shock to cause death. When conducting related operations, turn off the power and make sure the main
circuit DC voltage has dropped to a safe level, five minutes before the related operations.

8.2 Maintenance
All equipment, parts are all life, the right to life has been extended maintenance, but the damage
cannot be resolved equipment, devices, according to the requirements of life reached or are about to
reach the end of the device to be replaced.

Part name Life Cycle


Fan 2 to 3 years
Electrolytic capacitor 4 to 5 years
Printed circuit board 8 to 10 years
8.2.1 Fan
When replacing the cooling fan, use the original fan, buy original fan, and please contact the
dealer where you purchased the product or the company's sales department. Drive is equipped with a
plurality of cooling fan models. For a number of cooling fans with inverter, To maximize the useful life of
the product, when changing the cooling fan to simultaneously replace all the fans.

- 111 -
FR100 Series Multifunctional Compact Inverter
Fan Removal Method
Step1: Hold the elastic buckles on both sides of fan shown as figure 8-1(a), meanwhile use a little
harder to pull out in parallel, the fan cover will be removed from inverter.
Step2: Press the elastic buckles of fan lead terminal toward internal side shown as figure 8-1(b),
meanwhile pulling out the fan lead terminal with a little harder.
Step3: Please draw out the buckles of fan cover shown as figure 8-1(c), and then use a little harder
to separate cooling fan and fan cover.

(a) (b) (c)

Figure 8-1 Remove the fan


Fan Installation
1. Clip fan vertically into the fan cover shown as figure 8-2(a);
2. Press elastic buckles of fan lead terminals toward internal down side with fingers shown as
figure 8-2(b), meanwhile use a little harder to plug the lead terminal;
3. Vertically plug two elastic buckles of fan cover into the fan mounting rail of inverter shown as
figure 8-2(c)

Tags outward

(a) (b) (c)


Figure 8-2 Install the fan
Note:
1, do not related jobs in the state power is turned on, otherwise there is danger of electric shock to
cause death. When conducting related operations, turn off the power and make sure the main circuit
DC voltage has dropped to a safe level, five minutes before the related operations.
2, the drive to work due to the loss caused by the heat sink temperature, in order to prevent burns,
do not touch the heat sink fins must be confirmed sufficiently cooled to a safe temperature below then
replace the cooling fan.
3, in order to ensure that the inverter can maximize performance, please use the original fan.
8.2.2 Other Devices
Replacement of other devices to maintain familiarity with technology and products are very strict
and must go through rigorous testing to be put into use after the replacement, so I do not recommend
the user to replace the other internal components, if indeed need to be replaced, please contact the
dealer where you purchased the product or our sales department.

- 112 -
FR100 Series Multifunctional Compact Inverter

Appendix A: Modbus Communication Protocol

1. Application Scope
1. Applicable series: FRECON FR series
inverter
2. Applicable network: Support Modbus protocol, RTU format, with
single-master/multi-slave Communication network of RS485 bus.
The typical RTU message frame format:

Device Function
Start Bit Data CRC Stop Bit
Address Code
T1-T2-T3-T4 8Bit 8Bit n*8Bit 16Bit T1-T2-T3-T4

2. Physical Interface
RS485 is asynchronous half-duplex Communication mode. LSB has transmission priority.
Default data format of RS485 terminal: 1-8-N-1,bits rate: 9600bps.
Data format 1-8-N-1, 1-8-O-1, 1-8-E-1, optional bits rates 4800bps, 9600bps, 19200bps,
38400bps, 57600bps and 115200bps can be selected.
Shielded twisted-pair cable is recommended Communication cable to lower external
interference.
3. Protocol Format

The parity in ADU (Application Data Unit) is obtained via the CRC16 parity of the 1st three
Parts of ADU and switch the low bytes and high bytes. Low bytes of CRC parity go first, and high
bytes of it follow in the protocol format.
4. Description of Protocol Format
4.1 Address Code
Address of slave inverter. The setting range: 1~247, 0 is broadcast address.
4.2 Command Code

Command
Function
Code
03H Read parameters and status byte of inverter

06H Write single function code or control parameter of inverter

08H Circuit diagnosis and setting

- 113 -
FR100 Series Multifunctional Compact Inverter
4.3 Allocation of Register Addresses
name Description
High byte function code group number, F00~F31, U00, U01,
respectively, corresponding to the high byte address is 00H~1FH, 30H,
31H.
Low byte of the group function code number, from 0 to 99 corresponding
to the low byte address is 00H~63H.
For example: Modify F01.02 function code value, no power-down when
Function Code storing the corresponding register address (referred to as RAM address)
(F00.00~U01.99) to 0102H.
EEPROM is frequently modified, will reduce the life of the EEPROM. If
you modify the value of the function code-down storage needs, you can
make this function code is the highest position a high address. Note that
this address is only to write, not read.
For example: Modify F01.02 function code value, and the corresponding
need to power down when storing the register address (referred to as
EEPROM address) to 8102H.

Function code group RAM address high byte EEPROM address high byte
F00 0x00 0x80
F01 0x01 0x81
F02 0x02 0x82
F03 0x03 0x83
F04 0x04 0x84
F05 0x05 0x85
F06 0x06 0x86
F07 0x07 0x87
F08 0x08 0x88
F09 0x09 0x89
F11 0x0B 0x8B
F12 0x0C 0x8C
F13 0x0D 0x8D
F14 0x0E 0x8E
F15 0x0F 0x8F
F16 0x10 0x90
F17 0x11 0x91
F30 0x1E 0x9E
F31 0x1F 0x9F
U00 (Read Only) 0x30 --
U01 (Read Only) 0x31 --
4.4 Address and control command functions: (write only)
Command word address Command Function
0001: Forward run
0002: Reverse Run
0003: Inching Forward
2000H
0004: Reverse Jog
0005: Slowdown stop
0006: freewheel
0007: Fault reset
2001H Communication setting frequency (0~Fmax (Unit: 0.01Hz))
2002H PID given range (0 to 1000, 1000 corresponds to 100.0%)
2003H PID feedback range (0~1000, 1000 corresponds to 100.0%)
Torque set point (-3000~3000, 1000 corresponds to 100.0%
2004H
motor rated current)
2005H AO output,Range(0~1000,1000 corresponding to 100.0%)

- 114 -
FR100 Series Multifunctional Compact Inverter

4.5 The status and function of the read address Description: (read only)
Status word address functional status word

0000H: parameter setting


0001H: slave run
0002H: JOG operation
2100H
0003H: learning run
0004H: Slave parking
0005H: JOG parking
0006H: Fault Status
Bit0: 0 are given effective
1 Given negative effective
Bit1:0 frequency output Forward
1 frequency output inversion
Bit2~3:
00 Keyboard start-stop
01 terminal start-stop
10 start-stop communication
11 Reserved
Bit4:
2101H
0 Factory password is invalid
1 factory password is valid
Bit5:
0 user password is invalid
1 valid user password
Bit6~7:
00 basic function code group
01 user-defined function code group
10 different functions with the factory default code group
11 Others
2102H Inverter current fault type
5.Explanation of Command
Command code 0x03: Read parameter and status of inverter.
ADU Item Byte No. Range
Master requests:
Address of slave 1 0~127
Command Code 1 0x03
Register start address 2 0x0000~0xFFFF
The number of register 2 0x0000~0x0008
CRC parity(Low bytes go first) 2
Slave responds :
Address of slave 1 The local address
Command Code 1 0x03
Register start address 1 2*number of registers
The number of register 2*number of registers
CRC parity 2
Remarks: Read maximum 8 function codes consecutively.

- 115 -
FR100 Series Multifunctional Compact Inverter
Command code 0x06: Write single function code or control parameter of inverter.
ADU Item Byte No. Range
Master requests:
Address of slave 1 0~127
Command Code 1 0x06
Register start address 2 0x0000~0xFFFF
The number of register 2 0x0000~0xFFFF
CRC parity 2
Slave responds :
Address of slave 1 The local address
Command Code 1 0x06
Register start address 2 0x0000~0xFFFF
The number of register 2 0x0000~0xFFFF
CRC parity 2
Command code 0x08: Circuit Diagnosis and Setting
ADU Item Byte No. Range
Master requests:
Address of slave 1 0~127
Command Code 1 0x08
Register start address 2 0x0000~0xFFFF
The number of register 2
CRC parity 2
Slave responds :
Address of slave 1 The local address
Command Code 1 0x08
Register start address 2 0x0000~0xFFFF
The number of register 2
CRC parity 2
Remarks: Command code 0x08 is only for circuit check.

6.CRC Parity
Sending equipment calculates CRC parity value first, and then attaches it to the sending
message. Upon receipt of the message, receiving equipment will calculate CRC parity value again,
and compare the operation result with received CRC parity value. If the two values are different, it
indicates that there is error during transmission.
Calculation process of CRC parity:
1. Define a CRC parity register, and initialize it as FFFFH.
2. Conduct XOR calculation between the first byte of sending message and the value of CRC parity
register, and then upload the result to CRC parity register. Start from address code, the start bit and
stop bit will not be calculated.
3. Collect and check LSB (the least significant bit of CRC parity register).
4. If LSB is 1, shift each bit of CRC parity register rightwards by 1 bit, the highest bit filled with 0.
Conduct XOR calculation between the value of CRC register and A001H, and then upload the result to
CRC parity register.
5. If LSB is 0, shift each bit of CRC parity register rightwards by 1 bit, the highest bit filled with 0.
6. Repeat steps 3, 4 and 5 until completing 8 rounds of shifting.
7. Repeat steps 2, 3, 4, 5 and 6, and process the next byte of sending message. Repeat above process
continuously until each byte of sending message is processed.
8. CRC parity date will be saved in CRC parity register after calculation.
9. LUT (Look-up table) method is to obtain CRC parity in the system with limited time resources.
Simple CRC functions as shown in following (C language Programming):

- 116 -
FR100 Series Multifunctional Compact Inverter
unsigned int CRC_Cal_Value (unsigned char *Data, unsigned char Length)
{
unsigned int crc_value = 0xFFFF;
Int i = 0;
while (Length--)
{
crc_value ^= *Data++;
for (i=0; i<8; i++)
{
If (crc_value & 0x0001)
{
crc_value = (crc_value>>1) ^ 0xa001;
}
else
{
crc_value = crc_value>>1;
}
}
}
return (crc_value);
}

7.Error Message Response


Inverter will send an error message report when the master sends error data or inverter receives
the error data due to the external interference.
When Communication error occurs, slave combines the highest bit 1 of command code and error
code as the response to the master.
Responding data frame format when errors happened in Communication:
ADU Item Byte No. Range
Error response:
Address of slave 1 0~127
Error command code 1 The highest bit 1 of command code
Error code 1 0x01~0x13
CRC parity(Low bytes go first) 2
Responding command code at normal Communication and error Communication
Responding Command Code at Normal Responding Command Code at Error
Communication Communication
03H 83H
06H 86H
08H 88H
Description of Error Code:
error Description error Description
Exceptional command
01H 03H Illegal Data
code
02H Exceptional data address 04H Operation failed
For example, for U00.00 write data 50.00HZ frequency. The host sends the data frame (hex):
01H 06H 30H 00H 13H 88H 8BH 9CH
Because F00.00 is read only, inverter responds error message. Inverter responds data frame in
hexadecimal format:
01H 86H 02H C3H A1H
Command code is 86H in error message, the highest bit 1 of 06H. If error code detail is 11H, it means
the parameter is read only.
After responding to the error data receipt, master can revise the responding program via
resending data frame or based on the error message responded by the inverter.

- 117 -
FR100 Series Multifunctional Compact Inverter
8. Illustration
1, No. 01 reads the output frequency value (U00.00), returned 5000, that 50.00Hz.
To send data:
01 03 30 00 00 01 8B 0A
The received data is:
01 03 02 13 88 B5 12
2, No. 01 Drive communication given frequency 30.00Hz, send the data content of 3000.
To send data:
01 06 20 01 0B B8 D4 88
The received data is:
01 06 20 01 0B B8 D4 88
3, communications sent on the 1st drive forward run command, write to the address 2000H 01
To send data:
01 06 20 00 00 01 43 CA
The received data is:
01 06 20 00 00 01 43 CA
4, No. 01 communications sent inverter deceleration stop command, the address to write to
2000H 05
To send data:
01 06 20 00 00 05 42 09
The received data is:
01 06 20 00 00 05 42 09

- 118 -
FR100 Series Multifunctional Compact Inverter

Appendix B: Accessories

B.1 Braking Resistor


When deceleration or rapid deceleration in high inertia load, motor will be in the state of power
generation, the load power will pass the converter part to inverter DC part lead to the rise of inverter
bus voltage, when it is higher than a certain value, inverter will alarm with voltage fault, even damage
the power module, so we must configure braking system.

FR100 multi-functional compact inverter built-in braking unit in all series models, customer need to
only connect external braking resistor. We recommend below configuration of resistor power and
value. User can adjust the value in the range properly according to the load
Resistance
Resistance Resistance
Inverter model Motor(KW) connection wire
value(Ω) power(W)
(mm2)
Single phase:220V,50/60Hz
FR100-2S-0.2B 0.2 ≧360 ≧100 1
FR100-2S-0.4B 0.4 ≧360 ≧100 1
FR100-2S-0.7B 0.75 ≧180 ≧200 1.5
FR100-2S-1.5B 1.5 ≧180 ≧200 1.5
FR100-2S-2.2B 2.2 ≧90 ≧400 2.5
Three phase:380V,50/60Hz
FR100-4T-0.7B 0.75 ≧360 ≧200 1
FR100-4T-1.5B 1.5 ≧180 ≧400 1.5
FR100-4T-2.2B 2.2 ≧180 ≧400 1.5
FR100-4T-4.0B 4.0 ≧90 ≧800 2.5
Note: The wire in the table is for single resistor, when resistors in parallel, the wire should be
bigger. The withstand voltage of wire for single phase inverter is above AC300V, for three phase
inverter is above AC450V, temperature tolerance of wire 105℃
B.2 Uploading and Downloading Module
Uploading and downloading module(0.7BCOP)is specially developed for the FR series
inverter an option, Mainly has the following features:
●Upload and download inverter parameters.
●The baud rate up to 100KHz.
●Easy to carry, size almost like an ordinary USB.
●You can view and modify parameters via USB powered.
Uploading and downloading module structure diagram shown in figure B-1:

USB Cap

Upper case Connection socket


Under case
MIC-USB
Indicator light
Keychain hole

Figure B-1 Uploading and downloading module structure diagram


The following were introduced by uploading and downloading module to complete the parameter
copy and debugging steps

- 119 -
FR100 Series Multifunctional Compact Inverter
Applications 1:Upload and download inverter parameters steps
Step 1:Installing the uploading and downloading module to the inverter control board UP /
DOWNLOAD position(As shown in figure B-2)

Figure B-2 Uploading and downloading module installation


Seep 2:Powered through the inverter main circuit or power to the upload and download module
via the USB port, as shown in figure B-3.

(a)Powered through the inverter main circuit

Uploading and
downloading module
Work Location Map

Computer

Mobile Power

Data wire

(b)Powered through the USB


Figure B-3 Power to the uploading and downloading module
Step 3:Upload parameters, Setting F00.05 = 1, Press the ENT button, When F00.05 value
becomes 0, upload an end.
- 120 -
FR100 Series Multifunctional Compact Inverter
Step 4:Download Parameters, Setting F00.05 = 2 or 3, Press the ENT button, When F00.05
value becomes 0, upload an end.
Step 5:Inverter main circuit or USB power off,Unplug upload and download modules from the
inverter control board (When USB powered, hot-swappable, The direction as shown in figure B-3).
Step 6:End.

Figure B-4 Uploading and downloading module removal


Application 2:Powered by USB to view and modify the drive parameters
Step 1:Installing the upload and download module in the inverter control board UP / DOWNLOAD
location(As shown in figure B-1).
Step 2:Power to the upload and download module via USB(As shown in figure B-2(b).
Step 3:Query or modify inverter parameters.
Step 4:Unplug upload and download module from the inverter control board(As shown in figure
B-4).
Step 5:End.

- 121 -

You might also like