QBE2002-P10 SBT en Datasheet
QBE2002-P10 SBT en Datasheet
QBE2002-P10 SBT en Datasheet
1909P01
QBE2002-P…
Pressure Sensors QBE2102-P…
for liquid and gaseous media
Use
The pressure sensors are suitable for the measurement of static and dynamic positive
pressure in HVAC plant, particularly in hydraulic and pneumatic systems using liquid or
gaseous media (steam applications).
Technical design
The pressure sensors operate on the piezo-resistive measuring principle. The ceramics
diaphragm (thick-film hybrid technology) acquires the pressure through direct contact
with the medium. The measurement is converted electronically into a linear output
signal of DC 0...10 V or DC 4…20 mA.
CE1N1909en
2014-07-30 Building Technologies
Type summary
Ordering
Equipment combinations
The pressure sensors can be combined with all devices or systems capable of
processing the DC 0 ...10 V or DC 4…20 mA output signal from the pressure sensor.
Mechanical design
The pressure sensors are compact units and cannot be dismantled. No changes or
adjustments are possible.
Accessories
AQB22.1 Fixing bracket for sensor (for remote mounting). For dimensions, refer to
"Dimensions"
AQB2001 Mounting kit for remote mounting with 1 m
copper capillary line, both ends
prefabricated ready for connection.
Thread adapters and terminal nuts made of
brass. Pressure connection with G1/8“ or
G1/2“ outer threading.
2/6
Pressure measurement The tapping point should be at the side, near the bottom of
with liquids the pipe. Do not measure the pressure from the top of the
pipe (where it may be affected by airlocks) or the bottom
1909Z03
(where it may be affected by dirt).
Always evacuate the system.
Pressure measurement The tapping point should be at the top so that no condensate
with condensing gases reaches the sensor.
1909Z04
Remote mounting If the temperature of medium is lower
than 40 °C or higher than 80 °C,
the sensor should be fitted remotely,
taking care that no condensate can
reach the sensor.
3/6
The devices are considered electronics devices for disposal in terms of European
Directive 2012/19/EU and may not be disposed of as domestic waste.
Dispose of the device via the channels provided for this purpose.
Comply with all local and currently applicable laws and regulations.
Technical data
4/6
5/6
1909G01
BT terminal marking Color of core Meaning
QBE2002…
(+) ( ) (0) G (+) Brown Supply voltage
G U M AC 24 V or DC 18...33 V
U( ) Green Output signal DC 0...10 V
(signal ground GND)
M (0) White GND
19 07G 02
QBE2102… BT terminal marking Color of core Meaning
(+) ( ) G (+) Brown Supply voltage DC 11...33 V
G I( ) Green Output signal DC 4...20 mA
Dimensions
QBE2002-P… 20 10
1909M01
QBE2102-P…
ø 34,5
G1/2
SW 27
ca. 87
ca. 108
AQB22.1 37,5 37
M4
21
4,5
57
20
20
1909M02
ø 4,5
SW 27 10
Dimensions in mm