QBE2002-P10 SBT en Datasheet

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

1 909

1909P01

QBE2002-P…
Pressure Sensors QBE2102-P…
for liquid and gaseous media

Piezo-resistive measuring system


DC 0 ...10 V or DC 4…20 mA output signal
Measurement unaffected by changes in temperature
High temperature stability
No mechanical aging or creepage
External thread G½"
Excellent EMC characteristics

Use

The pressure sensors are suitable for the measurement of static and dynamic positive
pressure in HVAC plant, particularly in hydraulic and pneumatic systems using liquid or
gaseous media (steam applications).

Technical design

The pressure sensors operate on the piezo-resistive measuring principle. The ceramics
diaphragm (thick-film hybrid technology) acquires the pressure through direct contact
with the medium. The measurement is converted electronically into a linear output
signal of DC 0...10 V or DC 4…20 mA.

CE1N1909en
2014-07-30 Building Technologies
Type summary

Type reference Pressure range Output signal


QBE2002-P1 0...1 bar 0...100 kPa 0...14.5 psi 0…10 V
QBE2002-P2 0...2 bar 0...200 kPa 0...29.0 psi 0…10 V
QBE2002-P4 0...4 bar 0...400 kPa 0...58.0 psi 0…10 V
QBE2002-P5 0...5 bar 0...500 kPa 0...72.5 psi 0…10 V
QBE2002-P10 0...10 bar 0...1.0 MPa 0...145.0 psi 0…10 V
QBE2002-P16 0...16 bar 0...1.6 MPa 0...232.0 psi 0…10 V
QBE2002-P20 0...20 bar 0...2.0 MPa 0...290.0 psi 0…10 V
QBE2002-P25 0...25 bar 0...2.5 MPa 0...362.6 psi 0…10 V
QBE2002-P40 0...40 bar 0...4.0 MPa 0...580.0 psi 0…10 V
QBE2002-P60 0...60 bar 0...6.0 MPa 0...870.0 psi 0…10 V
QBE2102-P4 0...4 bar 0...400 kPa 0...58.0 psi 4…20 mA
QBE2102-P5 0...5 bar 0...500 kPa 0...72.5 psi 4…20 mA
QBE2102-P10 0...10 bar 0...1.0 MPa 0...145.0 psi 4…20 mA
QBE2102-P16 0...16 bar 0...1.6 MPa 0...232.0 psi 4…20 mA
QBE2102-P20 0...20 bar 0...2.0 MPa 0...290.0 psi 4…20 mA

Ordering

When ordering, please give name and type reference, e.g.:


Pressure sensor QBE2002-P1
Any accessories required must be ordered separately.

Equipment combinations

The pressure sensors can be combined with all devices or systems capable of
processing the DC 0 ...10 V or DC 4…20 mA output signal from the pressure sensor.

Mechanical design

The pressure sensors are compact units and cannot be dismantled. No changes or
adjustments are possible.

Accessories

AQB22.1 Fixing bracket for sensor (for remote mounting). For dimensions, refer to
"Dimensions"
AQB2001 Mounting kit for remote mounting with 1 m
copper capillary line, both ends
prefabricated ready for connection.
Thread adapters and terminal nuts made of
brass. Pressure connection with G1/8“ or
G1/2“ outer threading.

2/6

Siemens Pressure sensors QBE2002-P... CE1N1909en


Building Technologies 2014-07-30
Mounting notes

Mounting Instructions are enclosed with the sensor.


The sensors are designed for direct connection to screwed fittings with G½" threads.
Appropriate measures must be taken to ensure a leak-proof fitting.
To provide for test measurements without leakage of the medium, it is strongly
recommended that an appropriate test adapter and shutoff device be fitted.

Pressure measurement The tapping point should be at the side, near the bottom of
with liquids the pipe. Do not measure the pressure from the top of the
pipe (where it may be affected by airlocks) or the bottom

1909Z03
(where it may be affected by dirt).
Always evacuate the system.

Pressure measurement The tapping point should be at the top so that no condensate
with condensing gases reaches the sensor.

1909Z04
Remote mounting If the temperature of medium is lower
than 40 °C or higher than 80 °C,
the sensor should be fitted remotely,
taking care that no condensate can
reach the sensor.

For remote mounting, a fixing bracket


AQB22.1 and mounting kit AQB2001
can be delivered (refer to
"Accessories").

For remote mounting, the sensor can


be operated together with the AQB
pressure mounting kit in ambient
Condensate
temperatures of up to 70 °C for or liquid
medium temperatures of up to
180 °C. Care must be taken in this case to ensure that the cooling efficiency of the
copper pipe is not reduced by additional heat sources or by restrictions to the air
circulation. The admissible pressure is limited to 93 bar for temperatures >120 °C.

3/6

Siemens Pressure sensors QBE2002-P... CE1N1909en


Building Technologies 2014-07-30
Disposal

The devices are considered electronics devices for disposal in terms of European
Directive 2012/19/EU and may not be disposed of as domestic waste.
Dispose of the device via the channels provided for this purpose.
Comply with all local and currently applicable laws and regulations.

Technical data

Electrical interface Power supply with extra-low voltage only (SELV)


Supply voltage (QBE2002…)Current consumption AC 24 V ±15%, 50...60 Hz or DC 18...33 V< 6 mA
Supply voltage (QBE2102…) DC 11…33 V
Current consumption <20 mA
External supply line protection Fuse slow max. 10 A
or
Circuit breaker max. 13 A
Characteristic B, C, D according to EN 60898
or
Power source with current limitation of
max. 10 A
Output signal QBE2002… DC 0 ...10 V, RLoad > 10 k
(not galvanically separated, 3-wire connection,
short-circuit proof and protected against polarity
reversal)
Operating voltage – 11 V
Output signal QBE2102… DC 4…20 mA , RLoad Ohm
0.02 A
(not galvanically separated, 2-wire connection,
short-circuit proof and protected against polarity
reversal)
Functional data Application range refer to "Type summary"
Accuracy: (FS = Full Scale)
Total of linearity, hysteresis
and reproducibility < ± 0.4 % FS
Zero point, Full scale < ± 0.6 % FS
Temperature drift: balancing in bar
TC zero point < ± 0.04 % FS/K
TC sensitivity < ± 0.015 % FS/K

Response time < 5 ms


Nominal pressure relative pressure as in "Type summary"
(measurement of difference from ambient
pressure)
Max. admissible pressure 2 x scale end value of measuring range (FS)
Rupture pressure 3 x scale end value of measuring range (FS)
Media neutral and slightly corrosive liquids and gases
(suited for use with oil-contacting media)
Admissible temperature of medium 40... 80 °C
Maintenance maintenance-free
Mounting position Optional

4/6

Siemens Pressure sensors QBE2002-P... CE1N1909en


Building Technologies 2014-07-30
Degree of protection Protection degree of housing IP65 according to EN 60529
Protection class III according to EN 60730
2
Connections Connecting cable PVC, length 1.5 m, 3 x 0.25 mm stranded wires
Screwed fitting external thread G½", inside thread M5
Environmental conditions Operation to IEC 60 721-3-3
Climatic conditions class 3K7
Temperature 40... 80 °C
Humidity insensitive to condensation
Storage / transport IEC 60 721-3-2
Climatic conditions class 2K4
Temperature 4 0 ... 8 0 °C
Humidity insensitive to condensation
Directives and Standards Product standard EN 61326-1
Electrical equipment for measurement, control
and laboratory use. EMC requirements.
General requirements
*)
EU Conformity (CE) CE1T1909xx
RCM Conformity 8000078879
*)
Environmental compatibility The product environmental declaration CE1E1909 contains data on environmentally compatible
product design and assessments (RoHS compliance, materials composition, packaging, environmental
benefit, disposal).
Materials Base stainless steel (1.4305)
Measuring element ceramics diaphragm
Cover stainless steel (1.4305)
Sealant FPM fluor-caoutchouc spec.
Fixing bracket AQB22.1 die-cast aluminium
Mounting kit AQB2001 see "Accessories"
Weight Including packaging 0.265 kg
*) The documents can be downloaded from http://siemens.com/bt/download.

5/6

Siemens Pressure sensors QBE2002-P... CE1N1909en


Building Technologies 2014-07-30
Internal diagram

1909G01
BT terminal marking Color of core Meaning
QBE2002…
(+) ( ) (0) G (+) Brown Supply voltage
G U M AC 24 V or DC 18...33 V
U( ) Green Output signal DC 0...10 V
(signal ground GND)
M (0) White GND

19 07G 02
QBE2102… BT terminal marking Color of core Meaning
(+) ( ) G (+) Brown Supply voltage DC 11...33 V
G I( ) Green Output signal DC 4...20 mA

Dimensions

QBE2002-P… 20 10

1909M01
QBE2102-P…
ø 34,5
G1/2

SW 27

ca. 87

ca. 108

AQB22.1 37,5 37
M4
21

4,5
57
20
20

1909M02

ø 4,5
SW 27 10
Dimensions in mm

6/6 2005-2014 Siemens Switzerland Ltd. Subject to change

Siemens Pressure sensors QBE2002-P... CE1N1909en


Building Technologies 2014-07-30