User & Installation Manual: Intarblock Intartop
User & Installation Manual: Intarblock Intartop
intarblock intartop
MCV-N, MCV-C MCR-N, MCR-C
BCV-N, BCV-C BCR-N, BCR-C
MCV-I, BCV-I
Doc. CV / CR 3.3
January 2018
Once installed, your INTARSPLIT unit can be fully operated from the remote keyboard. The control
keyboard has the following functions and characteristics.
DIGITAL DISPLAY
It shows the room Operation LEDs
temperature. Press for 3 seconds
By pressing the set key to force a defrost
it will show the target cycle
temperature.
Press to switch on
Press to visualise
and off the room light
maximum temperature
record
Press for 3 seconds
Press to visualise to activate the energy
minimum temperature saving function
record
Refrigeration mode.- this is the normal operation mode. The display shows the room temperature
and by pressing the set key the target temperature is shown. During the operation the electronic
control keeps a record of the maximum and minimum room temperature ever measured, which can be
consulted at any time.
Defrost mode.- the time on time your unit will switch to the defrost mode to eliminate the frost that has
formed on the evaporator. You can also force a defrost cycle by pressing the corresponding key.
Fast cooling mode.- If you like you can activate this operation mode during the start-up of the cold
room. The unit will run continuously for the preset time in parameter “CCt”, even beyond the target
temperature.
Energy saving mode.- If you like you can activate or deactivate this operation mode to save energy
during the night or when the room will stay closed for a long time. By activating this function the target
temperature is increased according to preset value in parameter “HES”.
2
Downloaded from www.Manualslib.com manuals search engine
intarblock | intartop
Basic keyboard functions.-
II. CONTENTS
1. DESCRIPTION ........................................................................................................................4
2. IDENTIFICATION ....................................................................................................................4
3. OPERATION............................................................................................................................5
4. OPERATION LIMITS ...............................................................................................................6
5. COMPOSITION .......................................................................................................................7
6. TESTS ..................................................................................................................................... 8
7. SAFETY DEVICES ..................................................................................................................8
8. MCV SERIES TECHNICAL FEATURES ................................................................................9
9. BCV SERIES TECHNICAL FEATURES ...............................................................................11
10. MCR SERIES TECHNICAL FEATURES ..............................................................................12
11. BCR SERIES TECHNICAL FEATURES ...............................................................................14
12. COOLING CAPACITY R404A ...............................................................................................15
13. COOLING CAPACITY R134a ...............................................................................................15
14. DIMENSIONS ........................................................................................................................18
15. ELECTRICAL CONNECTIONS .............................................................................................20
16. EMERGENCY SYSTEM........................................................................................................21
17. SOUND PRESSURE LEVEL ................................................................................................21
18. TRANSPORT.........................................................................................................................21
19. DATA PLATE .........................................................................................................................22
20. SAFETY RECOMMENDATIONS ..........................................................................................22
21. INSTALLATION AND MOUNTING........................................................................................23
22. START-UP .............................................................................................................................27
23. MAINTENANCE ....................................................................................................................28
24. REFRIGERANT LOAD ..........................................................................................................29
25. DISPOSAL MANAGEMENT .................................................................................................. 30
26. CONTROL .............................................................................................................................30
27. PARAMETER LIST ................................................................................................................33
28. FAULT ANALYSIS .................................................................................................................37
29. GUARANTEE ........................................................................................................................40
3
Downloaded from www.Manualslib.com manuals search engine
1. DESCRIPTION
INTARBLOCK and INTARTOP units are monoblock refrigeration units in vertical and roof construction,
fullly tested and adjusted in Factory. They are assembled on a prelacquered galvanised steel shell and
have been designed for indoor installation, with easily removable panels to give access to fans,
refrigerant circuit, and electric board.
INTARBLOCK:
MCV Series are designed for positive temperature refrigeration applications from -5ºC (23ºF) to +10ºC
(50ºF) and consist of 12 models to cover a cooling capacity range from 0.5 kW to 3 kW
BCV Series are designed for positive temperature refrigeration applications from -15ºC (5ºF) to -25ºC
(13ºF) and consist of 9 models to cover a cooling capacity range from 0.4 kW to 2,5 kW
INTARTOP:
MCV Series are designed for positive temperature refrigeration applications from -5ºC (23ºF) to +10ºC
(50ºF) and consist of 10 models to cover a cooling capacity range from 0.5 kW to 2,5 Kw
BCR Series are designed for positive temperature refrigeration applications from -15ºC (5ºF) to -25ºC
(13ºF) and consist of 6 models to cover a cooling capacity range from 0.4 kW to 1,7 kW
2. IDENTIFICATION
INTARBLOCK and INTARTOP series are identified according to the following nomenclature on the
product data plate.
M C V - N F - 1 024
Compressor capacity
Construction size
R-404A refrigerant
(N) Standard (C) Centrifugal
Vertical construction
Compact construction
Medium temperature
4
Downloaded from www.Manualslib.com manuals search engine
intarblock | intartop
3. OPERATION
INTARBLOCK and INTARTOP are refrigeration machines operating under a vapour compression
cycle.
Refrigeration cycle
The refrigeration cycle uses a phase change refrigerant fluid in a closed circuit, with the following four
steps:
Expansion: refrigerant expansion takes place in the capillary tube between high and low pressure
sections. During the expansion, liquid refrigerant cools down to the evaporating temperature.
Evaporation: In the evaporator the refrigerant evaporates under constant temperature and pressure
absorbing heat from the cold room. Once the refrigerant vapour has been fully evaporated, it is slightly
overheated beyond the evaporation temperature.
Compression: The resultant refrigerant vapour is suctioned from the evaporator by the compressor
through the suction line. The compressor compresses the refrigerant vapour up to high pressure and
temperature.
Condensation: the hot high pressure gas is desuperheated and condensed, at a constant pressure
and temperature, in the el condenser by exhausting the latent evaporation to the outer ambient. Once
the refrigerant has been fully condensed, the liquid refrigerant is overcooled beyond the condensing
temperature.
High pressure liquid refrigerant is then driven to the capillary tube, and therefore closing the circuit.
Defrost cycle
Because of the evaporator temperature can be below 0ºC (32ºF), frost is likely to deposit on the
evaporator surface through the condensation of the water vapour contained in the air. To prevent the
air flow from being obstructed with the consequently loss of performance, the instrument switches
automatically to the defrost operation mode every given period of time.
During the defrost cycle, by opening the solenoid valve, part of the hot gas from the compressor
discharge is injected into the evaporator. The evaporator temperature is rapidly increased in order to
melt the frost on it while the inside fan is off.
The defrost water is collected in the drain tray and conducted to the drain bucket. This drain bucket
contains a hot gas coil to progressively evaporate the drain water to the outer ambient.
5
Downloaded from www.Manualslib.com manuals search engine
CAPILLARY TUBE /
CONDENSER THERMOSTATIC
EXPANSION VALVE EVAPORATOR
SOLENOID
VALVE
COMPRESSOR
AP
BP
DRAIN BUCKET
PRESSURE
REGULATOR
(only BCV/BCR)
4. OPERATION LIMITS
INTARBLOCK and INTARTOP units are designed for continuous operation within the following
temperature limits:
The unit should work beyond these limits only for short periods of time or during the start-up.
6
Downloaded from www.Manualslib.com manuals search engine
intarblock | intartop
5. COMPOSITION
MCV / BCV units are built on a self-contained construction. The components are assembled on a steel
structure and covered with a prelacquered galvanised steel shell. It consists of:
Refrigerant circuit
§ Hermetic reciprocating compressor with internal protection, assembled on silentblocs
§ R404-A or R134a refrigerant load.
§ HP and LP pressure switches.
§ HP and LP load nipples.
§ Thermostatic expansion valve (capillary tube in medium temperature models with power lower
than 1,5 HP (R404A) and 1 HP (R134a).
§ Antiacid dehydrating filter.
§ Evaporation coil in copper tubes and aluminium fins with stainless steel drain tray.
§ Condensation coil in copper tubes and aluminium fins.
§ Solenoid valve for the hot gas bypass.
§ Water drain bucket including hot gas coil for the automatic evaporation of drain water.
Air circuits
N/I version:
§ Direct driven axial fans with single phase motor. Dynamically equilibrated blades with protection
grill.
C version:
§ Direct driven centrifugal fans with single phase motor. Dynamically equilibrated rotor.
Electric board
§ Circuit breaker protection
§ Electric control XW270K with the following elements and features:
- transformer 230 VAC / 12 VCC,
- microprocessor,
- alarm relay,
- compressor relay,
- defrost relay,
- evaporator fan relay,
- cold room light relay,
- condenser fan relay,
- door switch digital input
- H/LP pressure switch input
- inside temperature NTC probe
- outside temperature NTC probe
- defrost NTC probe
- RS485 connection,
- programming key connection,
7
Downloaded from www.Manualslib.com manuals search engine
- V820 keyboard.
§ Compressor permanent condenser in single phase units.
§ Compressor start relay and condenser in single phase units.
§ Ground connection for compressor and motorfans.
§ Cold room light.
§ Door microswitch connection.
§ Door microswitch (as an option).
§ Door heating cable (only for BCV and BCR models).
§ Crankcase heater (as an option).
§ Draining pipe heating cable (only for BCV y BCR models).
6. TESTS
Every INTARBLOCK and INTARTOP units have been previously checked and tested in factory
according to the following test protocol:
§ Helium leak-proof test. A leak-proof certificate is supplied upon request.
§ Refrigerant load.
§ Operation test for refrigeration and defrost modes under nominal operating conditions.
§ Safety devices checking
7. SAFETY DEVICES
INTARBLOCK and INTARBLOCK units feature the following safety devices:
§ HP and LP pressure limit switches to protect the unit against unusual pressure levels.
§ Thermal switches with automatic restart in compressor and fans to protect motor wirings from
overloads.
§ Circuit breaker protection
§ Common ground connection.
8
Downloaded from www.Manualslib.com manuals search engine
intarblock | intartop
8. MCV SERIES TECHNICAL FEATURES
MCV Series R404A 0008 0010 0012 1010 1012 1014 1016 1018 1024 2024 2026 2034 3034 3038
Cooling capacity (1) (W) 610 728 808 799 930 1077 1184 1347 1468 1917 2149 2391 2690 3020
Cooling
Absorbed power (2) (W) 470 570 640 649 672 804 869 1020 1175 1356 1474 1946 2070 1970
capacity
COP performance 1,30 1,28 1,27 1,23 1,38 1,34 1,36 1,32 1,25 1,41 1,46 1,23 1,30 1,53
Installed power (3) (kW) 0,53 0,73 0,86 0,75 0,82 0,98 1,10 1,38 1,68 1,68 1,89 2,63 2,63 2,35
Power (W) - r.p.m 47W @ 2500 62W @ 2600 2 x 62W @ 2600 2x70W@2600
Swept volume (m3/h) 1,16 1,54 1,79 1,64 1,96 2,32 2,65 3,18 4,21 4,21 4,52 6,01 6,01 6,60
Nominal power (CV) 1/3 3/8 1/2 3/8 1/2 1/2 5/8 3/4 1 1 1 1/4 1 1/2 1 1/2 1 3/4
Type ACB
High Brand Danfoss
pressure
switch Model 061F8175
Max. 230 V / I ph / 50 Hz 4,5 5,9 6,7 5,1 6,1 6,7 7,6 8,9 11,1 11,9 12,3 16,9 17,1 N/D
absorbed
intensity 400 V / III ph / 50 Hz Not available 5,7 6,5 6,7 7,9
(A)(4)
Starting-up 230 V / I ph / 50 Hz 16,3 18,8 20,2 16,9 17,9 20,9 23,5 30,9 34,4 35,2 33,7 46,7 46,9 N/D
intensity (A) 400 V / III ph / 50 Hz Not available 19,7 24,7 24,9 17,9
9
Downloaded from www.Manualslib.com manuals search engine
MCV series R134a 0010 0015 1015 1026 1033 2033 2053 3053 3074 3108
Cooling capacity (1) (W) 610 794 972 1281 1454 1790 2153 2489 3239 3927
Cooling capacity Absorbed power (2) (W) 430 530 570 810 920 1090 1460 1510 1890 2480
COP performance 1,42 1,50 1,71 1,58 1,58 1,64 1,47 1,65 1,71 1,58
Installed power (3) (kW) 0,59 0,83 0,83 1,22 1,44 1,44 2,2 2,2 2,9 4,4
Range (m) 3 4
Evaporator fan Type Axial
2x 62W @
Power (W) - r.p.m 47W @ 2500 62W @ 2600 2x 70W @ 2600
2600
Swept volume (m3/h) 2,08 3,18 3,18 4,51 5,69 5,69 9,26 9,26 12,92 18,74
Type ACB
Brand Danfoss
High pressure switch
Model 061F6147
Max. absorbed 230 V / I ph / 50 Hz 5,9 6,9 7,0 10,7 10,9 11,1713,7714,19 19,74 -
intensity (A)(4) 400 V / III ph / 50 Hz Not available 18,5
Starting-up intensity 230 V / I ph / 50 Hz 13,2 20,7 20,7 27,0 30,0 30,0 46,0 46,0 55,0 -
(A) 400 V / III ph / 50 Hz Not available 65
10
Downloaded from www.Manualslib.com manuals search engine
intarblock | intartop
9. BCV SERIES TECHNICAL FEATURES
BCV Series R404A 0018 1018 1026 1034 2034 2054 2074 3074 3086 3096
Cooling capacity (1) (W) 479 489 720 866 1048 1349 1633 1930 2270 2460
Cooling capacity Absorbed power (2) (W) 620 688 914 1136 1187 1685 2014 2380 2320 2640
COP performance 0,77 0,73 0,79 0,76 0,88 0,80 0,81 0,81 0,98 0,93
Installed power (3) (kW) 0,87 0,88 1,29 1,76 1,76 2,60 3,39 3,39 3,46 4,31
Nominal air flow rate (m3/h) 375 575 1000 1350
Condenser fan
Type Axial
NF version
Power (W) - r.p.m 85W @ 1300 2 x 85W @ 1300 2 x 70W @ 1300
Nominal air flow rate (m3/h) 575 1000 1350
Condenser fan Available static pressure (Pa) 45 90 120
-
CF version Type Centrifugal
Power (W) 45 W 105 W 2 x 105 W
Nominal air flow rate (m3/h) 300 550 1050 1400
Range (m) 3 4
47W
Power (W) - r.p.m @ 62W @ 2600 2 x 62W @ 2600 2 x 70W @ 2600
2500
Swept volume (m3/h) 3,18 3,18 4,57 6,01 6,01 9,25 12,91 12,91 11,80 16,70
Nominal power (CV) 5/8 5/8 3/4 1 1/4 1 1/4 1 3/4 2 1/2 2 1/2 3 3 1/2
Type ACB
Max. absorbed 230 V / I ph / 50 Hz 4,8 7,2 8,4 10,9 11,7 17,7 25,7 25,9 No disponible
intensity (A)(4) 400 V / III ph / 50 Hz Not available 6,5 7,2 7,4 10,3 12,0
Starting-up 230 V / I ph / 50 Hz 21,9 21,9 29,9 40,9 41,7 69,7 82,7 82,9 No disponible
intensity (A) 400 V / III ph / 50 Hz Not available 24,7 29,7 29,9 26,9 33,9
11
Downloaded from www.Manualslib.com manuals search engine
10. MCR SERIES TECHNICAL FEATURES
MCR Series R404A 0008 0010 0012 1010 1012 1014 1016 1018 1024 2024 2026 2034
Cooling capacity (1) (W) 612 738 838 799 930 1087 1194 1378 1478 2020 2223 2527
Cooling
Absorbed power (2) (W) 470 580 650 652 672 811 880 1038 1201 1319 1425 1903
capacity
COP performance 1,30 1,27 1,29 1,23 1,38 1,34 1,36 1,33 1,23 1,53 1,56 1,33
Installed power (3) (kW) 0,53 0,73 0,86 0,75 0,82 0,98 1,10 1,38 1,68 1,68 1,89 2,63
Range (m) 3 4
Evaporator
fan Type Axial
2x 62W @ 2600
Power (W) - r.p.m 47@ 2500 rpm 62W @ 2600 rpm
rpm
Swept volume (m3/h) 1,16 1,54 1,79 1,64 1,96 2,32 2,65 3,18 4,21 4,21 4,52 6,01
Nominal power (CV) 1/3 3/8 1/2 3/8 1/2 1/2 5/8 3/4 1 1 1 1/4 1 1/2
Type ACB
Max. 230 V / I ph / 50 Hz 4,5 5,9 6,7 5,1 6,1 6,7 7,6 8,9 11,1 11,6 12,0 16,6
Absorbed
intensity(4)(A) 400 V / III ph /50 Hz Not available 5,4 6,2
Starting up 230 V / I ph / 50 Hz 16,3 18,8 20,2 16,9 17,9 20,9 23,5 30,9 34,4 34,9 33,4 46,4
intensity (A) 400 V / III ph /50 Hz Not available 19,4 24,4
Weight (kg) 62 64 65 73 73 73 82 83 83 98 99 99
12
Downloaded from www.Manualslib.com manuals search engine
intarblock | intartop
MRC series R134a 0010 0015 1015 1026 1033 2033 2053 2074
Cooling capacity (1) (W) 605 788 999 1265 1502 1911 2352 2940
Cooling capacity Absorbed power (2) (W) 430 530 580 930 1050 1210 1670 1830
COP performance 1,41 1,48 1,72 1,36 1,43 1,58 1,41 1,61
Installed power (3) (kW) 0,83 0,83 1,22 1,44 1,44 2,2 2,9
Range (m) 4
Evaporator fan
Type Axial
Swept volume (m3/h) 2,08 3,18 3,18 4,51 5,69 5,69 9,26 12,92
Type ACB
Brand Danfoss
High pressure switch
Model 061F6147
230 V / I ph / 50 Hz 16 22 22 29 30 30 46 55
Starting up intensity (A)
400 V / III ph /50 Hz Not available
13
Downloaded from www.Manualslib.com manuals search engine
11. BCR SERIES TECHNICAL FEATURES
BCR Series R404A 0008 1018 1026 1034 2034 2054 2074
Cooling capacity (1) (W) 515 502 734 876 1102 1443 1689
Cooling capacity Absorbed power (2) (W) 630 671 928 1160 1297 1830 2147
Installed power (3) (kW) 0,87 0,88 1,29 1,76 1,76 2,60 3,39
Nominal air flow rate (m3/h) 375 575 1150
Condenser fan
Type Axial
NF version
Power (W) - r.p.m 85 W @ 1300 rpm 120 W @ 1300 rpm
Nominal air flow rate (m3/h) 575 1150
Condenser fan Available static pressure (Pa) 45
-
CF version Type Centrifugal
Power (W) 45 W @ 1300 rpm 105 W @ 1300 rpm
Nominal air flow rate (m3/h) 300 600 1150
Range (m) 3 4
Evaporator fan Type Axial
47 W @
Power (W) - r.p.m 62 W @ 2600 rpm 2 x 62 W @ 2600 rpm
2500rpm
Swept volume (m3/h) 3,18 3,18 4,57 6,01 6,01 9,25 12,91
Nominal power (CV) 5/8 5/8 3/4 1 1/4 1 1/4 1 3/4 2 1/2
Type ACB
Max. absorbed 230 V / I ph / 50 Hz 4,8 7,2 8,4 10,9 11,4 17,4 25,4
intensity (A) 400 V / III ph / 50 Hz Not available 6,21 6,91
14
Downloaded from www.Manualslib.com manuals search engine
intarblock | intartop
12. COOLING CAPACITY R-404A
§ MCV series
§ BCV series
MCV series Cooling capacity Absorbed power Cooling capacity Absorbed power Cooling capacity Absorbed power
(W) (W) (W) (W) (W) (W)
0018 379 565 479 620 591 694
1018 383 611 489 668 655 747
Ambient Temp: 35 ºC
15
Downloaded from www.Manualslib.com manuals search engine
§ MCR Series
§ BCR Series
16
Downloaded from www.Manualslib.com manuals search engine
intarblock | intartop
13. COOLING CAPACITY R-134a
· Serie MCV
· Serie MCR
17
Downloaded from www.Manualslib.com manuals search engine
14. DIMENSIONS
CV-N-C Models
Centrifugal Box
only in 0 series
Exhaust
Dimensions (mm) A B C D E F G H I J K L M
duct
0 series 306 510 683 420 250 50 405 515 n/a Ø 150
1 series 340 330 880 400 514 122 380 335 75 41 295 13 233 Ø 150
2 series 340 330 920 620 514 122 600 335 75 36 523 13 233 Ø 150
3 series 365 470 920 735 514 122 710 475 75 41 611 22 356 2x Ø 150
CV-I Models
Dimensions (mm) A B C D E F G H
1 series 340 330 1060 400 514 115 380 335
2 series 340 330 1100 620 514 115 600 335
3 series 365 470 1100 735 514 115 710 475
18
Downloaded from www.Manualslib.com manuals search engine
intarblock | intartop
CR-N Models
ROOF FRAME
CR-C Models
19
Downloaded from www.Manualslib.com manuals search engine
15. ELECTRICAL CONNECTIONS
Before connecting the unit to the electrical supply, make sure that the electrical board is in good
conditions and please follow the following recommendations:
§ Consult the electrical schema supplied by manufacturer.
§ Only use electrical cables of the appropriate characteristics and capacity according to the following
table. Notice that single phase units have a three-wire supply and three phase units have a five-
wire supply, being always the ground wire in green-yellow colour.
MCV - MCR 0008 0010 0012 1010 1012 1014 1016 1018 1024 2024 2026 2034 3034 3038
Power supply 2 x 2,5 mm² +
2 x 1,5 mm² + T
220-I-50 T
Power supply
4 x 1,5 mm² + T
400-III-50
Cold room light 2 x 1 mm² + T
Door
2 x 1 mm²
microswitch
Remote
2 x 1 mm²
controller
BCV - BCR 0018 1018 1026 1034 2034 2054 2074 3074 3086 3096
§ Always install the appropriate protection device on the supply line. In case that more than one unit
is installed, always provide separate protection devices for each of the installed units.
§ Electrical wires section in power supply wiring is to be calculated according to the electrical data
provided by manufacturer in data plate, power supply wires length, wires type, etc.; always
according to electrical regalement.
§ Optionally install a door switch on the end of the supplied cable or close the end of the cable.
§ Install the room light in the supplied cable.
20
Downloaded from www.Manualslib.com manuals search engine
intarblock | intartop
16. EMERGENCY SYSTEM
The electronic regulation of the units involves control routines and emergency alarms for the following
causes:
§ Probe failure.
§ Too high and too low room temperature.
§ Too high or too low refrigerant pressure.
§ Too high ambient temperature
§ Electronic control failure
§ Opened door.
Once a failure an external alarm is activated, and the unit turns into emergency operation mode.
INTARBLOCK and INTARTOP units include low noise components. The following chart indicates
sound pressure levels calculated at 10 m from the source in open field distribution (directivity = 1):
18. TRANSPORT
Handle the unit with care to prevent damages during its transport. Please follow the following
instructions:
§ Always handle the unit in vertical position.
§ Never pile up the units during transport.
§ Never pile up the units during storage.
H
§ Use a forklift or a pallet jack to handle the unit.
§ Keep the unit on its pallet until its final destination.
Packaging dimensions (mm) L W H Weight
L
CV series 0 610 460 823 44 Kg
CV series 1 905 440 1065 76 Kg A
21
Downloaded from www.Manualslib.com manuals search engine
19. DATA PLATE
All All units are identified with the following data plate. In all communications with the manufacturer
please indicate the serial number.
Before operating on the unit, verify that the general supply is disconnected to avoid
electrical shocks.
§ Eye irritations or burns may be caused if refrigerant comes into contact with the skin.
Use a safety mask and a pair of gloves. Avoid any contact between the refrigerant and
the skin and mind any sharp end of the unit.
22
Downloaded from www.Manualslib.com manuals search engine
intarblock | intartop
In case of accident due to refrigerant inhalation follow the following instructions:
§ Move the victim where it could breathe fresh air. The victim should lay on its back or its shoulder.
§ Call emergency services if needed.
23
Downloaded from www.Manualslib.com manuals search engine
RECOMMENDED
SEPARATION
DOOR HEATER (Only BCV)
> 500 mm
DOOR MICROSWITCH
COLD
ROOM
LIGHT
SIDE
COVER
DOOR MICROSWITCH
> 500 mm
COLD
ROOM
LIGHT
INSULATING
RECOMMENDED PAD
SEPARATION
1 000 mm
§ Fix the unit to the wall panel by mean of 6 through screws of Ø 6 mm metric as indicated on the
drawing. For the drop mounting, two hang-in holes are available for Ø 8 mm metric.
24
Downloaded from www.Manualslib.com manuals search engine
intarblock | intartop
Dimensions (mm) A B C D E F G H
+0 +5 ±1 ±1
CV series 0 (plug-in mounting) 400 117 135 n/a 511 +5
A A
C C C C
±1
±1
52
Ø6 Ø6 Ø6 Ø6 Ø6 Ø6
72 +3
12
5 ±1
E
159
F F
H
+2
2
Ø8 Ø8
Ø2
Ø6 Ø6 Ø6 Ø6 Ø6 Ø6
C C C C
Dimensions (mm) A B C D E F G H
+0 +5 ±1 ±1 ±1 +5 ±1 ±2
CV series 1 375 469 125 726.5 34.5 122 208 330 +5
CV series 2 595 +0 +5 509 ±1 235 ±1 766.5 ±1 30.5 +5 222 ±1 208 ±2 330 +5
CV series 3 692 +0 +5 369 ±1 292 ±1 766.5 ±1 39.5 +5 267.5 ±1 356 ±2 470 +5
25
Downloaded from www.Manualslib.com manuals search engine
§ Centrifugal fan installation.- for CV-CF models.
1. Fix the unit to the cold room wall before installing the centrifugal fan.
2. Take out the side panels of the centrifugal box to access the fixing screws.
3. Screw the centrifugal box to the refrigeration unit and connect the fan electrical wiring.
4. Re install the side panels.
The INTARTOP unit series are specially designed for roof mounting. To do so, please follow below
steps:
§ Before assembling the roof of the cold room, cut out the roof frame as indicated in the plan and
dimensions chart (page 16)).
§ Once the cold room is assembled, place the unit on the roof.
MINIMUM 650 mm
RECOMMENDED
RECOMMENDED
SEPARATION
SEPARATION 500 mm
DOOR
MICROSWITCH
COLD
ROOM DOOR
LIGHT POWER HEATER
SUPPLY
§ In some operation conditions (e.g. intenstive use in wet environmment, air infiltrations, etc.), it
could be possible that the unit is not able to evaporate all condensing water. In that case, install a
draining pipe in the drain bucket to a permanent draining point.
§ Finally seal with silicon the gap between the unit and the wall panel.
To ensure good working conditions and easy access for maintenance, please keep free
the recommended separation around the unit.
§ Failing a detailed calculation, the following chart shows the recommended dimensions according
to the duct type, for an equivalent total length of 20 m and both air intake-outtake grilles.
26
Downloaded from www.Manualslib.com manuals search engine
intarblock | intartop
§ It is recommended a minimum length duct, avoiding placing unnecessary turns. Failing a detailed
calculation, it can be supposed that a 90º turn, with no internal radio, is equivalent to 5 m length.
§ If air intake is not ducted, an air intake adequate to the room should be planned.
§ It is not recommended the use of flexible ducts due to pressure loss, being only acceptable in case
of straight and very short stretches. If so, an aluminium semi-flexible duct as indicated diameters is
recommended.
22. START-UP
Before starting the unit,plese check that the unit is properly fixed on its supports and the electrical
connections are properly installed. If you have worked on the unit, take care not to forget tools or any
objects inside, that there is no gas leak and that assembly-connection are properly done.
Before starting up or after a stand-by periods, activating the crankage heater (when included) at
twelve hours in advance is recommended. Otherwise, the compressor must be warmed up in a
different way to ensure the refrigerant-oil separation. This operation is important, specially when
starting-ups in low ambiance temperatures.
Connect the electrical supply and switch on the unit with room door closed. The display will show the
room temperature and after the time as specified for Ods parameter the compressor will start.
Set the cold room temperature set point and wait until the cold room temperature reaches the set
point. The high temperature alarm will not be activated until the time of dAO parameter is elapsed.
Once the target temperature is reached, initialise the record of maximum and minimum temperature as
indicated in thism anual. You may check that auxiliary devices work properly:
§ Room light.- turn on and off the room light.
§ Door switch.- check that the compressor and fans stop when opening the door.
Force a manual defrost cycle to check this operation mode. make sure that the evaporation coil gets
clean and that the unit stays within the normal operating parameters without activating any safety
device.
Depending on the application you may need to modify defrost parameters, such as time
period between two consecutive defrost cycles, defrost cycle duration or termination
temperature. To do so, pay attention to the defrost cycles during normal operation.
27
Downloaded from www.Manualslib.com manuals search engine
Finally you can easily test the proper operation of some of the safety devices such as:
§ Open door alarm.- by leaving the door open beyond indicated in doA parameter.
§ High pressure switch or high temperature alarm.- by intentionally obstructing the air intake of
condenser.
§ Low pressure switch or Low temperature alarm.- by intentionally obstructing the air intake of
evaporator.
23. MAINTENANCE
INTARBLOCK and INTARTOP units are self-contained equipment not requiring specialised
maintenance. Nevertheless, to keep your unit in an optimal working state, we recommend to
periodically carrying out the following preventive maintenance tasks.
During the maintenance tasks, switch off the power supply and use gloves to avoid any
possible cut.
§ External cleaning.- To keep your unit free from dust and dirtiness, simply pass a wet cloth over the
cover. Do not use neither solvents nor detergents.
BATERIA DE TORNILLOS
SIDE SCREWS
CONDENSER COIL
CONDENSACION FIJACION
FIXING THE
CARCASA
EXTERNAL COVER
§ Condenser cleaning.- During the normal operation the dust and dirtiness will deposit on the coil
surface and will obstruct the air flow. Periodically, and depending on the surroundings, the
condenser should be cleaned. To do so, remove the external cover of the unit by removing the
side screws. Use compressed air blowing from inside or a vacuum cleaner to remove dirtiness on
the coil. Alternatively use a brush from the outer face of the coil. Do not force the fins to avoid
deformation.
§ Cleaning the evaporator (CV).- Remove any of the side covers of the evaporator block by
removing front and side screws. Blow air from outside or brush on the inner side to remove the
dirtiness on the coil.
SCREWS IN THE
COVER SIDE
EVAPORATION COIL
DRAIN TRAY
SCREWS IN THE
COVER SIDE
28
Downloaded from www.Manualslib.com manuals search engine
intarblock | intartop
§ Cleaning the evaporator (CR).- Remove the evaporator cover panel from inside cold room.
Deplace the cover to a side to access the coil. Blow or brush to clean it.
CONDENSATION
COIL
GRILLE
EVAPORATOR
COVER PANEL
§ Drain tray.- To clean the drain tray you can use commercial detergents. In that case, make sure to
remove the detergent from the drain bucket inside the condensation block. To do so you can clean
the bucket with water. For CR units it is posible to dissasemble the evaporator box to access the
condenser coil and the drain tray. To do so, unscrew the box from the condenser and from the
lower section.
EVAPORATOR
COIL
TRAY
The maintenance tasks shown in this manual do not exclude any maintenance task in regulations and
laws.
24. REFRIGERANT LOAD
INTARBLOCK units are specifically designed for R404A refrigerant. The use of any other refrigerant in
the unit invalidates its guarantee.
Any operation related to the load, removal or replacement of refrigerant must always be carried out by
qualified personnel and never by the user. Please refer to technical refrigeration manuals for such
operations.
Units must always be loaded with R404A refrigerant in liquid phase through the HP nipple, in the exact
quantity indicated on the data plate.
29
Downloaded from www.Manualslib.com manuals search engine
25. DISPOSAL MANAGEMENT
After the installation dispose the packaging and pallet in an environmentally friendly manner and
according to your regulations. When disposing your unit or any of its parts, do it through an authorised
waste management company according to laws and regulations.
26. CONTROL
The unit is managed by a electronic board and a control keyboard with the following operating modes:
Refrigeration mode
The refrigeration operation mode is driven by a thermostatic control according to the room temperature
and a temperature target fixed by the user. Thus, when the room temperature is greater than the
temperature target, plus a pre-set differential, the compressor starts and stops when the room
temperature reaches the target temperature.
During the operation mode the display shows the room temperatura. Target temperature can be
shown by pressing the key and can be modified by pressing and .
To protect the compressor from successive starts, short cycle timing is inbuilt.
The fast freezing operation mode can be activated or deactivated by pressing the key for 3
seconds. During this operation mode the compressor works continuously for a preset period as
configured through the “CCt” parameter.
Defrost mode
After every preset period (fixed by the parameter “Idf”) the unit executes a defrost cycle. The unit is
preset on a defrost mode controlled through the inner coil temperature. In this mode, when the
evaporator coil reaches a certain temperature (as predefined value through the parameter “dtE”), or
after certain time (as predefined value through the parameter “MdF”). After a defrost cycle the unit
stays idle for the drain time (preset time through the parameter “Fdt”) to allow the evacuation of all
defrosted water.
The unit is configured to stop fans during the defrost cycle (parameter “FnC”)
After the defrost cycle and during the beginning of the normal refrigeration mode, the evaporator fan
remains stopped for the time defined by parameter “Fnd”.
Room light
It consists of a display of 3 digits and a 7 key keyboard with LEDs to indicate operation mode and
alarms.
30
Downloaded from www.Manualslib.com manuals search engine
intarblock | intartop
Fan LED
Defrosting LED
Compressor LED
Fast-cooling mode LED
Defrosting key
Max. Temperature and fast-
cooling mode key Cold room Light switch
Min temperature key
Energy saving mode key
Target temperatura and
validation key Unit On/Off
To display and modify target set point; in programming mode it selects a parameter or confirm an operation.
By holding it pressed for 3s when max or min temperature is displayed it will be erased.
To see the max. stored temperature; in programming mode it browses the parameter codes or increases the
displayed value. By holding it pressed for 3s the fast freezing cycle is started.
To see the min stored temperature; in programming mode it browses the parameter codes or decreases the
displayed value.
31
Downloaded from www.Manualslib.com manuals search engine
Keyboard functions
§ To switch off the unit.-
1. hold pressed for 5 seconds and the display will show "OFF".
§ To show maximum temperature record.-
1. press
2. the display will show the value together with “Hi”.
3. press or wait 5 seconds to restore the normal display.
Do not forget to restart temperature records at the first start-up of the unit.
4. press and to modify the flasshing digit and confirm its value by pressing set, to enter
the password 321.
§ To modify a parameter.-
1. enter the parameter list,
2. select the parameter by pressing or and press set to visualise its value.
32
Downloaded from www.Manualslib.com manuals search engine
intarblock | intartop
3. press or to modify its value.
4. press set to confirm then ew value and jump to the next parameter.
5. to exit the programming mode press set and or wait for 15 seconds.
33
Downloaded from www.Manualslib.com manuals search engine
Code Description Range Default List
MT BT
IdF Interval between defrosting cycles. 1 ÷ 120 h 3h Pr1
Md Maximum defrosting legth.
0 ÷ 255 min 15 min Pr1
F
dFd Display during defrost:
rt, it,Set, dEF,
rt=real temperature ; it=last recorded temperature ; Set=set point it Pr2
dEG
; dEF= “dEF” message ; dEG= “dEG”message.
dAd Delay after defrosting to display cold room temperature 0 ÷ 255 min 15 min Pr2
dSd Defrosting start delay. 0 ÷ 99 min 0 min Pr2
Fdt Time defrosting end to compressor starting-up (draining time). 0 ÷ 60 min 2 min 3 min Pr2
dP Displayed if defrosting after starting-up.
n-y n Pr2
O
dAF Defrost delay after fast freezing. 0 ÷ 23 h 50
2,0 h Pr2
min
FANS
FnC Fans operating mode: With compressor (C) / always on (O) / C-n, C-y, O-n,
C-n Pr2
during defrosting (y=yes / n=no). O-y
Fnd Fans operation delay after defrosting. 0 ÷ 255 min 3 min 4 min Pr2
FSt Fans stop temperature. -50,0 ÷ 110,0
10 ºC 0 ºC Pr2
ºC
ALARMS
ALC Temperature alarm configuration (ALU and ALL):
rE - Ab rE Pr2
rE=relative ; Ab=absolute.
ALU Maximum temperature alarm rE: -50,0 ÷ 110,0
ºC 5,0 ºC Pr1
Ab: 0,0 ÷ 50,0 ºC
ALL Minimum temperature alarm rE: -50,0 ÷ 110,0
ºC 5,0 ºC Pr1
Ab: 0,0 ÷ 50,0 ºC
AFH Temperature alarm and fan differential 0,1 ÷ 25,5 ºC 2,0 ºC Pr2
ALd Temperature alarm delay. 0 ÷ 255 min 0 min Pr2
dAO Delay of temperature alarm after starting up. 0 ÷ 23 h 50
3h 4h Pr2
min
EdA Alarm delay at the end of the defrosting 0 ÷ 255 min 30 min Pr2
dot Delay of temperature alarm after closing the door 0 ÷ 255 min 30 min Pr2
doA Delay of opened door alarm 0 ÷ 255 min 15 min Pr2
rrd outputs restart after doA alarm n-y y Pr2
AL2 Condenser low temperature alarm -50,0 ÷ Au2 ºC -40 ºC Pr2
Au2 Condenser high temperature alarm AL2 ÷ 110,0
52 ºC Pr2
ºC
ALH Differential of condenser low temperature alarm (AL2). 0,1 ÷ 25,5 ºC 5 ºC Pr2
AtH Differential of condenser high temperature alarm (Au2). 0,1 ÷ 25,5 ºC 3 ºC Pr2
Ad2 Condenser temperature alarm delay 0 ÷ 255 min 0 Pr2
dA2 Condenser temperature alarm eclusion at starting up 0 ÷ 23h 50 min 0 Pr2
tbA Alarm signal silencing by pressing a key. n-y y Pr2
34
Downloaded from www.Manualslib.com manuals search engine
intarblock | intartop
Code Description Range Default List
MT BT
nPS Pressure switch activation number 0 ÷ 15 10 Pr2
ANALOGUE INPUTS
Ot Thermostat probe calibration -12,0 ÷ 12,0
0 Pr1
ºC
OE Evaporator probe -12,0 ÷ 12,0
0 Pr2
ºC
O3 Condenser probe calibration -12,0 ÷ 12,0
0 Pr2
ºC
P2P Evaporator probe presence:
n-y y Pr2
n=no (defrosting by time) ; y=sí (desescarche por tiempo y Tª)
P3P Condenser probe presence: n=no ; y=yesí n-y y Pr2
HE Temperature increase during the Energy Saving cycle -30,0 ÷ 30,0
2 ºC Pr2
S ºC
DIGITAL INPUTS
odc When door is open, switches off the compressor (CPr), fan (Fan), no, Fan, CPr,
F_C Pr2
both (F_C), or non of them (no) F_C
I1P Door micriswitch polrity. CL=Closed; OP=Opened CL - OP OP Pr2
I2P Pressure switches polarity: CL=Closed; OP=Opened CL - OP OP Pr2
I2F Digital input 2 configuration: PAL=Pressure switches. EAL, bAL,
PAL, dFr, PAL Pr2
AUS, Es, onF
did Digital input alarm relay 0 ÷ 255 min 60 Pr2
oP2 External alarm polarity: cL=closed ; oP=Opened. cL - oP cL Pr2
OTHERS
Adr Serial address. 1 ÷ 247 1 Pr1
rEL Software release solo lectura 8.4 Pr2
Ptb Dixell map code. solo lectura 2 Pr2
Prd Probe display values: thermostat “Pb1”, evaporator “Pb2” and
Pb1, Pb2, Pb3 solo lectura Pr2
condenser “Pb3”.
Pr2 Access Pr2 parameter list. Pr1
The unit has two digital inputs. One of them is always configured as a door switch. The other one is
preset as a pressure switch (PAL value assigned to parameter “I2F”). If during the interval time set by
“did” parameter, the pressure switch has reached the number of activation of the “nPS” parameter,
the “PAL” pressure alarm message will be displayed. When the digital input is ON the compressor is
always OFF.
The digital inputs polarity depends on “I1P” and “I2P” parameters: CL indicates the digital input is
activated by closing the contact; OP indicates the digital input is activated by opening the contact.
35
Downloaded from www.Manualslib.com manuals search engine
External communication
By mean of the TTL connector it is possible to connect the unit through a ModBUS-RTU compatible
net to a XWEB300 monitoring system. Same TTL input is used to download or upload parameter data
from a “Hot key”.
Alarm signals
Alarm recovery
Depending on the entered option in parameter “tBA”, alarm signals are turned off by pressing any key
or when the alarm cause ceases.
Probe alarms: “P1” (probe1 faulty), “P2” and “P3” automatically stop 10s after the probe restarts
normal operation.
Temperature alarms “HA” and “LA” automatically stop as soon as the thermostat temperature returns
to normal values or when the defrost starts.
36
Downloaded from www.Manualslib.com manuals search engine
intarblock | intartop
28. FAULT ANALYSIS
Syptom Cause Solution
The unit does not turn on a) faulty power supply a) Check protections, fuse, etc.
b) wrong connection of remote keyboard b) Check connection and polarity
The compressor does a) faulty power supply a) Check protections, fuse, etc.
not start up, LED b) faulty contactor b) Replace
compressor is on c) internal klixon is open c) Wait for recovery and check compressor
d) Compresor full of liquid intensity
d) Plug in the unit to activate crankase heater
(when included) and wait several hours before
switching on. Load-unload circuit alternatively
The compressor doesn’t a) faulty power supply a) Check pressure value and/or check safety
start. Compressor led b) faulty contactor devices (pressure switches) by checking
flashing c) internal klixon is open continuity in board connectors. Look for the
cause:
àLP switch closed: switch on-off the unit
à faulty pressure switches: identify and
replace.
b) Wait and/or check AC parameter
c) check electrical continuity in board terminals
The compressor stops a) Low supply voltage a) Check the power supply and look for the
some few seconds after b) Faulty starting kit (check the starting relay) voltage drop
having started. The (only single-phase units) b) Replace compressor and start kit (only
motor produces an c) Blocked compresor single-phase unit)
intermittent noise and the d) Blocked compresor c) Check oil level and oil return to the
internal klixon is opened. e) Liquid slug (the starting up was posibly compressor through the suction line. If needed
done without connecting the crankage heater install oil traps or remake the suction line.
with sufficient time d) Replace compressor
e) Plug in the unit to activate crankase heater
(when included) and vacuum for a time.
Reload and start-up the unit
Repetitive compressor a) if the compressor LED is flashing a) Check pressures and/or safety chain to look
starts and stops b) if the compressor LED is on (opened klixon) for the activated device.
c) Too small regulation differential or too à HP pressure switch: condenser is blocked,
powerful unit for the room size, or empty room poor ventilation, too much refrigerant, high
without any thermal inertia. room temperature, faulty control of condensing
temperature, etc.
à LP pressure switch: connect the
manometer to HP&LP switches and bypass
refrigerant from high pressure to low pressure
sectors. Then find out the reason (frost, leak,
condensation control, valves, etc
b) V Check oil level and oil return to the
compressor through the suction line. If needed
install oil traps or remake the suction line.
c) Increase regulation differential (parameter
Hy)
37
Downloaded from www.Manualslib.com manuals search engine
Syptom Cause Solution
The unit runs but the a) Faulty room temperature probe a) Check the probe value and calibrate
room temperature does b) Too often defrost cycles through parameters, check probe connections,
not goes down c) Too small unit for the room size or replace probe.
d) Insufficient air-flow b) Check defrost parameters
e) The condenser is dirty or obstructed c) Recalculate the necessary power
d) Check air flow (rate, reflow, outlets)
e) Clean it
The unit froze the a) Faulty room temperature probe a) Check wiring and parameter Prd (Pb1),
product, even in case of replace probe and/or adjust Ot parameter
positive temperature set
point
The unit works but loses a) Regulation differential (parameter Hy) too a) Decrease regulation differential (parameter
too much temperature high Hy) by 2 ºC.
before restarting
The evaporator gets too a) Too low evaporation pressure a) Check pressure and find out the reason
much frost and the drain b) Blocked drain-pipe b) Check draining pipe heater (for LT models)
tray overflows c) Cold room leak-proof fault and replace or connect the heater to continous
d) The door is opened too often, or there is too supply, set higher slope. Verify the heater is
much humidity placed all long the draining-pipe for LT
models)
c) Check continuity of steam barrier and seal
the joints. Check door leak-proof
d) Increase defrosting frequence
Condenser Alarm CSd or a) Insufficient air flow or air reflow in a) Check air flow (rate, reflow, outlets)
pressure alarm PAL condenser b) Repair or replace
b) Faulty condenser fan c) Check target temperature
Too high condensation c) Too high room temperature d) Clean condenser and air intakes
pressure d) Too dirty and obstructed condenser e) Check and replace refrigerant load
(HP Pressure switch e) Excess of refrigerant load f) Evacuate and replace refrigerant
activates) f) Air inside refrigerant circuit
Pressure alarm PAL a) Insufficient airflow in evaporator. a) Clean air intakes
b) Faulty evaporator fan b) Repair or replace
Too low evaporation c) Evaporator is always iced c) Check defrost and defrost parameters.
pressure (LP pressure d) Frozen drain pipe Increase defrost frequency
switch activates) e) Obstructed refrigerant filter (different inlet d) Check drain heater and replace if necesary
and outlet temperatures) (for low temperature units)
Ice block in evaporator f) lack of refrigerant (leakage) e) Change refrigerant filter
g) Too low condensation pressure f) Repair leakage, replace refrigerant load
h) Faulty solenoid valve g) Too low ambient temperature, too high
i) Faulty expansion valve airflow rate, check and adjust condensation
parameters (only for split units) or replace the
unit
h) Repair or replace
i) Check posible humidity inside the circuit
38
Downloaded from www.Manualslib.com manuals search engine
intarblock | intartop
Syptom Cause Solution
The condenser fan a) Condensation control is not working a) Compare Pb3 value by checking with a
works inttermitently and properly (only for split units) reliable thermometer, check probe isolation,
subsequently the replace probe and isolate it properly. Check
pressure switch turns off HP and LP values performance during starting
the unit. up, stop fan and modify ALH and AL2
parameters if neccesary
Evaporator fan does not a) LED ON and power in board connectors à a) Check electrical conexión or change
work. faulty electrical supply connection or faulty motorfan.
Blocked evaporator motorfan b) Check probe wiring or replace probe
(frost) B) LED off à wrong Pb2 probe value à
faulty probe or wrong probe wiring
Noisy compressor a) Loose compressor a) Check silentbloc screws
b) Low oil level b) Add oil to the recommended level
c) Faulty compressor c) Replace
Noisy unit a) Unit is installed without noise insulation a) Install insulating layer or supports under the
unit
Defrost mode doesn’t a) Faulty heater or solenoid valve a) Repair or replace
work b) Electrical fault. b) check contactor and fuse
c) Faulty evaporator probe c) Check value Pb2, check connections,
d) Wrong defrost parameters replace
e) Faulty solenoid valve (only for hot gas d) Check and adjust defrost parameters
defrosting units) e) Repair
P1 alarm and/or default Probe value is lower than cold room a) wrong wiring between cold room
thermostat reading temperature. The value decresases quickly temperatura probe and evaporator probe
when the unit is operating
b) Room temperature probe faulty or wiring b) check probe wiring (electrical connection
faulty between units for Split systems). Replace
probe
P2 alarm a) Evaporator probe faulty or wiring faulty a) Check probe wiring (electrical interconexion
for split units). Replace probe
P3 alarm a) Condenser probe faulty a) Check probe wiring. Replace probe
dA alarm a) open door micro-switch a) Check wiring and door switch or electrical
bridge.
BAL alarm and/or EAL a) Misconfigured board and/or board default a) Check board configuration. Check I2F=PAL
alarm parameter value and/or replace board
The unit does not work a) Wrong voltage a) Check phase connection for three-phase
and the keyboard shows units
the temperature value
and "---" alternatively
39
Downloaded from www.Manualslib.com manuals search engine
29. GUARANTEE
Validation of guarantee.- The user is called to fill the form trough INTARCON’s web site:
http://www.intarcon.com/en/contacto/registro-garantia/ during the following 20 days after the
purchasing date. Otherwise, the guarantee period will be in effect from the manufacturing date.
Coverage.- The manufacturer guarantees the products against any manufacturing default or working
vice for 12 months after the validation of the guarantee or from the manufacturing date.
During the period of guarantee the manufacturer is to assume the reparation of the product in its
facilities, the replacement of the product or the supply of replacement parts for faulty components,
what is less costly and technically possible; guarantying the repaired or replaced components during
the following 6 months. It is expressly excluded of the coverage the cost and taxes of refrigerant, in the
case it is not supplied by the manufacturer in products hermetically sealed.
The guarantee excludes the works on-site to replace the product or components, nor the indirect
damages or loss that could be attributed to the faulty operation of the product. In particular, the
manufacturer is not to cover any tax on the refrigerant emitted to the environment as a result of a leak
in a refrigeration equipment or component suitable to accomplish leakproof tests according to in-vigour
regulation.
Guarantee application.- Before claiming a guarantee application, the user is to assure the
accomplishment on the operation instructions and to verify the faulty operation is not due to a improper
use of the equipment.
In general terms, the distributor or installer that sold and installed the equipment is called to attend the
guarantee claims and to provide the guarantee service. The user is called to contact the distributor or
installer in a maximum time of two months from the fault first appearance.
Guarantee invalidation.- The guarantee will not be valid in the following cases:
- In case that reparations, modifications or manipulations by unauthorised personnel are perceived.
- In case that wilful damages, fraud or bad faith in the correct use of the equipment are perceived.
- In case that the equipment has been bumped or dropped.
- In case the serial number or the guarantee documentation of the equipment has been modified or
made illegible.
40
Downloaded from www.Manualslib.com manuals search engine
41
Downloaded from www.Manualslib.com manuals search engine
42
Downloaded from www.Manualslib.com manuals search engine
43
Downloaded from www.Manualslib.com manuals search engine
Headquarters and factory
Pol. Ind. Los Santos, Bulevar de Los Santos, 34, Po box. 410
14900 - Lucena - Córdoba (SPAIN)
Tlf. +34 957 50 92 93
www.intarcon.com
44
Downloaded from www.Manualslib.com manuals search engine