THREE-POLE CONTACTORS Series HR33-HR55 Up To 30 KW: Control Coil Codes (IH25) F G D U X C W B Z
THREE-POLE CONTACTORS Series HR33-HR55 Up To 30 KW: Control Coil Codes (IH25) F G D U X C W B Z
THREE-POLE CONTACTORS Series HR33-HR55 Up To 30 KW: Control Coil Codes (IH25) F G D U X C W B Z
USE
Series HR contactors are particularly suitable for controlling mo-
tors, heating elements and three-phase and single-phase loads
in general.
OPERATION AND INSTALLATION
Screw mounting, distance between centres for fixing to EN
50003 or snap fitted onto 35 mm metal rail EN50022-3 DIN
46277-3
N.B. for cables with a section above 2x10mm2 only use screw fi-
xing
Mounting tilt not exceeding ± 30° in relation to the vertical
Ambient temperature from -5°C to 40°C
Altitude up to 2,000 metres
Relative humidity not exceeding 50% at 40°C
STANDARDS AND APPROVALS
Compliance with recommendations and standards:
IEC 947-4, CEI EN 60947-1, CEI EN 60947-4-1, VDE 0660,
BS 60947-4-1, UTE - NCF 63-110, NEMA NBN C63158,
AS1029
APPROVALS:
R
40
Cable section
45÷60
HR33 2x10 mm2
HR40 2x10 mm2
H
HR46 25 mm2
HR55 25 mm2
5
1 3 5 13
A1 56 95
A2
Control coil codes (IH25)
2 4 6 14
Code F G D U X C W B Z
81
50 Hz -V 48 110 220 220 480
to 366 380 440 to
24 to to 240 to 500
60 Hz -V 58 115 230 440 400 528
CONTROL COIL
Alternating current absorption inrush VA 90
sealed VA 9
Direct current absorption inrush
sealed
W
W
130
8
H 1 3 5 13
Minimum and maximum supply voltage Un V from 0.85 to 1.1 V A1
HR33-tab
THREE-POLE CONTACTORS HR - electric life
Millions of cycles
A1
H
1 3 5 13
Operating current Ie (A) at 380/415V~ Operating current Ie (A) at 380/415V~
A2
2 4 6 14
Millions of cycles
HR-graf
ACCESSORIES FOR CONTACTORS SERIES HR
INSTANTANEOUS AUXILIARY CONTACT BLOCKS
to fix to the top of the contactors
Rated current Ie
TYPE Contacts Rated AC-15
diagram thermal EN 60947-5-1 IEC947-5-1
current 220V 380V
Ith 240V 415V 500V
21 31
IR02
22 32
21 33
IR11 IR11
22 34
21 31 43 53
10 A 3A 1.5 A 1A
IR22
22 32 44 54
21 31 41 53
IR13
22 32 42 54
21 33 43 53
IR22 IR31
22 34 44 54
23 35
IDC10 RA
24 36
10 A 3A 1.5 A 1A
IDC01 21 35
RA
22 36
UH25Y With blind cover and reset button standard, for contactors HR17-HR25
and direct starters HS17Y - HS25Y
UH13Y UH25YP With run-stop/reset buttons for direct starters HS17Y..P - HS25Y..P
2003/01
IR
THERMAL RELAY FOR CONTACTORS HR33-HR40-HR46-HR55
USE
For protection against overloads of three-phase users. For single-
phase loads, connect two poles of the thermal relay in series to ob-
tain heating of three bimetals.
SPECIFICATIONS
-Direct mounting on HR contactors
-Automatic compensation of ambient temperature
-Protection against phase failure
-Auxiliary contacts 1 NO + 1 NC
-Manual reset
-Stop/reset button
-Trip indicator and release test
-Operating temperature from -5°C to +55°C
-Storage temperature from -40°C to +70°C
-Relative Humidity from 45 to 85%
STANDARDS AND APPROVALS
-VDE 0660 CEI EN 60947-4-1 IEC 947-4-1
-Approval:
R
89
78
59
49
SELECTION TABLE 1 3 5 13
A1
REGULATION PROTECTION
FUSES(A) A2
SCALE CODES 2 4 6 14
aM gl 72
55 94
A 14 to 23 25 50
B 20 to 33 40 63
C 28 to 4 2 50 80
D 35 to 50 63 100
E 46 to 65 80 100
Contact specifications
Regulation Terminal diagram Unit Packs
Rated Rated current Ie
TYPE scale and numbering thermal Va.c.. Vd.c. weight of
current 220V 380V
A Ith 240V 415V 500V W Kg. No
From 14
JA46 at 65 10 A 6A 3A 1.5 A 100
(see
selection
table)
JA46
TECHNICAL SPECIFICATIONS THERMAL RELAYS JA25 - Ja46
THERMAL RELAY type: JA25 JA46
Rated insulation voltage Ui V~ 660 660
Admissible ambient temperature °C -25 to 50 -20 to 60
Temperature compensation °C -5 to 50 -20 to 60
Maximum humidity %RH 95% a 40°C 95% a 40°C
Reset manual and automatic manual and automatic
Trigger simulation button yes yes
Auxiliary contacts 1NO + 1NC 1NO+1NC
Rated thermal current a.c. Ith A 10 10
220/240V ~ A 3 6
RATED OPERATING
CURRENT IN CATEGORY Va.c . 380/415V ~ A 1.5 3
500V ~ A 1 1.5
Vd.c. W 50 100
A1
H
1 3 5 13 0.06 0.08 0.38 0.06 0.08 0.35
0.09 0.12 0.33
15 20 52 18.5 25 58.5 30 40 60 30 40 55 37 50 62 37 50 54 45 60 54 55 75 60
JA-tab
WIRING DIAGRAMS
CONTACTORS
CONTROL EXAMPLES:
HR..10 HM..10
With Run-Stop With Run-Stop With pilot and With pilot and Operation-Stop
switch(or remote pilot) buttons (only for HR..10) Auto-Continuous switch Run-Stop switch indication
HR..01 HM..01
H
N
A2
R RESET
97 95 O STOP
22
1 3 5 13
A1
2 4 6 98 96
A2
2 4 6 14 R RESET R RESET R RICARICA R RESET
A2
O STOP O STOP O STOP O STOP
HS..10
L1 L2 L3
A1 1 3 5 21
N R RESET
A2 97 95 O STOP
22
With Run-Stop With Run-Stop With pilot and With pilot and
switch (or remote pilot) buttons (only for HR..10) Autom-Continuous switch Run-Stop switch
2 4 6 98 96
A2
HS..01
IN WATERPROOF ENCLOSURES IP65 WITH RUN-STOP/RESET BUTTONS YP
R RESET R RESET
L1 L2 L3 O STOP O STOP
A1 1 3 5
13
N
A2 R RESET
14 97 O STOP
95
98 96
2 4 6
MARCIA
A2
R RESET
97 95 O STOP
A2 14
For single-phase loads, connect two poles of
2003/01
1)Equipment classified in category AC-3 may be used for occasional pulsed switching or reverse current
braking, for limited periods such as those relative to positioning the machine. During these limited periods,
the number of these operations must not exceed 5 per minute and exceed 10 in a period of 10 minutes.
2)Motors for refrigerator hermetic compressors are a combination composed of motor and compressor
enclosed in the same casing without external shaft, as the motor operates immersed in the coolant.
Alternating current Control of resistive loads and solid state loads with isolation
obtained with opto-isolators
Control of solid state loads with isolating transformer
H-norm