0% found this document useful (0 votes)
138 views2 pages

Characterstic Strength:: Annexure-Vc Structural Design of Combined Footing For Column

This document summarizes the structural design of a combined footing for a column. It provides details of the column dimensions, material strengths, load cases, and design parameters. It then summarizes the design checks performed for flexural reinforcement, one-way shear, two-way/punching shear, and rock anchors. The design checks showed the provided structural dimensions and reinforcement were adequate and met code requirements.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
138 views2 pages

Characterstic Strength:: Annexure-Vc Structural Design of Combined Footing For Column

This document summarizes the structural design of a combined footing for a column. It provides details of the column dimensions, material strengths, load cases, and design parameters. It then summarizes the design checks performed for flexural reinforcement, one-way shear, two-way/punching shear, and rock anchors. The design checks showed the provided structural dimensions and reinforcement were adequate and met code requirements.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 2

GMR Consulting Services Private Limited

ANNEXURE-VC
STRUCTURAL DESIGN OF COMBINED FOOTING FOR COLUMN

Characterstic strength:
Concrete, fck = 25 N/mm2
Allowable base pressure, qall = 1250 kN/m2
Steel, fy = 500 N/mm2
Section parameter: Depth of column, D = 600 mm
Width of column, W = 1200 mm

Location of Cloumn wrt to footing = Edge

Clear cover for tension reinf. = 50.0 mm


Dia. Of bar provided, d1 = 16.0 mm
Area of bar provided = 201 mm2

Design parameter: Staad Node 33


Load case 104
Factored Axial Load, P 2701.286 kN
Factored Major axis moment, Mx = 164.844 kNm
Factored Minor axis moment, Mz = 0 kNm
Partial load Factor = 1.5

Axial Load, P 1800.86 kN


Major axis moment, Mx = 109.90 kNm
Minor axis moment, Mz = 0.00 kNm
eccentricity due to moments
eccentricity, ex = 61 mm
eccentricity, ez = 0 mm
eccentricity due to column location
eccentricity, e'x = 0 mm
eccentricity, e'z = 800 mm

Footing Width provided, Lx = 4000 mm


Footing length provided, Lz = 2200 mm

Avg. base pressure at


P/A±6*P*ex/(Lx*A) Heel = 669.87 kN/m2
±6*P*ez/(Lz*A) Toe = -260.58 kN/m2

Depth of footing provided, Df= 850 mm


Effective depth provided, major axis = 792 mm
Effective depth provided, minor axis = 776 mm

Design for flexural reinforcement


For Mx' - Major axis
Interpolated base pressure at face of cloumn = 416.1 kN/m2
Maximum design moment at face of column = 597 kNm

Effective depth rqeuired = 285 mm OK


Ast. Required = 1770 mm2
Spacing required = 250 mm
Spacing provided = 200 mm OK
%Ast provided = 0.12 %

Check for one way shear


For major axis only
length D+d = 1392
Effective length for shear = 808 mm
Interpolated base pressure at d from face of col. = 81 kN/m2
Length under compression = 191.9 mm

Shear force = 46.71 kN


Design Shear Stresses = 0.01 N/mm2
b= 24.54
Permissible Stress (τc) = 0.29 N/mm2 OK

Check for two way/punching shear


Avg. Base pressure (considered) = 205 kN/m2
Design Shear force at d/2 from face of col.= 2213 kN
Design shear stress = 0.779 N/mm2
Limiting shear stress for two way shear = 1.25 N/mm2 OK
[ks*0.25*sqrt(fck)] where, ks = 2.500
(should not be >1)
Design Check of Rock anchors for tension
Length under tension = 616 mm
Width under tension = 4000 mm
Total force in tension = -321.1 kN (-) for tension
Dia. of rock anchors = 32 mm
Length of anchor = 3.5 m
Capacity of each anchor = 293.2 kN
No. of rock anchors required = 1.10
No. of rock anchors provided = 2 OK

P2 MZ P1

Column
X X MX X

LZ LZ
Z

P3
P4
LX

Bajoli Holi H.P.P.(180MW)


GMR Consulting Services Private Limited

ANNEXURE-VD
STRUCTURAL DESIGN OF COMBINED FOOTING FOR COLUMN

Characterstic strength:
Concrete, fck = 25 N/mm2
Allowable base pressure, qall = 1250 kN/m2
Steel, fy = 500 N/mm2
Section parameter: Depth of column, D = 600 mm
Width of column, W = 1200 mm

Location of Cloumn wrt to footing = Middle

Clear cover for tension reinf. = 50.0 mm


Dia. Of bar provided, d1 = 16.0 mm
Area of bar provided = 201 mm2

Design parameter: Staad Node 6884


Load case 102
Factored Axial Load, P 3728.298 kN
Factored Major axis moment, Mx = 233.598 kNm
Factored Minor axis moment, Mz = 0 kNm
Partial load Factor = 1.5

Axial Load, P 2486 kN


Major axis moment, Mx = 155.732 kNm
Minor axis moment, Mz = 0.000 kNm
eccentricity due to moments
eccentricity, ex = 62.6554 mm
eccentricity, ez = 0.0000 mm
eccentricity due to column location
eccentricity, e'x = 0 mm
eccentricity, e'z = 0 mm

Footing Width provided, Lx = 3000 mm


Footing length provided, Lz = 2200 mm

Avg. base pressure at


P/A±6*P*ex/(Lx*A) Heel = 423.79 kN/m2
±6*P*ez/(Lz*A) Toe = 329.40 kN/m2

Depth of footing provided, Df= 1000 mm


Effective depth provided, major axis = 942 mm
Effective depth provided, minor axis = 926 mm

Design for flexural reinforcement


For Mx' - Major axis
Interpolated base pressure at face of cloumn = 389.5 kN/m2
Maximum design moment at face of column = 586 kNm
Effective depth rqeuired = 282 mm OK
Ast. Required = 1450 mm2
Spacing required = 305 mm
Spacing provided = 200 mm OK
%Ast provided = 0.10 %

Check for one way shear


For major axis only
length D/2+d = 1242 mm
Effective length for shear = 0 mm
Interpolated base pressure at d from face of col. = 430 kN/m2

Shear force = 0.00 kN


Design Shear Stresses = 0.00 N/mm2
b= 28.87
Permissible Stress (τc) = 0.29 N/mm2 OK

Check for two way/punching shear


Avg. Base pressure (considered) = 377 kN/m2
Design Shear force at d/2 from face of col.= 1862 kN
Design shear stress = 0.361 N/mm2
Limiting shear stress for two way shear = 1.25 N/mm2 OK
[ks*0.25*sqrt(fck)] where, ks = 2.500
(should not be >1)

Z
P2 MZ P1

X X
MX Column LZ

Z
P3 P4
LX

Bajoli Holi H.P.P.(180MW)