SQ 05.2 - SQ 14.2 Auma Norm: Technical Data Part-Turn Actuators For Open-Close Duty With 1-Phase AC Motors

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

SQ 05.2 – SQ 14.

2
AUMA NORM
Technical data Part-turn actuators for open-close duty with 1-phase AC motors

Type Operating time Torque Valve attachment Valve shaft Handwheel Weight
for 90° range1)
in seconds
Standard Option Cylindrical Square Two-flat
Min. Max. EN ISO EN ISO max. max. max. Turns for approx.
50 Hz 60 Hz [Nm] [Nm] 5211 5211 [mm] [mm] [mm] Ø mm 90° [kg]
4 3 11
5.6 4.5 16
8 6 11
11 9 16 232)
SQ 05.2 50 150 F05/F07 F10 25.4 22 22 160
16 12 11 29 3)
22 17 16
32 25 11
63 50 11
4 3 11
5.6 4.5 16
8 6 11
11 9 16 232)
SQ 07.2 100 300 F05/F07 F10 25.4 22 22 160
16 12 11 293)
22 17 16
32 25 11
63 50 11
8 6 450 11
11 9 15
16 12 11 282)
SQ 10.2 22 17 200 F10 F12 38 30 27 200 15
600 323)
32 25 11
42 35 15
63 50 11
11 9 30
900
16 12 22
22 17 30
32 25 22 372)
SQ 12.2 400 F12 F14 50 36 41 200
45 35 30 453)
1,200
63 50 22
84 70 30
125 108 22
24 20 70
1,800
36 30 51 462)
SQ 14.2 48 40 800 F14 F16 60 46 46 200 70
72 60 2,400 51 573)
100 85 70

General information
Part-turn actuators AUMA NORM require external controls.
For sizes SQ 05.2 – SQ 14.2, AUMA offer AM or AC actuator controls. These can also easily be mounted to the actuator at a later date.

Notes on table
1) Torque range The tripping torque is adjustable for directions OPEN and CLOSE within the indicated torque range.
2) Weight Indicated weight includes part-turn actuator AUMA NORM with 1-phase AC motor, electrical connec-
tion in standard version, unbored coupling and handwheel
3) Weight with base and lever Indicated weight includes AUMA NORM part-turn actuator with 1-phase AC motor, electrical connec-
tion in standard version, and handwheel, including base and lever

Features and functions


Type of duty Short-time duty S2 - 10 min, classes A and B according to EN 15714-2
For nominal voltage, +40 °C ambient temperature and at load with 35 % of the max. torque
Motors 1-phase AC motor with integral permanent split capacitor (PSC), type IM B9 according to IEC 60034-7,
IC410 cooling procedure according to IEC 60034-6

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.293/003/en Issue 2.19 Page 1/4


SQ 05.2 – SQ 14.2
AUMA NORM
Technical data Part-turn actuators for open-close duty with 1-phase AC motors

Mains voltage, mains frequency Standard voltages:


1-phase AC current
Voltages/frequencies
Volt 110 – 120 110 – 120 220 – 240 220 – 240
Hz 50 60 50 60

Further voltages on request


Permissible variation of mains voltage: ±10 %
Permissible variation of mains frequency: ±5 %
Overvoltage category Category III according to IEC 60364-4-443
Insulation class Standard: F, tropicalized
Option: H, tropicalized
Motor protection Standard: Thermoswitches (NC)
Option: PTC thermistors (according to DIN 44082)
PTC thermistors additionally require a suitable tripping device in the actuator controls.
Motor heater (option) Voltages: 110 – 120 V AC, 220 – 240 V AC
Power: 12.5 W
Swing angle Standard: Adjustable between 75° and < 105°
Options: 15° to < 45°, 45° bis < 75°, 105° to < 135°, 135° to < 165°, 165° to < 195°, 195° to <
225°
Self-locking Yes (Part-turn actuators are self-locking if the valve position cannot be changed from standstill while
torque acts upon the output drive.)
Manual operation Manual drive for setting and emergency operation, handwheel does not rotate during electrical oper-
ation
Options: Handwheel lockable
Handwheel stem extension
Power tool for emergency operation with square 30 mm or 50 mm
Indication for manual operation Indication whether manual operation is active/not active via single switch (1 change-over contact)
(option) For further information refer to separate data sheet Technical data for switches.
Electrical connection Standard: AUMA plug/socket connector with screw-type connection
Options: Terminals or crimp-type connection
Gold-plated control plug (sockets and pins)
Threads for cable entries Standard: Metric threads
Options: Pg-threads, NPT-threads, G-threads
Terminal plan TPA01R1AA-101-000, 1-phase AC motor with permanent split capacitor
Splined coupling for connection to Standard: Coupling without bore
the valve shaft
Options: Machined coupling with bore and keyway, square bore or bore with two-flats according
to EN ISO 5211
Valve attachment Dimensions according to EN ISO 5211 without spigot

With base and lever (option)


Swing lever Made of spheroidal cast iron with two or three bores for fixing a lever arrangement. Considering the
installation conditions, the lever may be mounted to the output shaft in any desired position.
Ball joints (option) Two ball joints matching the lever, including lock nuts and two welding nuts, suitable for pipe accord-
ing to dimension sheet
Fixing Base with four holes for fastening screws

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.293/003/en Issue 2.19 Page 2/4


SQ 05.2 – SQ 14.2
AUMA NORM
Technical data Part-turn actuators for open-close duty with 1-phase AC motors

Electromechanical control unit


Limit switching Counter gear mechanism for end positions OPEN and CLOSED
Turns per stroke: 2 to 500 (standard) or 2 to 5,000 (option)
Standard: Single switch (1 NC and 1 NO) for each end position, not galvanically isolated
Options: Tandem switch (2 NC and 2 NO) for each end position, switch galvanically isolated
Triple switch (3 NC and 3 NO) for each end position, switch galvanically isolated
Intermediate position switches (DUO limit switching), adjustable for each direction of
operation
Torque switching Torque switching adjustable for directions OPEN and CLOSE
Standard: Single switch (1 NC and 1 NO) for each direction, not galvanically isolated
Option: Tandem switch (2 NC and 2 NO) for each direction, switch galvanically isolated
Switch contact materials Standard: Silver (Ag)
Option: Gold (Au), recommended for low voltage actuator controls
Position feedback signal, analogue Potentiometer or 0/4 – 20mA (electronic position transmitter)
(options)
Mechanical position indicator Continuous indication, adjustable indicator disc with symbols OPEN and CLOSED
Running indication Blinker transmitter
Heater in switch compartment Standard: Self-regulating PTC heater, 5 – 20 W, 110 – 250 V AC/DC
Options: 24 – 48 V DC/DC
A resistance type heater of 5 W, 24 V AC is installed in the actuator in combination with the AM or AC
actuator controls.

Electronic control unit (option, only in combination with AC actuator controls)


Non-Intrusive setting Magnetic limit and torque transmitter (MWG)
Position feedback signal Via actuator controls
Torque feedback signal Via actuator controls
Mechanical position indicator Continuous indication, adjustable indicator disc with symbols OPEN and CLOSED
Running indication Blinking signal via actuator controls
Heater in switch compartment Resistance type heater with 5 W, 24 V AC

Service conditions
Use Indoor and outdoor use permissible
Mounting position Any position
Installation altitude ≤ 2,000 m above sea level
> 2,000 m above sea level on request
Ambient temperature Standard: –30 °C to +70 °C
Options: –40 °C to +70 °C
–60 °C to +60 °C
Humidity Up to 100 % relative humidity across the entire permissible temperature range
Enclosure protection according to Standard: IP68 with AUMA 1-phase AC motor
EN 60529
Option: Terminal compartment additionally sealed against interior of actuator (double sealed)
According to AUMA definition, enclosure protection IP68 meets the following requirements:
• Depth of water: maximum 8 m head of water
• Duration of continuous immersion in water: Max. 96 hours
• Up to 10 operations during continuous immersion
Pollution degree according to IEC Pollution degree 4 (when closed), pollution degree 2 (internal)
60664-1
Vibration resistance according to 2 g, 10 to 200 Hz (AUMA NORM), 1 g, 10 to 200 Hz (for actuators with AM or AC integral controls)
IEC 60068-2-6 Resistant to vibration during start-up or for failures of the plant. However, a fatigue strength may not
be derived from this. Valid for part-turn actuators in version AUMA NORM and in version with integral
actuator controls, each with AUMA plug/socket connector. Not valid in combination with gearboxes.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.293/003/en Issue 2.19 Page 3/4


SQ 05.2 – SQ 14.2
AUMA NORM
Technical data Part-turn actuators for open-close duty with 1-phase AC motors

Corrosion protection Standard: KS Suitable for use in areas with high salinity, almost permanent condensation, and
high pollution.
Options: KX Suitable for use in areas with extremely high salinity, permanent condensation,
and high pollution.
KX-G Same as KX, however aluminium-free version (outer parts)
Coating Double layer powder coating
Two-component iron-mica combination
Colour Standard: AUMA silver-grey (similar to RAL 7037)
Option: Available colours on request
Lifetime AUMA part-turn actuators meet or exceed the lifetime requirements of EN 15714-2. Detailed informa-
tion can be provided on request.

Further information
EU Directives Electromagnetic Compatibility (EMC): (2014/30/EU)
Low Voltage Directive: (2014/35/EU)
Machinery Directive: (2006/42/EC)
Reference documents Brochure Electric actuators for industrial valve automation
Electrical data Part-turn actuators SQ 05.2 – SQ 14.2 with 1-phase AC motor
Technical data Electronic position transmitter/potentiometer
Technical data for switches
Technical data Sizing of reduction gearings

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.293/003/en Issue 2.19 Page 4/4

You might also like